0% found this document useful (0 votes)
32 views12 pages

Preprints202007 0325 v1

The document discusses using machine learning techniques to analyze thermal characteristics data from a data center to identify weaknesses in the cooling system and areas for improved energy efficiency. Clustering methods are applied to temperature data to locate hotspots and categorize servers based on surrounding air temperatures, with the goal of improving thermal management and reducing energy consumption.

Uploaded by

Maha Mas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views12 pages

Preprints202007 0325 v1

The document discusses using machine learning techniques to analyze thermal characteristics data from a data center to identify weaknesses in the cooling system and areas for improved energy efficiency. Clustering methods are applied to temperature data to locate hotspots and categorize servers based on surrounding air temperatures, with the goal of improving thermal management and reducing energy consumption.

Uploaded by

Maha Mas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.

v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

Type of the Paper (Research Article)

A Machine Learning Solution for Data Center


Thermal Characteristics Analysis
Anastasiia Grishina 1, Marta Chinnici 2,*, Ah-Lian Kor 3, Eric Rondeau 4 and Jean-Philippe Georges5
,1 ENEA, R. C. Casaccia; [email protected]
* ENEA, R. C. Casaccia; [email protected]
2,

3 Leeds Beckett University, Leeds, UK; [email protected]

4 Université de Lorraine, CNRS, CRAN, F-54000, Nancy, France; [email protected]

5 Université de Lorraine, CNRS, CRAN, F-54000, Nancy, France; [email protected]

* Correspondence: [email protected]; Tel.: +39-349-3553790 (M.C.)

Abstract: Energy efficiency of Data Center (DC) operations heavily relies on IT and cooling systems
performance. A reliable and efficient cooling system is necessary to produce a persistent flow of
cold air to cool servers that are subjected to constantly increasing computational load due to the
advent of IoT- enabled smart systems. Consequently, increased demand for computing power will
bring about increased waste heat dissipation in data centers. In order to bring about a DC energy
efficiency, it is imperative to explore the thermal characteristics analysis of an IT room (due to
waste heat). This work encompasses the employment of an unsupervised machine learning
modelling technique for uncovering weaknesses of the DC cooling system based on real DC
monitoring thermal data. The findings of the analysis result in the identification of areas for energy
efficiency improvement that will feed into DC recommendations. The methodology employed for
this research includes statistical analysis of IT room thermal characteristics, and the identification
of individual servers that frequently occur in the hotspot zones. A critical analysis has been
conducted on available big dataset of ambient air temperature in the hot aisle of ENEA Portici
CRESCO6 computing cluster. Clustering techniques have been used for hotspots localization as
well as categorization of nodes based on surrounding air temperature ranges. The principles and
approaches covered in this work are replicable for energy efficiency evaluation of any DC and thus,
foster transferability. This work showcases applicability of best practices and guidelines in the
context of a real commercial DC that transcends the set of existing metrics for DC energy efficiency
assessment.

Keywords: Data Center; Thermal Characteristics Analysis; Machine Learning, Energy Efficiency,
Hotspots, Clustering Technique, Unsupervised Learning

1. Introduction
Over the past decade, Data Centers (DC) have made considerable efforts to ensure energy
efficiency and reliability, and the size and stability of their facilities have been upgraded because of
the enormous increase in demand [1,2]. Currently, the amount of data to be processed is expanding
exponentially due to the growth of the information technology (IT) industry, advent of IoT, and AI
technologies. Consequently, new DC construction and smart DC management is on the rise to meet
this demand. If a data center experiences system failure or outage, it becomes challenging to ensure a
stable and continuous IT service provision (particularly smart businesses, social media, etc.). If such
a situation occurs on a large scale, it could lead to chaos to particularly the business sector and other
sectors (e.g. health, manufacturing, entertainment, etc…). In other words, a data center has emerged
as a mission-critical infrastructure [30] to the survival of businesses and other smart technologies
supported sectors. Therefore, it warrants a critical necessity for backup system management and
uninterruptible power supply (UPS) systems so that compute system stability can be maintained
even in emergency situations. DCs maintain their stability by having redundant power supply

© 2020 by the author(s). Distributed under a Creative Commons CC BY license.


Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

paths, including emergency generators, UPSs, etc. IT servers require uninterruptible supplies of not
only power but also cooling [3, 4]. For this purpose, in liquid cooling, central cooling systems are
designed and manage to allow for chilled water supply during cooling system outages by including
cooling buffer tanks for stable cooling of IT equipment. If the chillers are interrupted, the emergency
power and cooling system are activated, and then the chilled water is supplied again. Consequently,
the mission-critical facility management for the stable operation of DC leads to huge cost increases,
and careful reviews must be performed starting from the initial planning stage [5, 6]. Considering
that the number of times that such emergency situations occur during a DC life cycle is very small
and IT servers tolerance to various operational thermal environments has vastly improved
compared to that in the past due to the development of IT equipment, there is considerable room for
reducing the operating times and capacities of chilled-water storage tanks. Specifications of every IT
equipment are expressed as (but not limited to) different admissible ranges for temperature,
humidity, periods of overheating before automatic power off. Additionally, maintaining healthy
operational conditions is a complex task because IT devices might have different recommended
specifications for operation. Undeniably, covert factors such as bypass, recirculation, hotspots and
partial rack overheating could negatively affect the health of IT and power equipment that is critical
for efficient DC operations. For example, in the case where an IT room is divided into cold and hot
aisles, improper partitioning of the aisles may result in recirculation of hot air or cold air bypass [7].
Consequently, such emerging challenges call for the need for optimized thermal conditions within a
DC facility. Thermal management involves the reduction of excess energy consumption by cooling
systems, servers’ load processing, and their internal fans. It encompasses compliance of IT facility
environment to temperature requirements and standards that will inevitably result in reliability,
availability, and overall improved server performance. Thermal management in a DC could be the
primary contributor to IT infrastructure inefficiency due to hardware degradation and for this
reason, it is necessary to disperse dissipated waste heat so that there will be an even distribution of
waste heat within a premise to avoid overheating [31]. This work explores the thermal characteristics
analysis of an IT room (due to waste heat) using data mining techniques for the purpose of relevant
knowledge discovery. The primary goal is to use an unsupervised machine learning modelling
technique to uncover weaknesses in the DC cooling system based on real DC monitoring thermal
data. Analysis in this research leads to identification of areas for energy efficiency improvement that
will feed into DC recommendations. The proposed methodology includes statistical analysis of IT
room thermal characteristics, and identification of individual servers that frequently occur in the
hotspot zones. The reliability of the analysis has been enhanced due to the availability of big dataset
of ambient air temperature in the hot aisle of ENEA Portici CRESCO6 computing cluster. In brief,
clustering techniques have been used for hotspots localization as well as nodes categorization based
on surrounding air temperature ranges. The principles and approaches employed in this work are
replicable for energy efficiency evaluation of any DC and thus, foster transferability. This work
showcases applicability of best practices and guidelines in the context of a real commercial DC that
transcends the typical set of existing metrics for DC energy efficiency assessment.
The remainder of the paper is organized as follows: Section 1 is dedicated to introduction; Section 2
is focuses on background and discussion of Background and Related Work; Section 3 presents the
Methodology adopted for this work; Section 4 covers Results and Discussion; while Section 5
concludes the paper with future work.

2. Background and Related Work


In recent years, a small number of theoretical and practical studies have been conducted on DC
thermal management to understand the cooling systems under fault conditions, including system
thermal and energy performance, system distribution optimization, and simulation study. Thermal
management involves the reduction of excess energy consumption by cooling systems, servers’ load
processing, and their internal fans. It encompasses compliance of IT facility environment to
temperature requirements and standards that will inevitably result in reliability, availability, and
overall improved server performance. Existing data center-related thermal management research:
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

highlight the primary challenges of cooling high power density DCs [8]; recommend a list of thermal
management strategies based [9]; experiment the effect of a cooling approach on PUE, using direct
air with a spray system that evaporates water to cool as well as humidify incoming air [10];
investigate thermal performances of air-cooled data centers with raised and non-raised floor
configurations [11] and quantification of thermos-fluid processes through performance metrics [12];
propose a thermal model for joint cooling and workload management [13] while [14] explore
thermal-aware job scheduling, dynamic resource provisioning and cooling; utilise real thermal
information about servers, inlet/outlet air temperature, air mover speed to create thermal and power
maps to monitor the real-time status of a data center [15]. Majority of the previously listed research
focuses on simulations or numerical modelling [9-14], empirical research involving R&D or small
scale data center [10, 15] and thus there is a need for more empirical research involving real relevant
thermal-related data for big scale data centers. Undeniably, it is tremendously beneficial to identify
hotspots and air dynamics (particularly negative effects) within a DC IT room. Such useful
evidence-based information will help DC operators improve their DC thermal design and ensure
uninterrupted steady compute system operations. Additionally, it will be an added value if thermal
management related research adheres to [16] recommended thermal management framework at
varying granularity of DCs. Thermal metrics have been created by the research and enterprise DC
community to facilitate DC thermal management [7]. The employment of metrics aims to reveal the
underlying causes of thermal-related challenges within a DC IT room and to assess the overall
thermal conditions of the room. Finally, [28] proposes a holistic data centre assessment method
based on biomimicry by integrating data on energy consumption for powering and cooling ICT
equipment. This research work focuses on the analysis of a DC IT room thermal characteristics
analysis with machine learning techniques to uncover ways to render a more effective cooling
system as well as ways to effect even distribution of server waste heat within a DC.
This work focuses on the identification of individual servers in an IT room of a DC cluster that
frequently occurs in the hotspot zones applying a clustering algorithm to an available dataset with
thermal characteristics of ENEA Portici CRESCO6 computing cluster. This paper represents the
completion of the previous authors' work [7, 17, 18, 19, 20, 21, 31] in terms of exploring the intricacies
of deploying the theoretical framework applied in a real DC. Appropriate data analytics techniques
have been based on real server-level sensors data to identify potential risks caused by the possible
presence of negative covert factors related to the cooling strategy. This work is based first of all on
the statistical analysis of available real thermal data and to provide a complete thermal characteristic
analysis through machine learning techniques. However, ML has been generally employed for VM
allocation, global infrastructure management, prediction of electricity consumption and availability
of renewable energy [22]. Thus far, there is work on ML for thermal characteristics assessment and
weather conditions prediction but only limited work on thermal management. Typically,
Computational Fluid Dynamics (CFD) techniques have been employed for the exploration of DC
thermal management. Their drawbacks are high computational power and memory requirements.
Therefore, the added value of this research is utilization of less power demanding techniques for
thermal characteristics analysis (i.e. namely, hotspot localization).
Additionally, this paper aims to increase DC thermal awareness and provide recommendations for
thermal management based on the study of thermal characteristics of DC IT room environment and
IT equipment energy consumption of ENEA Portici CRESCO6 cluster using real monitored thermal
data. This work exploits machine learning analysis of IT room thermal characteristics. To achieve
this aim, the following research objectives are addressed:

