Sky Air
Sky Air
Duct Connection
Middle Static Pressure Type Wall Mounted
FBA50/60/71/100/125/140BVMA FAA71/100BVMA
Features
Ceiling Cassette
Round Flow
Stylish Model
Ceiling Suspended White color
Sophisticated design
Duct Connection
Middle Static Pressure Type
Wall Mounted
Comfort Comfortable Airflow Control High Efficiency
Programme “Dry” Left & Right directions (by remote controller)* DC fan motor improves efficiency
*Note: Applicable when BRC1E63 is used.
High fan speed mode
Up & Down directions (by hand)
Switchable fan speed: 3 steps & Auto
*Note: “Auto” is applicable when BRC1E63 is used.
Easy Maintenance
Easy Installation Convenience Long-life filter (standard) requires
Lightweight indoor unit Wireless remote controller (separate type) is no maintenance for about 1 year*
DIII-Net communication standard supplied in a set with a signal receiver (BRC4C66) *Note: For dust concentration of 0.15 mg/m3.
Ceiling Cassette Round Flow
1 Phase
Model Indoor unit FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM
Name Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF100CVM RZF125CVM RZF140CVM
Power supply Outdoor unit 1 Phase / 220-230V / 60Hz
Cooling Capacity1,2 5.0 6.0 7.1 10.0 12.5 14.0
kW
Rated (Min. - Max.) (3.2-5.6) (3.2-6.0) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
17,100 20,500 24,200 34,100 42,700 47,800
Btu/h
(10,900-19,100) (10,900-20,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 1.14 1.53 1.93 2.97 4.18 5.47
COP W/W 4.39 3.92 3.68 3.37 2.99 2.56
CSPF Wh/Wh 6.60 6.31 6.17 5.50 5.15 5.00
Indoor unit Colour Unit
Decoration panel Fresh white
Airflow rate m3/min 23.0 / 21.0 / 18.5 / 16.0 / 13.5 34.5 / 31.0 / 27.5 / 24.0 / 20.0 36.5 / 33.0 / 29.0 / 25.0 / 21.0
(H / HM / M / ML / L) cfm 812 / 741 / 653 / 565 / 477 1,218 / 1,094 / 971 / 847 / 706 1,288 / 1,165 / 1,024 / 883 / 741
Sound pressure level3 (H/HM/M/ML/L) dB(A) 37.0 / 34.5 / 32.0 / 29.5 / 27.5 45.0 / 41.5 / 38.0 / 35.0 / 32.5 46.0 / 43.0 / 40.0 / 36.0 / 32.5
Dimensions Unit mm 256 x 840 x 840 298 x 840 x 840
(HxWxD) Decoration panel mm 50 x 950 x 950
Machine Unit kg 22 24
weight Decoration panel kg 5.5
Certified Operation range °CWB 14 to 25
Outdoor unit Colour Ivory white
Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.30 1.60 2.40
Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54
pressure level Night quiet mode
3
dB(A) 44 45
Dimensions (HxWxD) mm 595 x 845 x 300 695 x 930 x 350 990 x 940 x 320
Machine weight kg 41 48 64
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm φ9.5
connections Gas (Flare) mm φ15.9
Drain Indoor unit mm VP25 (I.D. φ25xO.D. φ32)
Outdoor unit mm φ26.0 (Hole) φ18.0 (Hole) φ26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
3 Phase
Model Indoor unit FCF71CVM FCF100CVM FCF125CVM FCF140CVM
Name Outdoor unit RZF71CYM RZF100CYM RZF125CYM RZF140CYM
Power supply Outdoor unit 3 Phase / 380V / 60Hz
Cooling Capacity1,2 7.1 10.0 12.5 14.0
kW
Rated (Min. - Max.) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
24,200 34,100 42,700 47,800
Btu/h
(10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 1.93 2.97 4.18 5.47
COP W/W 3.68 3.37 2.99 2.56
CSPF Wh/Wh 6.17 5.50 5.15 5.00
Indoor unit Colour Unit
Decoration panel Fresh white
