S7-400 and M7-400 Module Specifications
S7-400 and M7-400 Module Specifications
RS 485 Repeater
11
M7-400 Expansions
14
Interface Submodules
15
Cycle and Reaction Times
of the S7-400
16
Appendices
Danger
! indicates that death, severe personal injury or substantial property damage will result if proper precau-
tions are not taken.
Warning
! indicates that death, severe personal injury or substantial property damage can result if proper precau-
tions are not taken.
Caution
! indicates that minor personal injury or property damage can result if proper precautions are not taken.
Note
draws your attention to particularly important information on the product, handling the product, or to a
particular part of the documentation.
Qualified Personnel
Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are
defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and sys-
tems in accordance with established safety practices and standards.
Correct Usage
Note the following:
Warning
! This device and its components may only be used for the applications described in the catalog or the
technical descriptions, and only in connection with devices or components from other manufacturers
which have been approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed cor-
rectly, and operated and maintained as recommended.
Trademarks
SIMATIC, SIMATIC HMI and SIMATIC NET are registered trademarks of SIEMENS AG.
Some of other designations used in these documents are also registered trademarks; the owner’s rights
may be violated if they are used by third parties for their own purposes.
Also listed in conjunction with the general technical specifications are the
standards and test values that the modules of the S7-400/M7-400 system conform
to and fulfill as well as the test criteria in accordance with which the
S7-400/M7-400 systems have been tested.
Approvals
• UL Recognition Mark
Underwriters Laboratories (UL) in accordance with Standard UL 508:
– Report E 85972
– Report 143289 for the modules in Table 1-1
• CSA Certification Mark
Canadian Standard Association (CSA) in accordance with Standard C 22.2
No. 142:
– Report LR 63533
– Report 111 879 for the modules in Table 1-1
• Factory Mutual Approval Standard Class Number 3611, Class I, Division 2,
Group A, B, C, D.
Temperature class: T4 at 60 °C ambient temperature
Exception: The following applies for the power supply modules in Table 1-1:
Temperature class T3C at 60 °C ambient temperature
Temperature class T4 at 40 °C ambient temperature
In the case of the modules in Table 1-1 the T4 temperature class is achieved for
the whole system if the ambient temperature does not exceed 40 °C during
operation.
Special requirements should also be observed which you can fulfill, for
example, by mounting the system in cabinets.
Warning
! Personal injury or property damage can result.
In hazardous areas, personal injury or property damage can result if you create or
break an electrical circuit during operation of an S7-400/M7-400 (for example, by
means of plug-in connections, fuses, switches).
Do not create or break live electric circuits unless you are certain there is no
danger of explosion.
Warning
! WARNING - DO NOT DISCONNECT WHILE CIRCUIT IS LIVE
UNLESS LOCATION IS KNOWN TO BE NON-HAZARDOUS.
CE Marking
SIMATIC products fulfill the requirements of the following EU directives.
EMC Directive
SIMATIC products meet the requirements of EU directive 89/336/EEC
“Electromagnetic Compatibility”.
SIMATIC products are intended for industrial use.
Low-Voltage Directive
The products listed below fulfill the requirements of EU directive 73/23/EEC
“Low-Voltage Directive”. Adherence to this EU directive was tested in accordance
with IEC 61131-2.
Declaration of Conformity
In accordance with the above-mentioned EU directive, the EU declarations of
conformity are held at the disposal of the competent authorities at the address
below:
Siemens Aktiengesellschaft
Bereich Automatisierungs- und Antriebstechnik
A&D AS E42
Postfach 1963
D-92209 Amberg
Introduction
All the components of the S7-400/M7-400 systems meet the requirements of the
standards in force in Europe provided they are installed in accordance with all the
appropriate regulations (see Installation Manual, Chapters 2 and 4).
Warning
! Installation of expansions that have not been approved for the S7-400/M7-400 can
result in violations of the requirements and regulations for safety and
electromagnetic compatibility.
Use only expansions that have been approved for the system.
This section contains information on the noise immunity of the modules of the
S7-400/M7-400 system as well as notes on the execution of radio interference
suppression measures.
Pulse-Like Interference
Table 1-2 shows the EMC response of the modules of the S7-400/M7-400 system
to pulse-like interference.
Note
Cables for data and analog signals must be shielded.
Cables for digital signals can be unshielded.
Table 1-2 EMC Response of the Modules of the S7-400/M7-400 Systems to Pulse-Like Interference
Pulse-Like Interference Test Voltage Corres-
ponds to
Severity
Level
Electrostatic discharge Discharge to air: ±8 kV
3
in accordance with IEC 61000-4-2 Contact discharge: ±6 kV
Bursts (fast transient interference in accordance 2 kV (power supply line)
with IEC 61000-4-4) 2 kV (signal line > 10 m) 3
1 kV (signal line > 10 m)
High-energy single pulse (surge) in accordance with IEC 61000-4-5 3
• Asymmetrical coupling 2 kV (supply line) DC voltage with
protective elements
2 kV (signal line/data line) > 10 m only,
possibly with protective elements
• Symmetrical coupling 1 kV (supply line) DC voltage with
protective elements
1 kV (signal line) > 10 m only, possibly
with protective elements
Sinusoidal Interferences
Table 1-3 shows the EMC response of the modules of the S7-400/M7-400 systems
to sinusoidal interference.
Table 1-3 EMC Response of the Modules of the S7-400/M7-400 Systems to Sinusoidal Interference
In accordance with IEC 61000-4-3 10 V/m with 50 % pulse modulation at 900 MHz
HF interference on cables and cable Test voltage 10 V with 80 % amplitude
shields in accordance with modulation of 1 kHz in the range 9 kHz to 3
IEC 61000-4-6 80 MHz
Additional Measures
If you want to connect an S7-400 or M7-400 system to the public line supply, you
must ensure limit value class B in accordance with EN 55022. Suitable additional
measures must be taken, if you need to enhance the noise immunity of the system
as a result of high external noise levels.
Permissible range
Free fall ≤ 1 m (up to 10 kg)
Temperature –40 °C to +70 ° C
Atmospheric pressure 1080 to 660 hPa (corresponds to a height of -1000 to
3500 m)
Relative humidity (at +25 °C) 5 to 95 %, without condensation
Sinusoidal vibrations in accor- 5 to 9 Hz: 3.5 mm
dance with IEC 60068-2-6 9 to 500 Hz: 9.8 m/s2
Shock in accordance with 250 m/s2, 6 ms, 1000 shocks
IEC 60068-2-29
Warning
! Improper handling of backup batteries can cause injury and material damage.
Wrongly handled backup batteries can explode or cause serious burns.
Please observe the following rules when handling the backup batteries used in the
S7-400/M7-400 systems:
• Never recharge the batteries
• Never heat them
• Never throw them onto a fire
• Never damage them mechanically (drill, crush, etc.)
Conditions of Use
The S7-400/M7-400 systems are designed for weather-protected, stationary use.
Conditions of use are in accordance with IEC 60721, Part 3, Class 3M3
(mechanical requirements) or Class 3K3 (ambient climatic requirements).
Conditions of use in accordance with ICE 60721 3-3 correspond to areas of
application with high traffic density and in the immediate vicinity of industrial plants
with chemical emissions.
Table 1-6 Ambient Mechanical Conditions for the MSM 478 Mass Storage Module in
Operation
Reduction of Vibrations
If the S7-400 or M7-400 is subject to high levels of shock or vibration, you must
take suitable measures to reduce the acceleration or amplitude.
We recommend that you secure the S7-400/M7-400 on shock-absorbent material
(for example, rubber-metal vibration dampers).
Test Voltages
The insulation resistance has been proved with different test voltages (in
accordance with IEC 61131-2):
Table 1-9 lists the test voltages in the insulation test.
Protection Class
Protection class I in accordance with IEC 60536 (VDE 0106, Part 1); that is a
protective cover connection to the power supply module is required!
Table 1-10 Ambient Climatic Conditions for the Modules Used in the M7-400
Racks 2
Chapter Overview
Introduction
The racks in the S7-400 have the following tasks:
• They hold the modules.
• They supply the modules with operating voltage.
• They connect the individual modules to each other via the signal buses.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
UL/CSA Note
Special requirements should be taken into consideration in the area of influence of
the UL/CSA; these may be fulfilled by installing the system in a cabinet.
Order Number
UR1: 6ES7 400-1TA01-0AA0
UR2: 6ES7 400-1JA01-0AA0
Introduction
The UR1 and UR2 racks are used for assembling central racks and expansion
racks.
The UR1 and UR2 racks have both an I/O bus and a communication bus.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9
40 mm
465 mm 240 mm
482.5 mm 257.5 mm
Order Number
6ES7 400-2JA00-0AA0
Introduction
The UR2-H rack is used for assembling two central racks or expansion racks in
one rack. The UR2-H rack essentially represents two electrically isolated UR2
racks on the same rack profile. The main area of application of the UR2-H is in the
compact structure of redundant systems (two subracks or subsystems in one
rack).
Subrack I Subrack II
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
290 mm 190 mm
40 mm
465 mm
482.5 mm
Caution
! Danger of damage to equipment.
If you insert a power supply module in a slot that is not permitted for power supply
modules, the module may be damaged. Slots 1 to 4 are permitted, whereby power
supply modules starting from slot 1 must be inserted without leaving gaps.
Make sure that power supply modules are only inserted in permitted slots. Take
particular notice of the option of swapping modules in slot 1 on subrack II and slot
9 on subrack I.
Rack UR2-H
Number of single-width slots 2x9
Dimensions W x H x D (in mm) 482.5 x 290 x 27.5
Weight (in kg) 3
Buses Segmented I/O bus,
segmented communication bus
Order Number
CR2: 6ES7 401-2TA01-0AA0
Introduction
The CR2 rack is used for assembling segmented central racks. The CR2 has both
an I/O bus and a communication bus. The I/O bus is split into two local bus
segments with 10 or 8 slots.
SEG1 SEG2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Communication bus
Rack CR2
Number of single-width slots 18
Dimensions W x H x D (in mm) 482.5 x 290 x 27.5
Weight (in kg) 3
Busses Segmented I/O bus,
continuous communication bus
Only one power supply module required
Order Number
ER1: 6ES7 403-1TA01-0AA0
ER2: 6ES7 403-1JA01-0AA0
Introduction
The ER1 and ER2 racks are used for assembling expansion racks.
The ER1 and ER2 racks have only one I/O bus with the following restrictions:
• Interrupts from modules in the ER1 or ER2 have no effect since there are no
interrupt lines provided.
• Modules in the ER1 or ER2 are not supplied with 24 V. Modules requiring a
24 V supply are not provided for use in the ER1 or ER2.
• Modules in the ER1 or ER2 are not backed up either by the battery in the power
supply module or by the voltage supplied externally to the CPU or the receive
IM (EXT.-BATT. socket).
Battery faults and backup voltage faults are not reported to the CPU.
The battery monitoring function of a power supply module installed in the ER1
or ER2 should therefore always be switched off.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
I/O bus
1 2 3 4 5 6 7 8 9
I/O bus
Note
A mains disconnecting device must be provided when installing AC power supply
modules.
Redundant Mode
You can configure a redundant power supply for a rack using two type PS 407
10A R power supply modules. This is recommended when you wish to enhance
the availability of your programmable controller, especially if you have to operate
the programmable controller on an unreliable network.
Characteristics
The redundant power supply of an S7-400 has the following characteristics:
• The power supply module delivers a making current in accordance with
NAMUR.
• Each of the power supply modules can take over the supply of power to the
whole rack if the other one fails. There is no loss of operation.
• Each of the power supply modules can be exchanged while the system is in
operation. No loss of power and no peak stress occurs with the effective
voltages when the modules are removed or inserted.
• Each of the power supply modules monitors its function and sends a message if
it fails.
• Neither of the power supply modules can generate an error which affects the
output voltage of the other power supply module.
• A redundant battery concept (backup concept) is only provided when two
backup batteries are used in each of the power supply modules. If only one
battery is used in each module, only non-redundant backup is possible, since
both batteries are being used at the same time.
• The failure of a power supply module is registered via a plug and remove
interrupt (default STOP). It is only when the power supply module is being used
in the second segment of the CR 2 that no message is sent if the module fails.
• If two power supply modules have been inserted but only one is switched on, a
startup delay of up to a minute occurs on power on.
Note
The check box “Startup if preset configuration not equal to actual configuration”
should be activated in the “Properties” dialog box of the CPU.
Introduction
The power supply modules of the S7-400 have a battery compartment for one or
two backup batteries. Use of these batteries is optional.
Battery Type
Only batteries authorized by Siemens can be used (see Chapter 12: Spare Parts
and Accessories).
The batteries can form a passivation layer. Depassivation takes place when the
batteries are inserted in the power supply module.
Backup Times
The maximum backup time depends on the load on the backup battery. A battery
capacity of 63% of the nominal capacity results in the following values:
Imax ≤ 200 µA Buffer time approximately 250 days
Imax ≤ 4 mA Buffer time approximately 12.5 days
The maximum backup current is 4 mA.
You can find the backup currents of the modules in the technical specifications for
the relevant modules.
Introduction
The power supply modules of the S7-400 have essentially the same controls and
indicators.
The main differences are:
• Not all power supply modules have a voltage selector switch.
• Power supply modules with a backup battery have an LED (BATTF) that
indicates an empty, defective, or missing backup battery.
Power supply modules with two redundant backup batteries have two LEDs
(BATT1F and BATT2F) for indicating empty, defective and missing batteries.
• Fixing screws
PS 407 20A
1 X 2 2 3
3 4
407-0RA00-0AA0
INTF
BAF
BATT1F
BATT2F • LEDs INTF,
DC 5 V
BAF, BATT1F, BATT2F, 5 VDC, 24 VDC
DC 24 V
+
BATT.1 BATT.2
+
Under cover
• Battery compartment
– –
BATT. INDIC.
2 BATT
OFF
• Switches BATT. INDIC.
1 BATT
2 BATT, OFF, 1 BATT
• Voltage selector switch (if present)
230
VOLTAGE
• Fixing screw
Figure 3-1 Front View of the PS 407 20A Power Supply Module
INTF, DC 5 V, DC 24 V
BAF, BATTF
Power supply modules with one backup battery have the following indications:
Note
Due to internal capacities, if you remove the battery or switch off the external
supply, some time may elapse before BAF, BATT1F, or BATT2F lights up.
FMR momentary- For acknowledging and resetting a fault indicator after correcting the
contact pushbut- fault
ton
Standby switch Switches the output voltages (5 VDC/24 VDC) to 0 V by intervening in
the control loop (no mains disconnection).
• I : Output voltages at nominal value
• : Output voltages 0 V
BATT INDIC Used for setting LEDs and battery monitoring
switch
Where one battery can be used (PS 407 4A, PS 405 4A):
• OFF: LEDs and monitor signals inactive
• BATT: BAF/BATTF LEDs and monitor signals active
Where two batteries can be used (PS 407 10A, PS 407 20A,
PS 405 10A, PS 405 20A)
• OFF: LEDs and monitor signals inactive
• 1 BATT: Only BAF/BATT1F LEDs (for battery 1) active.
• 2 BATT: BAF/BATT1F/BATT2F LEDs (for batteries 1 and 2) active.
Voltage selector For setting the primary voltage (120 VAC or 230 VAC), protected by its
switch (if present) own cover. (Please give due consideration to the note below)
Warning
! One of the following power supply modules can be damaged:
Power supply module PS 407 4A (6ES7 407-0DA00-0AA0)
Power supply module PS 407 20A (6ES7 407-0RA00-0AA0)
If you set the voltage selector switch on these AC power supply modules to the
120 V position and connect the powers supply modules to a 230 V mains supply,
the power supply modules may become defective. Any warranty lapses in this in-
stance.
Set the voltage selector switch on these AC power supply modules to the existing
mains voltage.
Cover
The battery compartment, battery selector switch, voltage selector switch, and
mains connection are housed under one cover. The cover must remain closed
during operation in order to protect these operator controls and to prevent static
electricity from affecting the battery connections.
If you have to take measurements on a module, discharge your body before
working. To do so, touch grounded metal objects. Use only grounded measuring
instruments.
Introduction
The power supply modules of the S7-400 indicate module faults and backup
battery faults via LEDs on the front plate.
BAF, BATTF
The following table applies to power supply modules with one battery if the BATT
INDIC switch is in the BATT position. It shows the faults indicated and lists how to
remedy the faults.
The following table applies to power supply modules with two batteries if the BATT
INDIC switch is in the 2BATT position. It shows the faults indicated and lists how to
remedy the faults.
Order Number
6ES7 407-0DA00-0AA0
Function
The PS 407 4A power supply module is designed for connecting to an AC line
voltage of 120 / 230 VAC and supplies 5 VDC /4 A and 24 VDC / 0.5 A on the
secondary side.
• Fixing screw
PS 407 4A
X 2
1
3 4
407-0DA00-0AA0
INTF
BAF
BATTF
• LEDs INTF,
5 VDC
BAF, BATTF,
24 VDC
DC 5 V, DC 24 V
Under cover
• Battery compartment
BATT. INDIC.
BATT • Switches BATT. INDIC.
OFF
BATT, OFF
•
230
Order Numbers
PS 407 10A: 6ES7 407-0KA01-0AA0 (standard)
PS 407 10A R: 6ES7 407-0KR00-0AA0 (redundancy capability,
refer to section 3.2)
Function
The PS 407 10A and PS 407 10A R power supply modules are designed for
connecting to either an AC line voltage of 85 to 264 VAC or a DC line voltage
of 88 to 300 VDC and supplies 5 VDC / 10 A and 24 VDC / 1 A on the secondary
side.
• Fixing screw
PS 407 10A
1 X 2
2
3 4
407-0KR00-0AA0
INTF
BAF
BATTF
BATTF • LEDs INTF,
5 VDC BAF, BATT1F, BATT2F,
24 VDC
DC 5 V, DC 24 V
+ + Under cover
• Battery compartment
– –
BATT. INDIC.
2 BATT
OFF
• Switches BATT. INDIC.
1 BATT
2 BATT, OFF, 1 BATT
• Fixing screw
Mains connection
In contrast to the instructions on assembling a power supply module in the manual
“S7-400 and M7-400 Programmable Controllers, Hardware and Installation”, an
AC power plug is used for connecting the PS 407 10A and the PS 407 10A R to
both an AC and a DC supply.
Order Number
6ES7 407-0RA00-0AA0
Function
The PS 407 20A power supply module is designed for connecting to an AC line
voltage of 120 / 230 VAC and supplies 5 VDC / 20A and 24 VDC / 1 A on the
secondary side.
• Fixing screws
PS 407 20A
1 X 2 2 3
3 4
407-0RA00-0AA0
INTF
• LEDs INTF,
BAF
BATTF
BATTF
5 VDC
BAF, BATT1F, BATT2F, DC 5 V, DC 24 V
24 VDC
FMR
• FMR pushbutton (Failure Message Reset)
• Battery compartment
– –
BATT. INDIC.
2 BATT
OFF
• Switches BATT. INDIC.
1 BATT
2 BATT, OFF, 1 BATT
• Voltage selector switch
230
VOLTAGE
• Fixing screw
Backup Battery
The PS 407 20A power supply module contains a battery compartment for two
batteries. If you use two batteries and set the switch to 2BATT, the PS 407 20A
defines one of the batteries as the backup battery. This assignment remains in
force until the battery is empty. When the backup battery is completely discharged,
the system switches to the reserve battery which is then in turn used as the
backup battery for the duration of its life. The status “backup battery” is also stored
in the event of a power failure.
Order Number
6ES7 407-0RA01-0AA0
Function
The PS 407 20A power supply module is designed for connecting to either an AC
line voltage of 85 to 264 VAC or a DC line voltage of 88 to 300 VDC and
supplies 5 VDC/20 A and 24 VDC /1 A on the secondary side.
• Fixing screws
PS 407 20A
1 X 2 2 3
3 4
407-0RA00-0AA0
INTF
• LEDs INTF,
BAF
BATTF
BATTF
5 VDC
BAF, BATT1F, BATT2F, DC 5 V, DC 24 V
24 VDC
FMR
• FMR pushbutton (Failure Message Reset)
• Battery compartment
– –
BATT. INDIC.
2 BATT
OFF
• Switches BATT. INDIC.
1 BATT
2 BATT, OFF, 1 BATT
• Fixing screw
Order Number
6ES7 405-0DA00-0AA0
Function
The PS 405 4A power supply module is designed for connecting to a DC line
voltage of 24 VDC and supplies 5 VDC / 4 A and 24 VDC / 0.5 A on the secondary
side.
• Fixing screw
PS 405 4A
X 2
1
3 4
405-0DA00-0AA0
INTF
• LEDs INTF,
BAF
BATTF
5 VDC
BAF, BATTF,
24 VDC
DC 5 V, DC 24 V
FMR
• FMR pushbutton (Failure Message Reset)
• Standby switch
Under cover
• Battery compartment
BATT. INDIC.
BATT
OFF • Switches BATT. INDIC.
BATT, OFF
• Fixing screw
Order Number
6ES7 405-0KA00-0AA0
Function
The PS 405 10A power supply module is designed for connecting to a DC line
voltage of 24 VDC and supplies 5 VDC / 10 A and 24 VDC / 1 A on the secondary
side.
PS 405 10 A
405-0KA00-0AA0
X
3
2
4
2
• Fixing screw
INTF
BAF
BATTF
BATTF • LEDs INTF,
5 VDC BAF, BATT1F, BATT2F,
24 VDC
DC 5 V, DC 24 V
FMR
• FMR pushbutton (Failure Message Reset)
• Standby switch
+
BATT.1 BATT.2
+
Under cover
• Battery compartment
– –
BATT. INDIC.
• Fixing screw
Order Number
PS 405 10A: 6ES7 405-0KA01-0AA0 (standard)
PS 405 10A R: 6ES7 405-0KR00-0AA0 (redundancy capability,
refer to section 3.2)
Function
The PS 405 10A and PS 405 10A R power supply modules are designed for
connecting to a DC line voltage of 19.2 VDC to 72 VDC and supplies 5 VDC/10 A
and 24 VDC/1 A on the secondary side.
Controls and Indicators on the PS 405 10A and the PS 405 10A R
PS 405 10 A
405-0KA00-0AA0
X
3
2
4
2
• Fixing screw
INTF
BAF
BATTF
BATTF • LEDs INTF,
5 VDC BAF, BATT1F, BATT2F,
24 VDC
DC 5 V, DC 24 V
FMR
• FMR pushbutton (Failure Message Reset)
• Standby switch
+
BATT.1 BATT.2
+
Under cover
• Battery compartment
– –
BATT. INDIC.
• Fixing screw
Order Number
6ES7 405-0RA00-0AA0
Function
The PS 405 20A power supply module is designed for connecting to a DC line
voltage of 24 VDC and supplies 5 VDC / 20 A and 24 VDC / 1 A on the secondary
side.
PS 405 20A
1 X
3 4
2 2 3
• Fixing screws
405-0RA00-0AA0
INTF
• LEDs INTF,
BAF
BATTF
BATTF
FMR
• FMR pushbutton (Failure Message Reset)
• Standby switch
BATT.1 BATT.2 Under cover
+ +
• Battery compartment
– –
BATT. INDIC.
• Fixing screws
Order Number
6ES7 405-0RA01-0AA0
Function
The PS 405 20A power supply module is designed for connecting to a DC line
voltage of 19.2 VDC to 72 VDC and supplies 5 VDC/20 A and 24 VDC/1 A on the
secondary side.
PS 405 20A
1 X
3 4
2 2 3
• Fixing screws
405-0RA00-0AA0
INTF
• LEDs INTF,
BAF
BATTF
BATTF
FMR
• FMR pushbutton (Failure Message Reset)
• Standby switch
BATT.1 BATT.2 Under cover
+ +
• Battery compartment
– –
BATT. INDIC.
• Fixing screws
CPU 412-1
6ES7412-1XF03-0AB0
Under cover
MPI/PROFIBUS-DP interface
Figure 4-1 Arrangement of the Operator Controls and Indicators on the CPUs 412-1
CPU 414-2
6ES7414-3XG03-0AB0
Under cover
MPI/PROFIBUS-DP interface
PROFIBUS-DP interface
Figure 4-2 Arrangement of the Operator Controls and Indicators on the CPUs 41x-2
CPU 416-3
6ES7416-3XL00-0AB0
IFM1F
MPI/PROFIBUS-DP interface
Module slot for
interface module
PROFIBUS-DP interface
FMOD1
FMOD2
MPI/PROFIBUS-DP interface
Submodule slot for
interface submodule 1
Figure 4-4 Arrangement of the Operator Controls and Indicators on the CPU 417-4
Figure 4-5 Arrangement of the Operator Controls and Indicators on the CPU 417 H
LEDs
Table 4-1 provides an overview of the LEDs on the individual CPUs.
Section 4.2 describes the states and faults indicated by these LEDs.
PROFIBUS-DP Interface
You can connect the distributed I/O, programming devices/operator panels, and
other DP master stations to the PROFIBUS-DP interface.
Note
You require external supply on the “EXT. BATT.” socket if you are replacing a
power supply module and you want to backup the user program stored in RAM
and the data mentioned above while you replace the module.
LED Meaning
RUN STOP
L D CPU is in the RUN state.
D L CPU is in STOP state. The user program is not executed. A hot, warm or
complete (cold) restart is possible. If the STOP state is the result of a
fault/error, the fault LED (INTF or EXTF) will also be set.
F F CPU is in the DEFECTIVE state. The LEDs INTF, EXTF, and FRCE also
2 Hz 2 Hz flash.
D = LED is dark; L = LED lights up; F = LED flashing with the specified frequency;
x = LED status irrelevant
LED Meaning
MSTR RACK0 RACK1
L x x CPU controls processing of switched I/O
x L D CPU on rack with number 0
x D L CPU on rack with number 1
LED Meaning
INTF EXTF FRCE
L x x An internal fault/error has been detected (programming error or
parameter assignment error).
x L x An external fault/error has been detected (that is, a fault whose
cause is not located in the CPU).
x x L A force job is active.
LED Meaning
BUS BUS2
1F F
H x A fault/error has been detected on the MPI/DP interface.
x H An fault/error has been detected on the PROFIBUS-DP interface.
B x One or more slaves on the PROFIBUS-DP interface 1 are not
responding.
x B One or more slaves on the PROFIBUS-DP interface 2 are not
responding.
Error LEDs and Special Events on the CPUs 41x-3 and 41x-4
The CPUs 41x-3 and 41x-4 continue to have the LED IFM1F and the LEDs
IFM1F and IFM2F respectively. These display errors related to the first and second
submodule interfaces.
LED Meaning
IFM1F IFM2F
H x An error was detected on the submodule slot 1.
x H An error was detected on the submodule slot 2.
B x One or more slaves connected to the PROFIBUS-DP interface in
submodule slot 1 do not respond.
x B One or more slaves connected to the PROFIBUS-DP interface in
submodule slot 2 do not respond.
Diagnostic buffer
To remove an error, you can read out the exact cause of the error with STEP 7
(PLC > Module Information) from the diagnostic buffer.
Positions
The mode selector is a key switch. Figure 4-6 shows the possible positions of the
mode selector switch.
RUN-P
RUN
STOP
MRES
Table 4-2 explains the positions of the mode selector switch. If an error occurs or if
there are restrictions to startup, the CPU remains in STOP, regardless of the
position of the mode selector switch.
Position Explanation
RUN-P If there is no error and no restriction to startup and the CPU can be switched to RUN
mode, the CPU processes the user program or stays idling. I/O accesses are possible.
The key cannot be removed in this position.
Programs can be
• Read out of the CPU with the programming device (CPU ⇒ PG),
• Downloaded to the CPU (PG ⇒ CPU).
RUN If there is no error and no restriction to startup and the CPU can be switched to RUN
mode, the CPU processes the user program or stays idling. I/O accesses are possible.
The key can be removed in this position to prevent unauthorized persons from
changing the operating mode.
Programs in the CPU can be displayed on the programming device (CPU ⇒ PG).
The program in the CPU cannot be changed in RUN mode
(see STEP 7). The protection level can be ignored if you set a password in the
“Configuring Hardware” application in STEP 7 (from STEP 7 V4.02 onwards); that
is, if you know this password, the program can also be changed when the CPU is
in RUN mode.
STOP The CPU does not execute the user program. The digital signal modules are disabled.
The key can be removed in this position to prevent unauthorized persons from
changing the operating mode.
Programs can be
• Read out of the CPU with the programming device (CPU ⇒ PG),
• Downloaded to the CPU (PG ⇒ CPU).