RO.1. To identify the clustering (grouping) algorithm that is appropriate for the purpose of this
research;
RO.2. To determine the criteria for features selection in cluster analysis of the thermal
characteristics;
RO.3. To determine the optimal number of clusters for thermal characteristics analysis;
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

RO.4. To perform sequential clustering and interpretation of results for repeated time series
clustering;
RO.5. To identify the IDs of servers that most frequently occur in clusters of colder and hotter
zones;
RO.6. To provide recommendations related to the thermal management of the IT room
appropriately address servers overheating resulting in local hotspots related issues.

3. Methodology
This section discusses the thermal characteristics analysis of ENEA cluster, CRESCO 6. A
Machine Learning clustering technique is chosen for a more in-depth analysis of hotspots
localization based on available dataset of CRESCO6 nodes temperature measurements. The
drawback of this the analysis of temperature measurements is that it could not pinpoint specific
nodes which cause rack hotspots. Hence, to address this gap, we have applied Machine Learning
techniques for node clustering to localize hotspots. Locating hotspots in the CRESCO6 group of
nodes (the term “group of nodes” stands for the DC “cluster” and note this term is not used to avoid
its confusion with clusters of data) is achieved through grouping of sequential sets of nodes into
clusters with higher or lower hot aisle and internal server temperatures.

3.1. Cluster and Dataset Description


The analysis is based on collected data related to server power consumption and ambient air
temperature of the CRESCO6 cluster in ENEA-Portici Research Center premises (up and running
since summer 2018). The cluster was created due to the growing demand for research center
computational and analytic activities as well as the general motivation to keep abreast with current
modern technologies. The High-Performance Computing cluster CRESCO6 has the nominal
computing power of around 1,4 PFLOPS (1000 TFLOPS the result obtained on High-Performance
Computing Linpack Benchmark, a computational power test that performs parallel calculations on
dense linear systems with 64bit precision). It complements the CRESCO4 HPC system, already
installed and still operating in the Portici Research Center, with nominal calculation powers of 100
TFLOPS. CRESCO6, on its own, provides an increase equal to a factor x7 of the entire computing
capability currently available for computational activities in the ENEA research center. The cluster
comprises 418 Lenovo nodes with FatTwinTM 2U form factor, housed in a total of 5 racks. Each node
houses two Intel® Xeon® Platinum 8160 CPUs, each with 24 cores and operating at a frequency
clock of 2.1 GHz, for a total of 20,064 cores. Each node also houses an overall RAMof 192 GB,
equivalent to 4 GB/core. Finally, the nodes are interconnected by an Intel® Omni-Path network with
15 switches of 48 ports each, bandwidth equal to 100 Gb/s, latency equal to 1 s. CRESCO6 could
satisfy the needs of high scalability in the execution of parallel codes. This resource is aimed to
support Research and Development activities in ENEA Research Center. In the last ten years,
CRESCO HPC system has enabled and supported ENEA participation in national and international
projects in various technological sectors which range from bio-informatics to structural biology with
effects in the medical and environmental fields, from the design of new materials to fluid dynamics
with relapses in different energy sectors (e.g., photovoltaic, nuclear, energy from the sea,
combustion). Furthermore, thanks to the availability of the CRESCO infrastructure, ENEA is a
partner of the European Center of Excellence EoCoE (Energy oriented Center of Excellence), Focus
CoE (Center of Excellence) projects: one of eight Centers for HPC applications financed by the
Horizon2020 program. EoCoE intends to contribute to accelerating the transition to a carbon-free
economy by exploiting the growing computational power of HPC infrastructures. Apart from
enhanced hardware, improvement has also been made to the monitoring system of the new cluster.
It comprises energy and power meters, temperature and airflow sensors and fans speed registration.
Measurements were taken throughout the period from cluster initialization and performance tuning
in the months of May-July 2018 to the months of cluster utilization by end-users in September
2018-February 2019 for approximately 9 months in total with a break in the month of August 2018 as
represented in Figure 1. The measurement system covered all 216 nodes, out of which 214-215 nodes
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

were consistently monitored, and other 1-2 nodes had missing values or were turned off. The
monitoring the system consisted of energy meter, power meter of CPU, RAM and the entire IT
system utilization of every node, CPU temperature for both processing units of each node with
thermal sensors installed inside the servers, inlet and exhaust in cold and hot aisle respectively
placed in the front and rear parts of every node.

