0% found this document useful (0 votes)
18 views1 page

VEB Mipromex MAT V1.1x - ATEX09 38

This document provides details on a printed circuit board for mounting in 19-inch racks, monoracks, walls, and tables. It lists the connections and functions of 32 terminals on the board including power inputs, relay outputs, digital and analog I/O, and RS-485 communications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views1 page

VEB Mipromex MAT V1.1x - ATEX09 38

This document provides details on a printed circuit board for mounting in 19-inch racks, monoracks, walls, and tables. It lists the connections and functions of 32 terminals on the board including power inputs, relay outputs, digital and analog I/O, and RS-485 communications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

mipromex® Type MAT

Manual V11427/8

7.4. Printed circuit board for 19"-Rack, Monorack, Wall- and


Table Top housing
The Cage Clamp® connection clamps for cable diameter 0.08 – 2.5 mm2 bared length 5 – 6 mm /0.22 in (without
cable cover) are mounted with a special pre spanning tool.
Color coding:
 To the blue clamps: connection of the intrinsically safe field circuit. This one being allowed, with connection
lines in accordance to DIN EN 60079-14, to be routed into the hazardous area.
 The black/orange- clamps are polarity independent current- inputs or -outputs
Dimension: H x B x T 137 x 77 x 210 mm / for 19“-plug in module Euro 3 HE/12TE profundity 160 mm
Anschluss an: Microprocessor unit mipromex®
Artikel-Nr.: 02.03.18.011
PE1 Earthing FI32: d/z6
1. Mains 24 V AC/DC 50/60 Hz FI32: z30
(polarity independent)
2. Mains 24 V AC/DC 50/60 Hz FI32: d30
(polarity independent)
Relay Opto-e. coupler
3. 1 NO output E- FI32: z24
4. 1 COM output C+ FI32: d24
5. 1 NC - FI32: z22
6. 2 NO output E- FI32: z16
7. 2 COM output C+ FI32: d16
8. 2 NC - FI32: z14
9. MC1 analog output 1 - FI32: d14
10. MC1 analog output 1 + FI32: z12
11. MC1 MTI 1 K1 FI32: z2
12. MC1 MTI 1 K2 FI32: d2

21. Rackbus RS 485 A FI32: z32


22. Rackbus RS 485 B FI32: d32
23. Analog input - FI32: d18
24. Analog input + FI32: d12
25. Digital input 1 (+24 V) FI32: d10
26. Digital input 2 (+24 V) FI32: z10
27. Digital input 3 (+24 V) FI32: d8
-0 Digital input D1-3 (0 V) FI32: z8
-1 Digital input D1-3 (0 V) FI32: z8
28. MC2 Analog output 2 - FI32: d22
29 MC2 Analog output 2 + FI32: z20

31. MC2 MTI 2 K1 FI32: z4


32. MC2 MTI 2 K2 FI32: d4

Pic. 5 Connection print to mipromex

Page 38