MRES Key position for carrying out a memory reset on the CPU and for a cold restart (see
(memory reset) following pages).
Protection Levels
With the S7-400 CPUs, a protection level can be set with which the programs in
the CPU can be protected from unauthorized access. The protection level
determines which programming device (PG) functions a user can execute on the
respective CPU without special authorization (password). With a password, all PG
functions are permitted.
If different settings for the protection levels are set using the mode selector switch
and in STEP 7, the higher priority setting is valid (3 before 2, 2 before 1).
Cold Restart
With a cold restart, the user program is started again from the beginning. All the
data, including retained data, are deleted.
Hot Restart
During a hot restart the application is relaunched at the point where it was
interrupted.
The S7-400 must have battery backup for the hot restart following power-on
(automatic hot restart).
Warm Restart
In a warm restart, the user program is restarted from the beginning. Data that has
been stored in non-retentive areas is deleted.
Operating Sequence for a Warm or Hot Restart (CPU 412, 414, 416 and 417)
1. Turn the switch to the STOP position.
Result: The STOP LED lights up.
2. Turn the switch to the RUN/RUN-P position.
Whether the CPU carries out a warm restart or a hot restart depends on the CPU
configuration. With the CPU 417-4H there is no hot restart.
Note that the CPU 417-4H does not support the warm restart.
Note
A maximum of 8 nodes (CPU, PG/OP, FM/CP with own MPI address) are
permitted in a subnet when using a speed of 19.2 Kbps for communicating with
S7-200. You cannot configure global data communication.
Note that earlier S7-400 CPUs did not support the 19.2 Kbps transmission rate.
You can set the 19.2 Kbps transmission rate from STEP 7 V4.02 onwards.
You can find more information on connecting a S7-200 to a MPI subnet in the
system manual “Programmable Controller S7-200”
Note
Interrupt reaction times may be delayed due to read and write jobs of a maximum
data size (approx. 460 bytes).
Connectors
Use only bus connectors with slanted outgoing cables for PROFIBUS-DP or PG
cables for connecting devices to the multipoint interface (see Installation Manual,
Chapter 7).
Suitable Devices
You can connect the following nodes to the PROFIBUS-DP interface:
• S7-300 as an intelligent slave (for example, CPU 315-2 with PROFIBUS-DP
connection)
• ET 200M (distributed station with S7-300 I/O)
• All other PROFIBUS DP slaves in the ET 200 system family
• Other standard PROFIBUS-DP slaves
• Further S7 DP masters (programming devices, OPs, etc.)
The CPU is the active DP master station that is connected to the passive slave
stations or further DP masters via the PROFIBUS-DP field bus.
Some devices that can be connected require a 24-V supply from the interface. This
voltage is available here in non-isolated form.
Connectors
Use only bus connectors for PROFIBUS-DP or PROFIBUS cables for connecting
devices to the PROFIBUS-DP interface (see Installation Manual, Chapter 7).
Default Values
When shipped, all parameters are set to the default values. The S7-400 can be
used right away and without any further parameter setting using these default
values that are suitable for a whole range of standard applications.
You can determine the CPU-specific default values with the “Configuring
Hardware” application in STEP 7.
Blocks of Parameters
The response and the properties of the CPU are defined by means of parameters
(which are stored in system data block). The CPUs have a defined default setting
so as to guarantee a reproducible response. You can change this default setting by
modifying the parameters.
The following list provides an overview of the system properties which can be
assigned in the CPUs.
• General properties (for example, MPI node number)
• Startup (for example, enable following hot restart)
• Scan cycle/clock memory (for example, cycle time monitoring)
• Retentivity (number of memory bits, timers and counters stored retentively)
• Memory
Note: The available work memory for program code and data blocks increases
or decreases as you increase or decrease the default values for image process,
the number of diagnostic buffer entries, the maximum number of interrupt-8
blocks and blocks for S7 communication, for example.
• Interrupt assignment (hardware interrupts, delay interrupts, asynchronous error
interrupts) for the priority classes
• Time-of-day interrupts (for example, start, interval duration, priority)
• Cyclic interrupts (for example, priority, interval duration)
• Diagnostics/clock (for example, time synchronization)
• Protection levels
• High availability system parameters specific to the CPU 417-4H
Note
In the default setting, 16 memory bits and 8 counters are stored retentively,
meaning they are not deleted when a warm restart is carried out on the CPU.
Note
If you make changes to the current settings for the following parameters the
operating system will initialize settings in the same way as with a cold restart.
• Size of the process-image input
• Size of the process-image output
• Size of the local data
• Number of diagnostic buffer entries
• Communication resources
These initial settings are as follows:
– Data blocks are initialized with the load values
– Bit memory, timers, counters, inputs, and outputs are deleted, irrespective
of whether they are retentive (0)
– Data blocks generated via system functions are deleted
– Programmed, dynamic connections are disconnected as well as
non-configured connections between X/I blocks from the active
side of the connection
– All priority classes have their default values
When you use a module that generates process interrupts in the S7-400H system,
it is possible that the process values that can be read in the process interrupt OB
by means of direct access might not correspond to the process values at the time
of the interrupt. You should instead evaluate the temporary variables (start
information) in the process interrupt OB.
When you use the SM 321-7BH00 module, which generates process interrupts, it
therefore does not make sense to respond to rising and falling edges differently via
one and the same input because the I/O would have to be accessed directly. If you
want to respond differently in your user program to the two edge changes, put the
signal on two inputs from different channel groups and set one input for rising
edges and the other input for falling edges.
Associated program packa- STEP7 5.0 or higher; • settable retentivity from MB 0 to MB 4095
ge Service Pack 2 • preset from MB 0 to MB 15
Memory Clock memory 8 (1 memory byte)
Work memory Data blocks max. 512 (DB 0 reserved)
• integrated 48 Kbytes for program • size max. 48 Kbytes
48 Kbytes for data Local data (settable) max. 8 Kbytes
• expandable no • preset 4 Kbytes
Load memory Blocks
• integrated 256 Kbytes RAM OBs see Instruction List
• expandable FEPROM with memory card • size max. 48 Kbytes
(FEPROM) up to 64 Mbytes
Nesting depth
• expandable RAM with memory card (RAM)
up to 64 Mbytes • per priority class 24
Backup yes • within an error OB 2 additional
• with battery all data FBs max. 256
• without battery none • size max. 48 Kbytes
Process Times FCs max. 256
Process times for • size max. 48 Kbyte
• bit operations min. 0.2 s Address Areas (I/Os)
• word operations min. 0.2 s Total I/O address area 4 Kbytes/4 Kbytes
• fixed point arithmetic min. 0.2 s • distributed
• floating point arithmetic min. 0.6 s – MPI/DP interface 2 KBytes/2 KBytes
Timers/Counters and their Retentivity – DP interface 2 KBytes/2 KBytes
S7 counters 256 Process image 4 KBytes/4 KBytes (setta-
ble)
• settable retentivity from Z 0 to Z 255
• preset 128 bytes/128 bytes
• preset from Z 0 to Z 7
• number of process max. 8
• counter range 1 to 999 image sections
IEC counter yes Digital channels 32768/32768
• type SFB • local 32768/32768
S7 timers 256 Analog channels 2048/2048
• settable retentivity from T 0 to T 255 • local 2048/2048
• preset no retentivity
• timer range 10 ms to 9990 s
IEC timer yes
• type SFB
S5 compatible yes (via CP and loadable • address area max. 2 Kbytes I / 2 Kbytes O
communication FC) • useful data per max. 244 bytes I/
• useful data per job max. 8 Kbytes DP slave 244 bytes O
Standard communication yes (via CP and loadable Programming language LAD, FBD, STL, SCL
FC) Available operations see Instruction List
• useful data per job depending on CP Nesting levels 8
– consistent depending on CP System functions (SFC) see Instruction List
Number of connection re- 16 Number of simultaneously
sources active SFCs
Interfaces • WR_REC 8
1st Interface • WR_PARM 8
Type of interface integrated interface module • PARM_MOD 1
Physical interface RS 485 • WR_DPARM 2
Optically isolated yes • DPNRM_DG 8
Power supply at interface max. 150 mA • RDSYSST 1 ... 8
(15 to 30 V DC)
System function blocks see Instruction List
Number of connection re- 16 (SFB)
sources
Program security password protection
Functionality
Dimensions
• MPI yes
Mounting dimensions 25290219
• PROFIBUS DP DP master WHD (mm)
• point-to-point no Slots necessary ca. 1
connection
Weight ca. 0.72 kg
MPI
Voltages, Currents
• services
Power supply voltage nominal value 24 V DC
– PG/OP yes
communication Current consumption from typ. 1.5 A
S7-400 bus (5 V DC) max. 1.6 A
– routing yes
– global data yes Current consumption from max. 0.15 A
communication S7-400 bus (24 V DC)
Associated program packa- STEP7 5.0 or higher; • settable retentivity from MB 0 to MB 4095
ge Service Pack 2 • retentivity preset from MB 0 to MB 15
Memory Clock memory 8 (1 memory byte)
Work memory Data blocks max. 512 (DB 0 reserved)
• integrated 72 Kbytes for program • size max. 64 Kbytes
72 Kbytes for data Local data (settable) max. 8 Kbytes
• expandable no • preset 4 Kbytes
Load memory Blocks
• integrated 256 Kbytes RAM OBs see Instruction List
• expandable FEPROM with memory card • size max. 64 Kbytes
(FEPROM) up to 64 Mbytes
Nesting depth
• expandable RAM with memory card (RAM)
up to 64 Mbytes • per priority class 24
Backup yes • within an error OB 2 additional
• with battery all data FBs max. 256
• without battery none • size max. 64 Kbytes
Process Times FCs max. 256
Process times for • size max. 64 Kbytes
• bit operations min. 0.2 s Address Areas (I/Os)
• word operations min. 0.2 s Total I/O address area 4 Kbytes/4 Kbytes
• fixed point arithmetic min. 0.2 s • distributed
• floating point arithmetic min. 0.6 s – MPI/DP interface 2 Kbytes/2 Kbytes
Timers/Counters and their Retentivity – DP interface 4 Kbytes/4 Kbytes
S7 counters 256 Process image 4 Kbytes/4 Kbytes
(settable)
• settable retentivity from Z 0 to Z 255
• preset 128 bytes/128 bytes
• preset from Z 0 to Z 7
• number of process max. 8
• counter range 1 to 999 image sections
IEC counter yes Digital channels 32768/32768
• type SFB • local 32768/32768
S7 timers 256 Analog channels 2048/2048
• settable retentivity from T 0 to T 255 • local 2048/2048
• preset no retentivity
• timer range 10 ms to 9990 s
IEC timer yes
• type SFB
• MPI yes
– PG/OP yes
communication
• PROFIBUS DP DP master
– routing yes
• point-to-point connec- no – lateral yes
tion communication
MPI – SYNC/FREEZE yes
• services – activate/deactivate no
DP slaves
– PG/OP yes
communication • transmission speed up to 12 Mbps
– routing yes • number of DP slaves max. 64
– global data yes • address area max. 4 Kbytes I/4 Kbytes O
communication
• useful data per max. 244 bytes I/
– S7 basic yes DP slave 244 bytes O
communication
– S7 communication yes
• transmission speed up to 12 Mbps
Programming Dimensions
Programming language LAD, FBD, STL, SCL Mounting dimensions 25290219
WHD (mm)
Available operations see Instruction List
Slots necessary 1
Nesting levels 8
Weight ca. 0.72 kg
System functions (SFC) see Instruction List
Voltages, Currents
Number of simultaneously
active SFCs Power supply voltage nominal value 24 V DC
• WR_REC 8 Current consumption from typ. 1.5 A
S7-400 bus (5 V DC)
• WR_PARM 8 max. 1.6 A
Associated program packa- STEP7 5.0 or higher; • settable retentivity from MB 0 to MB 8191
ge Service Pack 2 • retentivity preset from MB 0 to MB 15
Memory Clock memory 8 (1 memory byte)
Work memory Data blocks max. 1024 (DB 0 reserved)
• integrated 128 Kbytes for program • size max. 64 Kbytes
128 Kbytes for data Local data (settable) max. 16 Kbytes
• expandable no • preset 8 Kbytes
Load memory Blocks
• integrated 256 Kbytes RAM OBs see Instruction List
• expandable FEPROM with memory card • size max. 64 Kbytes
(FEPROM) up to 64 Mbytes
Nesting depth
• expandable RAM with memory card (RAM)
up to 64 Mbytes • per priority class 24
Backup yes • within an error OB 2 additional
• with battery all data FBs max 1024
• without battery none • size max. 64 Kbytes
Process Times FCs max. 1024
Process times for • size max. 64 Kbytes
• bit operations min. 0.1 s Address Areas (I/Os)
• word operations min. 0.1 s Total I/O address area 8 Kbytes/8 Kbytes
• fixed point arithmetic min. 0.1 s • distributed
• floating point arithmetic min. 0.6 s – MPI/DP interface 2 Kbytes/2 Kbytes
Timers/Counters and their Retentivity – DP interface 6 Kbytes/6 Kbytes
S7 counters 256 Process image 8 Kbytes/8 Kbytes
(settable)
• settable retentivity from Z 0 to Z 255
• preset 256 bytes/256 bytes
• preset from Z 0 to Z 7
• number of process max. 8
• counter range 1 to 999 image sections
IEC counter yes Digital channels 65536/65536
• type SFB • local 65536/65536
S7 timers 256 Analog channels 4096/4096
• settable retentivity from T 0 to T 255 • local 4096/4096
• preset no retentivity
• timer range 10 ms to 9990 s
IEC timer yes
• type SFB
• IM 463 max. 6
– 100 ms interval max. 128
– 500 ms interval max. 256
Number of DP masters
– 1000 ms interval max. 512
• integrated 2
Process diagnostic yes
• via interface module none messages
• via IM/CP max. 10 • simultaneously active max. 100
Number of plug-in S5 max. 6 interrupt-S blocks
modules via adapter casing Process control messages yes
(in central controller)
Interrupt-8 blocks yes
Operable function modules
and communication • number of instances for max. 600
processors interrupt-8 blocks and
blocks for
• FM limited by number of slots S7 communication
and connections (settable)
• CP, point-to-point limited by number of slots • preset max. 300
and connections
Number of archive IDs that 16
• CP, LAN limited by number of slots can be logged in simulta-
and connections neously
– with S5 compatible max. 4 Test and Commissioning Functions
communication
Status/control variable yes
Time of Day
• variable I/Os, bit operations, DB,
Clock yes distributed I/Os, timers,
counters
• buffered yes
• accuracy upon
• number variable max. 70
Force function yes
– POWER DOWN daily deviation 1.7 s
– POWER ON daily deviation 8.6 s
• variable I/Os, bit operations,
distributed I/Os
Operating hours counter 8
• number variable max. 256
• number 0 to 7
Status block yes
• value range 0 to 32767 hours
Single sequence yes
• granularity 1 hour
Breakpoint 4
• retentive yes
Diagnostic buffer yes
Time of day yes
synchronization
• number of entries max. 400
(settable)
• on the PLC master/slave
• preset 120
• at the MPI master/slave
Communication Functions
S7 Message Functions
PG/OP communication yes
Number of stations for max. 8
Global data communication yes
message functions, which
can be activated (e.g. OS) • number of GD
packages
SCAN process yes
– sender max. 8
• services – activate/deactivate no
DP slaves
– PG/OP yes
communication • transmission speed up to 12 Mbps
Programming Dimensions
Programming language LAD, FBD, STL, SCL Mounting dimensions 25290219
WHD (mm)
Available operations see Instruction List
Slots necessary 1
Nesting levels 8
Weight ca. 0.72 kg
System functions (SFC) see Instruction List
Voltages, Currents
Number of simultaneously
active SFCs Power supply voltage nominal value 24 V DC
• WR_REC 8 Current consumption from typ. 1.5 A
S7-400 bus (5 V DC)
• WR_PARM 8 max. 1.6 A
Associated program packa- STEP7 5.0 or higher; • settable retentivity from MB 0 to MB 8191
ge Service Pack 2 • preset retentivity from MB 0 to MB 15
Memory Clock memory 8 (1 memory byte)
Work memory Data blocks max. 1024 (DB 0 reserved)
• integrated 384 Kbytes for program • size max. 64 Kbytes
384 Kbytes for data Local data (settable) max. 16 Kbytes
• expandable no • preset 8 Kbytes
Load memory Blocks
• integrated 256 Kbytes RAM OBs see Instruction List
• expandable FEPROM with memory card • size max. 64 Kbytes
(FEPROM) up to 64 Mbytes
Nesting depth
• expandable RAM with memory card (RAM)
up to 64 Mbytes • per priority class 24
Backup yes • within an error OB 2 additional
• with battery all data FBs max. 1024
• without battery none • size max. 64 Kbytes
Process Times FCs max. 1024
Process times for • size max. 64 Kbytes
• bit operations min. 0.1 s Address Areas (I/Os)
• word operations min. 0.1 s Total I/O address area 8 Kbytes/8 Kbytes
• fixed point arithmetic min. 0.1 s • distributed
• floating point arithmetic min. 0.6 s – MPI/DP interface 2 Kbytes/2 Kbytes
Timers/Counters and their Retentivity – DP interface 6 Kbytes/6 Kbytes
S7 counters 256 Process image 8 Kbytes/8 Kbytes
(settable)
• settable retentivity from Z 0 to Z 255
• preset 256 bytes/256 bytes
• preset from Z 0 to Z 7
• number of process max. 8
• counter range 1 to 999 image sections
IEC counter yes Digital channels 65536/65536
• type SFB • local 65536/65536
S7 timers 256 Analog channels 4096/4096
• settable retentivity from T 0 to T 255 • local 4096/4096
• preset no retentivity
• timer range 10 ms to 9990 s
IEC timer yes
• type SFB
• IM 463 max. 6
– 100 ms interval max. 128
– 500 ms interval max. 256
Number of DP masters
– 1000 interval max. 512
• integrated 2
Process diagnostic yes
• via interface module 1 messages
• via IM/CP max. 10 • simultaneously active max. 100
Number of plug-in S5 max. 6 interrupt-S blocks
modules via adapter casing Process control messages yes
(in central controller)
Interrupt-8 blocks yes
Operable function modules
and communication • number of instances for max. 600
processors interrupt-8 blocks and
blocks for
• FM limited by number of slots S7 communication
and connections (settable)
• CP, point-to-point limited by number of slots • preset max. 300
and connections
Number of archive IDs that 16
• CP, LAN limited by number of slots can be logged in simulta-
and connections neously
– with S5 compatible max. 4 Test and Commissioning Functions
communication
Status/control variable yes
Time of Day
• variable I/Os, bit operations, DB,
Clock yes distributed I/Os, timers,
counters
• buffered yes
• accuracy upon
• number variable max. 70
Force function yes
– POWER DOWN daily deviation 1.7 s
– POWER ON daily deviation 8.6 s
• variable I/Os, bit operations,
distributed I/Os
Operating hours counter 8
• number variable max. 256
• number 0 to 7
Status block yes
• value range 0 to 32767 hours
Single sequence yes
• granularity 1 hour
Diagnostic buffer yes
• retentive yes
• number of entries max. 3200 (settable)
Time of day yes
synchronization
• preset 120
Communication Functions
• on the PLC master/slave
PG/OP communication yes
• at the MPI master/slave
Global data communication yes
S7 Message Functions
Number of stations for max. 8
• number of GD
packages
message functions, which
can be activated (e.g. OS) – sender max. 8
SCAN process yes – receiver max. 16
Associated program packa- STEP7 5.0 or higher; • settable retentivity from MB 0 to MB 16383
ge Service Pack 2 • preset retentivity from MB 0 to MB 15
Memory Clock memory 8 (1 memory byte)
Work memory Data blocks max. 4096 (DB 0 reserved)
• integrated 0.8 Mbytes for program • size max. 64 Kbytes
0.8 Mbytes for data Local data (settable) max. 32 Kbytes
• expandable no • preset 16 Kbytes
Load memory Blocks
• integrated 256 Kbytes RAM OBs see Instruction List
• expandable FEPROM with memory card (FLASH) • size max. 64 Kbytes
up to 64 Mbytes
Nesting depth
• expandable RAM with memory card (RAM)
up to 64 Mbytes • per priority class 24
Backup yes • within an error OB 2 additional
• with battery all data FBs max 2048
• without battery none • size max. 64 Kbytes
Process Times FCs max. 2048
Process times for • size max. 64 Kbytes
• bit operations min. 0.08 s Address Areas (I/Os)
• word operations min. 0.08 s Total I/O address area 16 Kbytes/16 Kbytes
• fixed point arithmetic min. 0.08 s • distributed
• floating point arithmetic min. 0.48 s – MPI/DP interface 2 Kbytes/2 Kbytes
Timers/Counters and their Retentivity – DP interface 8 Kbytes/8 Kbytes
S7 counters 512 Process image 16 Kbytes/16 Kbytes
(settable)
• settable retentivity from Z 0 to Z 511
• preset 512 bytes/512 bytes
• preset from Z 0 to Z 7
• number of process max. 8
• counter range 1 to 999 image sections
IEC counter yes Digital channels 131072/131072
• type SFB • local 131072/131072
S7 timers 512 Analog channels 8192/8192
• settable retentivity from T 0 to T 511 • local 8192/8192
• preset no retentivity
• timer range 10 ms to 9990 s
IEC timer yes
• type SFB
• IM 463 max. 6
– 100 ms interval max. 128
– 500 ms interval max. 512
Number of DP masters
– 1000 ms interval max. 1024
• integrated 2
Process diagnostic yes
• via interface module none messages
• via IM/CP max. 10 • simultaneously active max. 200
Number of plug-in S5 max. 6 interrupt-S blocks
modules via adapter casing Process control messages yes
(in central controller)
Interrupt-8 blocks yes
Operable function modules
and communication • number of instances for max. 1800
processors interrupt-8 blocks and
blocks for
• FM limited by number of slots S7 communication
and connections (settable)
• CP, point-to-point limited by number of slots • preset max. 600
and connections
Number of archive IDs that 32
• CP, LAN limited by number of slots can be logged in simulta-
and connections neously
– with S5 compatible max 4 Test and Commissioning Functions
communication
Status/control variable yes
Time of Day
• variable I/Os, bit operations, DB,
Clock yes distributed I/Os, timers,
counters
• buffered yes
• accuracy upon
• number variable max. 70
Force function yes
– POWER DOWN daily deviation 1.7 s
– POWER ON daily deviation 8.6 s
• variable I/Os, bit operations,
distributed I/Os
Operating hours counter 8
• number variable max. 512
• number 0 to 7
Status block yes
• value range 0 to 32767 hours
Single sequence yes
• granularity 1 hour
Diagnostic buffer yes
• retentive yes
• number of entries max. 3200 (settable)
Time of day yes
synchronization
• preset 120
Communication Functions
• on the AS master/slave
PG/OP communication yes
• at the MPI master/slave
Global data communication yes
S7 Message Functions
Number of stations for max. 12
• number of GD
packages
message functions, which
can be activated (e.g. OS) – sender max. 16
SCAN process yes – receiver max. 32
Programming Dimensions
Programming language LAD, FBD, STL, SCL Mounting dimensions 25290219
WHD (mm)
Available operations see Instruction List
Slots required 1
Nesting levels 8
Weight ca. 0.72 kg
System functions (SFC) see Instruction List
Voltages, Currents
Number of simultaneously
active SFCs Power supply voltage nominal value 24 V DC
• WR_REC 8 Current consumption from typ. 1.5 A
S7-400 bus (5 V DC)
• WR_PARM 8 max. 1.6 A
Associated program packa- STEP7 5.0 or higher; • settable retentivity from MB 0 to MB 16383
ge Service Pack 2 • retentivity preset from MB 0 to MB 15
Memory Clock memory 8 (1 memory byte)
Work memory Data blocks max. 4096 (DB 0 reserved)
• integrated 1.6 Mbytes for program • size max. 64 Kbytes
1.6 Mbytes for data Local data (settable) max. 32 Kbytes
• expandable no • preset 16 Kbytes
Load memory Blocks
• integrated 256 Kbyte RAM OBs see Instruction List
• expandable FEPROM with memory card (FLASH) • size max. 64 Kbytes
up to 64 Mbytes
Nesting depth
• expandable RAM with memory card (RAM)
up to 64 Mbytes • per priority class 24
Backup yes • within an error OB 2 additional
• with battery all data FBs max 2048
• without battery none • size max. 64 Kbytes
Process Times FCs max. 2048
Process times for • size max. 64 Kbytes
• bit operations min. 0.08 s Address Areas (I/Os)
• word operations min. 0.08 s Total I/O address area 16 Kbytes/16 Kbytes
• fixed point arithmetic min. 0.08 s • distributed
• floating point arithmetic min. 0.48 s – MPI/DP interface 2 Kbytes/2 Kbytes
Timers/Counters and their Retentivity – DP interface 8 Kbytes/8 Kbytes
S7 counters 512 Process image 16 Kbytes/16 Kbytes
(settable)
• settable retentivity from Z 0 to Z 511
• preset 512 bytes/512 bytes
• preset from Z 0 to Z 7
• number of process max. 8
• counter range 1 to 999 image sections
IEC counter yes Digital channels 131072/131072
• type SFB • local 131072/131072
S7 timers 512 Analog channels 8192/8192
• settable retentivity from T 0 to T 511 • local 8192/8192
• preset no retentivity
• timer range 10 ms to 9990 s
IEC timer yes
• type SFB
• IM 463 max. 6
– 100 ms interval max. 128
– 500 ms interval max. 512
Number of DP masters
– 1000 ms interval max. 1024
• integrated 2
Process diagnostic yes
• via interface module 1 messages
• via IM/CP max. 10 • simultaneously active max. 200
Number of plug-in S5 max. 6 interrupt-S blocks
modules via adapter casing Process control messages yes
(in central controller)
Interrupt-8 blocks yes
Operable function modules
and communication • number of instances for max. 1800
processors interrupt-8 blocks and
blocks for
• FM limited by number of slots S7 communication
and connections (settable)
• CP, point-to-point limited by number of slots • preset max. 600
and connections
Number of archive IDs that 32
• CP, LAN limited by number of slots can be logged in simulta-
and connections neously
– with S5 compatible max. 4 Test and Commissioning Functions
communication
Status/control variable yes
Time of Day
• variable I/Os, bit operations, DB,
Clock yes distributed I/Os, timers,
counters
• buffered yes
• accuracy upon
• number variable max. 70
Force function yes
– POWER DOWN daily deviation 1.7 s
– POWER ON daily deviation 8.6 s
• variable I/Os, bit operations,
distributed I/Os
Operating hours counter 8
• number variable max. 512
• number 0 to 7
Status block yes
• value range 0 to 32767 hours
Single sequence yes
• granularity 1 hour
Diagnostic buffer yes
• retentive yes
• number of entries max. 3200 (settable)
Time of day yes
synchronization
• preset 120
Communication Functions
• on the PLC yes
PG/OP communication yes
• at the MPI yes
Global data communication yes
S7 Message Functions
Number of stations for max. 12
• number of GD
packages
message functions, which
can be activated (e.g. OS) – sender max. 16
SCAN process yes – receiver max. 32
3. Schnittstelle Dimensions
Type of interface pluggable interface module Mounting dimensions 50290219
WHD (mm)
Insertable interface module IF-964-DP
Slots necessary 2
Technical properties as for 2nd interface
Weight ca. 1.07 kg
Programming
Voltages, Currents
Programming language LAD, FBD, STL, SCL
Power supply voltage nominal value 24 V DC
Available operations see Instruction List
Current consumption from typ. 1.6 A
Nesting levels 8
S7-400 bus (5 V DC) max. 1.8 A
System functions (SFC) see Instruction List
Current consumption from max. 0.3 A
Number of simultaneously S7-400 bus (24 V DC)
active SFCs
Backup current typ. 50 A
• WR_REC 8
max. 460 A
• WR_PARM 8
External feed for CPU 5 V DC up to 15 V DC
• PARM_MOD 1 backup voltage
• WR_DPARM 2 PG supply on MPI (15 to max. 150 mA
• DPNRM_DG 8
30 V DC)
Associated program packa- STEP7 5.0 or higher; • settable retentivity from MB 0 to MB 16383
ge Service Pack 2 • retentivity preset from MB 0 to MB 15
Memory Clock memory 8 (1 memory byte)
Work memory Data blocks max. 8192 (DB 0 reserved)
• integrated 2 Mbytes for program • size max. 64 Kbytes
2 Mbytes for data Local data (settable) max. 64 Kbytes
• expandable up to 10 Mbytes for • preset 32 Kbytes
program
up to 10 Mbytes for data Blocks
• type SFB
• IM 463 max. 6
– 100 ms interval max. 128
– 500 ms interval max. 512
Number of DP masters
– 1000 ms interval max. 1024
• integrated 2
Process diagnostic yes
• via interface module 2 messages
• via IM/CP max. 10 • simultaneously active max. 200
Number of plug-in S5 max. 6 interrupt-S blocks
modules via adapter casing Process control messages yes
(in central controller)
Interrupt-8 blocks yes
Operable function modules
and communication • number of instances for max. 10000
processors interrupt-8 blocks and
blocks for
• FM limited by number of slots S7 communication
and connections (settable)
• CP, point-to-point limited by number of slots • preset max. 1200
and connections
Number of archive IDs that 64
• CP, LAN limited by number of slots can be logged in simulta-
and connections neously
– with S5 compatible max. 4 Test and Commissioning Functions
communication
Status/control variable yes
Time of Day
• variable I/Os, bit operations, DB,
Clock yes distributed I/Os, timers,
counters
• buffered yes
• accuracy upon
• number max. 70
Force function yes
– POWER DOWN daily deviation 1.7 s
– POWER ON daily deviation 8.6 s
• variable I/Os, bit operations,
distributed I/Os
Operating hours counter 8
• number max. 512
• number 0 to 7
Status block yes
• value range 0 to 32767 hours
Single sequence yes
• granularity 1 hour
Diagnostic buffer yes
• retentive yes
• number of entries max. 3200 (settable)
Time of day yes
synchronization
• preset 120
Communication Functions
• on the PLC master/slave
PG/OP communication yes
• at the MPI master/slave
Global data communication yes
S7 Message Functions
Number of stations for max. 16
• number of GD
packages
message functions, which
can be activated (e.g. OS) – sender max. 16
SCAN process yes – receiver max. 32
Associated program packa- STEP7 5.0 or higher; • settable retentivity from MB 0 to MB 16383
ge Service Pack 2 • retentivity preset from MB 0 to MB 15
Memory Clock memory 8 (1 memory byte)
Work memory Data blocks max. 8192 (DB 0 reserved)
• integrated 2 Mbytes for program • size max. 64 Kbytes
2 Mbytes for data Local data (settable) max. 64 Kbytes
• expandable up to 10 Mbytes for • preset 32 Kbytes
program
up to 10 Mbytes for data Blocks
• type SFB
Functionality
• point-to-point connec- no
tion
• MPI yes
DP Master
• PROFIBUS DP DP master • services
• point-to-point connec- no – PG/OP yes
tion communication
MPI – routing yes
• services – lateral no
communication
– PG/OP yes
communication – SYNC/FREEZE no
Note
Startup of the digital modules with the default parameters is only possible in the
CR.