Figure 1. Period of available measurements data in May-December 2018 and January-February 2019

3.1. Data Analytics


Data analytics encompasses the investigation on temperature variation in different parts of the
IT room and evaluation of thermal metrics. However, the variability of thermal data and
uncertainties in defining temperature thresholds for hotspots (identified via statistical analysis) has
invoked a need for unsupervised learning. Therefore, a K-means clustering algorithm has been
employed to address the limitations of typical statistical techniques. With Machine Learning
techniques, the number of clusters is determined using two indices (Silhouette metric and
Within-Cluster Sum of Squares), and available thermal characteristics (i.e. exhaust temperature,
CPUs temperatures) are inputs to a clustering algorithm. Subsequently, a series of clustering results
are intersected to unravel nodes (identified by IDs) that frequently fall into high-temperature areas
of the cluster racks. As depicted in Figure 2, an adapted data lifecycle methodology has been
employed for this work. The methodology comprises stages of data preprocessing, data analysis as
well as results interpretation and exploitation in the form of recommendations for the DC.

Figure 2. Data Analytics lifecycle methodology adapted to sequential clustering based on DC


thermal characteristics.

Figure 2 also depicts substages of this work: Data Analysis Sequential Clustering involves the
Machine Learning clustering techniques (K-Means clustering) for a deeper analysis of hotspots
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

localization and applied to the dataset of CRESCO6 nodes temperature measurements. All data
analytics stages represented in the Figure 2 are described in detail below.
Data preprocessing step consists of data cleansing and data set organization. This data set is
cleansed of zero and missing values. It is organized as shown in Table 1. This table summarizes both
the results of monitoring of the overall number of nodes in CRESCO6, N. In addition, data
preprocessing involves timestamps, user information formatting for further exploitation. The system
is configured so that with an interval of around 15 minutes, the monitoring system records the
thermal and other measured data for every node with a slight latency between each node readings.
The readings result in a set of N rows with information for every node ID. As shown in Table 1, data
preprocessing, includes extracting important thermal data features and removing direly incomplete
or erroneous data. The Data Analysis stage includes several substages. In the Data Analysis stage,
sequential clustering involves the following: determining the optimal number of clusters (done with
the use of two indices); actual clustering of servers into groups with low, medium and high
surrounding air temperature ranges; and consolidation of results to ascribe the most frequently
occurred cluster label for each server (i.e. low, medium or high). The analysis is based on the
aforementioned data preprocessing step, Table 1. Clustering is performed M times, where M is the
overall number of time labels at which measurements are taken from all cluster nodes. Each new set
of monitoring system readings is labelled with a time label. The exact timestamp for the extracted
information is marked with for every node l. Depending on the available dataset, a number of
relevant features describe the state of every node and their different combinations can be used as a
basis for clustering (RO.2 will be more considered in detail in Section 3).

Time Real Node Inlet T°C Exhaust CPU 1 CPU 2 T°C Cluster
Label Time ID T°C T°C label

𝑡1 + 𝑡1𝑛1 𝑛1 𝑇𝑖𝑛11 𝑇𝑒𝑥ℎ11 𝑇𝐶𝑃𝑈111 𝑇𝐶𝑃𝑈211 𝐶1 𝑏𝑎𝑠𝑒𝑟𝑎𝑛𝑔𝑒

𝑡1 … … … … … … …

𝑡1 + 𝑡1𝑛𝑁 𝑛𝑁 𝑇𝑖𝑛1𝑁 𝑇𝑒𝑥ℎ1𝑁 𝑇𝐶𝑃𝑈11𝑁 𝑇𝐶𝑃𝑈2𝑠1𝑁 𝐶1 𝑏𝑎𝑠𝑒𝑟𝑎𝑛𝑔𝑒


𝑇𝑖𝑛21 𝑇𝑒𝑥ℎ21 𝑇𝐶𝑃𝑈121 𝑇𝐶𝑃𝑈221 𝐶2 𝑏𝑎𝑠𝑒𝑟𝑎𝑛𝑔𝑒
𝑡2 + 𝑡2𝑛1 𝑛1

𝑡2 … … … … … …

𝑡2 + 𝑡2𝑛𝑁 𝑇𝑖𝑛2𝑁 𝑇𝑒𝑥ℎ2𝑁 𝑇𝐶𝑃𝑈12𝑁 𝑇𝐶𝑃𝑈2𝑠2𝑁 𝐶2 𝑏𝑎𝑠𝑒𝑟𝑎𝑛𝑔𝑒


𝑛𝑁

Table 1. Dataset using for clustering analysis.