Airflow rate m3/min 23.0 / 21.0 / 18.5 / 16.0 / 13.5 34.5 / 31.0 / 27.5 / 24.0 / 20.0 36.5 / 33.0 / 29.0 / 25.0 / 21.0
(H / HM / M / ML / L) cfm 812 / 741 / 653 / 565 / 477 1,218 / 1,094 / 971 / 847 / 706 1,288 / 1,165 / 1,024 / 883 / 741
Sound pressure level3 (H/HM/M/ML/L) dB(A) 37.0 / 34.5 / 32.0 / 29.5 / 27.5 45.0 / 41.5 / 38.0 / 35.0 / 32.5 46.0 / 43.0 / 40.0 / 36.0 / 32.5
Dimensions Unit mm 256 x 840 x 840 298 x 840 x 840
(HxWxD) Decoration panel mm 50 x 950 x 950
Machine Unit kg 22 24
weight Decoration panel kg 5.5
Certified Operation range °CWB 14 to 25
Outdoor unit Colour Ivory white
Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.60 2.40
Refrigerant charge (R32) kg 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54
pressure level3 Night quiet mode dB(A) 44 45
Dimensions (HxWxD) mm 695 x 930 x 350 990 x 940 x 320
Machine weight kg 48 64
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm φ9.5
Connections Gas (Flare) mm φ15.9
Drain Indoor unit mm VP25 (I.D. φ25 x O.D. φ32)
Outdoor unit mm φ18.0 (Hole) φ26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
Ceiling Suspended
1 Phase
Model Indoor unit FHA50BVMA FHA60BVMA FHA71BVMA FHA100BVMA FHA125BVMA FHA140BVMA
Name Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF100CVM RZF125CVM RZF140CVM
Power supply Outdoor unit 1 Phase / 220-230V / 60Hz
Cooling Capacity1,2 5.0 6.0 7.1 10.0 12.5 14.0
kW
Rated (Min. - Max.) (3.2-5.6) (3.2-6.0) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
17,100 20,500 24,200 34,100 42,700 47,800
Btu/h
(10,900-19,100) (10,900-20,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 1.20 1.53 2.30 3.24 4.29 5.40
COP W/W 4.17 3.92 3.09 2.91 2.59
CSPF Wh/Wh 6.30 6.11 5.91 5.17 5.09 4.78
Indoor unit Colour White
Airflow rate m3/min 15.0 / 13.5 / 12.0 / 11.0 / 10.0 20.5 / 18.8 / 17.0 / 15.5 / 14.0 28.0 / 26.0 / 24.0 / 22.0 / 20.0 31.0 / 29.0 / 27.0 / 25.0 / 23.0 34.0 / 31.5 / 29.0 / 26.5 / 24.0
(H / HM / M / ML / L) cfm 530 / 477 / 424 / 388 / 353 724 / 664 / 600 / 547 / 494 988 / 918 / 847 / 777 / 706 1,094 / 1,024 / 953/ 883 / 812 1,200 / 1,112 / 1,024 / 935 / 847
Sound pressure level3
dB(A) 37.0 / 36.0 / 35.0 / 33.5 / 32.0 38.0 / 37.0 / 36.0 / 35.0 / 34.0 42.0 / 40.0 / 38.0 / 36.0 / 34.0 44.0 / 42.5 / 41.0 / 39.0 / 37.0 46.0 / 44.0 / 42.0 / 40.0 / 38.0
(H / HM / M / ML / L)
Dimensions (HxWxD) mm 235 x 960 x 690 235 x 1270 x 690 235 x 1590 x 690
Machine weight kg 25 32 38
Certified Operation range °CWB 14 to 25
Outdoor unit Colour Ivory white
Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.30 1.60 2.40
Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54
pressure level3 Night quiet mode dB(A) 44 45
Dimensions (HxWxD) mm 595 x 845 x 300 695 x 930 x 350 990 x 940 x 320
Machine weight kg 41 48 64
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm φ9.5
connections Gas (Flare) mm φ15.9
Drain Indoor unit mm VP20 (I.D. φ20xO.D. φ26)
Outdoor unit mm φ26.0 (Hole) φ18.0 (Hole) φ26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
3 Phase
Model Indoor unit FHA71BVMA FHA100BVMA FHA125BVMA FHA140BVMA
Name Outdoor unit RZF71CYM RZF100CYM RZF125CYM RZF140CYM
Power supply Outdoor unit 3 Phase / 380V / 60Hz
Cooling Capacity1,2 7.1 10.0 12.5 14.0
kW