5.2 Diagnostics
Fault/Error Messages
You can use SFCs to read out system-wide and channel-specific diagnostic
messages from the module at any time.
You can read out the cause of the fault from the diagnostic buffer.
Note
Fault/error messages are not possible via the diagnostic interrupt if the module is
plugged into ER-1/ER-2.
If a diagnostic interrupt is enabled for a module in ER-1/ER-2, module diagnostics
can no longer be updated after the occurence of the first diagnostic message.
Fault Description
Internal fault The internal fault (INTF) LED indicates faults detected by the module
(INTF) within the module.
This LED indicates on the front of the module the status of the internal fault
diagnostic bit.
The LED remains lit until all internal faults have been corrected.
If the diagnostic interrupt has been enabled, the LED remains lit until all
internal faults have been corrected and acknowledged.
External fault The external fault (EXTF) LED indicates faults detected by the module on
(EXTF) the process side.
This LED indicates on the front of the module the status of the external
fault diagnostic bit.
The LED remains lit until all external faults have been corrected.
If the diagnostic interrupt has been enabled, the LED remains lit until all
external faults have been corrected and acknowledged.
Order Number
6ES7 421-1BL00-0AA0
Characteristics
The SM 421; DI 32 x 24 VDC is a digital input module with the following
characteristics:
• 32 inputs, isolated in a group of 32, that is, all inputs are connected to a
common ground.
• Nominal load voltage: 24 VDC
• Suitable for switches and 2-wire proximity switches (BEROs, IEC1131 Type 2).
Note
The status LEDs indicate the process status.
Process Module
1
2
L+ 3 L+ t
4 0
5 1
6 2
7 3
8 4
9 5
10 6
11 7
12
13
14
Order number
6ES7 421-1BL01-0AA0
Properties
The SM 421;DI 32 x DC 24 V is a digital input module with the following properties:
• 32 inputs, optically isolated in one group of 32 – in other words, all inputs share
a common ground.
• Rated input voltage: 24 V DC
• Suitable for switches and 2–wire proximity switches (BEROs, IEC 1131,
Type 1).
Note
The status LEDs indicate the process status.
Process Module
1
2
L+ 3
4 0
5 1
6 2
7 3
8 4
9 5
10 6
11 7 M
12
13
14
15 0
16 1
17 2
18 3
Order Number
6ES7 421-7DH00-0AB0
Characteristics
The SM 421; DI 16 x 24/60 VUC is a digital input module with the following
characteristics:
• 16 inputs, individually isolated, that is, each input is connected to its own
ground.
• Nominal load voltage 24 VUC to 60 VUC
• Suitable for switches and 2-wire proximity switches (BEROs)
• Diagnostic capability
• Hardware interrupt capability (for rising and/or falling edge)
• Setting of input delay possible
• Wire-break detection
Note
The status LEDs indicate the process status.
Process Module
1 INTF
Front connector jumper
2 EXTF
3
L 4 0 Input
N Adapter Diagnostics
5 1N
L Input
6 1
N Adapter Diagnostics
7 2N
L 8 2
Input
N Adapter Diagnostics
9 3N
L Input
10 3
N Adapter Diagnostics
11 4N
12
13
14
L Input
15 4
N Adapter Diagnostics
16 5N
L Input
17 5
N Adapter Diagnostics
18 6N
L 19 6
Input
N Adapter Diagnostics
Hardware Interrupt
The SM 421; DI 16 x 24/60 VUC can trigger a hardware interrupt either at a rising
edge, a falling edge or at both edges of the input signal. The setting can be made
by channel and can be changed (in RUN) at any time. Irrelevant channels can be
assigned parameters so that they can be used as input channels without triggering
a hardware interrupt. You set the parameters with STEP 7.
If a hardware interrupt has been triggered by the module, no other channel can be
signaled by the system until the interrupt has been acknowledged. A diagnostic
interrupt can be triggered during this time. If a further edge change occurs on the
same channel during the time from triggering the hardware interrupt to
acknowledging it, the loss of the hardware interrupt is signaled to the system by
means of a diagnostic interrupt, other channels are subsequently signaled
following acknowledgement.
The interrupt-triggering channels are stored in the local data of the interrupt OBs
(OB40 to OB47). One bit is assigned per channel.
Channels are assigned in the hardware interrupt supplementary information.
The hardware interrupt supplementary information is two words long. These words
have bit numbers 0 to 31. Bits 16 to 31 are not assigned. In the assigned bits, the
bit numbers correspond to the channel numbers.
Parameters
Diagnostic Parameter
The module checks for internal and external faults. You can activate the individual
diagnostic types with YES. The diagnostic function is executed and any fault/error
is signaled by
• A diagnostic entry and
• A fault/error LED.
Note
If you select the value 0.5 ms as the input delay, do not select a diagnostic
function. The internal execution time for diagnostic functions can be greater than
0.5 ms.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
LEDs
The SM 421; DI 16 x 24/60 VUC has two red LEDs for internal or external faults.
Diagnostic Functions
The SM 421; DI 16 x 24/60 VUC uses the following diagnostic options:
0 0 0 0 0 0 0
RUN/STOP
3 DS0/DS1
7 0 Diagnostic byte 4
0 0 0 0 0 0
EPROM fault
5 DS1
7 0 Length of information per channel
0 0 0 0 1 0 0 0 ^ 8 bits long
=
6 DS1
7 0 Number of channels
0 0 0 1 0 0 0 0 ^ 16 : 16 channels on module
=
8 DS1
7 0 Channel fault vector
9 to 25 DS1
7 0 Diagnostic byte
(channel-specific)
0 0 0 0 0 0
Parameter error
Wire break
0 = default value 0; the module does not process this diagnostic function
1 = default value 1; the module uses constants
- = no default; the module uses variables, value 1 corresponds to a fault
Test voltage
Voltage check
• Between the inputs 1500 VAC
• Between the inputs and the
central grounding point 1500 VAC
• Between S7-400 bus and
central grounding point 500 VDC
Module Cycle Times
• Without interrupt processing max. 250 s
• With hardware interrupt max. 450 s
processing
• With hardware interrupt and max. 2 ms
diagnostics
1) IEC 1131 gives no specifications for UC modules. However, the values have been adapted to IEC 1131 as
far as possible.
2) Minimum quiescent current is necessary in the case of wire-break monitoring.
Order Number
6ES7 421-1FH00-0AA0
Characteristics
The SM 421; DI 16 x 120/230 VUC is a digital input module with the following
characteristics:
• 16 inputs, isolated
• Nominal input voltage:120/230 V AC/DC
• Suitable for switches and 2-wire proximity switches (BEROs)
Note
The status LEDs indicate the process status.
4 4 4 4
4 4 4 4
4 4 4 4
4 4 4 4
Parallel → Serial
Bus
ASIC
S7-400 bus
Process Module
1
2
3
4 0
5
6 1
7
8 2
Order Number
6ES7 421-1EL00-0AA0
Characteristics
The SM 421; DI 32 x 120 VUC is a digital input module with the following
characteristics:
• 32 inputs, isolated
• Nominal input voltage:120 V AC/DC
• Suitable for switches and 2-wire proximity switches (BEROs)
Note
The status LEDs indicate the process status.
8 8 8 8
8 8 8 8
8 8 8 8
8 8 8 8
Parallel → Serial
Bus
ASIC
S7-400 bus
Process Module
1
2
3
4 0
5 1
6 2
7 3
8 4
9 5
10 6
11 7
12
13 1N
Order Number
6ES7 421-5EH00-0AA0
Characteristics
The SM 421; DI 16 x 120 VAC is a digital input module with the following
characteristics:
• 16 inputs, isolated
• Nominal input voltage: 120 VAC
• Suitable for switches and 2-wire proximity switches (BEROs, IEC1131 Type 2).
Terminal
block
16
Input
circuit
16
Optocoupler
16
Filter
16
Parallel → Serial
Bus
ASIC
S7-400 bus
1
2
Byte 0 3
4 0
5 1N
6 1
7 2N
8 2
9 3N
10 3
11 4N
12
13
14
15 4
16 5N
17 5
18 6N
19 6
20 7N
21 7
22 8N
23
24
25
Byte 1 26
27 0
28 9N
29 1
30 10N
31 2
32 11N
33 3
34 12N
35
36
37
38
39 4
40 13N
41 5
42 14N
43 6
44 15N
45 7
46 16N
47
48
Order Number
6ES7 422-5EH00-0AB0
Characteristics
The SM 422; DO 16 x 20 to 120 VAC/2 A is a digital output module with the
following characteristics:
• 16 outputs, isolated in groups of 1
• Nominal output voltage: 20 to 120 VAC
• Diagnostic interrupt capability
• Output level selectable in STOP mode
Fault/Error Messages
You can use SFCs to read out system-wide, module-specific, and channel-specific
diagnostic messages from the module at any time.
You can read the fault cause from the diagnostic buffer in STEP 7.
Outputs
Backplane 16 galv. Front
bus Control logic isolated connector
outputs
(Fuse, Triac, L x 16
P bus Bus Buffer x16
EPROM 16 LEDs overvoltage
ASIC
16 optos protector) Q x 16
x16 x16
Front
connector
plugged
Diagnostics
1 INTF
2 EXTF
Byte 0 3
4 0
5 1L1
6 1
7 2L1
8 2
9 3L1
10 3
11 4L1
12
13
14
15 4
16 5L1
17 5
18 6L1
19 6
20 7L1
21 7
22 8L1
23
24
25
Byte 1 26
27 0
28 9L1
29 1
30 10L1
31 2
32 11
33 3
34 12L1
35
36
37
38
39 4
40 13L1
41 5
42 14L1
43 6
44 15L1
45 7
46 16L1
47
48
Diagnostic Parameter
The module checks for internal and external faults. You can activate the individual
diagnostic types under “Module Properties” in STEP 7.
• Fuse fault: the module monitors all outputs and checks the fuses. For the fuse
monitoring function to work, the load voltage and load must be connected.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
Default Parameters
If you have not assigned parameters to the relevant module using STEP 7, all
output channels will work with the default settings of all parameters after a warm
restart.
Note
Startup of the digital modules with the default parameters is only possible in the
CR.
You can change dynamic parameters in the user program via SFC instructions.
Diagnostic Functions
You can display the following diagnostic information from the SM422; DO16 x 20 to
120 VAC/2A with SFC51.
0 0 0 0 0 0 0
RUN/STOP
3 DS0/DS1
7 0 Diagnostic byte 4
0 0 0 0 0 0 0
EPROM fault
4 DS1
7 0 Channel type
0 1 1 1 0 0 1 0
^ 72 h : DO
=
6 DS1
7 0 Number of channels
0 0 0 1 0 0 0 0 ^ 16 : 16 channels on module
=
8 DS1
7 0 Channel fault vector
9 to 25 DS1
7 0 Diagnostic byte (channel-specific)
0 0 0 0 0 0
Parameter error
Fuse failed
0 = default value 0; the module does not process this diagnostic function
1 = default value 1; the module uses constants
- = no default; the module uses variables, value 1 corresponds to a fault
Warning
! May cause personal injury.
When you change a fuse without disconnecting the front connector from the
module, you may experience injury from an electric shock.
Remove the front connector before you change a fuse.
Order Number
6ES7 422-1BL00-0AA0
Characteristics
The SM 422; DO 32 x 24 VDC/0.5 A is a digital output module with the following
characteristics:
• 32 outputs, isolated in a group of 32, that is, all outputs are connected to a
common ground
• Output current 0.5 A
• Nominal load voltage: 24 VDC
Note
The status LEDs indicate the system state even if the front connector is not
plugged in.
Process Module
1
1L+
2
3 1L+
4 0
5 1
6 2
7 3
8 4
40 1
41 2
42 3
43 4
44 5
45 6
46 7
47
48 M
L+ M
Order Number
6ES7 422-1BH10-0AA0
Characteristics
The SM 422; DO 16 x 24 VDC/2 A is a digital output module with the following
characteristics:
• 16 outputs, isolated in two groups of 8, that is, each group of 8 outputs is
connected to the same ground.
• Output current 2 A
• Nominal load voltage: 24 VDC
Note
To start up the module, connect the nominal load voltage at least once to each
group of 8 outputs.
The status LEDs indicate the system state even if the front connector is not
plugged in.
Caution
! To commission the module, each group of 8 inputs must be supplied at least once
with rated load voltage (for example, connection of 1L and 3L). If a group is not
supplied – for example, due to a failure of 1L and 2L – all outputs including those
in the second group are turned off. The function of the status LED remains as it is.
Process Module
1
2
3 1L+
4 0
5
6 1
7
43 6
44
45 7
46
47 2M
48 2M
Order Number
6ES7 422-1FF00-0AA0
Characteristics
The SM 422; DO 8 x 120/230 VAC/5 A is a digital output module with the following
characteristics:
• 8 outputs, isolated in groups of 1
• Nominal output voltage: 120/230 VAC
Note
The status LEDs indicate the system state even if the front connector is not
plugged in.
Status
LEDs
Int./ext. Int./Ext.
Comparator Optocoupler
error error
indication detector
Galvanic
isolation
Process Module
1 INFT
2 EXTF
3 t
4 0
5 1L
6 F100
7 1N
8
9
10 1
11 2L
12 F200
13 2N
14
43
44
45 7
46 8L
47 F800
48 8N
Warning
! May cause personal injury.
When you change a fuse without disconnecting the front connector from the
module, you may experience injury from an electric shock.
Remove the front connector before you change a fuse.
Order Number
6ES7 422-1FH00-0AA0
Characteristics
The SM 422; DO 16 x 120/230 VAC/2 A is a digital output module with the
following characteristics:
• 16 outputs, isolated in four groups of four channels
• Nominal output voltage: 120/230 VAC
Note
The status LEDs indicate the system state even if the front connector is not
plugged in.
Status
LEDs
Int./ext. Int./Ext.
Comparator Optocoupler
error error
indication detector
Galvanic
isolation
Process Module
39 4
40
41 5
42
43 6
44
45 7
46 4L
47 F4
48 4N
Warning
! May cause personal injury.
When you change a fuse without disconnecting the front connector from the
module, you may experience injury from an electric shock.
Remove the front connector before you change a fuse.
Order Number
6ES7 422-1HH00-0AA0
Characteristics
The SM 422; DO 16 x 30/230 VUC/Rel 5 A is a relay output module with the
following characteristics:
• 16 outputs, isolated in 8 groups of two channels
• Nominal output voltage: 230 VAC/ 125 VDC
Note
The status LEDs indicate the system state even if the front connector is not
plugged in.
S7-400 bus
Output
disable Bus
logic ASIC
4 4 4 4
2 2 2 2 2 2 2 2
2 2 2 2 2 2 2 2
1
2
3
4 0
5 1
6 1L
7
8
39 4
40 5
41 7L
42
43
44 6
45 7
46 8L
47
48
Order Number
6ES7 422-5EH10-0AB0
Reverse-polarity
protection & fault Lx2
detection
Front connector
detection
Diagnostics
1 INTF
2 EXTF
Byte 0 3
4 0
5
6 1
7
8 2
9
10 3
11
12
-+ 13 L1+
14 L1+
15 4
16
17 5
18
19 6
20
21 7
22
23 M1
24
25
Byte 1 26
27 0
28
29 1
30
31 2
32
33 3
34
35
36
-+ 37 L2+
38 L2+
39 4
40
41 5
42
43 6
44
45 7
46
47 M2
48 M2
Diagnostic Parameter
The module checks for internal and external faults. You can activate the individual
diagnostic types under “Module Properties” in STEP 7.
• Missing load voltage: The module monitors the voltage supply for both output
groups. An error indicates that the voltage is too low (typically less than 14 V),
the L+ or M connection is missing, or a fuse has blown.
• Short circuit to ground: The module reports on a channel-by-channel basis
outputs that have been overloaded or shorted.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
Note
Startup of the digital modules with the default parameters is only possible in the
CR.
You can change dynamic parameters in the user program via SFC instructions.
The structure of the dynamic parameters for data set 1 is shown below:
Diagnostic Functions
You can display the following diagnostic information from the
SM422; DO 16 x 20-120 VAC/1.5 A using SFC51.
0 0 0 0 0 0 0
Operating state RUN/STOP
3 DS0/DS1
7 0 Diagnostic byte 4
0 0 0 0 0 0 0
EPROM fault
4 DS1
7 0 Channel type
0 1 1 1 0 0 1 0
^ 72 H : DO (Digital Output)
=
5 DS1
7 0 Length of information per channel
0 0 0 0 1 0 0 0 ^ 8 bits long
=
Fault in channel 8
Fault in channel 9
Fault in channel 10
Fault occurred in channel 11
Fault in channel 12
Fault in channel 13
Fault in channel 14
Fault in channel 15
9 to 25 7 0 Diagnostic byte DS1
0 0 0 0 0 (channel-specific)
Parameter error
Short circuit to ground overload
Load voltage missing
0 = default value 0; the module does not process this diagnostic function
1 = default value 1; the module uses constants
- = no default; the module uses variables, value 1 corresponds to a fault
Warning
! May cause personal injury.
When you change a fuse without disconnecting the front connector from the
module, you may experience injury from an electric shock.
Remove the front connector before you change a fuse.
Order Number
6ES7 421-1FH20-0AA0
Characteristics
The SM 421; DI 16 x 120/230 VUC; input characteristic to IEC 1131, Type 2 is a
digital input module with the following characteristics:
• 16 inputs, isolated in groups of 4
• Nominal input voltage: 120/230 VUC
• Characteristic to IEC 1131, Type 2
• Suitable for switches and 2-wire proximity switches (BEROs)
Note
The status LEDs indicate the process status.
1
2
3
4 0
5
6 1
7
Order Number
6ES7 421-7BH00-0AB0
Characteristics
The SM 421; DI 16 x 24 VDC is a digital output module with the following
characteristics:
• 16 inputs, isolated in two groups of eight channels
• Nominal input voltage: 24 VDC
• Suitable for switches and 2-wire proximity switches (BEROs, IEC1131 Type 2).
• Two short-circuit-proof sensor supplies for eight channels each
• External redundant supply to the sensor supply possible
• Group fault display for internal faults (INTF) and external faults (EXTF)
• Status indicated ”Sensor voltage (Vs) OK”
• Setting of input delay possible
• Hardware interrupt capability for rising and/or falling edge
• Substitute values can be set in the input rangere
• Diagnostic capability (wire-break detection, sensor supply fault)
• Diagnostic interrupt capability
Note
The status LEDs indicate the process state.
Note
To ensure that the wire break is detected, you will require an external sensor
protective circuit (10 to 18 k resistor (exception: operating 2-wire BEROs; no
additional protective circuit is necessary here). The resistor has to be connected in
parallel to the contact. The resistor should be positioned as close as possible to
the sensor. If the wire-break diagnostics are not assigned, this resistor is not
required.
Hardware Interrupt
If a hardware interrupt was triggered by the module, no further channel can be
registered until the interrupt is acknowledged by the system. Hardware interrupts
from channels not currently registered which occurred in the meantime are
subsequently signaled following acknowledgement. A diagnostic interrupt can be
triggered during this time. If a further edge change occurs on the same channel
during the time from triggering the hardware interrupt to acknowledging it, the loss
of the hardware interrupt is signaled to the system by means of a diagnostic
interrupt, other channels are subsequently signaled following acknowledgement.
The interrupt-triggering channels are stored in the local data of the interrupt OBs
(OB40 to OB47). One bit is assigned per channel.
The hardware interrupt supplementary information is two words long. These words
have bit numbers 0 to 31. Bits 16 to 31 are not assigned. In the assigned bits, the
bit numbers correspond to the channel numbers.
Note
Starting up digital input modules with the default parameter assignments is only
possible in the CR.
Diagnostic Parameter
The module checks for internal and external faults. You can activate the individual
diagnostic types with YES. The diagnostic function is executed and any fault/error
is signaled by
• A diagnostic entry and
• A fault/error LED.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
Only byte-wise setting of the input delay is possible, that is, the setting for
channel 0 applies to inputs 0 to 7 and the value for channel 8 applies to inputs 8 to
15. The parameters entered for remaining channels (1 to 7 and 9 to 15) must be
the same as the value 0 or 8 otherwise the relevant channels will be signaled as
being wrongly assigned. Any hardware interrupts which occurred in the meantime
are subsequently signaled following acknowledgement.
5.17.5 Diagnostics
Fault Description
Internal fault The internal fault (INTF) LED indicates faults detected by the module
(INTF) within the module.
This LED indicates on the front of the module the status of the internal fault
diagnostic bit.
The LED remains lit until all internal faults have been corrected.
If the diagnostic interrupt has been enabled, the LED remains lit until all
internal faults have been corrected and acknowledged.
External fault The external fault (EXTF) LED indicates faults detected by the module on
(EXTF) the process side.
This LED indicates on the front of the module the status of the external
fault diagnostic bit.
The LED remains lit until all external faults have been corrected.
If the diagnostic interrupt has been enabled, the LED remains lit until all
external faults have been corrected and acknowledged.
Fault/Error Messages
You can use SFCs to read out system-wide and channel-specific diagnostic
messages from the module at any time.
You can read the cause of the fault from the diagnostic buffer.
Note
Fault/error messages are not possible via diagnostic interrupts if the module is
plugged into ER-1/ER-2.
If a diagnostic interrupt is enabled for a module in ER-1/ER-2, module diagnostics
can no longer be updated after the occurence of the first diagnostic message.
Module fault
Internal fault
External fault
Channel fault
External auxiliary voltage missing
Front connector missing
Not assigned
Wrong parameters
1 7 0 Diagnostic byte 2 DS0/DS1
0 0 0 1 1 1 1
Module class
Channel information available
2 7 0 Diagnostic byte 3 DS0/DS1
0 0 0 0 0 0
RUN/STOP
Internal voltage failed
3 7 0 Diagnostic byte 4 DS0/DS1
0 0 0 0 0 0
EPROM fault
Parameter error
Wire break
Sensor supply missing
0 = default value 0; the module does not process this diagnostic function
1 = default value 1; the module uses constants
- = no default; the module uses variables, value 1 corresponds to a fault
Response to Faults/Errors
The following table shows the input values of the module depending on possible
causes of faults.
The process value of incorrectly set channels is connected with the “0” signal
independent of the parameter “Response to Fault/Error”.
If an input delay of 100 µs is assigned and the response to the fault is set to RLV
or the response to the fault is set to SSV and the substitute value is assigned as
“1”, if a fault occurs at a channel which had the process value “1”, “0” may briefly
be output as the process data and a hardware interrupt may be generated before
the last valid value or the substitute value (“1”) is displayed.
CPU Operating State Supply Voltage L+ to Digital Input Value of Digital Module
Module
POWER ON RUN L+ present Process value
L+ missing 0 signal *)
STOP L+ present Process value
L+ missing 0 signal*)
POWER – L+ present –
OFF
L+ missing –
Order Number
6ES7 422-7BL00-0AB0
Characteristics
The SM 422; DO 32 x 24 VDC/0.5 A is a digital output module with the following
characteristics:
• 32 outputs, isolated in groups of eight channels
• Output current 0.5 A
• Nominal load voltage: 24 VDC
• Short-circuit protection of the outputs
• Parallel switching of 2 outputs for the redundant triggering of a load or to
increase performance
• Group fault display for internal faults (INTF)
• Group fault display for external faults (EXTF)
• Diagnostic capability
• Diagnostic interrupt capability
• Wire-break detection
• Short-circuit detection
• Substitute values can be set
Note
The status LEDs indicate the system state even if the front connector is not
plugged in.
1L+ monitoring 1
1L+ INTF
2
Fuse monitoring EXTF
3 1L+
1L+ +
Triggering Triggering 4
0
Channel 5
status 1
display 6
Diagnostics 2
7
3
8
Output status 4
9
5
10
6
11
7
1M 1M 12 1M
2L+ 13
2L+ 2L+ 14 2L+
+
0 15
1 16
2 17
3 18
4 19
5 20
Backplane bus connection
6 21
7 22
2M 23
2M
2M 24
3L+ 25
3L+ 3L+ 26 3L+
+
0 27
1 28
2 29
3 30
4 31
5 32
6 33
7 34
3M
3M 35
3M 36
4L+ 37
4L+ 4L+
4L+ 38
+
0 39
1 40
2 41
3 42
4 43
5 44
6 45
7 46
4M 47
4M 4M 48
L+
24V
Digital Output Module SM 422; Value Range Default Values Area Affected
DO 32 x 24 VDC/0.5A
Static Parameters
Target CPU for interrupt 1/2/3/4 1 Module
Diagnostics: load voltage L+ missing Yes/No No Channel group
/ sensor supply missing
Diagnostics: wire break Yes/No No Channel
Short circuit to ground Yes/No No Channel
Short circuit to L+ Yes/No No Channel
Dynamic Parameters
Diagnostic interrupt enable Yes/No No Module
Reaction to CPU STOP Switch to substitute value Switch to Module
(SSV)/ substitute value
Retain last valid value (SSV)
(RLV)
Switch substitute values 1 Yes/No No Channel
Note
Starting up digital output modules with the default parameter assignments is only
possible in the CR.
Diagnostic Parameter
The module checks for internal and external faults. You can activate the individual
diagnostic types with YES. The diagnostic function is executed and any fault/error
is signaled by
• A diagnostic entry and
• A fault/error LED.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
5.18.4 Diagnostics
Fault Description
Internal fault The internal fault (INTF) LED indicates faults detected by the module
(INTF) within the module.
This LED indicates on the front of the module the status of the internal fault
diagnostic bit.
The LED remains lit until all internal faults have been corrected.
If the diagnostic interrupt has been enabled, the LED remains lit until all
internal faults have been corrected and acknowledged.
External fault The external fault (EXTF) LED indicates faults detected by the module on
(EXTF) the process side.
This LED indicates on the front of the module the status of the external
fault diagnostic bit.