In Table 1, in the last column, base is an indicator of one of the three combinations of
measurements used as the basis for clustering and corresponds to the temperature of the cluster
centroid. In this work, the K-Means algorithm is chosen for clustering the nodes for several reasons
(RO.1):
- The number of features used for clustering is small. Therefore, the formulated clustering
problem is simple and does not require complex algorithms;
- K-Means has linear computational complexity which renders it fast to use for the type of
problem in question. While the formulation of the problem is simple, it requires several
thousands of repetitions of clustering for each set of N nodes. From this point of view, the
speed of the algorithm becomes an influential factor;
- K-Means has a weak point, namely random choice of initial centroids, which can lead to
different results when different random generators are used. This does not pose any issue in
this use case since the nodes are clustered several times based on sets of measurements taken
at different timestamps and minor differences brought by randomness is mitigated by the
repetition of the clustering procedure.
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

The number of clusters K, i.e. number of ranges for Ci baserange , is an unknown parameter which is
estimated for each of the three combinations separately using two metrics: average Silhouette
Coefficient and Within Cluster Sum of Squares (WCSS) metric [91], [92] (RO.3). The methods of these
two indices application are shown in Appendix A. In brief, Silhouette coefficient is computed for each
clustered sample and shows how much the clusters are isolated from each other or the quality of
clustering. The +1 value of Silhouette index for a specific number of clusters K indicates the high
density of clusters, -1 shows incorrect clustering; and 0 stands for overlapping clusters. Therefore, we
focus on local maxima of this coefficient. WCSS is used in the Elbow method of determining the
number of clusters and is used here to support the decision obtained from Silhouette coefficient
estimation. It measures the compactness of clusters, and the optimal value of K is the one that results in
the “turning point” or an “elbow” of the WCSS(K) graph. In other words, increasing the number of
clusters after reaching the elbow point does not result in significant improvement of clusters
compactness. Although it could be argued that other indices could be additionally used for
determining the number of clusters, the combination of the two aforementioned methods has
converged on the same values of K, which is assumed to be sufficient for this current research. Once
the optimal number of clusters is obtained, actual clustering is performed for the chosen bases. For
every cluster base, we further examine how frequently every node is assigned to each cluster and
deduce the final cluster label as one of Cbaserange and corresponding sets of nodes as Nbaserange .
Subsequently, sets of nodes in the hot range for every cluster base are intersected to unravel nodes that
are clustered to be in “danger” or hot zone with the highest frequency by three clustering algorithms:
Nhot = ⋂bases {Nbasehot range } (RO.4). The next section will discuss results of this clustering procedure
and list the nodes that fall in the hot zone.

4. Results and Discussions

High-granularity Analysis of this work has considered temperature ranges of the surrounding air
of individual servers to identify and localize frequently overheated servers. A machine learning
technique, K-Means clustering, has been applied to sequential sets of thermal measurements for all the
cluster servers. To reiterate, before clustering, the number of possible clusters has been evaluated with
the use of two methods: Within-Cluster Sum of Squares and Silhouette index. Sequential clustering has
been performed several times with different combinations of measured data. For every combination of
measured thermal data, the results of servers clustering into cold, medium and hot temperature ranges
have been further analyzed to calculate the frequency of occurrences of each node in each cluster and
determine their final frequency label (i.e. cluster label or temperature range). These labels are further
intersected for labels obtained with different bases. Sequential clustering is further performed for each
set of N=216 samples based on three combinations of available thermal data: exhaust (base 1), CPU
(base 2), exhaust and CPU temperature measurements (base 3) (RO.2). The full dataset consists of
M=15569 sets of temperature monitoring data where each set consists of 216 node samples with data
from sensors installed in different locations: in the front (inlet), rear (exhaust) of every node and two
sensors inside each node (CPU temperature). The optimal number of clusters depends on the base
chosen for clustering. Two metrics are computed for random sets to be clustered. Their visualization
can be found in Appendix A. Identified optimal number of clusters K is 3, 5 and 3 for bases 1-3
(exhaust, CPU, exhaust and CPU measurements), which are used in sequential clustering with these
bases.
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

Figure 2. Proportion of nodes clustered into different temperature ranges based on (a) Exhaust temperature, (b)
Exhaust and CPU temperature, (c) CPU temperature

During sequential clustering, each node has been labelled with a certain temperature range cluster.
Since clustering is repeated for each set of measurements grouped by time label, every node is
clustered several times and tagged with different labels while the algorithm is in progress (RO.4).
Figure. 2 (a-c) shows the frequency of occurrence of every node in a particular cluster based on
available measurements and clustering algorithm. This information indirectly implies “duration” of a
particular node exists in a certain temperature range (see legend in Figure 2 (a-c)). Here, the majority of
the nodes frequently occur in the medium temperature range for all cluster bases. However, some
nodes remain in the hot range for more than 50% of clustering cases. When nodes remain in the hot
range for a prolonged period or frequently fall in this range, it implies that they are overheated.
Consequently, this brings about hardware degradation where the nodes have reduced reliability and
accessibility as they automatically switch to lower power mode when overheated. Therefore, we
continue with the analysis to identify the actual node IDs that have most frequently been clustered
within the hot ranges. Table 2 provides an insight into the ratio of nodes with the highest frequency of
occurrences in cold, medium or hot range (RO.5). Depending on the cluster base, 50 to 86% of all nodes
have the highest frequency of occurrence in the medium range. The hot range encompasses 11-37% of
all nodes, and only 0.5-4% have been clustered within the cold range. Finally, to cross-validate the
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