Rated (Min. - Max.) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
24,200 34,100 42,700 47,800
Btu/h
(10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 2.30 3.24 4.29 5.40
COP W/W 3.09 2.91 2.59
CSPF Wh/Wh 5.91 5.17 5.09 4.78
Indoor unit Colour White
Airflow rate m3/min 20.5 / 18.8 / 17.0 / 15.5 / 14.0 28.0 / 26.0 / 24.0 / 22.0 / 20.0 31.0 / 29.0 / 27.0 / 25.0 / 23.0 34.0 / 31.5 / 29.0 / 26.5 / 24.0
(H / HM / M / ML / L) cfm 724 / 664 / 600 / 547 / 494 988 / 918 / 847 / 777 / 706 1,094 / 1,024 / 953 / 883 / 812 1,200 / 1,112 / 1,024 / 938 / 847
Sound pressure level3 (H/HM/M/ML/L) dB(A) 38.0 / 37.0 / 36.0 / 35.0 / 34.0 42.0 / 40.0 / 38.0 / 36.0 / 34.0 44.0 / 42.5 / 41.0 / 39.0 / 37.0 46.0 / 44.0 / 42.0 / 40.0 / 38.0
Dimensions (HxWxD) mm 235 x 1270 x 690 235 x 1590 x 690
Machine weight kg 32 38
Certified Operation range °CWB 14 to 25
Outdoor unit Colour Ivory white
Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.60 2.40
Refrigerant charge (R32) kg 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54
pressure level3 Night quiet mode dB(A) 44 45
Dimensions (HxWxD) mm 695 x 930 x 350 990 x 940 x 320
Machine weight kg 48 64
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm φ9.5
Connections Gas (Flare) mm φ15.9
Drain Indoor unit mm VP20 (I.D. φ20 x O.D. φ26)
Outdoor unit mm φ18.0 (Hole) φ26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
Duct Connection Middle Static Pressure Type
1 Phase
Model Indoor unit FBA50BVMA FBA60BVMA FBA71BVMA FBA100BVMA FBA125BVMA FBA140BVMA
Name Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF100CVM RZF125CVM RZF140CVM
Power supply Indoor unit
1 Phase / 220-230V / 60Hz
Outdoor unit
Cooling Capacity1,2 5.0 6.0 7.1 10.0 12.5 14.0
kW
Rated (Min. - Max.) (3.2-5.6) (3.2-6.0) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
17,100 20,500 24,200 34,100 42,700 47,800
Btu/h
(10,900-19,100) (10,900-20,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 1.35 1.64 2.15 3.01 4.44 5.69
COP W/W 3.70 3.66 3.30 3.32 2.82 2.46
CSPF Wh/Wh 5.51 5.30 5.19 4.88 4.70 4.47
Indoor Colour
unit Fan Airflow rate m3/min 18.0 / 15.0 / 12.5 23.0 / 19.5 / 16.0 32.0 / 27.0 / 22.5 36.0 / 30.5 / 25.0
(H / M / L) cfm 635 / 530 / 441 812 / 688 / 565 1,130 / 953 / 794 1,271 / 1,077 / 883
External static pressure3 Pa Rated 50 (50-150)
Sound pressure level4 (H / M / L) dB(A) 35.0 / 33.0 / 31.0 38.0 / 35.0 / 33.0 40.0 / 37.5 / 35.0
Air Filter5
Dimensions (HxWxD) mm 245 x 1000 x 800 245 x 1400 x 800
Machine weight kg 37 47
Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white
unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.30 1.60 2.40
Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54
pressure level4 Night quiet mode dB(A) 44 45
Dimensions (HxWxD) mm 595 x 845 x 300 695 x 930 x 350 990 x 940 x 320
Machine weight kg 41 48 64
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm φ9.5
connections Gas (Flare) mm φ15.9
Drain Indoor unit mm VP25 (I.D. φ25xO.D. φ32)
Outdoor unit mm φ26.0 (Hole) φ18.0 (Hole) φ26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
3 Phase
Model Indoor unit FBA71BVMA FBA100BVMA FBA125BVMA FBA140BVMA
Name Outdoor unit RZF71CYM RZF100CYM RZF125CYM RZF140CYM
Power supply Indoor unit 1 Phase / 220-230V / 60Hz