The LED remains lit until all external faults have been corrected.
If the diagnostic interrupt has been enabled, the LED remains lit until all
external faults have been corrected and acknowledged.
Fault/Error Messages
You can use SFCs to read out system-wide and channel-specific diagnostic
messages from the module at any time.
You can read the cause of the fault from the diagnostic buffer.
Note
Fault/error messages are not possible via diagnostic interrupt if the module is
plugged into ER-1/ER-2.
If a diagnostic interrupt is enabled for a module in ER-1/ER-2, module diagnostics
can no longer be updated after the occurence of the first diagnostic message.
Module fault
Internal fault
External fault
Channel fault
External auxiliary voltage missing
Front connector missing
Not assigned
Wrong parameters
1 Diagnostic byte 2 DS0/DS1
7 0
0 0 0 1 1 1 1
Module class
Channel information available
2 7 0 Diagnostic byte 3 DS0/DS1
0 0 0 0 0 0
RUN/STOP
Internal voltage failed
3 7 0 Diagnostic byte 4 DS0/DS1
0 0 0 0 0 0 0
EPROM fault
4 7 0 Channel type DS1
0 1 1 1 0 0 1 0
^ 72 h : DO
=
5 7 0 Length of information per channel DS1
0 0 0 0 1 0 0 0 ^ 8 bits long
=
6 7 0 Number of channels DS1
0 0 1 0 0 0 0 0 ^ 32 : 32 channels on module
=
7 7 0 Channel fault vector DS1
0 = default value 0; the module does not process this diagnostic function
1 = default value 1; the module uses constants
- = no default; the module uses variables, value 1 corresponds to a fault
Introduction
There are two ways of setting the type of measurement and measuring ranges of
the analog input channels of the S7-400 analog modules.
• With a measuring range submodule and STEP 7.
• Using the wiring of the analog input channel and STEP 7.
The method used with the individual analog modules is module-specific and is
described in detail in the module section.
This section describes how to set the type of measurement and measuring range
using measuring range submodules.
Setting the Type of Measurement and Measuring Ranges via Measuring Range
Submodules
If the analog modules have measuring range submodules, they will be supplied
with the measuring range submodules plugged in.
You might have to reconnect the measuring range submodules to change the type
of measurement or measuring range. Please note that the measuring range
submodules are located on the analog input module side. It is therefore necessary
to make sure before installing the analog input module, whether or not you have to
set the measuring range submodules to another type of measurement and another
measuring range. The assignment of measuring range submodules to measuring
ranges is described under the relevant analog modules and printed on the module
next to the measuring range submodules.
D
AB
C
Markings on the
AB
C
measuring range
D
submodule
2. Insert the measuring range submodule into the analog input module at the
desired setting (1).
3. The measuring range that points to marking point (2) is the one selected.
Introduction
Depending on their functionality, the analog input modules use a subset of the
parameters or value ranges listed below.
± 25 mV
± 50 mV
± 80 mV
± 250 mV
± 500 mV
±1V
± 2.5 V
±5V
1 to 5 V
± 10 V
± 5 mA
± 10 mA
0 to 20 mA
4 to 20 mA
± 20 mA
4 to 20 mA
48
150
300
600
6000
Resistance measuring range, 3-wire connection
48
150
300
600
6000
Type B
Type N
Type E
Type R
Type S
Type J
Type L
Type T
Type K
Type U
Diagnostics
Ground fault
Check for short circuit to ground
Check for short circuit to phase
Wire break
Reference channel check
Underflow
Overflow
None
50 Hz interference suppression
60 Hz interference suppression
400 Hz interference suppression
Smoothing
None
Weak smoothing
Medium smoothing
Strong smoothing
Reference junction
None
RTD on channel 0
Reference temperature value dynamic
End-of-cycle interrupt
Basic setting
Reference Junction
If you have connected a thermocouple, you have the following possible methods
for determining the reference junction:
Reference Explanations
Junction
None The module captures only the temperature difference between the
measuring junction and the free ends of the thermocouple or
equalizing conductor.
RTD on channel 0 Connect a platinum or nickel resistance thermometer at channel 0
that captures the reference junction in the climatic temperature range.
In this case, you can use any thermocouple types on the remaining
channels.
Reference Select this specification if there is a constant temperature at your
temperature reference junction or if the temperature of the reference junction is
captured by another module.
You can specify the temperature value in the “Reference
temperature” parameter and correct dynamically in RUN.
Reference Temperature
Here, you can specify the reference junction temperature in 0.01o C (climatic
temperature range) for capturing temperatures by means of thermocouples.
You can correct these parameters via your user program. This means you can
capture the reference junction temperature via another module.
Smoothing
The individual measured values are smoothed with digital filtering. Depending on
the module, you can choose between no smoothing, weak, medium, or strong
smoothing. The stronger the smoothing, the greater the time constant of the filter.
Diagnostics
Below is a description of the possible diagnostic types. The individual modules use
a subset of the diagnostic types listed, depending on their functionality. You will find
detailed information under the module descriptions.
The module checks for internal and external faults. You can activate the individual
diagnostic types with YES. The diagnostics are carried out and in the event of a
fault
• The value 7FFFH is indicated,
• A diagnostic entry is made, and
• This is indicated by the fault LED lighting up.
If you have deactivated diagnostics, the fault will not be indicated.
You cannot deactivate checks not listed here such as the check to see whether the
front connector is plugged in or if the load voltage is present.
Diagnostic Explanations
Type
Ground The module checks that the permissible common-mode voltage is being
fault observed.
Short circuit The sensor supply of 2-wire transducers is monitored for short circuit to the
to ground ground potential.
Reference You enable the group error signal of the reference junction here. If this
channel indicates an error, for instance, wire break on channel 0 or overflow of the
error reference temperature value, the reference channel error is signaled here for
the thermocouple channel to be set.
Underflow If the digitized measured value drops below the limit 8100H or the relevant
limit of the temperature sensor, the measured value is generally set to
8000H. If you have activated the monitor, a fault will be signaled as well.
Overflow If the digitized measured value exceeds the limit 7EFFH or the relevant limit
of the temperature sensor, the measured value is generally set to 7FFFH. If
you have activated the monitor, a fault will be signaled as well.
Wire break We distinguish between physical and computer wire-break checks.
• In the case of the physical wire-break check, a test current is sent across
the voltage or resistance sensor and the current flow is detected.
This procedure is normally only possible in the case of passive sensors
(thermocouples and resistance sensors).
In the case of active sensors, the function depends on the loop resistance
which is primarily determined by the internal resistance of the sensor.
If the module can no longer drive the test current against the connected
measured value sensor, a wire-break signal is generated in certain
circumstances at higher voltages. We therefore recommend that you
switch off the wire-break check completely in the measuring range 10 V
by means of STEP 7.
If you use an active re-adjusting sensor, the measured value can be
corrupted under certain circumstances. In this case, you should switch off
the wire-break check using STEP 7.
If you have wired a sensor to two modules in parallel, the check current of
one module would interfere with the capture of the measured value by the
other module. You must also switch off the wire-break check in this case.
• The computer wire-break check is executed in the life-zero measuring
ranges. If the value drops below the limit ED00H (-4864) (see Table 6-3
“Life-Zero Input Ranges”) this is interpreted as a wire break.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
Example
A hardware interrupt is also generated if the measured value comes back down
below the upper limit again or back up above the lower limit.
Measured value
Upper limit
Lower limit
t
Hardware interrupt
Upper limit
exceeded 1 0 0 0
Lower limit
exceeded 0 0 1 0
Note
If you use the module in the ER-1/ER-2, you must leave these parameters at their
default values because the interrupt lines are not available in the ER-1/ER-2.
Fault/Error Messages
The module supplies the value 7FFF for the inputs if
• Parameters do not match (validity check),
• Parameters and the set measuring range do not match,
• A parameter contains coding unknown to the module.
You will find specific basic requirements under the individual module descriptions.
Note
If you use the module in the ER-1/ER-2, you must set this parameter to NO
because the interrupt lines are not available in the ER-1/ER-2.
Default Parameters
If you have not assigned parameters to the relevant module in STEP 7, all input
channels will work with the default settings of all parameters after a warm restart.
This means specifically:
Note
Startup of the analog modules with the default parameters is only possible in the
CR.
Caution
! Danger of destroying the module.
If you have not set the measuring range submodules correctly, the module can be
destroyed.
Set the measuring range submodules correctly.
* Only for modules with diagnostic capability and depending on parameter assignment
Effect of Faults/Errors
Faults/errors result in a diagnostic entry and a diagnostic interrupt in analog
modules with diagnostic capability and the relevant parameter assignment (see
Section 6.13). The LED on the analog module lights up.
Limit value comparisons are not carried out in the case of detected faults/errors.
The LED also lights up in the case of external faults, regardless of the operating
state of the CPU.
6.3.1 Conversion Time and Cycle Time of the Analog Input Channels
Conversion Time
The conversion time consists of the basic conversion time and the additional
conversion times for:
• Resistance measurement
• Wire-break monitoring
The basic conversion time depends on the conversion method (integrated method,
successive approximation) of the analog input channel. In the case of the
integrated conversion methods, the integration time is incorporated in the
conversion time. See the technical specifications for the integration times of the
individual analog modules. The integration time depends on the interference
frequency suppression you set with STEP 7.
Cycle Time
Analog-digital conversion and transfer of the digitized measured values to the
memory or along the backplane bus of the S7-400 takes place sequentially, that is,
the analog input channels are converted in order one after the other. The cycle
time; that is, the time until an analog input value has been converted again, is the
sum of the conversion times of all activated analog input channels of the analog
input module. Deactivate unused analog input channels in STEP 7 in order to
minimize the cycle time.
The figure below gives a breakdown of the cycle time for an n-channel analog input
module.
Structure of Thermocouples
A thermocouple consists of
• The thermocouple (sensors) itself and
• The relevant installation and connection parts.
The thermocouple itself comprises two wires, made of different metals or metal
alloys, whose ends are soldered or welded together. There are different
thermocouple types, for example, K, J, N, depending on the different materials
used. The measuring principle is the same for all thermocouples regardless of their
type.
Measuring
junction
Thermocouple with plus and
minus shanks
Connection point
Equalizing conductor
Reference
junction
Supply lead
(Cu)
°C
Connecting Thermocouples
Connect the thermocouple directly or via equalizing conductors to the inputs of the
module. Independently of the other channels, each channel can use one of the
possible thermocouple types supported by the analog module.
M+
M-
M+
M-
Equalizing conductor
IC +:Constant current line (positive)
IC -:Constant current line (negative)
M +:Measuring line (positive)
M -:Measuring line (negative)
Non-Isolated Thermocouples
If you use non-isolated thermocouples, you must ensure that the permissible
common-mode voltage is maintained.
M+
M-
I C+
Equalizing
conductor I C-
M+
M-
M+
M-
Reference
Copper
junction conductor IC +:Constant current line (positive)
IC -:Constant current line (negative)
M +:Measuring line (positive)
M -:Measuring line (negative)
Figure 6-2 Connecting Isolated Thermocouples of the Same Type with External
Compensation by a Resistance Thermometer Connected to Channel 0
Voltage sensors
The figure below shows you how to connect voltage sensors to an analog input
module. (The L+ supply is not necessary in the case of voltage sensors.)
+ M+
U M-
- M+
+ M-
U
-
MANA*
Four-wire transducers with voltage output are connected in the same way as
voltage sensors.
+24 V
Sensor, e.g.
pressure gauge 2-wire L+
transducer 4 to 20 mA
+ M+
P M-
-
M+
P +
2-wire M-
transducer -
M M
The figure below shows how to connect current sensors as 2-wire transducers to
the SM 431; 8 x 13 bit module.
+24 V
Sensor, e.g.
pressure gauge 2-wire MV+
transducer
+ MI+
P MI+
-
M-
P +
2-wire MV+
transducer -
MI+
MI+
M-
M MANA
VA
Sensor, e.g.
pressure gauge 4-wire
transducer M+
P +
M-
-
M+
P
+ M-
4-wire
transducer -
VA
MANA*
The figure below shows how to connect current sensors as 4-wire transducers to
the SM 431; 8 x 13 bit module.
VA
VA
MANA
VA = Auxiliary power
Introduction
The resistance thermometers/resistances are measured in a 4-wire or 3-wire
connection. A constant current is supplied to the resistance
thermometers/resistances via the IC + and IC - connections. The voltage occurring
at the resistance thermometer/resistance is measured via the M + and M -
connections. This achieves a high degree of accuracy in the measured results for
4-wire connection.
4-Wire Connection
The figure below shows you how to connect 4-wire connections of resistance
thermometers/resistances.
M+
M-
IC+
IC-
IC
In the case of 2-wire and 3-wire connections, you must apply the relevant jumpers
on the module between M + and IC + and M - and IC - . However, you must reckon
with losses in accuracy in the measured results here.
3-Wire Connection
The figure below shows you how to connect 3-wire connections of resistance
thermometers/resistances.
M+
M-
IC+ IM+
IC- IM-
Introduction
The relevant precautions must be taken to prevent the permissible potential
difference DCM (common mode) being exceeded when connecting sensors. These
measures differ between isolated measured value sensors and non-isolated
measured value sensors.
Isolated
measured
value sensors M+
+
VI1
- M-
+
DCM1 M+
- +
VI2
- M-
+
DCM2
-
MANA*
DISO
Local
VI = Input voltage ground
* Connection required for modules with MANA
Introduction
This section gives an overview of the parameters of the analog output modules.
Depending on their functionality, the modules use a subset of the parameters or
value ranges listed below.
You can set the parameters using STEP 7.
Output Type/Range
Here you select an output type for the corresponding channel. For each output
type you have the possibility of entering a subset of the parameters or value
ranges listed below. You can set the parameters using STEP 7.
Default Parameters
If you have not assigned parameters to the relevant module in STEP 7, all output
channels will work with the default settings of all parameters after a warm restart.
This means specifically:
Note
Starting up the analog modules with the default parameters is only possible in the
CR.
Conversion Time
The conversion time of the analog output channels includes the transfer of the
digitized output values from the internal memory and the digital-analog conversion.
Cycle Time
The data of the analog output channels are converted sequentially.
The cycle time; that is, the time until an analog value has been converted again, is
the sum of the conversion times of all active analog output channels of the analog
output module.
The figure below gives a breakdown of the cycle time for an n-channel analog
output module.
Settling Time
The settling time (t2 to t3); that is, the time between the presence of the converted
value and reaching the specified value at the analog output, depends on the load.
Here, a distinction must be made between resistive, capacitive, and inductive load.
Response Time
The response time (t1 to t3), that is the time between the presence of the digital
output values in the internal memory and reaching the specified value at the analog
output, is, in the worst case, the sum of the cycle time and the settling time. The
worst case arises if the analog channel is converted shortly before transfer of a
new output value and converted back only after conversion of the other channels
(cycle time).
The figure below shows the response time of the analog output channels.
tR
tS
tc
t1 t2 t3
tA = Response time
tC = Cycle time corresponds to n conversion time
(n = activated channels)
tE = Settling time
t1 = New digitized output value available
t2 = Output value received and converted
t3 = Specified output value reached
RL
MANA
M
0V
You must connect the sensor lines (S +, S -) directly to the load. This allows the
voltage to be measured and corrected immediately at the load
You can also use only QV and MANA, with loss of accuracy, by jumpering QV with
S+ and MANA with S- on the front connector. The line resistances are not
compensated for in this case.
Introduction
The analog values for all measuring ranges and output ranges that you can use
with the S7-400 analog modules are represented in this section.
All modules use the same analog value representation but have different
resolutions.
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign
The sign (SI) of the analog value is always in bit number 15:
• ”0”
• ”1”
Example
In the example below, you can see how the unused positions in the case of low
resolution are written with “0”.
Bit pattern of a 16-bit and a 13-bit analog value
Input Ranges
The input ranges represented in Tables 6-1 to 6-3 are defined in the twos
complement representation:
27649 100.004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1
27648 100.000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0
1 0.003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Nominal
range
0 0.000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
-1 -0.003617 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Underrange
- 4864 -17.593 1 1 1 0 1 1 0 1 0 0 0 0 0 0 0 0
27649 100.004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1
27648 100.000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0
1 0.003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Nominal
range
0 0.000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
-1 - 0.003617 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Underrange
- 4864 -17.593 1 1 1 0 1 1 0 1 0 0 0 0 0 0 0 0
Introduction
The tables in this section contain the measured value representations for the
individual measuring ranges of the analog input modules. The table values apply
for all modules with the relevant measuring ranges.
Table 6-7 Analog Value Representation in the Current Measuring Ranges ± 20 mA to ± 3.2 mA
*155o C 250o C
130o C *1000 oC
*295 oC Overrange
850o C
250o C
0.003617 % 1 1 0.01o C 0.01o C 0.1o C 0.1o C
0% 0 0 0.00o C 0.00o C 0.0o C 0.0o C Nominal range
-1 FFFF - 60o C
- 200o C Underrange
60o C *- 105o C
*- 243o C
*-105o C
- 120o C Underflow
*- 145o C
*Overrange or underrange: The rise in the characteristic curve that exists on exiting the linearized nominal
range is retained in the overrange/underrange.
*-120o C
*-170o C *-170o C - 270o C - 270o C
Underrange
*-390o C *-390o C
Underflow
*Overrange or underrange: The rise in the characteristic curve that exists on exiting the linearized nominal
range is retained in the overrange/underrange.
Underflow
*Overrange or underrange: The rise in the characteristic curve that exists on exiting the
linearized nominal range is retained in the overrange/underrange.
Output Range
32512 0% 0 1 1 1 1 1 1 1 x x x x x x x x Overflow
32511 117.589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Overrange
27649 100.004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1
27648 100.000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0
1 0.003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Nominal
range
0 0.000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
-1 -0.003617 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Underrange
- 6912 -25.000 1 1 1 0 0 1 0 1 0 0 0 0 0 0 0 0
- 6913 1 1 1 0 0 1 0 0 1 1 1 1 1 1 1 1 Limited to
overcontrol
-25.000 range,
- 32512 1 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 lower limit
0 V or 0 mA
- 32513 - 25 % 1 0 0 0 0 0 0 0 x x x x x x x x Underflow
Introduction
The tables in this section contain the measured value representations for the
individual measuring ranges of the analog output modules. The table values apply
for all modules with the relevant measuring ranges.
Voltage Range ± 10 V
*Underrange
Current Range ± 20 mA
*Underrange
Example
A module without diagnostic capability is operated in the life-zero measuring range
4 to 20 mA. The current of the measured value sensor drops to a value around
0 mA. The module enters the digitized measured value 7FFFh for this channel
because it has detected a computer wire break.
Internal Fault The internal fault (INTF) LED indicates faults detected by the module
(INTF) within the module.
The LED remains lit until all internal faults have been corrected.
If the diagnostic interrupt has been enabled, the LED remains lit until
all internal faults have been corrected and acknowledged.
External Fault The external fault (EXTF) LED indicates faults detected by the
(EXTF) module on the process side.
The LED remains lit until all external faults have been corrected.
If the diagnostic interrupt has been enabled, the LED remains lit until
all external faults have been corrected and acknowledged.
Fault/Error Messages
You can use SFCs to read out system-wide and channel-specific diagnostic
messages from the module at any time.
You can read the cause of the fault from the diagnostic buffer (see STEP 7).
Note
Fault/error messages are not possible via diagnostic interrupt if the module is
plugged into ER-1/ER-2.
If a diagnostic interrupt is enabled for a module in ER-1/ER-2, module diagnostics
can no longer be updated after the occurrence of the first diagnostic message.
Order Number
6ES7 431-1KF00-0AB0
Characteristics
The SM 431; AI 8 x 13 Bits is an analog input module with the following
characteristics:
• 8 inputs for voltage/current measurement
• 4 inputs for resistance measurement
• Resolution 13 bits
• Isolated
• Permissible common-mode voltage 30 VAC
MV0+
MI0+
MI0+
M0–
D
Protective circuit, current routing
CH0
S7-400 bus
Bus controller
CH 1 CH1
CH7 CH7
Front connector
F_CON check
+5V
+5V
M ANA S7-400 bus
0V 0V
S7-400 bus
–5V
1
2
3
4
5
6 MV0+ MV0+ M0+
7 V MI0+
CH0 Word 0 CH0
8 MI0+
9 M0- M0- M0-
10 CH0 Word 0
11 MV1+ MV1+ IC0+
12 MI1+
CH1 Word 2 CH1
13 A MI1+
14 M1- M1- IC0-
15
16 MV2+ MV2+ M1+
17 MI2+
CH2 Word 4 CH2
18 MI2+
19 M2- M2- M1-
20 CH2 Word 4
21 MV3+ MV3+ IC1+
22 MI3+
23 CH3 Word 6 CH3
MI3+
24 M3- M3- IC1-
25 MANA
26 M ANA
27
28 MV4+ MV4+ M2+
29 V MI4+
CH4 Word 8 CH4
30 MI4+
31 M4- M4- M2-
32 CH4 Word 8
33 MV5+ MV5+ IC2+
34 MI5+
35 CH5 Word 10 CH5
A MI5+
36 M5- M5- IC2-
37
38 MV6+ MV6+ M3+
39 MI6+
CH6 Word 12 CH6
40 MI6+
41 M6- M6- M3-
42
CH6 Word 12
43 MV7+ MV7+ IC3+
44 MI7+
45 CH7 Word 14 MI7+ CH7
46 M7- M7- IC3-
47
48
Warning
! The module can be damaged.
The shunt resistance of an input channel can be destroyed if you accidentally
connect a voltage sensor to the M-/MI+ clamps of a channel.
Make sure that the front connector wiring is correct in accordance with the
connection diagram.
Parameters
The analog input module SM 431; AI 8 x 13 Bits uses the following static parameters
stored in data set 0.
Reason:
The connections of channel n+1 are used to supply the resistance connected to
channel n.
Nominal load voltage L+ Not required • Cycle time Number of active channels x
basic conversion time
Voltage supply
fortransducers No • Resolution in bits
Galvanic isolation between (incl. overrange/
bus, analog section and Yes representation in twos 13 13
local ground complement)
Basic error limits (operating error limits at 25° C, Data for Selecting a Sensor
related to input range)
Input ranges (nominal
• 1V 0.7 % ranges)/input resistance
• 10 V 0.4 % • For voltage ranges 1V/>200 k
• 1 to 5 V 0.5 % 10 V/>200 k
1 to 5 V/>200 k
• 20 mA 0.7 %
• For current ranges 20 mA/80
• 4 to 20 mA 0.7 %
4 to 20 mA/80
• 0 to 500 0.8 %
Temperature error (related to • For resistance range 0 to 600
input range) (useful to 500
• In the resistance measuring 0.02 %/K
range 0.007 %/K Permissible input voltage max. 50 V constant;
• In all other measuring for voltage input 75 V for max. 1 ms
ranges (destruction limit) (mark-space ratio
1:20)
Linearity error (related to input
range) 0.05 % Permissible input current
for current input 50 mA constant
Repetition accuracy (in settled
(destruction limit)
state at 25° C, related to input
range) Connection of signal
0.1 % sensors
Code gaps Code gaps occur • For voltage Possible
systematically in measurement
the ranges • For current Possible
1 V, 1 to 5 V, measurement
4 to 20 mA • As 2-wire transducer Possible, with
Status, Interrupts, Diagnostics external transducer
supply
Interrupts
• As 4-wire transducer Possible
• Limit value interrupts No
• For resistance Possible, line
• Diagnostic interrupt No measurement with resistances are also
Diagnostic functions 2-wire connection measured
• Fault indicators on the
module
for internal faults No 3-wire connection Not possible
for external faults No 4-wire connection Possible
• Diagnostic information Characteristic curve
display No linearization No
Temperature
compensation No
Order Number
6ES7 431-1KF10-0AB0
Characteristics
The SM 431; AI 8 x 14 Bits is an analog input module with the following
characteristics:
• Especially suitable for temperature acquisition
• 8 inputs for current and voltage measurement or
4 inputs for resistance measurement
• Resolution 14 bits
• Input ranges for voltage
• Input ranges for current
• Input ranges for resistance-type sensors
• Input ranges for resistance thermometers
• Input ranges for thermocouples
• Temperature sensor types can be assigned
• Linearization of sensor characteristic curves
• Any input ranges selectable
Adaptation of the measuring type using the measuring range submodules in
groups of 2
• Supply voltage: 24 VDC; only required when connecting 2-wire transducers
• Isolated
• Permissible common-mode voltage 120 VAC
CH0 Measuring
range
CH1 submodule 0
S7-400 bus
Bus controller
A
MULTIPLEXER
OPTO-RELAY
CH6 Measuring
range
CH7 submodule 3
+ 5V ENABLE
+ 15V +5V S7-400 bus
L+
M 0V 0V S7-400 bus
– 15V
Warning
! The module can be damaged.
The shunt resistance of an input channel can be destroyed if you accidentally
connect a voltage sensor to the channel and you set the measuring range
submodule to position C (current/4-wire transducer).
Please make sure that the measuring range submodule is in the correct position
before you connect a sensor to the module.
Parameters
The analog input module SM 431; AI 8 x 14 Bits uses static uses static parameters
stored in data set 0 and dynamic parameters stored in data set 1. The table below
shows which static parameters the module uses.
Smoothing None
Weak
Medium
Strong
Reference junction None
RTD on chanel 0
Reference temperature value dynamic
The table below shows which dynamic parameters the module uses.
None 1
Weak 4
Medium 32
Strong 64
xn (k – 1) yn–1
yn :
k
yn = Transfer value to the system in the current cycle n
Step Response
The figure below shows the step response for different smoothing factors
depending on the number of module cycles.
1
Step Response
0.63
0.5
200
0 50 100 150
k=4 Module cycles
k = 32
k = 64
Reason:
The physical wire-break check is not possible with current sensors.
Reason:
The connections of channel n+1 are used to supply the resistance connected to
channel n.
Note
If you use thermocouples, you should always set the wire-break check since then,
in the event of a wire break, the measured value automatically goes into overflow
and is detected using the measured value 7FFFH.
The measuring range submodule sets two channels. For this reason, there are
restricting parameter assignment conditions for two neighboring channels (0/1),
(2/3), (4/5), (6/7).
Measuring Range Deac- Vol- Current Current Resi- Resi- Thermo Thermo Ther-
Channel n+1 tiva- tage 4-wire- 2-wire- stance stance resi- resi- mocou-
Measuring ted trans.* trans.* 4-wire 3-wire stance stance ples
Range Channel n 4-wire 3-wire
Deactivated x x x x x
Voltage x x x
Current x x
4-wiretrans.*
Current x x
2-wiretrans.*
Resistance 4-wire x
Resistance 3-wire x
Thermo resistance x
4-wire
Thermo resistance x
3-wire
Thermocouples x x x
* trans. = transducer
Example
If you have selected the current measuring range parameter for 2-wire transducers
for channel 6, you must select only measuring range deactivated or current
measuring range for 2-wire transducers for channel 7.
Table 6-21 Thermocouples
Reason:
Specifying a reference junction temperature only makes sense in the case of
thermocouples.
If you select an RTD on channel 0 for reference junction compensation, the
following also applies:
Table 6-22 Thermocouple with Reference Junction Compensation via RTD on Channel 0
Reason:
If channel 0 is to be used as the reference junction, a resistance sensor must be
connected there that captures absolute temperatures in the climatic range. By
connecting the resistance sensor, channels 0 and 1 are assigned. You can
therefore use only channels 2 to 7 for the option.