clustering, we have taken the intersection of nodes clustered into cold, medium and hot ranges. Only
one node (or 0.5% of all nodes) has been clustered in the cold range for all three bases algorithms; the
medium-range has the highest intersection range while 8% (or 18 nodes) are captured in the hot range.
The principle result of this analysis is the identification of the hot range node IDs, and this could be
exploited by DC operators to improve thermal conditions in the cluster IT room. Possible solutions
could comprise nodes localization in the room, upgrading the cooling system to directional cooling
with pumps that could push cold air to the hottest nodes in addition to existing natural convection
approach, and improving load scheduling to avoid overloading and overheating of identified nodes.

𝑵𝒆𝒙𝒉𝒄𝒐𝒍𝒅 𝑵𝒆𝒙𝒉𝒎𝒆𝒅 𝑵𝒆𝒙𝒉𝒉𝒐𝒕


Ratio, % 2.8 86.0 11.2
𝑵𝑪𝑷𝑼𝒄𝒐𝒍𝒅 𝑵𝑪𝑷𝑼𝒎𝒆𝒅𝟏 𝑵𝑪𝑷𝑼𝒎𝒆𝒅𝟐 𝑵𝒆𝒙𝒉𝒉𝒐𝒕𝟏 𝑵𝒆𝒙𝒉𝒉𝒐𝒕𝟐
Ratio, % 4.2 20.0 28.4 31.2 16.2
𝑵𝒆𝒙𝒉_𝑪𝑷𝑼𝒄𝒐𝒍𝒅 𝑵𝒆𝒙𝒉_𝑪𝑷𝑼𝒎𝒆𝒅 𝑵𝒆𝒙𝒉_𝑪𝑷𝑼𝒉𝒐𝒕
Ratio, % 2.0 63.0 35.0
𝑵𝒄𝒐𝒍𝒅 𝑵𝒎𝒆𝒅 𝑵𝒉𝒐𝒕
Ratio, % 0.5 40.0 8.0
30, 31, 32, 45, 46, 48, 68,
Hot Range
- - 79, 94, 96, 105, 117, 118,
Node ID
120, 182, 183, 189, 198

Table 2. . Ratio of cluster sizes and intersection of node labels from three bases.

The present work has contributed to thermal characteristics analysis of the DC cluster addressing an
issue of hotspots. It has two positive effects in terms of sustainability. Firstly, being a thermal design
pitfall, hotspots impose a risk of local overheating and deterioration of servers exposed to high
temperature for prolonged periods. In this regard, localization of hotspots is crucial for better
overview and control of the IT room temperature distribution. It provides a direction of future
thermal management improvements that would mitigate the mentioned risk. Secondly, a clustering
technique used in this phase requires less computational resources than computational fluid
dynamics modelling and/or simulations performed on existing simulation packages. Such models
provide an overview of the entire IT room ambient temperature distribution, whereas racks and
their immediate proximity limit the area of interest. Therefore, with less computational power (and
thus energy consumption) analysis techniques of this phase have brought about sufficient
information to incentivize improvement of thermal conditions in data centers. Finally, the results
infer that the majority of the servers operated in the medium and hot temperature ranges. Given that
8% of all cluster servers have been labelled as most frequently hot range nodes, a list of
recommendations is suggested below to address the issue of hotspots (RO.6).
The proposed methodology for IT room thermal characteristics assessment of an air-cooled DC
cluster (located in the region where free air cooling is unavailable) comprises:
- Locate nodes by identified hot range IDs and find possible underlying patterns in
overheated nodes (e.g. position in the rack, and proximity to the PDUs);
- Tune load sharing so that these ‘hot’ nodes are not overloaded in the future;
- Add directional cooling, for example, spot cooling;
- Continue monitoring IT room thermal conditions in the immediate proximity of the nodes
to evaluate the effectiveness of recommended actions and their effects on IT room
temperature.
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

4. Conclusion
Analysis of IT and cooling systems is necessary for the investigation of DC operations-related
energy efficiency. A reliable cooling system is essential to produce a persistent flow of cold air to cool
the servers due to increasing demand on computational load. Energy efficiency has been addressed in
this work from the point of thermal characteristics analysis of an IT room. In particular, a machine
learning technique applied to a real DC monitoring data has resulted in the identification of areas for
energy efficiency improvement that feed into appropriate DC recommendations. The research
methodology discussed in this paper, includes statistical analysis of IT room thermal characteristics,
thermal metrics evaluation. and the identification of individual servers that frequently occur in the
hotspot zones (using a machine learning algorithm). Clustering techniques are used for effective
hotspots localization as well as categorization of nodes based on surrounding air temperature ranges.
This methodology has been applied to available big dataset with thermal characteristics of ENEA
Portici CRESCO6 computing cluster. The concepts covered in this work are useful for energy efficiency
evaluation of any DC and ensures a high degree of transferability. This work showcases applicability
of best practices and guidelines to a real DC and goes beyond the set of existing metrics for DC energy
efficiency assessment.