Outdoor unit 3 Phase / 380V / 60Hz
Cooling Capacity1,2 7.1 10.0 12.5 14.0
kW
Rated (Min. - Max.) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
24,200 34,100 42,700 47,800
Btu/h
(10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 2.15 3.01 4.44 5.69
COP W/W 3.30 3.32 2.82 2.46
CSPF Wh/Wh 5.19 4.88 4.70 4.47
Indoor Colour
unit Fan Airflow rate m3/min 23.0 / 19.5 / 16.0 32.0 / 27.0 / 22.5 36.0 / 30.5 / 25.0
(H / M / L) cfm 812 / 688 / 565 1,130 / 953 / 794 1,271 / 1,077 / 883
External static pressure3 Pa Rated 50 (50-150)
Sound pressure level4 (H / M / L) dB(A) 38.0 / 35.0 / 33.0 40.0 / 37.5 / 35.0
Air Filter5
Dimensions (HxWxD) mm 245 x 1000 x 800 245 x 1400 x 800
Machine weight kg 37 47
Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white
unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.60 2.40
Refrigerant charge (R32) kg 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54
pressure level4 Night quiet mode dB(A) 44 45
Dimensions (HxWxD) mm 695 x 930 x 350 990 x 940 x 320
Machine weight kg 48 64
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm φ9.5
connections Gas (Flare) mm φ15.9
Drain Indoor unit mm VP25 (I.D. φ25xO.D. φ32)
Outdoor unit mm φ18.0 (Hole) φ26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
External static pressure is changeable in 11 stages by remote controller.
4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
5
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.
Floor Standing
1 Phase
Model Indoor unit FVA50AMVM FVA60AMVM FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM
Name Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF100CVM RZF125CVM RZF140CVM
Power supply Outdoor unit 1 Phase / 220-230V / 60Hz
Cooling Capacity1,2 5.0 6.0 7.1 10.0 12.5 14.0
kW
Rated (Min. - Max.) (2.3-5.6) (2.6-6.3) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
17,100 20,500 24,200 34,100 42,700 47,800
Btu/h
(7,800-19,100) (8,900-21,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 1.23 1.79 2.51 3.48 4.48 5.71
COP W/W 4.07 3.35 2.83 2.87 2.79 2.45
CSPF Wh/Wh 6.03 4.86 4.46 4.19 4.67 4.18
Indoor unit Colour Fresh White
Airflow rate m3/min 18 / 16 / 14 28 / 25 / 22 28 / 26 / 24 30 / 28 / 26
(H / M / L) cfm 635 / 565 / 494 988 / 883 / 777 988 / 918 / 847 1,059 / 988 / 918
Sound pressure level3 (H / M / L) dB(A) 43 / 41 / 38 50 / 47 / 44 51 / 48 / 46 53 / 51 / 48
Dimensions (HxWxD) mm 1850 x 600 x 270 1850 x 600 x 350
Machine weight kg 42 50
Certified Operation range °CWB 14 to 25
Outdoor unit Colour Ivory white
Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.30 1.60 2.40
Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54
pressure level3 Night quiet mode dB(A) 44 45
Dimensions (HxWxD) mm 595 x 845 x 300 695 x 930 x 350 990 x 940 x 320
Machine weight kg 41 48 64
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm φ9.5
connections Gas (Flare) mm φ15.9
Drain Indoor unit mm VP20 (I.D. φ20xO.D. φ26)
Outdoor unit mm φ26.0 (Hole) φ18.0 (Hole) φ26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
3 Phase
Model Indoor unit FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM
Name Outdoor unit RZF71CYM RZF100CYM RZF125CYM RZF140CYM
Power supply Outdoor unit 3 Phase / 380V / 60Hz