Module-Specific Data
• from S7-400 bus (5 VDC) max. 600 mA
typ. 550 mA
Number of inputs
• From load current
• For current/voltage supply L+ max. 200 mA
measurement 8
Only necessary for
• For resistance 4
supplying 2-wire
measurement
transducers,
Cable length, shielded 200 m depending on the
• For the input range phase control of the
80 mV and transducer
thermocouples 50 m Power losses max. 3.5 W
• Surge-protection in External protection Analog Value Generation
accordance with devices required in
Measuring principle Integrating
IEC1000-4-5 the supply lines and
signal lines Interference frequency suppression
Voltages, Currents, Potentials • Can be set for interference
Load voltage L+ 24 VDC frequency f1 in Hz 60 50
Only necessary for supplying 2-wire transducers, Resulting in:
depending on the phase control of the transducer
Integration time/conversion time/resolution(per
• Reverse polarity Yes channel)
protection
Voltage supply for
• Possible integration time in ms 16.7 20
transducers • Possible basic conversion time
• Short-circuit protected Yes in ms 20.1 23.5
• Feed current per channel typ. 50 mA Additional conversion time for
Galvanic isolation Yes resistance measurement for
3-wire connection in ms 40.2 47
Galvanic isolation between
or
bus, analog section and
additional conversion time for wire
local ground Yes
break monitoring except in the
Test voltage case of resistance measurement 4.3 4.3
• Between bus and L+/M 2120 VDC in ms
or
• Between bus and analog
additional conversion time for
section 2120 VDC
wire break monitoring in the case 5.5 5.5
• Between bus and local of
ground 500 VDC resistance measurement in ms
• Between analog section
and L+/M 707 VDC
• Cycle time Number of active channels x
basic conversion time
• Between analog section
and local ground 2120 VDC • Possible resolution in bits
(incl. overrange) with smoothing 14 14
• Between L+/M and local
switched on 16 16
ground 2120 VDC
Common-mode test voltage
• Inputs to each other 120 VAC
• Between input and central
grounding point (input
voltage 0 V) 120 VAC
Interference Suppression, Error Limits Basic error limits (operating error limits at 25° C,
related to input range)
Interference voltage
suppression • 80 mV 0.17 %
for f = nx (f1 1 %), • 250 mV 0.15 %
(f1 = interference frequency)
• 500 mV 0.15 %
• Common-mode interference > 100 dB
(VPP < 120V)
• 1 V 0.15 %
> 50 dB
• Normal-mode interference • 2.5 V 0.15 %
• 500 mV 0.35 %
• 0 to 150 4-wire meas. 0.15 %
• 1 V 0.35 %
• 0 to 300 4-wire meas. 0.15 %
• 2.5 V 0.35 %
• 0 to 600 ; 4-wire meas. 0.15 %
• 5 V 0.35 %
• 0 to 5000
4-wire measurement
• 1 to 5 V 0.35 % (in the range of 6000 0.15 %
• 10 V 0.35 % • 0 to 300 3-wire meas. 0.3 %
• 0 to 20 mA 0.35 % • 0 to 600 3-wire meas. 0.3 %
• 20 mA 0.35 % • 0 to 5000
• 4 to 20 mA 3-wire measurement
4-wire transducer 0.35 % (in the range of 6000 0.3 %
• 4 to 20 mA Temperature error (related to
2-wire transducers 0.35 % input range) 0.004%/K
• 0 to 48 4-wire meas. 0.35 % Linearity error (related to
• 0 to 150 , 4-wire meas. 0.35 % input range) 0.01%
• 0 to 300 4-wire meas. 0.35 % Repetition accuracy (in
• 0 to 600 ; 4-wire meas. 0.35 % settled state at 25° C, related
to input range) 0.1%
• 0 to 5000 ;
4-wire measurement
(in the range of 6000 0.35 %
• 0 to 300 ; 3-wire meas. 0.5 %
• 0 to 600 ; 3-wire meas. 0.5 %
• 0 to 5000 Ω;
3-wire measurement
(in the range of 6000 0.5 %
Order Number
6ES7 431-1KF20-0AB0
Characteristics
The SM 431; AI 8 x 14 Bits is an analog input module with the following
characteristics:
• High-speed A/D conversion, therefore especially suitable for high-dynamic
processes
• 8 inputs for current/voltage measurement
• 4 inputs for resistance measurement
• Resolution 14 bits
• Input ranges for voltage
• Input ranges for current
• Input range for resistance-type sensor
• Free choice between voltage and current
• Supply voltage: 24 VDC
• Isolated
CH0 Measuring
range
CH1 submodule 0
S7-400 bus
Bus controller
A
MULTIPLEXER
Measuring
CH6 range
submodule 3
CH7
+ 5V ENABLE
+ 15V +5V S7-400 bus
L+
0V 0V S7-400 bus
M
– 15V
Figure 6-3 Circuit Block Diagram of the Analog Input Module SM 431; AI 8 x 14 Bits
Warning
! The module can be damaged.
The shunt resistance of an input channel can be destroyed if you accidentally
connect a voltage sensor to the channel and you set the measuring range
submodule to position C (current/4-wire transducer).
Please make sure that the measuring range submodule is in the correct position
before you connect a sensor to the module.
Parameters
The analog input module SM 431; AI 8 x 14 Bits uses the following static
parameters stored in data set 0.
1
Step Response
0.63
0.5
0
0 Filter settling time t
Smoothing
With the smoothing parameter, you choose between the two value ranges
no smoothing/strong smoothing
Switching on additional smoothing only makes sense if you have also set
interference frequency suppression. If you have only set smoothing, the measured
value resolution will be reduced to 9 bits.
The figure below shows the step response when interference frequency
suppression and smoothing are activated.
1
Step Response
0.63
0.5
0
0 Filter settling time t
Table 6-23 Measuring Range Deactivated, Resistance Measuring Range, Resistance Thermometers
Reason:
The connections of channel n+1 are used to supply the resistance connected to
channel n.
The measuring range submodule sets two channels. For this reason, there are
restricting parameter assignment conditions for two neighboring channels (0/1),
(2/3), (4/5), (6/7).
* trans. = transducer
Order Number
6ES7 431-0HH00-0AB0
Characteristics
The SM 431;AI 16 x 13 Bit has the following characteristics:
• 16 inputs for current/voltage measurement
• Resolution13 bits
• Non-isolated (no isolation between bus section and analog section)
• Permissible common-mode voltage 2 VDC/VAC
Voltage measurement
Current measurement
1
2
3
L+ L+
4
5
6 M0+ CH0 Word 0
7 M0-
8 M1+ CH1 Word 2
9 M1-
10
11 M2+ CH2 Word 4
12 M2-
13 M3+ CH3 Word 6
14 M3-
15
16 Tr M4+ CH4 Word 8
17 M4-
18 Tr M5+ CH5 Word 10
19 M5-
20
21 Tr M6+ CH6 Word 12
22 M6-
23 Tr M7+ Word 14
CH7
24 M7-
25
26
27
28 M8+ CH8 Word 16
29 M8-
30 M9+ CH9 Word 18
31 M9-
32
33 M10+ CH10 Word 20
34 M10-
35 M11+ CH11 Word 22
36 M11-
37
38 M12+ CH12 Word 24
Tr
39 M12-
40 M13+ CH13 Word 26
Tr
41 M13-
42
43 Tr
M14+ CH14 Word 28
44 M14-
45 Tr M15+ CH15 Word 30
46 M15-
47
M M
48
Figure 6-4 Terminal Connection Diagram of the Analog Input Module SM 431;AI 16 x 13 Bit
Tr
Tr
Tr
Tr
ADC
* Tr = Transducer
Tr
Tr
Tr
Figure 6-5 Block Diagram of the SM 431 Analog Input Module; AI 16 x 13 Bit
Warning
! The module can be damaged.
The shunt resistance of an input channel can be destroyed if you accidentally
connect a voltage sensor to the channel and you set the measuring range module
to position C (current/4-wire transducer).
Please make sure that the measuring range module is in the correct position
before you connect a sensor to the module.
Parameters
The analog input module SM 431;AI 16 x 13 Bit use the following static parameters
which are stored in data set 0.
The measuring range module sets two channels. For this reason, there are
restricting parameter assignment conditions for two neighboring channels (0/1),
(2/3), (4/5), (6/7).
* trans. = transducer
Order Number
6ES7 431-7QH00-0AB0
Characteristics
The SM 431; AI 16 x 16 Bits is an analog input module with the following
characteristics:
• Diagnostic capability and
• Hardware interrupt capability, therefore especially suitable for processes
requiring close monitoring
• 16 inputs (max. 8 in the case for resistance measurements)
• Resolution 16 bits
• Input ranges for voltage
• Input ranges for current
• Input ranges for resistance sensors, resistance thermometers
• Input ranges for thermocouples
• Temperature sensor types can be assigned
• Linearization of sensor characteristic curves
• Supply voltage: 24 VDC; only required when connecting
2-wire transducers
• Isolated
• Permissible common-mode voltage 120 VAC
CH0 Measuring I
CH1 range const
submodule 0
D
Bus controller
S7-400 bus
Signal
routing PGA
A
Opto-Relay
Multiplexer
Measuring
CH14 range
CH15 submodule 7
+ 15 V
L+ + 5V +5V
Diagnostics
0V S7-400 bus
L+ circuit
M - 15 V 0V
Warning
! The module can be damaged.
The shunt resistance of an input channel can be destroyed if you accidentally
connect a voltage sensor to the channel and you set the measuring range
submodule to position C (current/4-wire transducer).
Please make sure that the measuring range submodule is in the correct position
before you connect a sensor to the module.
Module fault
Internal fault
External fault
Channel fault
External auxiliary voltage missing
Front connector missing
Module not assigned parameters
Wrong parameters
1 7 0 Diagnostic byte 2 DS0/DS1
0 0 0 0 1 0 1
Module class
Channel information available
2 Diagnostic byte 3 DS0/DS1
7 0
0 0 0 0 0 0
Wrong measuring range
submodule or measuring
range submodule missing
Operating state RUN/STOP
3 7 0 Diagnostic byte 4 DS0/DS1
0 0 0 0
EPROM fault
RAM fault
ADC/DAC error
Hardware interrupt lost
Parameter error
Short circuit to ground
Wire break
Reference channel error
Underflow
Overflow
0 = default value 0; the module does not process this diagnostic function
1 = default value 1; the module uses constants
- = no default; the module uses variables, value 1 corresponds to a fault
None 1
Weak 2
Medium 16
Strong 32
xn (k – 1) yn–1
yn :
k
yn = Transfer value to the system in the current cycle n
1
Step Response
0.63
0.5
0 20 40 60 80 100
Module cycles
k=2
k = 16
k = 32
Table 6-27 Resistance Measuring Range, Resistance Thermometer with Linearization, 3-Wire and 4-Wire
Connection
Reason:
The connections of channel n+1 are used to supply the resistance connected to
channel n.
The measuring range submodule sets two channels. For this reason, there are
restricting parameter assignment conditions for two neighboring channels (0/1),
(2/3), (4/5), (6/7) (8/9), (10/11), (12/13), (14/15).
Measuring Range Deac- Vol- Current Current Resi- Resi- Thermo Thermo Ther-
Channeln+1 tiva- tage 4-wire- 2-wire- stance stance resi- resi- mocou-
Measuring ted trans.* trans.* 4-wire 3-wire stance stance ples
Range Channel n 4-wire 3-wire
Deactivated x x x x x
Voltage x x x
Current x x
4-wiretrans.*
Current x x
2-wiretrans.*
Resistance 4-wire x
Resistance 3-wire x
Thermo resistance x
4-wire
Thermo resistance x
3-wire
Thermocouples x x x
* trans. = transducer
Example
If you have selected the current measuring range parameter for 2-wire transducers
for channel 6, you must select only measuring range deactivated or current
measuring range for 2-wire transducers for channel 7.
Reason:
Assigning a reference junction only makes sense with thermocouples.
The following also applies if you select an RTD on channel 0 as the reference
junction:
Reason:
If you want to use channel 0 as the reference junction, a resistance sensor must
be connected there that captures absolute temperatures in the climatic range.
Connection of the resistance sensor occupies channels 0 and 1 so that you can
only use channels 2 to 15 with this parameter.
Reason:
You can only check for short-circuit to ground if you have connected a 2-wire
transducer.
Reason:
Wire break check is not possible in the case of current sensors, with the exception
of life-zero ranges.
Requirement: You have connected a thermocouple
Reason:
The reference channel is only checked if a thermocouple has been connected
whose reference junction is the “RTD on channel 0” or the “reference temperature
value” entered in DS1.
Reason:
There is no underflow in life-zero ranges. A value that is too low or a negative
value is interpreted as a wire break.
Reason:
You can set only one cycle interrupt.
Operating error limits (in the entire temperature Basic error limits (operating error limits at 25° C,
range, related to the input range) related to input range)
• 25 mV 0.35 % • 25 mV 0.23 %
• 50 mV 0.32 % • 50 mV 0.19 %
• 80 mV 0.31 % • 80 mV 0.17 %
• 250 mV 0.3 % • 250 mV 0.15 %
• 500 mV 0.3 % • 500 mV 0.15 %
• 1 V 0.3 %
• 1 V 0.15 %
• 2.5 V 0.3 %
• 5 V 0.3 % • 2.5 V 0.15 %
• 1 to 5 V 0.3 % • 5 V 0.15 %
• 10 V 0.3 % • 1 to 5 V 0.15 %
• 0 to 20 mA 0.3 % • 10 V 0.15 %
• 5 mA 0.3 % • 0 to 20 mA 0.15 %
• 10 mA 0.3 % • 5 mA 0.15 %
• 20 mA 0.3 % • 10 mA 0.15 %
• 4 to 20 mA
4-wire transducer 0.3 %
• 20 mA 0.15 %
• 4 to 20 mA • 4 to 20 mA
2-wire transducers 0.3 % 4-wire transducer 0.15 %
• 0 to 48 4-wire meas. 0.3 % • 4 to 20 mA
• 0 to 150 , 4-wire meas. 0.3 % 2-wire transducers 0.15 %
• 0 to 300 4-wire meas. 0.3 % • 0 to 48 4-wire meas. 0.15 %
• 0 to 600 ; 4-wire meas. 0.3 % • 0 to 150 4-wire meas. 0.15 %
• 0 to 5000 ; • 0 to 300 4-wire meas. 0.15 %
4-wire measurement
(in the range of 6000 0.3 %
• 0 to 600 ; 4-wire meas. 0.3 %
• 0 to 300 ; 3-wire meas. 0.4 % • 0 to 5000
• 0 to 600 ; 3-wire meas. 0.4 % 4-wire measurement
(in the range of 6000 0.3 %
• 0 to 300 3-wire meas. 0.3 %
• 0 to 600 3-wire meas. 0.3 %
• 0 to 5000
3-wire measurement
(in the range of 6000 0.3 %
Temperature error
(related to input range) 0.004%/K
Linearity error
(related to input range) 0.01%
Repetition accuracy
Repetition accuracy (in
settled state at 25° C,
related to the input range) 0.1%
Order Number
6ES7 431-7KF10-0AB0
Characteristics
The SM 431; AI 8 x RTD x 16 Bits is an analog input module with the following
characteristics:
• 8 differential inputs for resistance thermometers (RTD)
• Resistance thermometer (RTD) can have parameters assigned
• Linearization of the RTD characteristic curves
• Resolution 16 bits
• 25 ms update rate for 8 channels
• Galvanically isolated (programmable controller-to-field), 1500 VAC
• Permissible common-mode voltage 120 VAC
• Diagnostic capability
• Hardware interrupt capability, especially suitable for processed requiring close
monitoring
• No external power requirements
Note
This analog module does not use the measuring range submodules desribed in
the S7-400, M7-400 Programmable Controllers, Module Specifications Reference
Manual. The upper and lower limit values and the overflow ranges are different
from the ranges shown in Chapter 6.
SO+7
SE+7
SM400
SE-7 S7-400
ASIC
AGND Ch7 diff. bus
buffer AMP
Command
register and Isolated DC-DC converter
latch
+5
+9
+5 V from
-5
Mode backplane
-9
register
Overrange,
wire-break
register
INTF 1
EXTF 2
3
4
5
6 SE+0
7 SE-0
CH0 Word 0
8 SO0
9 AGND
10
11 SE+1
12 SE-1
CH1 Word 1
13 SO1
14 AGND
15
16 SE+2
17 SE-2
18 CH2 Word 2
SO2
19 AGND
20
21 SE+3
22 SE-3
CH3 Word 3
23 SO3
24 AGND
25
26
27
28 SE+4
29 SE-4
CH4 Word 4
30 SO4
31 AGND
32
33 SE+5
34 SE-5
CH5 Word 5
35 SO5
36 AGND
37
38 SE+6
39 SE-6
CH6 Word 6
40 SO6
41 AGND
42
43 SE+7
44 SE-7
CH7 Word 7
45 SO7
46 AGND
47
48
Diagnostic functions
The SM 431; AI 8 x RTD x 16 Bits uses the following diagnostic possibilities:
EPROM fault
Analog/digital converter fault
Hardware interrupt lost
4 7 0 Channel type DS1
0 1 1 1 0 0 0 1
71H : AI (analog input)
5 7 0 Length of information per channel DS1
0 0 0 1 0 0 0 0 10H : 16 bits long
Parameter error
Wire break
Underflow
Overflow
9, 11 to 7 0 Channel-specific DS1
23 diagnostic byte 2
0
User connector not wired
Sense + lead open
Sense - lead open
Calibration error*
Out of range
Current source line open
User calibration mismatch with
parameter assignment
0 = default value 0; the module does not process this diagnostic function
1 = default value 1; the module uses constants
- = no default; the module uses variables, value 1 corresponds to a fault
Smoothing
Smoothing can be set to four different levels for each channel. The smoothing filter
function is implemented in the module by providing a rolling average of the number
of readings determined by the smoothing level parameter you assign for each
channel. The number of samples used in the rolling average for a given smoothing
level is shown below.
None 1
Weak 2
Medium 16
Strong 32
Step Response
The amount of smoothing assigned to a given channel determines the step
response for that channel. The figure below shows the response to a step of 50° C
for a 100-ohm 0° C RTD using weak, medium, and strong smoothing.
Temperature
in degrees C
60
50
40
30
20
10
0
0 1 2 3 4 5 6
Step response time in seconds
Smoothing
Strong
Medium
Weak
Parameter Error
The module has diagnostic capability. Parameter errors are indicated via diagnostic
information:
• Module fault
• Internal fault
• Wrong parameters
• Module not assigned parameters
If the fault can be assigned to specific channels, the following diagnostic
information is indicated:
• Module fault
• Internal fault
• Channel fault
• Wrong parameters
• Channel information available
• Channel fault vector
• Channel parameter error
• Calibration mismatch with parameter assignment
Temperature Range
System Word Pt 100, Pt 500 Pt 1000 Ni 100 Ni 1000
Decimal Hex. Pt 200 0.00385 0.003916 0.003902 0.00392 0.00618 0.00672 0.00618 0.00672
32767 7FFF
Overflow
9350 2486 935.0
9130 23AA 913.0
8910 22CE 891.0
8800 2260 880.0 880.0
8500 2134 850.0
8300 206C 830.0
8100 1FA4 810.0
8000 1F40 800.0 800.0
1 1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-1 FFFF -0.1 -0.1 -0.1 -0.1 -0.1 -0.1 -0.1 -0.1 -0.1 -0.1
Nominal range
Overrange/underrange
Overflow/underflow
Order Number
6ES7 431-7KF00-0AB0
Characteristics
The SM 431; AI 8 x 16 Bits is an analog input module with the following
characteristics:
• 8 isolated differential analog inputs
• Input range for voltage
• Input range for thermocouple
• Input range for 4-wire transducer
• Can have parameters assigned for voltage, current, and thermocouple
• Linearization of the thermocouple characteristic curves
• Isolated bus to analog inputs
• Diagnostic capability
• Hardware interrupt capability, especially suitable for processed requiring close
monitoring
• Permissible common-mode voltage 120 VAC
• Internal current sense resistor
• Field connector (6ES7 431-7KF00-6AA0) with internal reference temperature
(shipped with module)
• Analog-to-digital conversion resolution 24 bits (including sign)
• Analog value resolution 16 bits (including sign)
• No external power requirements
Note
This analog module does not use the measuring range submodules desribed in
the S7-400, M7-400 Programmable Controllers, Module Specifications Reference
Manual. The upper and lower limit values and the overflow ranges are different
from the ranges shown in Chapter 6.
Input 0
Thermocouple connector
6ES7 431-7KF00-6AA0
Cold junction
sensor 1
+15V
-15V Cold junction
Data bus
+5V
GND sensor 2
Cold junction
sensor 3
Input 1
Cold junction
sensor 4
Input 2 Micro-
processor EEPROM
80C32
Input 3
EPROM
Input 4
RAM Reset
logic
Address bus
Input 5
S7-400 bus
Input 6
SM400
bus interface
Input 7
Diagnostic Functions
The SM 431; AI 8 x 16 Bits uses the following diagnostic possibilities:
EPROM fault
RAM fault
Analog/digital converter fault
Hardware interrupt lost
4 7 0 Channel type DS1
0 1 1 1 0 0 0 1
71H : AI (analog input)
5 7 0 Length of information per channel DS1
0 0 0 1 0 0 0 0 10H : 16 bits long
0 = default value 0; the module does not process this diagnostic function
1 = default value 1; the module uses constants
- = no default; the module uses variables, value 1 corresponds to a fault
Smoothing
Smoothing can be set to four different levels for each channel. The smoothing filter
function is implemented in the module by calculating the output of a digital filter.
The number of readings (smoothing factor) used in calculating the digital filter
output for a given smoothing level is shown below.
None 1
Weak 2
Medium 16
Strong 32
Step Response
The amount of smoothing assigned to a given channel determines the step
response for that channel. The figure below shows the full range response for any
analog input signal using none, weak, medium, and strong smoothing. The time
the output value takes to read the specified accuracy is determined by the
interference suppression selected.
Smoothing
None
Weak
Medium
Strong
displayed 1 2 16 32
values
10 Hz 100 200 1600 3200 ms
50 Hz 20 40 320 ms 640 ms
Parameter Errors
The module has diagnostic capability. Parameter errors are indicated via diagnostic
information:
• Module fault
• Internal fault
• Wrong parameters
• Module not assigned parameters
If the fault can be assigned to specific channels, the following diagnostic
information is indicated:
• Module fault
• Internal fault
• Channel fault
• Wrong parameters
• Channel information available
• Channel fault vector
• Channel parameter error
• Calibration mismatch with parameter assignment
Overflow
18200 4718 1820.0
1 1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-1 FFFF -0.1 -0.1 -0.1 -0.1 -0.1 -0.1 -0.1 -0.1 -0.1
Nominal range
Overflow/underflow
Order Number
6ES7 432-1HF00-0AB0
Characteristics
The SM 432; AO 8 x 13 Bits is an analog input module with the following
characteristics
• 8 outputs
• Resolution 13 bits
• Output ranges for voltage
• Output ranges for current
• Supply voltage: 24 VDC
• Isolated
• Permissible common-mode voltage 3 VDC
CH0
A
CH1
Bus controller
CH3
CH4
CH5
D
CH6
CH7
24 V
L+/M
Analog supply
1
2
3
L+ L+ L+
4
5
6 QV0 CH0 Word 0 QI0 CH0 Word 0
7 S0+
8 S0-
9
10
11 QV1 CH1 Word 2 QI1 CH1 Word 2
12 S1+
13 S1-
14
15
16 QV2 CH2 Word 4 QI2 CH2 Word 4
17 S2+
18 S2-
19
20
21 QV3 CH3 Word 6 QI3 CH3 Word 6
22 S3+
23 S3-
24
25 MANA M ANA M ANA
26
27
28 QV4 CH4 Word 8 QI4 CH4 Word 8
29 S4+
30 S4-
31
32
33 QV5 CH5 Word 10 QI5 CH5 Word 10
34 S5+
35 S5-
36
37
38 QV6 CH6 Word 12 QI6 CH6 Word 12
39 S6+
40 S6-
41
42
43 QV7 CH7 Word 14 QI7 CH7 Word 14
44 S7+
45 S7-
46
47
M
48 M
Function
The send and receive interface modules are required if one or more expansion
units (ER) are to be connected to one central rack (CR). This configuration is
described in the Installation Manual, Chapter 4.
Configuration
Interface modules must always be used together. While the send modules (send
IMs) are plugged into the CR, the associated receive modules (receive IMs) are
plugged into the ER connected in series in each case.
IM 461-0 Receive IM for local link without power transmission; with communication
bus
IM 460-1 Send IM for local link with power transmission; without communication bus
IM 461-1 Receive IM for local link with power transmission; without communication
bus
Terminating Connectors
The bus must be terminated in the last ER of a chain. For this purpose, plug the
prescribed terminating connector into the lower front connector of the receive IM in
the last ER of the chain. Unused front connectors of a send IM need not be
terminated.
The following figure shows a typical configuration with send IMs, receive IMs, and
terminating connectors.
Receive IM
Terminating
Receive IM Connectors
Send IM
CR
Connecting Cables
There are prefabricated cables available in different fixed lengths for connecting
the individual interface modules to each other (see Chapter 12: Spare Parts and
Accessories).
IM 460-1 and IM 461-1 6ES7 468-3 (I/O bus is transferred; rack is supplied with
current via the IM)
Caution
! Data loss or data corruption can result.
If you remove or plug in the interface modules and/or the associated connecting
cables when live, this can result in data loss or data corruption.
Switch off the power supply modules of the CR and ERs on which you are working
before carrying out such actions.
Order Numbers
IM 460-0 (send IM) 6ES7 460-0AA00-0AB0
IM 461-0 (receive IM) 6ES7 461-0AA00-0AA0
IM 460-0 IM 461-0
LEDs
EXTF INTF
C1 EXTF
C2
Coding switch
External battery
supply
under cover
X1 connector:
C1 interface IN
X2 connector:
C2 interface OUT
Function
The IM 460-0 (send IM) and IM 461-0 (receive IM) interface modules are used for
local links (up to a maximum total of 3 m). Data are transferred on the
communication bus at the full transmission rate.
LED EXTF (red) Lights up in the event of an external fault. Chain 1 or chain 2 contains a
fault (terminating connector missing or cable break).
LED C1 (green) Chain 1 (via front connector X1, connection 1) is in order.
LED C1 An ER in the chain is not ready for operation because
(green flashing) • The power supply module is not switched on
• A module has not yet completed the initialization run
LED C2 (green) Chain 2 (via front connector X2, connection 2) is in order.
LED C2 An ER in the chain is not ready for operation because
(green flashing) • The power supply module is not switched on
• A module has not yet completed the initialization run
Front connector Connector plug (output) for chain 1 and chain 2.
X1 and X2 X1 = upper front connector; X2 = lower front connector
LED INTF (red) Lights up if the rack number has been set > 21 or = 0.
Lights up if you have modified the module while the power was
switched on.
LED EXTF (red) Lights up in the event of an external fault (chain fault, for example, if
the terminating connector has not been plugged in or if a module has
not yet completed the initialization run, but not if the central controller
is switched off)
Coding switch Coding switch for setting the number of the rack.
Order Numbers
IM 460-1 (send IM) 6ES7 460-1BA00-0AB0
IM 461-1 (receive IM) 6ES7 461-1BA00-0AA0
Position of the Operator Controls and Indicators of the IM 460-1 and IM 461-1
IM 460-1 IM 461-1
LEDs
EXTF INTF
C1 EXTF
C2
5 VDC
Coding switch
under cover
X1 connector:
C1 interface IN
X2 connector:
C2 interface
OUT
Function
The IM 460-1 (send IM) and IM 461-1 (receive IM) interface modules are used for
local links (up to a maximum total of 1.5 m). These interface modules are also
used to transfer the 5 V supply voltage. Please note the following points:
• The power requirements of the modules plugged into the ER must not exceed
5 V/5 A.
• You must connect only one ER per chain.
• The modules in this rack are not supplied with 24 V and are not backed up.
• Data are not transferred on the communication bus in the case of the IM 460-1
and IM 461-1.
• You must not use a power supply module in the ER.
Note
If you connect an ER via a local link with 5 V transmission, ungrounded operation
is prescribed for the ER (see Installation Manual, Chapter 4).
1. Set the switch of the power supply module in the CR to the position (output
voltages 0 V).
2. Enter the number via the coding switch.
3. Switch the power supply module back on.
LED EXTF (red) Lights up in the event of an external fault. Chain 1 or chain 2 contains a
fault (terminating connector missing or cable break).
LED C1 (green) Chain 1 (via front connector X1, connection 1) is in order.
LED C1 A module has not yet completed the initialization run.
(green flashing)
LED C2 (green) Chain 2 (via front connector X2, connection 2) is in order.
LED C2 A module has not yet completed the initialization run.
(green flashing)
Front connector Connector (output) for chain 1 and chain 2
X1 and X2 X1 = upper front connector; X2 = lower front connector
LED INTF (red) Lights up if the rack number has been set > 21 or = 0.
Lights up if you have modified the module while the power was
switched on.
LED EXTF (red) Lights up in the event of an external fault (chain fault, for example, if
the terminating connector has not been plugged in or if a module
has not yet completed the initialization run, but not if the central
controller is switched off)
5 VDC (green) Power supply in the ER is in order.
Coding switch Coding switch for setting the number of the rack.
Front connector X1 Upper connector (input) for the connecting cable from the previous
interface module.
Front connector X2 Lower connector (output) for connecting cable to the next interface
module or for the terminating connector.
Caution
! Modules can be damaged.