Acknowledgments: In this section you can acknowledge any support given which is not covered by the author
contribution or funding sections. This may include administrative and technical support, or donations in kind
(e.g., materials used for experiments). EMJMD PERCCOM Project [29]. Moreover, the authors would like to
express their gratitude to the research HPC group at the ENEA-R.C. Portici for the useful advice on modelling
and control of ENEA-Data Center.

Appendix A

A number of clusters could be determined employing several approaches that are currently
used widely by data scientists. However, none of them is considered accurate as they merely
provide an approximate value. This work utilizes two methods: Within Cluster Sum of Squares
(WCSS) or an elbow method, and average Silhouette Index. These indices are computed for a range
of cluster numbers K and an optimal value is then chosen based on the indices’ values. WCSS is a
measure of the cluster’s compactness, and it calculates as follows:

𝐾
2
𝑊𝐶𝑆𝑆(𝐾) = ∑ ∑ ‖𝑥 − 𝜇𝑗 ‖ , (1)
𝑗=1 𝑥∈𝐶𝑗

Where K is the number of clusters, C is a set of clusters (C1, C2, …Cj), is the cluster, and µj denotes a
particular cluster sample mean. WCSS should be minimized and, in practice, an optimal value is a
turning point of the graph where the rate of WCSS decrease slows down or an elbow of the graph.
The method is based on the idea that increasing the number of clusters after the turning point or an
elbow is not meaningful since WCSS decreases only slightly and the positive impact of every next is
low. In the Average Silhouette method, a Silhouette index is computed for every data point (or every
member of every cluster) and then is averaged over all data points. It estimates consistency of the
data within clusters and should be maximized for better separation of the clusters. The Silhouette
index is calculated for every data point as follows:

𝑏(𝑖) − 𝑎(𝑖)
𝑠(𝑖) = , (2)
𝑚𝑎𝑥{𝑏(𝑖), 𝑎(𝑖)}
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

Where, a is the mean intra cluster distance (i.e. mean distance between a data point and all other
points in the same cluster), while b is the mean nearest cluster distance (i.e. distance between a
sample and all other points in the next nearest cluster). Example of these indices utilization is shown
in Figure 3. for one step of sequential clustering based on the exhaust air temperature. The optimal
elbow point of WCSS is =3 and the same for Silhouette index local maximum.

Figure 3. a) WCSS estimation for clustering based on exhaust temperature; b) Average Silhouette
Index estimation for clustering based on exhaust temperature.

References
1. Hashem, I.A.T., Chang, V., Anuar, N.B., Adewole, K., Yaqoob, I.,Gani, A., et al. The role of big data in
smart city. International Journal of Information Management 2016; 36(5):748–758.
2. Zhang, K.; Zhang, Y.; Liu, J.; Niu, X. Recent advancements on thermal management and evaluation for
data centers. Appl. Therm. Eng. 2018, 142, 215–231.
3. Nadjahi, C.; Louahlia, H.; Lemasson, S. A review of thermal management and innovative cooling
strategies for data center. Sustain. Comput. Inf. Syst. 2018, 19, 14–28.
4. ASHRAE, Data Center Power Equipment Thermal Guidelines and Best Practices. Tech. Rep; 2016.
5. Hartmann, B.; Farkas, C. Energy efficient data centre infrastructure—Development of a power loss model.
Energy Build. 2016, 127, 692–699.
6. He, Z.; Ding, T.; Liu, Y.; Li, Z. Analysis of a district heating system using waste heat in a distributed
cooling data center. Appl. Therm. Eng. 2018, 141, 1131–1140.
7. Capozzoli, A., Serale, G., Liuzzo, L., Chinnici, M.., Thermal Metrics for Data Centers: A Critical Review.
Energy Procedia, 2014; 62:391–400.
8. Bash, C.E., Patel, C.D., Sharma, R.K.. Efficient thermal management of data centers—immediate and
long-term research needs. HVAC&R Research 2003;9(2):137–152.
9. Zhang, K., Zhang, Y., Liu, J., Niu, X.. Recent advancements on thermal management and evaluation for
data centers. Applied Thermal Engineering 2018;142:215 – 231.
10. Fredriksson, S., Gustafsson, J., Olsson, D., Sarkinen, J., Beresford, A., Käufeler, M., et al. Integrated thermal
management of a 150kw pilot open compute project style data center. In: 2019 IEEE 17th International
Conference on Industrial Informatics (INDIN) 2019,vo.l, p. 1443–1450.
11. Srinarayana, N., Fakhim, B., Behnia, M., Armfield, S.W.., Thermal performance of an air-cooled data center
with raised floor and non-raised-floor configurations. Heat Transfer Engineering 2014;35(4):384–397.
12. Schmidt, R.R., Cruz, E.E., Iyengar, M.. Challenges of data center thermal management. IBM Journal of
Research and Development 2005;49(4.5):709–723.
13. Mirhoseini Nejad, S., Moazamigoodarzi, H., Badawy, G., Down, D.G.. Joint data center cooling and
workload management: A thermal-aware approach. Future Generation Computer Systems 2020; 104:174-186.
040.
14. Fang, Q., Wang, J., Gong, Q., Song, M.. Thermal-aware energy management of an hpc data center via
two-time-scale control. IEEE Transactions on Industrial Informatics 2017;13(5):2260–2269.
15. Zhang, S., , Zhou, T., , Ahuja, N., , Refai-Ahmed, G., , Zhu, Y., , Chen, G., , et al. Real time thermal
management controller for data center. In: Fourteenth Intersociety Conference on Thermal and
Thermomechanical Phenomena in Electronic Systems (ITherm). 2014, p. 1346–1353.
Preprints (www.preprints.org) | NOT PEER-REVIEWED | Posted: 15 July 2020 doi:10.20944/preprints202007.0325.v1