Cooling Capacity1,2 7.1 10.0 12.5 14.0
kW
Rated (Min. - Max.) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
24,200 34,100 42,700 47,800
Btu/h
(10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 2.51 3.48 4.48 5.71
COP W/W 2.83 2.87 2.79 2.45
CSPF Wh/Wh 4.46 4.19 4.67 4.18
Indoor unit Colour Fresh white
Airflow rate m3/min 18 / 16 / 14 28 / 25 / 22 28 / 26 / 24 30 / 28 / 26
(H / M / L) cfm 635 / 565 / 494 988 / 883 / 777 988 / 918 / 847 1,059 / 988 / 918
Sound pressure level3 (H / M / L) dB(A) 43 / 41 / 38 50 / 47 /44 51 / 48 / 46 53 / 51 / 48
Dimensions (HxWxD) mm 1,850 x 600 x 270 1,850 x 600 x 350
Machine weight kg 42 50
Certified Operation range °CWB 14 to 25
Outdoor unit Colour Ivory white
Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.60 2.40
Refrigerant charge (R32) kg 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54
pressure level3 Night quiet mode dB(A) 44 45
Dimensions (HxWxD) mm 695 x 930 x 350 990 x 940 x 320
Machine weight kg 48 64
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm φ9.5
Connections Gas (Flare) mm φ15.9
Drain Indoor unit mm VP20 (I.D. φ20 x O.D. φ26)
Outdoor unit mm φ18.0 (Hole) φ26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
Wall Mounted
1 Phase & 3 Phase
Model Indoor unit FAA71BVMA FAA71BVMA FAA100BVMA FAA100BVMA
Name Outdoor unit RZF71CVM RZF71CYM RZF100CVM RZF100CYM
Power supply Outdoor unit 1 Phase / 220-230V / 60Hz 3 Phase / 380V / 60Hz 1 Phase / 220-230V / 60Hz 3 Phase / 380V / 60Hz
Cooling Capacity1,2 7.1 10.0
kW
Rated (Min. - Max.) (3.2-8.6) (5.0-11.2)
24,200 34,100
Btu/h
(10,900-27,300) (17,100-38,200)
Power consumption Cooling kW 3.60 3.60
COP W/W 2.78 2.78
CSPF Wh/Wh 5.25 4.05
Indoor Colour Unit Fresh white
unit Airflow rate m3/min 18.0 / 16.0 / 14.0 26.0 / 23.0 / 19.0
(H / M / L) cfm 635 / 565 / 494 918 / 812 / 671
Sound pressure level3 (H / M / L) dB(A) 45 / 42 / 40 49 / 45 / 41
Dimensions (HxWxD) Unit mm 290 x 1050 x 238 340 x 1200 x 240
Machine weight Unit kg 13 17
Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white
unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.30 1.60
Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m)
Sound Cooling dB(A) 48 49
pressure level3 Night quiet mode dB(A) 44 45
Dimensions (HxWxD) mm 595 x 845 x 300 695 x 930 x 350
Machine weight kg 41 48
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm φ9.5
Connections Gas (Flare) mm φ15.9
Drain Indoor unit mm VP13 (I.D. φ13 x O.D. φ18)
Outdoor unit mm φ26.0 (Hole) φ18.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
Note:
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
www.daikin.com.ph
Authorized Dealer
Tel No.: (02) 5318 - 6800 | Customer Service: (02) 5318 - 6820
Branches:
ILOCOS Tel No.: (077) 600 - 2720 ILOILO Tel Fax: (033) 323 - 2340
DAGUPAN Tel No.: (075) 615 - 2791 CEBU Tel No.: (032) 348 - 0085
NAGA Tel Fax: (054) 871 - 4177 CDO Tel Fax: (088) 868 - 6800
DAVAO Tel Fax: (082) 285 - 6008
● Specifications, designs, and other content appearing in this brochure are current as of May 2019 but subject to change without notice. DPH-SAINV-052019B
● 1 year warranty for parts and labor | 5 years warranty for compressor only (Labor and Consumables are chargeable after 1 year).