If you want to connect an ER via the IM 461-1 interface module and you use a
power supply module in this ER, the modules could be damaged.
Do not use a power supply module in the ER that you want to connect to the CR
via the IM 461-1 interface module.
Order Numbers
IM 460-3 (send IM) 6ES7 460-3AA00-0AB0
IM 461-3 (receive IM) 6ES7 461-3AA00-0AA0
Position of the Operator Controls and Indicators of the IM 460-3 and IM 461-3
IM 460-3 IM 461-3
LEDs
EXTF INTF
C1 EXTF
C2
Coding switch
under cover
X1 connector:
C1 interface IN
X2 connector:
C2 interface OUT
Function
The IM 460-3 (send IM) and IM 461-3 (receive IM) interface modules are used for
remote links (up to a maximum total of 100 m). Data are transferred on the
communication bus at the full transmission rate.
Parameter Assignment
You must set the number of the rack containing the receive IM using the two-digit
coding switch on the front plate of the module. The permissible range is 1 to 21.
If required, you can change the distance specification of the chain via STEP 7 on
the programming device.
The default setting for the distance specification is 100 m.
Match the distance specification as closely as possible to the actual length (sum of
all connecting cables per chain) to accelerate data transmission.
Note
The distance specification set must always be greater than the actual cable length
per chain.
LED EXTF Lights up in the event of an external fault. Chain 1 or chain 2 contains a
(red) fault (terminating connector missing or cable break).
LED C1 Chain 1 (via front connector X1, connection 1) is in order.
(green)
LED C1 An ER in the chain is not ready for operation because
(green flashing) • The power supply module is not switched on
• A module has not yet completed the initialization run
LED C2 Chain 2 (via front connector X2, connection 2) is in order.
(green)
LED C2 An ER in the chain is not ready for operation because
(green flashing) • The power supply module is not switched on
• A module has not yet completed the initialization run
LED INTF (red) Lights up if the rack number has been set > 21 or = 0.
Lights up if you have modified the module while the power was
switched on.
LED EXTF (red) Lights up in the event of an external fault (chain fault, for example, if
the terminating connector has not been plugged in or if a module has
not yet completed the initialization run or if the central controller is
switched off)
Coding switch Coding switch for setting the number of the rack.
External battery You can connect an external battery (5 V to 15 V) or a central backup
supply socket at this socket when replacing the rack power supply. This achieves
EXT.-BATT. uninterrupted backup of the relevant ER. If you use the receive IM in
a cabinet, use an angled plug for the battery supply to save space.
Front connector X1 Upper connector (input) for the connecting cable from the previous
interface module.
Front connector X2 Lower connector (output) for connecting cable to the next interface
module or for the terminating connector.
Order Numbers
The order numbers for the memory cards are listed in the technical specifications.
Design
The memory card is slightly larger than a credit card and protected by a strong
metal casing. It is plugged into a receptacle at the front of the CPU; the end to be
inserted is obvious from the design of the memory card.
The following figure shows the design of the memory card.
Side elevation
Type plate
Grip
Front elevation
Function
The memory card and an integrated memory area on the CPU together form the
load memory of the CPU. In operation, the load memory contains the complete
user program including comments, symbols, special additional information that
permits decompiling of the user program, and all the module parameters.
Note
Non-Siemens memory cards cannot be used in the S7-400.
RAM Card
If you use a RAM card, you must plug this into the CPU to load the user program.
The user program is loaded with the help of the programming device (PG).
You can load the entire user program or the individual parts such as FBs, FCs,
OBs, DBs, or SDBs into the load memory in STOP mode or in RUN-P mode.
If you remove the RAM card from the CPU, the information stored on it is lost. The
RAM card does not have a built-in backup battery.
If the power supply has a functioning backup battery or if an external backup
voltage is supplied to the CPU via the “EXT. BATT.” socket, the contents of the
RAM card are retained after switching off the power supply provided the RAM card
remains plugged into the CPU and the CPU remains in the rack.
Flash Card
If you use a Flash card, there are two ways of loading the user program:
• Set the CPU to STOP with the mode selector, plug the Flash card into the CPU,
and load the user program into the load memory with the help of the
programming device (PG).
• Load the user program into the Flash card in offline mode at the programming
device and then insert the Flash card into the CPU.
You can only load your complete user program with the Flash card. You can load
smaller program sections into the integrated load memory on the CPU using the
programming device. In the case of larger program changes, you must always
reload the Flash card with the complete user program.
The Flash card does not require voltage to store its contents, that is, the
information stored on it is retained even when you remove the Flash card from the
CPU or if you operate your S7-400 system without backup (without backup battery
in the power supply module or without backup voltage at the “EXT. BATT.” socket
of the CPU).
Note
If the memory card is not removed in the STOP mode, the CPU goes to the STOP
state and the STOP indicator flashes every 3 seconds to prompt you to carry out a
memory reset. This sequence cannot be influenced by error OBs.
Technical Specifications
Order Number
IM 467 6ES7 467-5GJ00-0AB0 (RS 485)
IM 467 6ES7 467-5GJ01-0AB0 (RS 485)
IM 467 6ES7 467-5GJ02-0AB0 (RS 485)
IM 467 FO 6ES7 467-5FJ00-0AB0 (FO)
Use
PROFIBUS DP, standardized according to EN 50170, allows fast communication in
the field area between programmable logic controllers, PCs, and field devices.
Field devices include distributed I/O devices (ET 200), drives, valve islands,
switching devices, and many others.
The IM 467/IM 467 FO interface module is intended for use in an S7-400
programmable logic control system. It enables you to connect an S7-400 to
PROFIBUS DP.
Design
• Configuration according to the rules for an S7-400
• Can be operated without a fan
• A maximum of four IM 467/IM 467 FO modules can be used in the central rack.
No slot rules apply
• A total of four IM 467/IM 467 FO and CP 443-5 Extended modules can be used
together
• Various transmission rates between 9.6 Kbps and 12 Mbps can be set in the
software
• Configuration and programming are possible via PROFIBUS DP although
PROFIBUS parameters must not be changed !
• IM 467 with 9-pin sub-D female connector for attachment to PROFIBUS DP
(6ES7 467-5GJ00-0AB0, 6ES7 467-5GJ01-0AB0, 6ES7 467-5GJ02-0AB0)
• IM 467 FO with fiber-optic cable for attachment to PROFIBUS DP
(6ES7 467-5FJ00-0AB0)
LED displays
Mode switch
PROFIBUS-DP interface
9-pin sub-D
Communication Services
The IM 467/IM 467 FO provides you with two possible means of communication:
• PROFIBUS DP
The IM 467/IM 467 FO is a PROFIBUS-DP master which conforms to
EN 50 170. It is configured completely with STEP 7. In principle, its behavior is
the same as that of the integrated PROFIBUS-DP interfaces on the CPU
modules (for differences, refer to the technical data of the IM 467/IM 467 FO).
No function calls are necessary in the STEP 7 user program for DP
communication.
• S7 functions
The S7 functions ensure optimized simple communication in a SIMATIC
S7/M7/C7 automation system. For IM 467/IM 467 FO, the following
S7 functions are used:
– Programming device functions via PROFIBUS DP
– Operator monitoring and control functions via PROFIBUS DP
Communication requires no further configuration on the IM 467/IM 467 FO.
The S7 functions can be used alone or parallel to the PROFIBUS-DP protocol.
If they are used parallel to DP communication, this will affect the
PROFIBUS-DP round-trip time.
LED Display
The LED display bar on the front panel of the IM 467/IM 467 FO is occupied by
4 display elements:
INTF
EXTF
RUN
STOP
IM operating status
The LED displays show information about the IM operating status as in the
following scheme:
RUN
STOPPING
STOP
Interface error/
System error
Legend: on off flashing
Loadable Firmware
The IM 467/IM 467 FO supports the update of the firmware (FW) per FW-Loader.
The FW-Loader is a component of the projecting software NCM S7 for
PROFIBUS DP. An authorization is here not required. After an FW-update the
central rack must be switched off and on again before going into normal operation.
Note
For additional information on loading the firmware please refer to the manual
NCM S7 for PROFIBUS DP and, if necessary, the README file of the projecting
software NCM S7 for PROFIBUS DP.
Note
The IM 467 FO requires an optical bus terminal (OBT) for FW-loading.
9.2 Configuration
The IM 467/IM 467 FO is configured with STEP 7. The process data is maintained
even at power loss; a memory module is not required. The S7 functions facilitate
remote programming and projecting of all IM 467/IM 467 FO connected to the
network and of all CPUs connected via SIMATIC S7-400 backplane bus.
Prerequisite is SIMATIC STEP 7
• STEP 7 V3.1
From STEP7 Version 3.1, the IM 467 with the MLFB number
6ES7 467-5GJ00-0AB0 can be configured.
• STEP 7 V4.02
From STEP7 Version 4.02, the IM 467 with the MLFB number
6ES7 467-5GJ01-0AB0 can be configured additionally with the functional
extensions according to chapter 6 (SYNC/FREEZE).
• STEP 7 from Version 5.00
From STEP 7 Version 5.00, the IM 467/IM 467 FO with the MLFB number
6ES7 467-5GJ02-0AB0/6ES7 467-5FJ00-0AB0 can be additionally configured
with the functional extensions according to chapter 6 (routing of PG-Functions,
DP cross traffic, equidistance).
Prerequisites
The IM 467/IM 467 FO is supported by all CPU operating systems with the output
states shown below.
In addition, determine on hand of the table:
• The number of IM 467/IM 467 FO which can be operated by one CPU
• Multi-processor operation support
Note
The baud rates of 3 MB and 6 MB are not approved for the IM 467-FO.
Transfer rate 9.6 19.2 93.75 187.5 500 1500 3000 6000 12000
in Kbps
max. length of a bus 1.000 1.000 1.000 1.000 400 200 100 100 100
segment in m
max. number of bus 10 10 10 10 10 10 10 10 10
segments 1)
max. length in m 10.000 10.000 10.000 10.000 4.000 2.000 1.000 1.000 1.000
1)Bus segments are coupled via RS 485 repeater
INTF
EXTF
used by
Pin. Signal PROFIBUS
RS 485
RUN No Name Description
STOP
RUN
STOP 1 PE Ground Yes
2 - - -
3 RxD/TxD-P Data line B Yes
4 RTS (AG) Control - A -
5 M5V2 Data reference potential Yes
6 P5V2 Supply Plus Yes
7 BATT - -
8 RxD/TxD-N Data line A Yes
9 - - -
C
P43-5 X2
43-5FX 3E04
00-0X
IN
T
FF
E
X
T
RSU
N
T
O
P
R U
N
STO
P
A
U
I/T
P
Required accessories
• Package with Simplex connectors and polishing sets (6GK1901-0FB00-0AA0)
• Package with plug adapters (6ES7 195-1BE00-0XA0)
Plug-in adapter
for IM 467 FO
Note
If you insert a used FOC into the connecting adapter, you must shorten the FOC
cables by the bent length and remount the Simplex connectors.
By this measure you will avoid possible damping loss caused by repeatedly bent
and extreme stress of the FOC cable.
Caution
! Do not look directly into the opening of the optical transmitter diodes.
The emitted light beam can harm your eyes.
PROFIBUS DP
Transmitter Grip
R Receiver
T Transmitter
R Receiver
Receiver
T Transmitter
6ES7 467-5FJ00-0AB0
The IM 467 FO technical data is listed below.
Characteristics
The cable duct and the fan subassembly have the following characteristics
• The air inflow area is variable.
• Shield and cable clamping are possible.
In addition, the fan subassembly has the following characteristics:
• Fans and filter frames can be replaced from the front during operation.
• The fan function is controlled by means of speed monitoring.
• Operation with filter frames is optional.
In this section, you will find out how to monitor the fans.
There is a signaling concept example at the end of the section.
LEDs
The three red LEDs are assigned to the individual fans. From left to right, these
are:
F1 – for fan 1
F2 – for fan 2
F3 – for fan 3
Fans
The fans have a redundant design. The fan subassembly continues to function
even if one fan fails.
Fan Monitoring
The function of the fans is controlled by means of speed monitoring. If the speed of
a fan drops below the limit speed of 1750 rpm, the LED assigned to it lights up. In
addition, the relay K1 drops out.
If the speed of a second fan drops below the limit speed, the LED assigned to it
lights up; in addition, the relay K2 drops out.
The following table is the function table for the fan monitoring.
Evaluation
(digital input module) 1
L+ 2 ... to the monitor
Evaluation 3 K1
(digital input module)
4
... to the monitor
5
K2
24 V 6
Order Number
6ES7 408-0TA00-0AA0
Function
The cable duct is used in installations outside the cabinet for
• Cable clamping and/or for
• Shielding or for
• Air circulation without fan assistance
Eye for
clamping cable
Shielding clamp
(Side elevation
Scale 1:1)
Shielding Clamps
If you do not require the shielding clamps supplied, do not install them in the cable
duct.
Technical Specifications
Order Number
6ES7 408-1TB00-0XA0
Relay contacts
1, 2, 3
Relay contacts
4, 5, 6
Voltage
selector switch
Fuse
compartment
PCB
Toroidal-core Base
current transformer
Shielding clamp
(Side elevation
Scale 1:1)
Fuse
Included in this fan subassembly are standard cartridge fuse links,
5 x 20 mm, conforming to DIN
• 250 mAT for 120 V
• 160 mAT for 230 V.
The fuse for the 230 V range is already installed on shipping from the factory.
Note
If you change the voltage range, you must also insert the fuse for this voltage
range in the fan subassembly. You will find a description of how to change the fuse
in the Installation Manual, Chapter 9.
Shielding Clamps
If you do not require the shielding clamps supplied, do not install them in the fan
subassembly.
Technical Specifications
Warning
! Electrical current can lead to personal injury.
If you remove the left cover when installing or removing the fan subassembly, the
terminals on the transformer are accessible briefly.
Remove the voltage from the fan subassembly before you install or remove it.
Disconnect the supply cable before you remove the fan subassembly.
Caution
! Danger of damage to equipment.
If you mix up the power supply PCB and the monitoring PCB in the fan
subassembly, the fan subassembly may be damaged.
During maintenance of the unit, make sure you do not mix up the power supply
PCB and the monitoring PCB.
Monitoring Function
In the case of a fault (defective fans) the fans are not switched off. Once you have
replaced the defective fan(s), the fault is acknowledged automatically as soon as
the fans have reached the required speed. Any faults that occur are not stored.
When you switch on the fan subassembly, the fans start running. After
approximately 10 s the current status of the fans is indicated via LEDs and relays.
Order Number
6ES7 408-1TA00-0XA0
Relay contacts
1, 2, 3
1 AT
Relay contacts
4, 5, 6
1 AT
Fuse
compartment
Characteristics
The 24 VDC fan subassembly has the same construction and functional
characteristics as the 120/230 VAC fan subassembly.
Installation
Installing the 24 VDC fan subassembly is the same as for the 120/230 VAC fan
subassembly.
Wiring
You connect the 24 VDC fan subassembly to the 24 VDC supply in the same
manner as for the 120/230 VAC fan subassembly. You should note the polarity of
the spring connections L+ and L–.
Signaling Concept
The signaling concept of the 24 VDC fan subassembly is identical to the signaling
concept of the 120/230 VAC fan subassembly.
Fuse
Included in this fan subassembly are standard cartridge fuse links,
5 x 20 mm, conforming to DIN
• 1.0 AT for 24 V
The fuse is already installed on shipping from the factory.
Shielding Clamps
If you do not require the shielding clamps supplied, do not install them in the fan
subassembly.
Technical Specifications
Caution
! Danger of damage to equipment.
If you insert the monitoring PCB in the wrong position in the fan subassembly, the
fan subassembly may be damaged.
During maintenance of the unit, make sure you do not replace the monitoring PCB
in the wrong position.
Monitoring Function
In the case of a fault (defective fans) the fans are not switched off. Once you have
replaced the defective fan(s), the fault is acknowledged automatically as soon as
the fans have reached the required speed. Any faults that occur are not stored.
When you switch on the fan subassembly, the fans start running. After
approximately 10 s the current status of the fans is indicated via LEDs and relays.
Further information
You will find further information on the RS 485 repeater in the Configuration, CPU
Data manuals, in the section ”Configuring an MPI Network or a PROFIBUS-DP
Network”.
Chapter Overview
Order Number
6ES7 972-0AA01-0XA0
Rules
If you want to construct a bus with RS 485 repeaters, the following rules apply:
• No more than 9 RS 485 repeaters can be connected in series.
• The maximum cable length between two nodes must not exceed the values
given in Table 11-2 for the RS 485 repeater:
Transmission Rate Maximum Cable Length between Two Nodes (in m) with
RS 485 Repeaters (6ES7 972-0AA01-0XA0)
9.6 to 187.5 Kbps 10000
500 Kbps 4000
1.5 Mbps 2000
3 to 12 Mbps 1000
The following table shows the appearance of the RS 485 repeater and lists its
functions.
Grounded or Ungrounded
The RS 485 repeater is ...
• Grounded if all nodes in the segment are also operated in a grounded
configuration
• Ungrounded if all nodes in the segment are also operated in an ungrounded
configuration
Note
Bus segment 1 is grounded if you connect a programming device (PG) to the
PG/OP socket of the RS 485 repeater. The ground connection is made because
the MPI in the PG is grounded and the PG/OP socket in the RS 485 repeater is
connected internally to bus segment 1.
Terminal connection
When the repeater is installed with non–grounded reference potential (ungrounded
operation), interference currents and static charges are drained via an RC network
integrated in the repeater (see Figure 11-1) to the protective conductor.
PE
DC
24 V M PE M 5.2
22 nF 10 MΩ
M
A1 B1 A1 B1
Ground Bus
Figure 11-1 RC Network with 10 MΩohm for Installation with Non–Grounded Reference
Potential
DC
24 V M PE M 5.2
A1 B1 A1 B1
ON
PG/OP PG
OFF
DP1
interface OP
DP2
ON
Connection for bus segment 2
Galvanic SIEMENS
RS 485 REPEATER
isolation A2 B2 A2 B2
Technical Specifications
Power supply
• Rated voltage 24 VDC
• Ripple 20.4 to 28.8 VDC
Current consumption at rated voltage
• Without load on the PG/OP socket 200 mA
• Load on the PG/OP socket (5 V/90 mA) 230 mA
• Load on the PG/OP socket (24 V/100 mA) 200 mA
Galvanic isolation Yes, 500 VAC
Connection of fiber–optic cables Yes, via repeater adapters
Redundant operation No
Transmission rate (detected automatically by the 9.6 Kbps, 19.2 Kbps, 45.45 Kbps,
repeater) 93.75 Kbps, 187.5 Kbps, 500 Kbps,
1.5 Mbps, 3 Mbps, 6 Mbps, 12
Mbps
Degree of protection IP 20
Dimensions W H D (in mm) 45 128 67
Weight (incl. packaging) 350 g
Segment 1 Segment 2
A1 A2
Logic
B1 B2
A1 A2
B1 B2
PG/OP 5V 1M 5V 1M
socket
24V 24V
L+ (24 V) L+ (24 V)
M M
A1
B1 PE
5V M 5.2
M5 V
For Racks
Number wheel for slot labeling C79165-Z1523-A22
Spare slot covers (qty 10) 6ES7 490-1AA00-0AA0
For Power Supplies
Spare connector for PS 405 (DC) 6ES7 490-0AA00-0AA0
Spare connector for PS 407 (AC) 6ES7 490-0AB00-0AA0
Backup battery 6ES7 971-0BA00
For CPUs
Key for CPU mode selector switch 6ES7 911-0AA00-0AA0
2 Mbyte memory submodule 6ES7 911-0AA00-0AA0
4 Mbyte memory submodule 6ES7 911-0AA00-0AA0
For Digital Modules/Analog Modules
Cover foil (10 x) for labeling strips of the SMs 6ES7 492-2XX00-0AA0
Cover flap for fuse receptacle on the AC modules 6ES7 422-0XX00-7AA0
Measuring range module for analog modules 6ES7 974-0AA00-0AA0
Front connector screw-type connection 6ES7 492-1AL00-0AA0
Front connector spring connection 6ES7 492-1BL00-0AA0
Front connector crimp connection 6ES7 492-1CL00-0AA0
Crimping tool for crimp contacts 6XX3 071
Crimp contacts (package of 250) 6XX3 070
Extraction tool for crimp contacts 6ES5 497-4UC11
Fuses (fusible cutouts)
For IMs
Terminating connector for IM 461-0 6ES7 461-0AA00-7AA0
Terminating connector for IM 461-1 6ES7 461-1AA00-7AA0
Terminating connector for IM 461-3 6ES7 461-3AA00-7AA0
IM 463-2, send IM, 600 m to IM 314 of the S5 6ES7 463-2AA00-0AA0
IM cable with communication bus, 0.75 m 6ES7 468-1AH50-0AA0
IM cable with communication bus, 1.5 m 6ES7 468-1BB50-0AA0
IM cable with communication bus, 5 m 6ES7 468-1BF00-0AA0
IM cable with communication bus, 10 m 6ES7 468-1CB00-0AA0
IM cable with communication bus, 25 m 6ES7 468-1CC50-0AA0
IM cable with communication bus, 50 m 6ES7 468-1CF00-0AA0
IM cable with communication bus, 100 m 6ES7 468-1DB00-0AA0
IM cable with current transmission, 0.75 m 6ES7 468-3AH50-0AA0
IM cable with current transmission, 1.5 m 6ES7 468-3BB50-0AA0
For CP 441
IF963-RS232 interface submodule 6ES7 961-1AA00-0AA0
IF963-TTY interface submodule 6ES7 961-2AA00-0AA0
IF963-X27 interface submodule 6ES7 961-3AA00-0AA0
IF module L2-DP 6ES7 964-2AA00-0AB0
For Interfacing / Networking
RS 485 repeater 6ES7 972-0AA00-0XA0
DIN rail 6ES5 710-8MA...
PROFIBUS bus cable 6XV1 830-0BH10
6XV1 830-3BH10
PROFIBUS internal cable 6XV1 830-0BH10
PROFIBUS grounding cable 6XV1 830-3BH10
PROFIBUS bus connector without PG socket 6ES7 972-0BA00-0XA0
PROFIBUS bus connector with PG socket 6ES7 972-0BB10-0XA0
PROFIBUS bus connector without PG socket for CPU 417 6ES7 972-0BA40-0X40
PROFIBUS bus connector with PG socket for CPU 417 6ES7 972-0BB40-0X40
PROFIBUS RS 485 bus terminal 6GK1 500-0AA00
6GK1 500-0AB00
6GK1 500-0DA00
PG cable, short 6ES7 901-0BF00-0AA0
PG 705 cable 6ES7 705-0AA00-7BA0
PC/MPI cable (5 m) 6ES7 901-2BF00-0AA0
PC/MPI cable (16 m) 6ES7 901-2CB60-0AA0
For Fan Subassembly
Spare fan for fan subassembly 6ES7 408-1TA00-6AA0
Filters (qty 10) for fan subassembly 6ES7 408-1TA00-7AA0
Monitoring PCB for fan subassembly 6ES7 408-1TX00-6XA0
Power supply PCB for fan subassembly 6ES7 408-1XX00-6XA0
Cabinets
Cabinet 2200 x 800 x 400 with extension set for 8 MC 2281-7FC11-8DA1
SIMATIC S7-400
Extension set for SIMATIC S7-400 8 MC 1605-0BS70-0AA0
Cables
Connecting cables for printers with
• Serial port (COM, 10 m) 9AB4 173-2BN10-0CA0
• Parallel port (Centronics) 6AP1 901-0AL00
Connecting cable for interface module
• 1m 6ES7 368-3BB00-0AA0
• 2.5 m 6ES7 368-3BC00-0AA0
• 5m 6ES7 368-3BF00-0AA0
• 10 m 6ES7 368-3CB00-0AA0
V.24 cable 9AB4 173-2BN10-0CA0
Connector housing, gray
• 9-pin V42254-A6000-G109
• 15-pin V42254-A6000-G115
• 25-pin V42254-A6000-G125
Connector housing, black
• 9-pin V42254-A6001-G309
• 15-pin V42254-A6001-G315
• 25-pin V42254-A6001-G325
Memory cards
• Flash EPROM, 1 Mbyte 6ES7 952-1KK00-0AA0
• Flash EPROM, 2 Mbytes 6ES7 952-1KL00-0AA0
• Flash EPROM, 4 Mbytes 6ES7 952-1KM00-0AA0
• Flash EPROM, 8 Mbytes 6ES7 952-1KP00-0AA0
• Flash EPROM, 16 Mbytes 6ES7 952-1KS00-0AA0
10 cover foils for SM labeling strips 6ES7 492-2XX00-0AA0
Cover flap for fuse receptacle, AC-SM 6ES7 422-0XX00-7AA0
12 spare submodule covers 6ES7 398-0BA00-0AA0
6 connecting clips 6ES7 498-6BA00-0AA0
Chapter Overview
Introduction
There are two CPUs with different clock frequencies available for use with the
automation computer.
Table 13-1 gives you an overview of the most important performance features of
these CPUs.
(6ES7486-3AA00-0AB0) (6ES7488-3AA00-0AB0)
Processor Pentium 75 MHz Pentium 120 MHz
MEM 478 DRAM memory submodules*
for main memory
• Expansion capability 16 Mbytes 16 Mbytes
• Supply voltage 3.3 V 3.3 V
Second-level cache No 250 Kbytes
Submodule receptacle for memory card Yes
Submodule receptacles for interface 2
submodules
Connection of expansions max. 3
MPI Yes
Watchdog * Yes
* see M7-SYS User Manual
The following table contains the technical specifications of the CPUs for the
M7-400 automation computer.
(6ES7486-3AA00-0AB0) (6ES7488-3AA00-0AB0)
Nominal voltage 5 VDC (4.75 to 5.25 VDC)
Typical current consumption 2.75 A 3.0 A
Maximum permissible power 3.25 A 3.5 A
consumption
Maximum permissible power losses 16.25 W 17.5 W
Maximum permissible power losses with
interface submodules 19.25 W 20.5 W
Forced ventilation required No
Weight 1300 g
Dimensions W x H x D (mm) 50 x 290 x 219
Introduction
In this section you will become familiar with the individual function elements of the
CPU 486-3 and CPU 488-3. You require the information here to be able to respond
to displays, start up, and operate an M7-400 automation computer and handle
further components (for example, memory cards, expansions).
In addition, you will find information on the watchdog, the BIOS setup and the
address assignments and interrupt assignments.
General View
Figure 13-1 shows the front and rear view of the CPU 486-3 and CPU 488-3
without covering flap. The positions of the indicators, operator controls, and other
elements required for operation can be seen from this figure.
2 1
9
3
8
4
7
4 6
1 =
Receptacle for memory card 7 = Expansion socket
2 =
Status and fault LEDs 8 = Cover for memory submodule
3 =
Mode selector switch receptacle → 2 x DRAM
4 =
Submodule receptacle for 9 = Dongle interface
interface submodules (in preparation)
5 = External battery supply
6 = MPI
Figure 13-1 Front and Rear View of a CPU 486-3 and CPU 488-3 without Covering Flap
CPU Elements
The following table gives the meanings of the individual elements of the CPU 486-3
and CPU 488-3.
Element Meaning
Status and fault LEDs The status and fault LEDs indicate the operating state of your
CPU.
See page 13-6 for more detailed explanations.
Submodule receptacle A long memory card can be inserted in the submodule
for memory card receptacle. The system and user software can be loaded from
this card into the main memory during startup. See page 13-8
for more detailed explanations.
Element Meaning
Mode Selector The mode selector switch is a key switch. See page 13-9 for
more detailed explanations.
Submodule receptacles Interface submodules can be plugged into these submodule
for interface receptacles.
submodules See page 13-11 for more detailed explanations.
Main memory The main memory is freely accessible via a cover on the
left-hand side of the housing. This allows problem-free insertion
and replacement of memory submodules.
See page 13-13 for more detailed explanations.
Expansion socket Expansions such as the EXM expansion module, AT adapter
module, ATM and MSM mass storage can be connected via the
expansion socket.
See page 13-14 for more detailed explanations.
MPI The CPU 486-3 and CPU 488-6 are equipped with a multipoint
(9-pin sub D socket) interface. See page 13-15 for more detailed explanations.
External battery supply An external battery can be connected via this socket so that, for
example, the contents of the SRAM and the time of day are not
lost if the power supply fails. The same technical details apply
as for the S7-400 CPUs, see Section 4.1.