Peer-reviewed version available at Energies 2020, 13, 4378; doi:10.3390/en13174378

16. Sharma, R.K., Bash, C.E., Patel, C.D., Friedrich, R.J., Chase, J.S.. Balance of power: dynamic thermal
management for internet data centers. IEEE Internet Computing 2005;9(1):42–49.
17. Capozzoli, A., Chinnici, M., Perino, M., Serale, G.. Review on performance metrics for energy efficiency in
data center: The role of thermal management. Lecture Notes in Computer Science (including subseries
Lecture Notes in Artificial Intelligence and Lecture Notes in Bioinformatics) 2015;8945:135–151.
18. Grishina, A., Chinnici, M., De Chiara, D., Guarnieri, G., Kor, A.L., Rondeau, E., et al. DC Energy Data
Measurement and Analysis for Productivity and Waste Energy Assessment. In: 2018 IEEE International
19. Conference on Computational Science and Engineering (CSE). Bucharest, Romania: IEEE. ISBN
978-1-5386-7649-3; 2018, p. 1– 11.
20. Grishina, A., Chinnici, M., De Chiara, D., Rondeau, E., Kor, A.L.. Energy-Oriented Analysis of HPC
Cluster Queues: Emerging Metrics for Sustainable Data Center. Applied ph ed. Dubrovnik, Croatia:
Springer; 2019, p. 286–300.
21. Grishina, A., Chinnici, M., Kor, A.L., Rondeau, E., Georges, J.P., De Chiara, D.. Data Center for Smart
Cities: Energy and Sustainability Issue. Chapter book In: Pop, F., editor. Big Data Platforms and Applications
- Case Studies, Methods, Techniques, and Performance Evaluation; Springer; 2020.
22. Athavale, Jayati, Minami Yoda, and Yogendra Joshi., Comparison of data driven modeling approaches for
temperature prediction in data centers, International Journal of Heat and Mass Transfer, 135 (2019): 1039-1052.
23. L. Kaufman and P. J. Rousseeuw, Finding Groups in Data: An Introduction to Cluster Analysis. Hoboken,
NJ, USA: John Wiley & Sons, Inc., 1990.
24. A. Kassambara, Determining The Optimal Number Of Clusters: 3 Must Know Methods, [Online].
Available:https://www.datanovia.com/en/lessons/determining-the-optimal-number-of-clusters-3-must-kn
ow-methods/. [Accessed: 06-May-2019].
25. Chinnici, M., Capozzoli, A., Serale, G.. Measuring energy efficiency in data centers. In: Pervasive
Computing: Next Generation Platforms for Intelligent Data Collection; chap. 10. ISBN 9780128037027; 2016, p.
299–351.
26. Quintiliani, A., Chinnici, M., De Chiara, D.. Understanding workload-related metrics for energy efficiency
in Data Center. In: 2016 20th International Conference on System Theory, Control and Computing (ICSTCC).
Sinaia, Romania: IEEE. ISBN 978-1- 5090-2720-0; 2016, p. 830–837.
27. Chinnici, M., Chiara, D.D., Quintiliani, A. Data Center, a Cyber-Physical System: Improving Energy
Efficiency Through the Power Management. In: DASC/PiCom/DataCom/CyberSciTech. Orlando, FL, USA:
IEEE. ISBN 978-1-5386-1956-8; 2017, p. 269– 272.
28. S. Kubler, E. Rondeau, J.P Georges, P. Lembi Mutua, M. Chinnici, Benefit-Cost model for
comparing data center performance from a Biomimicry perspective, Journal of Cleaner
Production, Vol 231, 817-834, 10 Sept 2019.
29. A.L. Kor, E. Rondeau, K. Andersson, J. Porras, J.P. Georges, Education in Green ICT and Control
of Smart Systems: A First Hand Experience from the International PERCCOM Masters
Programme, 12th Symposium on Advances in Control Education (ACE 2019), 7-9 July 2019,
Philadelphia, USA.
30. https://www.datacenterknowledge.com/industry-perspectives/critical-look-mission-critical-infrastructure
31. D. De Chiara, M. Chinnici, AL Kor, Data Mining for Big Dataset-Related Thermal Analysis o
High Performance Computing (HPC) Data Center, Computational Science – ICCS 2020 pp 367-381,
Ed. Springer, 2020