INTF
EXTF
SD
HD
USR1
USR2
RUN
STOP
Figure 13-2 Status and Fault LEDs on the CPU 486-3 and CPU 488-3
Table 13-4 Meaning of the Status and Fault LEDs on the CPU 486-3 and CPU 488-3
Introduction
The CPU 486-3 and CPU 488-3 offer the possibility of operating a memory card in
the same way as a diskette. In this section, you will learn how you can use these
options.
Note
If the power fails during a write access to the memory card, the entire contents of
the memory card can be damaged under unfavorable conditions.
Please note that in contrast to a diskette, a memory card is only designed for a
limited number of write accesses.
Memory Card
A memory card emulates a diskette from which an operating system can also be
booted. In addition, a memory card can also be used to exchange user software
and user data.
Memory cards with Flash EPROM are available for the CPUs (see the ordering
data).
Drive Assignment
The memory card is accessed by the operating system in the same way as a
conventional drive.
You can set the drive assignment in the BIOS setup (Section 13.4.11, page 13-35).
Boot Sequence
You can set the boot sequence in the BIOS setup (Section 13.4.12, page 13-36).
Formatting
Memory cards are formatted with the program FTLFORM.EXE included with the
system software. Read the relevant sections in the M7-SYS User Manual.
Note
The memory capacity specified for the memory card is the actual physical memory
capacity (gross). Formatting reduces the gross memory capacity to approximately
80% (net) that is then available to the operating system for storing data/programs.
UNDELETE: Files which were deleted from the memory card cannot be restored
using UNDELETE programs.
RUN-P
RUN
STOP
MRES
Activating MRES
To generate a hardware reset via MRES, follow the steps outlined below:
1. Turn the mode selector switch to the STOP position.
Result: The STOP LED lights up.
2. Turn the mode selector switch to the MRES position and hold it there.
Result: The STOP LED goes dark for a second, lights up for a second, goes
dark again, and then remains lit.
3. Turn the switch back to the STOP position and then, in the next 3 seconds, to
the MRES position again and back to STOP.
Result: The STOP LED flashes for approximately 3 seconds at 2 Hz (a
memory reset is being carried out) and then remains lit.
4. If the STOP LED does not flash or other LEDs light up or flash, you must repeat
steps 2 and 3.
Note
Resetting by activating MRES is controlled by the system software. If this has not
been started, the CPU must be reset by switching the power supply off and on. If
a keyboard is connected to the CPU, it is also possible to initiate a complete
restart via hot keys (see Table 13-7 on page 13-19).
Submodule
receptacle
Figure 13-4 Position of the Receptacles for Interface Submodules on the CPU 486-3 and
CPU 488-3
6 9 12
3 7 10 13
0 8 11 14
Submodule Covers
Unused submodule receptacles are protected by submodule covers.
Introduction
You must order the MEM 478 DRAM memory submodules for the main memory of
the CPUs separately. They are also shipped separately. These memory
submodules must be inserted before plugging into the mounting rack.
Warning
! DRAM memory submodules can be damaged.
If you use memory submodules for the main memory other than the DRAM
submodules designed for the purpose, the submodules can be damaged.
Use only the MEM 478 DRAM memory submodules for the main memory.
Introduction
The CPU 486-3 and CPU 488-3 are each equipped with an expansion socket. The
ISA bus is continued via the expansion socket.
X1 Interface
The X1 interface of the CPU 486-3 and CPU 488-3 for connecting devices such as
PCs/programming devices is a multipoint interface (MPI) and is connected via a
9-pin sub D connector.
Suitable Devices
You can connect the following at the MPI:
• Programming devices (PGs/PCs)
• Operator panels (OPs)
• Additional CPUs.
You can address up to 127 communications partners (programming devices, OPs,
CPUs) via the multipoint interface of the CPU 486-3 and CPU 488-3. A maximum
of 44 connections can be made to the CPU.
Connectors
Use only bus connectors or PG cables for connecting devices to the MPI (see
Chapter 7).
Overview
The BIOS setup handles the configuration of the relevant CPUs in your M7-400
system. The settings and technical information concerning the configuration of this
programmable module are displayed in the BIOS setup. The CPUs already have a
default setup. It is set in such a way that the minimal configuration of a CPU (with
memory card drive) will power up via BIOS setup without programming.
You can change the default settings in the BIOS setup. This becomes necessary if,
for example, you want to connect expansions to your CPU (expansion module with
interface submodules, mass storage module with diskette and hard disk drives, or
AT adapter module with short AT card). You must inform the operating system of
these expansions.
If you want to make settings in the BIOS setup, you can do so:
• Directly at the relevant module if your M7-400 is equipped with interface
submodules and I/O devices such as a monitor and keyboard (interface
submodule IF962-VGA).
• Remote setup with a terminal program (for example, HyperTerminal under
Windows 95) on programming device/PC or with an ANSI terminal via the
COM1 port (interface submodule IF962-COM).
Remote Setup
To run BIOS settings via the Remote Setup without the interface submodule
IF962-VGA, follow the steps outlined below:
1. Switch off the line voltage to your M7-400.
2. Connect the programming device to the COM1 port of the SIMATIC M7 device
(see Section 8.7.2 of the Installation Manual).
3. On your programming device under Windows 95 select “Start > Accessories >
Hyperterminal”.
4. In the HyperTerminal window, select the menu command “File > New
Connection”. Enter a connection description and select the COM port with the
following transmission properties: 19200 bps, 8 data bits, no parity, 1 stop bit,
no flow control.
5. Switch on the line voltage to the M7-400 and hold the “Q” key pressed during
startup until the M7-400 registers itself in the HyperTerminal with the hardware
tests (a “U” appears).
6. Press the ESC button immediately.
Result: You are in the BIOS setup.
If no error occurs, all LEDs on the CPU are switched off with the exception of the
STOP LED.
Warm Restart
After a warm restart of the CPU, the following window appears signaling an
accelerated system power up (see Section 13.4.2 “BIOS Hot Keys”).
Table 13-7 BIOS Hot Keys with German and English Key Assignments
CTRL + Alt + HOME STRG + Alt + POS1 Cold restart of the module
(power off/on with
initialization of all blocks)
CTRL + Alt + ↓ STRG + Alt + ↓ IDE hard disk in standby
mode
CTRL + Alt + PGDN STRG + Alt + Bild ↓ Screen saver on (dark
screen)
CTRL + Alt + PGUP STRG + Alt + Bild ↑ Screen saver off
Note
These functions can be overlaid by other operating systems or user programs
such as Windows.
↓ ↑ With the cursor control keys, you can jump from line to line within a
list box. The line you are in is marked with a dark bar.
You can page with the cursor control keys within an edit box if
there are several values available for selection within the box.
You activate an option button if you position the cursor at the
button using the cursor control keys.
← → With the cursor control keys, you can jump from character to
character within an edit box.
With the spacebar, you can confirm the selected lines as selected
or activate a check box.
INS Holding the INSERT key pressed during a complete restart of the
module leads to certain BIOS default settings being loaded which
are required for a safe startup.
F1 With this function key, a context-sensitive help window is
displayed.
Figure 13-8 shows an example.
The Remote Setup can either be operated with the keyboard of the remote
computer or with the keyboard of the M7-400. In both cases the above key
assignments apply.
In the edit windows:
OK Button
Activating this button returns to the Setup menu.
Representation of Information
Information cannot be edited. It is shown on this setup page in gray type. The gray
type is not available in Remote Setup and is replaced there with black type.
Interrupt Source
Here, you set interrupts A to C (see the “Interface Submodules” chapter) provided
for the interface submodule. The values positioned on the left are setpoints. You
can edit these. The value indicated in gray type to the right of these is the actual
value (determined at the last CPU power up). It cannot be edited.
Note
For the IF 961-AIO, IF 961-DIO and IF 961-CT1 interface modules there are no
default interrupts in the BIOS setup (default values are always 0xFF). Additionally,
no error message is given if no interrupt is set for an interface module, which is
configured for interrupt generation.
Shared Dest.
Here, you set a shared interrupt for the interface submodule (see the “Interface
Submodules” and “M7-400 Expansions” chapters). This value is entered only once
per expansion module at the first submodule receptacle (0, 3, 6, 9, etc.). The value
on the left-hand side is the setpoint value, which you can edit. The value indicated
in gray type to the right of it is the actual value (determined at the last CPU power
up). It cannot be edited.
DMA Request
Enter here the DMA request A and B for the interface submodule (see the
“Interface Submodules” chapter). The values positioned on the left are setpoints.
You can edit these. The value indicated in gray type to the right of these is the
actual value (determined at the last CPU power up). It cannot be edited.
Config. Index
Here, you can address the 40 H configuration space of the interface submodules
(0H to 3FH). You will find the address in the Table “Offset Address for the
Configuration Register” of each interface submodule in the “Interface Submodules”
chapter.
SIG Source
Here, you enter the signal source if the relevant interface submodule is designed
for it (“Interface Submodules” chapter). The values for the signal source positioned
on the left are the setpoints. You can edit these. The values shown to the right of
this in gray type (black type in Remote Setup) are the actual values (determined at
the last power up of the CPU).
SIG Dest.
Here you enter the signal destination if the relevant interface submodule is
designed for it (“Interface Submodules” chapter). This value is entered only once
per expansion module at the first submodule receptacle (0, 3, 6, 9, etc.). The value
for the signal destination positioned on the left is the setpoint. You can edit this
value. The signal destination value shown to the right of this in gray type (black
type in Remote Setup) is the actual value (determined at the last power up of the
CPU). It cannot be edited.
OK Button
Returns to the Setup menu when activated. Changes on the setup page are
retained.
CANCEL Button
Returns to the Setup menu when activated. Deletes all changes you have made on
the setup page.
Timeout Mode
Timeout mode offers you the following possible selections:
Delay Time
In this edit box, you enter the time in minutes that has to elapse after the last entry
or the last hard disk access before the timeout function activates.
OK Button
Activating this button returns to the Setup menu. Changes on the setup page are
retained.
CANCEL Button
Activating this button returns to the Setup menu. Deletes all changes you have
made on the setup page.
Device Security
Floppy Disk Read Only
When this check box is activated, write access to the hard disk is no longer
possible.
Hard Disk Read Only
When this check box is activated, write access to the hard disk is no longer
possible.
Password
Enter Setup
By activating this check box, you can assign a password that authorizes access to
the Setup.
System Boot
By activating this check box, you can assign a password that permits booting of
the operating system.
You can only set this password if a valid password was already entered for “Enter
Setup”.
Note
The password can have a maximum of 8 alphanumeric characters. Upper and
lower case are distinguished. If you use the American keyboard to enter the
password and then change, for example, to using another national keyboard such
as the German, this can have consequences for the password. For the password
Johnny_* you would then have to enter Johnnz?(.
Write down your password and keep it in a safe place where you can find it again.
If you lose or forget your password, contact your local Siemens dealer.
OK Button
Activating this button returns to the Setup menu. Changes on the setup page are
retained.
CANCEL Button
Activating this button returns to the Setup menu. Deletes all changes you have
made on the setup page.
Date
You enter the date in the form dd-mm-yyyy (day, month, year) in this edit box.
Time
You enter the time in the form hh:mm:ss (hour, minute, second) in this edit box.
The seconds in the setup page are updated continuously and only stopped when
you select the seconds field. You can then accept the value displayed or set by
pressing the RETURN key.
OK Button
Activating this button returns to the Setup menu. Changes on the setup page are
retained.
CANCEL Button
Activating this button returns to the Setup menu. Deletes all changes you have
made on the setup page with the exception of the time.
Figure 13-16 “Hard Disk” Setup Page with only the Master Hard Disk Present
Auto
Sets the type and all parameters for the corresponding hard disk automatically
during BIOS startup if the check box is activated.
Translation Mode
In Translation Mode you have four possible settings:
• Auto
reads the hard disk parameters and automatically sets the correct mode
(Normal, LBA, Large). The Translation Mode “Auto” is set as the default.
• Normal
used for hard disks with a memory capacity of 504 Mbytes.
• LBA (Logical Block Addressing)
is used for hard disks with a memory capacity of 504 Mbytes.
• Large
must be set for hard disks with a memory capacity of 504 Mbytes which do
not support the LBA mode.
Block Mode
Sets the block mode for DMA transfers. As the hard disks in the M7-400 are not
being operated in DMA mode, this check box should not be activated.
32 bits
Sets 32-bit access mode. As this is not supported by ISA hard disk controllers, this
check box should not be activated.
Fast PIO
Sets a faster Programmed Input Output mode.
OK Button
Activating this button returns to the Setup menu. Changes on the setup page are
retained.
CANCEL Button
Activating this button returns to the Setup menu. Deletes all changes you have
made on the setup page.
Boot Sequence
By activating the relevant option button, you select here the drive from which the
CPU is to boot at power up.
• Drive A represents the floppy disk drive or memory card, depending on which of
them has been entered as Drive A in the “Floppy/Card” setup page. If there is
no medium with boot capability in the floppy disk drive, the system will next try
to boot from the memory card (“Floppy/Card” setup page –> Drive B).
• Drive C represents the hard disk drive.
It is possible to designate a primary and secondary drive, that is, if there is no boot
program in the primary drive, the system boots automatically from the secondary
drive if there is a boot program there.
If neither Drive A nor Drive C contain a boot program, a message on the screen
prompts you to insert a medium with boot capability and to confirm this by
pressing RETURN .
Halt On ...
Here you can choose which error messages are displayed in an error window
during booting. Displaying an error window delays booting by approximately
2 seconds.
Keyboard State
Typematic Settings Enabled
If you activate this check box, the values “Typematic Rate” and “Typematic Delay”
are set by the BIOS.
Typematic Rate
This value is used to set the maximum keyboard rate in characters per second.
Typematic Delay
This value is used to set the delay time in milliseconds, after which characters are
transferred with the maximum keyboard rate.
Num Lock On
If you activate this check box, “Num Lock” becomes active after BIOS power up.
System Memory
If this check box is activated, only sample tests are made of the main memory at
power up so the test is especially fast.
OK Button
Activating this button returns to the Setup menu. Changes on the setup page are
retained.
CANCEL Button
Activating this button returns to the Setup menu. Deletes all changes you have
made on the setup page.
DEFAULT Button
When this button is activated, the default settings are entered in the setup page
again. The original settings are deleted.
System Cache
System Cache offers you the following possible selections:
System Cache
For the memory areas of the System ROM, the VIDEO ROM, and the addresses
of BIOS expansions, you can set whether they are copied to the Shadow RAM and
whether the cache should be used.
Note
If you have switched off the cache memory in the “Primary and Secondary
Cache” field, the setting in the “System ROM” field does not change
automatically.
OK Button
Activating this button returns to the Setup menu. Changes on the setup page are
retained.
CANCEL Button
Activating this button returns to the Setup menu. Deletes all changes you have
made on the setup page.
DEFAULT Button
When this button is activated, the default settings are entered in the setup page
again. The original settings are deleted.
Introduction
This section gives you detailed information, in the form of a table, on the I/O
address space assignment, main memory and interrupt assignments of the CPUs.
Memory Assignment
The main memory is assigned as follows in the M7-400:
Address Content
1 MB to 15 MB User memory area
15 MB to 16 MB PROFIBUS DP*), otherwise free
E 8000H to F FFFFH BIOS
E 0000H to E 7FFFH Free (32 K)
D 0000H to D FFFFH Free (64 K)
C F000H to C FFFFH Free (4 K)
C C000H to C EFFFH Memory card, otherwise free (12 K)
C 8000H to C BFFFH Free (16 K)
C 0000H to C 7FFFH Shadow VGA BIOS (32 K)
A 0000H to B FFFFH VGA (128 K)
0 0000H to 9 FFFFH 640 K system area
*) If the interface submodule IF 964-DP is not plugged in the preferred slot (see Table 15-3 on
page 15-4)
SRAM Area
The size of the SRAM with battery backup is 64 Kbytes (net for data blocks
56 Kbytes). If the battery is removed and inserted again when there is no power
connected, the SRAM content will be lost. This is indicated by the BAF LED.
Interrupt Assignment
Interrupt Function
NMI Group interrupt for faults and reset signals
IRQ0 System timer
IRQ1 Reserved for keyboard
IRQ2 Cascading of the 2nd interrupt controller
IRQ3 Assigned to COM2, otherwise free
IRQ4 Assigned to COM1, otherwise free
IRQ5 Assigned to LPT2, otherwise free
IRQ6 Assigned to floppy disk drive, otherwise free
IRQ7 Assigned to LPT1, otherwise free
IRQ8 Real-time clock
IRQ9 Software interrupt, rerouted to IRQ2
IRQ10 IF 964-DP, otherwise free
IRQ11 CP 1401, otherwise free
IRQ12 Assigned to trackball/mouse
IRQ13 Assigned to numeric coprocessor
IRQ14 Assigned to hard disk drive, otherwise free
IRQ15 Assigned
14.1 Overview
Introduction
You can expand your automation computer from the M7-400 range by adding
expansion modules for interface submodules, short AT modules, and/or the mass
storage module. The interface submodules can include the IF 962-COM,
IF 962-LPT, ... .
The following expansion modules are available:
• EXM 478 expansion module for up to 3 interface submodules
• ATM 478 AT adapter module for one short AT module
• MSM 478 mass storage module with hard disk and floppy disk drive and an
LPT1 printer port.
Expansion Socket
On the right-hand side of a CPU or an M7-400 application module there is a
120-pin socket (AT-ISA bus) for connecting expansions. There is a matching
connector for this socket on the left-hand side of the EXM 478, ATM 478, and
MSM 478 expansion modules (Figure 14-1).
The EXM 478, ATM 478 and MSM 478 expansion modules have one expansion
socket each on the right-hand side so that further expansion modules can be
plugged in.
Expansion
connector
Expansion
socket
Maximum Expansion
Figure 14-2 shows the maximum possible expansion using expansion modules for
a CPU 486-3, CPU 488-3, or FM 456.
e.g. FM 456-4 e.g. EXM 478 e.g. MSM 478 e.g. ATM 478
Permissible Combinations
You can see from the table below which expansions can be connected to the
programmable M7-400 modules.
Table 14-1 Expansion Possibilities of the CPU 486-3, CPU 488-3, or FM 456
Order Number
EXM 478 6ES7 478-2AC00-0AC0
Characteristics
The EXM 478 expansion module is used to house up to three interface
submodules. By installing the relevant interface submodule in this expansion
module, such as the IF 962-VGA and IF 962-LPT, you can connect, for example, a
VGA monitor, a keyboard, and a printer to your automation computer.
The EXM 478 expansion module has a 120-pin connector on the left-hand side and
a 120-pin socket on the right-hand side for connecting a further expansion module
or a mass storage module.
Introduction
In order to be able to program the interface submodules in the EXM 478 expansion
module, you must be able to determine their addresses. There are the following
addressing methods:
• Addressing in the AT-compatible I/O address area
• Addressing in the M7-400-specific I/O address area
In this section, you will find information on both methods of addressing the
interface submodules.
3 6 9
0 4 7 10
1 5 8 11
Figure 14-4 Submodule Receptacle Numbers for the FM 456-4 and EXM 478
6 9 12
3 7 10 13
0 8 11 14
Figure 14-5 Submodule Receptacle Numbers for the CPU 486-3, CPU 488-3, and
EXM 478
80
Submodule receptacle
number 6
40
Reserved
Cr00 00
FF
3. EXM 478
Expansion Module Submodule receptacle
Cq00 number 5
C0
2) EXM 478
Expansion Module Submodule receptacle
Cp00 number 4
80
1) EXM 478
Expansion Module Submodule receptacle
Co00 number 3
40
e.g. FM 456-4
Reserved
Cn00
00
BF
n .. q = Number of the slot of the
Submodule receptacle
module in the mounting
number 1
rack 80
(in hexadecimal notation)
Figure 14-6 Base Addresses of the Expansion Modules and the Interface Submodules
Interface Submodule
Base Address Modules in Submodule
Receptacle ...
Cn40H FM 456-4 Number 0
Cn80H Slot n Number 1
Co40H Nummer 3
Co80H 1st EXM 478 in slot o = n + 1 Number 4
CoC0H Number 5
Cp40H Number 6
Cp80H 2nd EXM 478 in slot p = n + 2 Number 7
CpC0H Number 8
Cq40H Number 9
Cq80H 3rd EXM 478 in slot q = n + 3 Number 10
CqC0H Number 11
n .. q = Number of the module slot in the mounting rack in hexadecimal notation.
Table 14-4 Base Addresses of the Expansion Modules with CPU 486-3,
CPU 488-3
Interface Submodule
Base Address Modules in Submodule
Receptacle ...
Cn40H CPU 486-3, CPU 488-3 Number 0
Slot n
Co40H CPU 486-3, CPU 488-3 Nummer 3
Slot o = n + 1
Cp40H Number 6
Cp80H 1st EXM 478 in slot p = n + 2 Number 7
CpC0H Number 8
Cq40H Number 9
Cq80H 2nd EXM 478 in slot q = n + 3 Number 10
CqC0H Number 11
Cr40H Number 12
Cr80H 3rd EXM 478 in slot r = n + 4 Number 13
CrC0H Number 14
n .. r = Number of the module slot in the mounting rack in hexadecimal notation.
Introduction
Up to three interrupts per interface submodule are permitted in an EXM 478
expansion module. The various possible methods of interrupt assignment or
interrupt operation are described below.
Interrupt Assignment
When configuring the interface submodules in the BIOS setup, you can assign ISA
interrupts to the three interrupts of an interface submodule (IRQa, IRQb, IRQc).
For this purpose, enter the ISA interrupt provided in the relevant screen form.
If you enter the value “F0H” instead of the ISA interrupt, this interrupt is processed
via a shared interrupt. See below for details.
Shared Interrupt
Since the number of interrupts is limited due to AT-compatibility, it is possible to
assign several individual interrupts of the interface submodules to a shared
interrupt in the EXM 478 expansion modules. The shared interrupt is shared by all
interface submodule interrupts within an expansion module where the interrupt
assignment “F0H” has been entered.
The shared interrupt is assigned to the ISA interrupt during configuration of the
interface submodule in the BIOS setup.
Signal Switching
In an EXM 478 expansion module, two interface submodule signals can be
switched to another (signal switching). This signal switching is done during
configuration of the interface submodule in the BIOS setup.
Refer to the interface submodule description to find out if an interface submodule
requires signals from a further interface submodule, that is, if signal switching is
necessary.
Note
You will find a detailed description of the BIOS setup in the M7-400 application
module or CPU description.
EXM 478
6ES7 478-2AC00-0AC0
Performance Features
Number of connectable 3
interface modules
Connection of Yes
expansion modules
Technical Specifications
Supply voltage 5 VDC
Current consumption
(without interface
submodules) 0.2 A
Power losses
(without interface
submodules) 0.5 W
Permissible power losses
(with 3 interface
submodules)
• Without forced max. 10 W
ventilation
• With forced ventilation max. 12 W
Dimensions
W x H x D (mm) 25 x 290 x 210
Weight 0.65 kg
Note
The sum of the power losses of the EXM 478 expansion module and the interface
submodules it contains must not exceed the maximum permissible power losses.
Order Number
ATM 478: 6ES7 478-2CA00-0AC0
Characteristics
The ATM 478 AT adapter module is used to accommodate a short AT module
(card).
The ATM 478 AT adapter module has a 120-pin connector on the left-hand side
and a 120-pin socket on the right-hand side for connecting a further expansion
module or a mass storage module.
Pin Assignments
The ATM 478 AT adapter module has a 98-pin standard direct connector for short
AT modules (see Figure 14-8).
8 bit data
16 bit data
Figure 14-8 ATM 478 AT Adapter Module, 98-Pin Standard Direct Connector
See the following table for the pin assignments of the 98-pin standard direct
connector.
Table 14-5 Pin Assignments of the 98-Pin Standard Direct Connector (ATConnector)
Table 14-5 Pin Assignments of the 98-Pin Standard Direct Connector (ATConnector)
Current consumption
(without AT module) 0.12 A
Current consumption of See calculation of
the AT module current consumption
Power losses
(without AT module) 0.6 W
Permissible power losses
(with AT module)
• Without forced max. 10 W
ventilation
• With forced ventilation max. 12 W
Dimensions
W x H x D (mm) 25 x 290 x 230
Weight (without AT module) 0.74 kg
Table 14-6 Calculation Example for Total Power Losses of an ATM 478 with AT Module
In this example, the power losses are 6.94 W. The ATM 478 AT adapter module
can be operated without forced ventilation.
106.5 max.
100.33
0.8
3 min.
108.76
164 max. 2.84
4.3
18.4
14
10.9
0 2.85
0
5.9
8
12.2
Order Number
MSM 478: 6ES7 478-2BA00-0AC0
Characteristics
The MSM 478 mass storage module is used for storing programs and larger
quantities of data. It also has an AT-compatible parallel port (LPT).
The MSM 478 mass storage module has the following function units:
• One 3.5’’/1.44-Mbyte floppy disk drive
• One hard disk drive with a capacity of ≥ 516 x 106 bytes
• One AT-compatible parallel port LPT1
The MSM 478 mass storage module has a 120-pin connector on the left-hand side
and a 120-pin socket on the right-hand side for connecting further expansion
modules.
Characteristics
The MSM 478 mass storage module has an AT-compatible parallel port (LPT) for
connecting a printer with Centronics interface. The parallel port can also be used
as a bi-directional data interface. There is a 25-pin sub D socket connector on the
frontside of the submodule for plugging in the connecting cable.
This parallel port is always configured by the BIOS as LPT1 regardless of the slot
occupied by the MSM 478 mass storage module.
Addressing
I/O address of the parallel port (LPT): 03BCH (to 03BEH )
Device name: LPT1
Interrupt Request
The parallel port (LPT) supplies the interrupt request IRQ7.
Cable length
The cable length on the LPT1 parallel port should not exceed approximately 3 m.
Table 14-7 MSM 478 Parallel Port, Socket X1 (25-Pin Sub D Socket)
Note
Operational ground (GND signal) at the COMa or COMb ports is referenced to
internal ground.
Suitable measures may be required on the process side to avoid ground loops.
Note
The ambient conditions specified are limit values determined by the hard disk
drive. The values must not be exceeded on the hard disk drive.
Introduction
The interface submodules are designed for use in the M7-300 and M7-400
automation computers. They can be operated in the M7-400 programmable
modules and in the EXM 378/EXM 478 expansion modules. The interface
submodules are controlled via the ISA bus.
The interface submodules are labeled on the front plate and so can be identified
even when installed.
Handling
Interface submodules and their front connectors must only be plugged in or
removed when the power is switched off. Avoid confusing front connectors since
this can destroy the interface submodules or the connected devices.
ESD Guidelines
The interface submodules are not enclosed on the underside. For this reason, you
must observe ESD guidelines when handling these modules.
Submodule ID
Each interface submodule has a submodule ID stored in read-only memory. This
information is required in the BIOS Setup.
Interrupt Assignments
When configuring the interface submodules in the BIOS setup, you can assign ISA
interrupts to the three interrupts of an interface submodule (IRQa, IRQb, IRQc).
For this purpose, enter the ISA interrupt provided in the relevant screen form. See
the table below for the format for entering the interrupt.
Table 15-1 Format of the Interrupt Entry in the BIOS Setup of the Interface Submodule
If you enter the value “F0H” instead of the ISA interrupt (“EXH”), this interrupt is
processed via a shared interrupt.
Shared Interrupt
Since the number of interrupts is limited due to AT-compatibility, it is possible to
assign several individual interrupts of the interface submodules to a shared
interrupt. The shared interrupt is shared by all interface submodule interrupts within
an expansion module where the interrupt assignment “F0H” has been entered.
The shared interrupt is assigned to the ISA interrupt during configuration of the
interface submodule in the BIOS setup.
Signal Switching
In an EXM 478 expansion module, two interface submodule signals can be
switched to another (signal switching). This signal switching is done during
configuration of the interface submodule in the BIOS setup.
Refer to the interface submodule description to find out if an interface submodule
requires signals from a further interface submodule, that is, if signal switching is
necessary.
Submodule IDs
The following table contains an overview of the submodule IDs for the interface
submodules.
Table 15-2 Overview of the Submodule IDs for the Interface Submodules
Insertion Rules
The interface submodules cannot be operated in all submodule receptacles. The
following table shows the insertion rules for those interface submodules that
cannot be used in all receptacles:
Table 15-3 Insertion Rules for Interface Submodules that Cannot be Used in All Receptacles
Order Number
6ES7 962-1BA00-0AC0
Characteristics
The IF 962-VGA interface submodule is used to connect a keyboard and a VGA
screen. The interfaces to the keyboard and the screen are AT-compatible.
As an alternative to a “normal” AT keyboard, a keyboard with an integrated
trackball can be connected (for example, the PG 740 keyboard).
The IF 962-VGA interface submodule is designed for the local area and the
distance to the I/O devices should not exceed approximately 2.5 m.
Note
You can operate a maximum of one keyboard/graphics submodule on one
programmable module (CPU or FM).
Table 15-4 Socket X1, VGA Screen Connection IF 962-VGA (15-Pin High-Density Sub D
Socket Connector)
Pin Meaning
1 Analog red
2 Analog green
3 Analog blue
4
5 Signal GND
6 Analog GND red
7 Analog GND green
8 Analog GND blue
9
10 Signal GND
11
12
13 Horizontal sync
14 Vertical sync
15
4
6
2
1 5
3
X2 socket
Figure 15-2 X2 Socket, Keyboard Plug Connection IF 961-VGA (6-Pin Mini DIN Socket
Connector)
Addressing
Addressing corresponds to the AT standard.
The following addresses are occupied by the IF 962-VGA interface submodule:
Memory addresses: A0000H to C7FFFH
I/O addresses: 060H to 06FH, 3B0H to 3BBH, 3BFH to 3DFH
Interrupt Request
The interface submodule supplies the following interrupts:
• IRQ a: Keyboard interrupt
• IRQ b: Mouse interrupt (trackball)
• IRQ c: VGA interrupt
The BIOS routes these interrupts to ISA interrupts in accordance with Table 15-6.
Submodule ID
The IF 962-VGA interface submodule has the submodule ID 81H.
Technical Specifications
The IF 962-LPT interface submodule receives its supply voltage from the M7-400
programmable modules or from the M7-300/400 expansion modules. The current
consumption given in the technical specifications is the consumption required for
dimensioning the power supply, that is, the current consumption is referenced to
24 V in the M7-300 and to 5 V in the M7-400.
6ES7 962-1BA00-0AC0
Technical Specifications
Supply voltage Supplied from the
M7-400
programmable
modules or from the
M7-300/400
expansion modules
Current consumption in the
M7-300
(for dimensioning the 24 V
current supply) 0.21 A
Current consumption in the
M7-400
(for dimensioning the 5 V
current supply) 0.6 A
VGA controller WD90C24
Video controller 1 Mbytes
Submodule ID 81H
Power losses 2.5 W
Dimensions
W x H x D (mm) 18.2 x 67 x 97
Weight 0.085 kg
Operating Modes
The WD90C24 VGA controller is used on the IF 962-VGA interface submodule.
Table 15-7 shows you the video modes supported by the BIOS of the IF 962-VGA
interface submodule.
Order Number
6ES7 962-3AA00-0AC0
Characteristics
The IF 962-COM interface submodule is used to connect devices with a serial port.
It contains two serial AT-compatible ports (COMa, COMb).
Up to four COM ports can be accessed on AT I/O addresses in one programmable
module using standard PC drivers. This also includes COM ports located on the
programmable module itself and those located on expansions. The IF 962-LPT
interface submodules can be operated in the AT-compatible address area and, if
special drivers are used, also in the M7-300/400-reserved address area.
Connector X1 corresponds to the COMa port, connector X2 to the COMb port. The
signal levels are defined in accordance with RS232C.
The cable length on the IF 962-COM interface submodule should not exceed
approximately 10 m.
Note
Operational ground (signal GND) at the COMa or COMb ports is referenced to
internal ground.
Suitable measures may be required on the process side to avoid ground loops.
Addressing
The IF 962-COM interface submodule can be addressed in the following two ways:
• In the AT-compatible I/O address area
• In the M7-300/400-reserved I/O address area (from C000H).
Table 15-9 Addressing the COM Ports in the AT-Compatible Address Area
Table 15-10 Offset Address Assignments for the IF 962-COM Interface Submodule
Offset Function Remarks
Address
00H Configuration register Read/write
08H - 0FH UART 16C552 parallel port Unused
10H - 17H COMa UART 16C552 Read/write
18H - 1FH COMb UART 16C552 Read/write
Configuration Register
The BIOS setup defines in which AT-compatible I/O address area the COM
interface is to be operated or whether it is only to be operated in the reserved I/O
address area and this information is stored in the configuration register.
Tables 15-11 to 15-13 give you an overview of the possible settings in the
configuration register.
Table 15-11 Offset Address for the Configuration Register (IF 962-COM)
Offset Function Remarks
Address
00H Configuration register Read/write
Table 15-12 Meaning of the Data Bits in the Configuration Register (IF 962-COM)
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Addressing type COM b 0 Addressing type COM a
Table 15-13 Meaning of the Addressing Type Bits in the Configuration Register
(IF 962-COM)
Addressing Type COM b/a
I/O Address
Bit 6/2 Bit 5/1 Bit 4/0
Addressing only possible in the reserved I/O address area
0 0 0
(from C000H) (default)
280H 0 0 1
2E8H 0 1 0
2F8H 0 1 1
380H 1 0 0
3E8H 1 0 1
3F8H 1 1 0
0 1 1 1
Note
The AT-compatible I/O address can only be set once for each COM port of an
automation computer (including those permanently installed in a programmable
module).
COM Ports
The COM ports (COMa and COMb) of the UART 16C552 can be addressed from
offset addresses 10H or 18H in accordance with component specification 16C552.
Data Formats
The following data formats can be set in the IF 962-COM interface submodule:
Data bits: 5 bits, 6 bits, 7 bits, 8 bits
Parity: Even, odd, disable
Stop bit: 1 bit, 1.5 bits, 2 bits
Transmission Speed
The following transmission speeds (transmission rates) can be set in the
IF962-COM interface submodule:
AT-compatible transmission speeds and transmission speeds up to 115.2 Kbps.
Note
Please note that a safe level of transmission speed depends on factors such as
cable length, cable type, and environmental interference.
Interrupt Request
The interface submodule supplies an interrupt request (IRQa and IRQb) for each
serial port.
You can define the assignment of the interrupt requests IRQa and IRQb to the
appropriate processor interrupt requests in the BIOS Setup.
Default settings in the BIOS are: IRQ 4 for COM1 and IRQ3 for COM2.
Submodule ID
The IF 962-COM interface submodule has the submodule ID 41H.
Technical Specifications
The IF 962-COM interface submodule receives its supply voltage from the M7-400
programmable modules or from the M7-300/400 expansion modules. The current
consumption given in the technical specifications is the consumption required for
dimensioning the power supply, that is, the current consumption is referenced to
24 V in the M7-300 and to 5 V in the M7-400.
6ES7 962-3AA00-0AC0
Technical Specifications
Supply voltage Supplied from the M7-400
programmable modules or
from the M7-300/400
expansion modules
Current consumption in the
M7-300
(for dimensioning the 24 V
current supply) 0.04 A
Current consumption in the
M7-400
(for dimensioning the 5 V
current supply) 0.1 A
Submodule ID 41H
Power losses 0.5 W
Dimensions
W x H x D (mm) 18.2 x 67 x 97
Weight 0.080 kg
Order Number
6ES7 962-4AA00-0AC0
Characteristics
The IF 962-LPT interface submodule contains an AT-compatible parallel (LPT) port
for connecting a printer with Centronics interface. The IF962-LPT submodule can
also be used as a bi-directional data interface. There is a 25-pin sub D socket
connector on the frontside of the submodule for plugging in the connecting cable.
Up to four LPT ports can be accessed on AT I/O addresses in one programmable
module using standard PC drivers. This also includes LPT ports located on the
programmable module itself and those located on expansions. The IF 962-LPT
interface submodules can be operated in the AT-compatible address area and, if
special drivers are used, also in the M7-300/400-reserved address area.
The cable length on the IF 962-LPT interface submodule should not exceed
approximately 3 m.
X1 Socket
Note
Operational ground (GND signal) at the COMa or COMb ports is referenced to
internal ground.
Suitable measures may be required on the process side to avoid ground loops.
Addressing
The IF 962-LPT interface submodule can be addressed in the following two ways:
• In the AT-compatible I/O address area
• In the M7-300/400-reserved I/O address area (from C000H)
Note
The LPT port in the M7-400 expansion module MSM 478 is always at the I/O
address 03BCH. For this reason, the I/O address 03BCH must not be set for the
IP 962-LPT interface submodule if an MSM 478 is in use.
Table 15-17 Offset Address Assignments for the IF 962-LPT Interface Submodule
Configuration register
The BIOS setup defines in which AT-compatible I/O address area the LPT
interface is to be operated or whether it is only to be operated in the reserved I/O
address area and this information is stored in the configuration register. Tables
15-18 to 15-20 give you an overview of the possible settings in the configuration
register.
Table 15-18 Offset Address for the Configuration Register (IF 962-LPT)
Table 15-19 Meaning of the Data Bits in the Configuration Register (IF 962-LPT)
Table 15-20 Meaning of the Addressing Type Bits in the Configuration Register
(IF 962-LPT)
Addressing Type
I/O Address
Bit 1 Bit 0
Addressing only possible in the reserved I/O address area
(fromC000H) 0 0
(default)
378H 0 1
278H 1 0
3BCH 1 1
Note
The AT-compatible I/O address can only be set once for each LPT port of a
programmable module.
The LPT port in the M7-400 expansion module MSM 478 is always at the I/O
address 03BCH. For this reason, the I/O address 03BCH must not be set for the
IP 962-LPT interface submodule if an MSM 478 is in use.
Parallel Port
The parallel port of the interface submodule’s UART 16C552 can be addressed
from offset address 10H in accordance with component specification 16C552.
Interrupt Request
The interface submodule supplies an interrupt request (IRQa).
You can define the assignment of the IRQa interrupt request to the relevant
processor interrupt request in the BIOS setup.
Submodule ID
The IF 962-LPT interface submodule has the submodule ID 44H.
Technical Specifications
The IF 962-LPT interface submodule receives its supply voltage from the M7-400
programmable modules or from the M7-300/400 expansion modules. The current
consumption given in the technical specifications is the consumption required for
dimensioning the power supply, that is, the current consumption is referenced to
24 V in the M7-300 and to 5 V in the M7-400.
6ES7 962-4AA00-0AC0
Technical Specifications
Supply voltage Supplied from the M7-400
programmable modules or
from the M7-300/400
expansion modules
Current consumption in the
M7-300
(for dimensioning the 24 V
current supply) 0.04 A
Current consumption in the
M7-400
(for dimensioning the 5 V
current supply) 0.1 A
Submodule ID 44H
Power losses 0.5 W
Dimensions
W x H x D (mm) 18.2 x 67 x 97
Weight 0.07 kg
Order Number
6ES7 961-1AA00-0AC0
Characteristics
The IF 961-DIO interface submodule has the following characteristics:
• 8 inputs, isolated in groups of 2
Input level 24 VDC; 8.5 mA
Input interrupt at rising and/or falling edge
Input delay can be set in common for all channels: approx. 750 µs or approx.
3 ms
• 8 outputs, isolated in groups of 4
Level 24 VDC; 0.1A
Outputs short-circuit protected via electronic fuse.
X1 Socket
There is a 25-pin sub D socket connector on the frontside of the submodule for
plugging in the connecting cable.
Figure 15-6 shows the pin assignments of the submodule.
1
14 NC
1M 2
15 DO7
DI0 3
16 DO6
DI1 4
17 DO5
2M 5
18 DO4
DI2 6
19 6L+
DI3 7
20 6M
3M 8
21 DO3
DI4 9
22 DO2
DI5 10
23 DO1
4M 11
24 DO0
DI6 12
25 5L+
DI7 13 5M
Figures 15-7 and 15-8 show the circuit block diagrams and the terminal connection
diagrams for wiring the digital inputs and digital outputs.
1
1M 14 NC
2 DO7
DI0 15
3 DO6
Internal DI1 16
4 DO5
data bus 2M 17
5 DO4
DI2 18
6 6L+
DI3 19
7 6M
Minternal 3M 20
8 DO3
DI4 21
9 DO2
DI5 22
Circuit block 10 DO1
4M 23
diagram 11 DO0
DI6 24
12 5L+
DI7 25 13 5M
Figure 15-7 Circuit Block Diagram and Terminal Connection Diagram for Wiring the Digital Inputs
1
14 NC
1M 2 DO7
DI0 15
3 DO6
DI1 16
4 DO5
2M 17
5 DO4 L+
DI2 18
6 6L+
DI3 19 Internal
7 6M
3M 20 data bus
8 DO3
DI4 21
9 DO2
DI5 22
10 DO1
4M 23
11 DO0 Minternal
DI6 24
12 5L+
DI7 25 13 5M
M
Terminal connection diagram Circuit block diagram
Figure 15-8 Circuit Block Diagram and Terminal Connection Diagram for Wiring the Digital Outputs
Table 15-21 Offset Address Assignments for the IF 961-DIO Interface Submodule
Table 15-22 Offset Address for the Digital Input Function (IF 961-DIO)
Offset Function Remarks
Address
0 User data digital input function Read only
Table 15-23 Assignment of the Digital Input (DI) Channels to the Bits (IF 961-DIO)
Bit Function =0 =1
20 DI channel 0 In the range In the range
-30 V to 5 V from 13 V to 30 V
: : : :
27 DI channel 7 In the range In the range
-30 V to 5 V from 13 V to 30 V
Table 15-24 Offset Address for the Digital Output Function (IF 961-DIO)
Offset Function Remarks
Address
1 User data digital output function Read/write
Table 15-25 Assignment of the Digital Output (DO) Channels to the Bits (IF 961-DIO)
Bit Function =0 =1
20 DO channel 0 0V + 24 V
: : : :
27 DO channel 7 0V + 24 V
Acknowledgment Register
The interrupt is acknowledged in this register. Tables 15-26 and 15-27 give an
overview of the acknowledgement register.
Table 15-26 Offset Address for the Acknowledgment Register (IF 961-DIO)
Offset Function Remarks
Address
2 Acknowledgment register Write only
Table 15-27 Meaning of the Bits in the Acknowledgment Register (IF 961-DIO)
Bit Function =0 =1
20 Reserved
: :
26 Reserved
27 Acknowledge interrupt No Yes
Interrupt Register
The cause of the interrupt is stored in this register. Tables 15-28 and 15-29 give an
overview of the interrupt register.
Table 15-28 Offset Address for the Interrupt Register (IF 961-DIO)
Offset Function Remarks
Address
3 Interrupt register Read only
Table 15-29 Meaning of the Bits in the Interrupt Register (IF 961-DIO)
Bit Function =0 =1
20 Level change at DI channel 0 No Yes
: : : :
27 Level change at DI channel 7 No Yes
Table 15-30 Offset Address for the Interrupt Enable Register (IF 961-DIO)
Table 15-31 Meaning of the Bits in the Interrupt Enable Register (IF 961-DIO)
Bit Function =0 =1
20 Reserved
: :
26 Reserved
27 Interrupt Disabled Enabled
Table 15-32 Offset Address for the Selection Register Rising Edge (IF 961-DIO)
Table 15-33 Meaning of the Bits in the Selection Register Rising Edge (IF 961-DIO)
Bit Function =0 =1
20 Interrupt generation at rising edge of the Disabled Enabled
digital input channel 0
: : : :
27 Interrupt generation at rising edge of the Disabled Enabled
digital input channel 7
Table 15-34 Offset Address for the Selection Register Falling Edge (IF 961-DIO)
Offset Address Function Remarks
6 Selection register falling edge Read/write
Table 15-35 Meaning of the Bits in the Selection Register Falling Edge (IF 961-DIO)
Bit Function =0 =1
20 Interrupt generation at falling edge of the digital Disabled Enabled
input channel 0
: : : :
27 Interrupt generation at falling edge of the digital Disabled Enabled
input channel 7
Mode Register
Tables 15-36 and 15-37 give an overview of the mode register.
Table 15-36 Offset Address for the Mode Register (IF 961-DIO)
Offset Address Function Remarks
7 Mode register Read/write
Table 15-37 Meaning of the Bits in the Mode Register (IF 961-DIO)
Bit Function =0 =1
20 Input delay 3 ms 750 ms
21 Reserved
: :
27 Reserved
Reset Status
After switching on the interface submodule, the input delay is set to 3 ms.
Interrupt Request
The interface submodule supplies an interrupt request (IRQa).
You can define the assignment of the IRQa interrupt request to the relevant
processor interrupt request in the BIOS setup.
Submodule ID
The IF 961-DIO interface submodule has the submodule ID 02H.
Technical Specifications
The IF 961-DIO interface submodule receives its supply voltage from the M7-400
programmable modules or from the M7-300/400 expansion modules. The current
consumption given in the technical specifications is the consumption required for
dimensioning the power supply, that is, the current consumption is referenced to
24 V in the M7-300 and to 5 V in the M7-400.
Order Number
6ES7 961-2AA00-0AC0
Characteristics
The IF 961-AIO interface submodule has the following characteristics:
• 4 analog inputs, each as voltage and current input
• 2 analog outputs, each as voltage and current output
• 24 VDC external power supply of the analog circuit section
• Hardware interrupt capability and diagnostic capability
Special Feature of the Measuring Range Selection and Output Range Selection
You select the measuring type (current measuring or voltage measuring) of an
input channel via the wiring of the analog inputs (see Figure 15-10 ). You select the
output type (current or voltage output) via the wiring of the analog outputs (see
Figure 15-10).
X1 Socket
There is a 25-pin sub D socket connector on the frontside of the submodule for
plugging in the connecting cable.
Figure 15-10 shows the assignments for the X1 socket and the terminal
connection diagram of the submodule.
Figure 15-10 X1 Socket Assignments (25-Pin Sub D Connector) and Terminal Connection Diagram of the
IF 961-AIO
Note
Use only shielded cables for connecting the inputs and outputs.
Meaning of Signals
The following table shows the meanings of the signals in Figure 15-10.
Table 15-38 Meaning of the Signals of the X1 Socket of the IF 961-AIO Interface
Submodule
Signal Meaning
MV0+ ... MV3+ Analog inputs: Voltage
MI0+ ... MI3+ Analog inputs: Current
M0- ... M3- Reference potential of the analog inputs
QV0, QV1 Analog outputs: Voltage
QI0, QI1 Analog outputs: Current
S0, S1 Reference potential of the analog outputs
L+ Voltage supply input 24 VDC
L1+, L2+ Outputs for supplying the 2-wire transducers (24 VDC)
M Ground (0 V)
Inputs
U
I CH 0
A U
CH 1
I
D U
CH 2
I
U CH 3
I
Internal
data bus L1+
Current
limiter
L2+
Outputs
A U
I CH 0
D U CH 1
I
L+
Internal
M
supply
+ Transducer
-
Analog
input :
:
+ Transducer
-
QV0
S0
CH 0 RL
-1
QI0
Analog QV1
output
S1
CH 1
QI1
(2)
RL
L+ L+ Load current
M supply
M
(3)
IF 961-AIO Ground point
Figure 15-12 Grounding the Analog Inputs/Outputs of the Interface Submodule IF 961-AIO
Introduction
Depending on the measuring type, you can connect various measured value
sensors to the analog inputs:
• Voltage sensors
• Current sensors as
– 2-wire transducers
– 4-wire transducers
• Resistance
This section describes how to connect the measured value sensors and what to
look out for when connecting the measured value sensors.
Unswitched Channels
You must short-circuit unswitched input channels and ground them. This achieves
optimal noise immunity for the analog module.
Note
Ensure that the VCM (common mode voltage) does not exceed the permissible
value. Violation of the permissible value can result in wrong measured values.
Isolated measured
value sensors
MV0+
+
VE0
- M0-
+
VCM0 MV1+
- +
VE1
- M1-
+
VCM1
-
MSENSOR
Ground bus
Non-isolated
measured value
MV0+
sensors +
VE0 M0-
-
MV1+
+
VE1 M1-
-
MSENSOR
Ground bus
L+
+24 V
+ MV0+
U M0-
-
+ MV1+
U M1-
-
VCM0 VCM1
0V M
+24 V
L+
Sensor,
e. g. pressure
gauge + L1+
P 2-wire -
transducers 4 to 20 mA MI0-
M0- Vm
+
P 2-wire - MI1+
transducers 4 to 20 mA Vm
M1-
0V M
+24 V
Sensor, L+
e. g. pressure
gauge + MV0+
transducer
P
- M0-
4-wire
P + MV1+
- M1-
VCM0 VCM1
0V M
+24 V L+
MV0+
M0-
QI0+
IC
MV1+
M1-
QI1+
IC
0V M
+24 V L+
MV0+
M0-
QI0+
IC
MV3+
M3-
0V M
Abbreviations Used
The abbreviations used in Figures 15-20 to 15-21 have the following meanings:
QI: Analog output current
QV: Analog output voltage
S: Reference potential of the analog circuit
RL: Load resistance
Figures 15-20 and 15-21 show you how you must connect loads/actuators to the
current or voltage outputs of the analog output module.
L+ +24 V
QI
RL
VCM
M 0V
Ground bus
L+ +24 V
QV1
S1
RL1
QV0
S0
RL2
0V VCM1 VCM0
M
Ground bus
15.7.4 Conversion Time and Cycle Time of the Analog Input Channels
Introduction
This section contains the definitions of and relationships between the conversion
time and the cycle time of analog input modules.
Conversion Time
The conversion time consists of the conversion time of the analog-digital converter
(ADC) and the settling time of the multiplexer.
Cycle Time
Analog-digital conversion and transfer of the digitized measured values takes place
upon request or by way of multiplexing (parameter assignment required), that is
the analog input channels are converted in sequence one after the other. The cycle
time, that is, the time until an analog input value has been converted again, is the
sum of the conversion times of all analog input channels of the interface
submodule.
Figure 15-22 gives a breakdown of the cycle time for an 4-channel analog input
module.
Introduction
This section contains the definitions and relationships of times relevant to the
analog output modules.
Conversion Time
The conversion time of the analog output channels includes the transfer of the
digitized output values from the internal memory and the digital-analog conversion.
Settling Time
The settling time, that is, the time between the presence of the converted value
and reaching the specified value at the analog output, depends on the load. Here,
a distinction must be made between resistive, capacitive, and inductive load.
Response Time
The response time, that is, the time between the presence of the digital output
values in the internal memory and reaching the specified value at the analog
output, is, in the worst case, the sum of the cycle time and the settling time. The
worst case arises if the analog channel is converted shortly before transfer of a
new output value and converted back only after conversion of the other channels
(cycle time).
Figure 15-23 shows the response time of the analog output channels.
tA
tE
tZ
t1 t2 t3
tA = Response time
tC = Cycle time corresponds to n x conversion time (n = activated channels)
tS = Settling time
t1 = New digitized output value available
t2 = Output value received and converted
t3 = Specified output value reached
Electrical Installation
You must connect the ground terminal (M and S0/S1) of the analog input/output
module with the ground terminal of the load power supply. Use a cable with a
cross-section of 1 mm2 for this purpose.
Unswitched Channels
You must short-circuit unswitched input channels. This achieves optimal noise
immunity for the analog module.
Leave unswitched output channels open.
15.7.7 Addressing
Addressing
The IF 961-AIO interface submodule is addressed with the M7-300/400-reserved
I/O address area (starting from C000H).
Table 15-39 Offset Address Assignments for the IF 961-AIO Interface Submodule
Offset Function when Function when
Address Reading Writing
00H ADC data channel 0 (20 - 215) ADC data channel 0 (20 - 215)
02H ADC data channel 1 (20 - 215) ADC data channel 1 (20 - 215)
04H ADC data channel 2 (20 - 215) Reserved
06H ADC data channel 3 (20 - 215) Reserved
08H Indication of settings such as automatic Setting of automatic conversion,
conversion, cycle time, interrupt enable cycle time and interrupt enable
0AH Indication of channel number Output of channel number
0CH Indication of end of conversion (EOC) Start of analog-digital conversion
and voltage fault
0EH Reserved Interrupt acknowledgment
Table 15-40 Meaning of the Data Bits in the Analog Output Function (IF 961-AIO)
Offset Remark
Writing
Address D15 D0
00H 211 210 29 28 27 26 25 24 23 22 21 20 0 0 0 0 DAC data
channel 0
Table 15-41 Meaning of the Input Bits in the Analog Input Function (IF 961-AIO)
Offset Remark
Reading
Address D15 D0
00H 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 ADC data channel 0
02H 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 ADC data channel 1
04H 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 ADC data channel 2
06H 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 ADC data channel 3
I
A
08H N 0 0 0 0 0 0 0 0 0 0 0 ta ta ta Control register 1
C
T
ADC
0AH 0 0 0 0 0 0 0 0 0 0 0 0 0 Control register 2
channel no.
E
P
0CH 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O Status register ADC
F
C
ta = 000 5.7 ms cycle time of the automatic conversion function
ta = 001 2.8 ms
ta = 010 1.3 ms
ta = 011 600 µs
ta = 100 185 µs
INT Interrupt enable, INT = 0 = not enabled, INT = 1 = enabled
AC = 1 Automatic conversion of all ADC channels active
ADC channel no. Number of the selected ADC channel (in the case of conversion on request)
(individual encoding)
ADC = 001 Channel 0
ADC = 010 Channel 1
ADC = 011 Channel 2
ADC = 100 Channel 3
PF = 1 Power failure, no external voltage
EOC = 1 End of conversion, end of the analog-digital conversion of the selected channel
Table 15-42 Meaning of the Control Bits in the Analog Input Function (IF 961-AIO)
Offset Remark
Writing
Address D15 D0
I
A
08H N 0 0 0 0 0 0 0 0 0 0 0 ta ta ta Control register 1
C
T
ADC
0AH 0 0 0 0 0 0 0 0 0 0 0 0 0 Control register 2
channel no.
S
0CH 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Status register ADC
C
Acknowledge interrupt
0EH x x x x x x x x x x x x x x x x
x = any
ta = 000 5.7 ms cycle time of the automatic conversion function
ta = 001 2.8 ms
ta = 010 1.3 ms
ta = 011 600 µs
ta = 100 185 µs
AC = 1 Automatic conversion of all ADC channels active
INT = 1 Generation of an interrupt after end of cycle
ADC channel no. Number of the selected ADC channel:
ADC = 001 channel 0
ADC = 010 channel 1
ADC = 011 channel 2
ADC = 100 channel 3
SC = 1 Start of analog-digital conversion, (SC = Start of conversion in the case of individual
encoding)
Table 15-43 Representation of the Digitized Measured Value for the Analog Input Function (Voltage and
Current Measuring Range)
Table 15-44 Representation of the Analog Output Ranges (Voltage and Current Output Ranges)
Interrupt Request
The interface submodule supplies an interrupt request (IRQa).
You can define the assignment of the IRQa interrupt request to the relevant
processor interrupt request in the BIOS setup.
Submodule ID
The IF 961-DIO interface submodule has the submodule ID 01H.
Technical Specifications
The IF 961-AIO interface submodule receives its supply voltage from the M7-400
programmable modules or from the M7-300/400 expansion modules. The current
consumption given in the technical specifications is the consumption required for
dimensioning the power supply, that is, the current consumption is referenced to
24 V in the M7-300 and to 5 V in the M7-400.
Interference Suppression, Error Limits for Analog Value Generation for the Outputs
Inputs Resolution (incl. overrange) 12 bits, bipolar, twos
Interference voltage complement
suppression for Cycle time (all channels) Per software
f = n (50/60 Hz 1 %)
Interference Suppression, Error Limits for
n = 1, 2, ...
Outputs
• Common-mode Cross-talk attenuation > 60 dB
interference (Vpp < 1 V) > 60 dB between the outputs
• Normal-mode Operating error limits (over
interference the entire temperature
(Peak value of range related to the output
interference < nominal range)
value of the input range) 0 dB
Cross-talk attenuation • Voltage output 1.0 %
between the inputs > 60 dB • Current output 1.0 %
Operating error limits Basic error limit (operating
(in the entire temperature error limits at 25 _C, related
range, related to the input to output range)
range) • Voltage output 0.8 %
• Voltage input 0.8 % • Current output 0.8 %
• Current input 0.8 % Output ripple (related to “full
Basic error limits (operating scale” of the output range;
error limits at 25° C, related bandwidth 50 kHz) 0.1 %
to input range) Data for Selecting an Actuator
• Voltage input 0.7 % Output ranges (nominal ± 10 V
• Current input 0.7 % values) ± 20 mA
Linearity error (related to 0.05 % Load impedance
input range) • At voltage output min. 2 kW
Repetition accuracy (in • At current output max. 500 W
settled state at 25° C,
• With capacitive load max. 1.6 mF
related to the input range) 0.2 %
Voltage output
Data for Selecting a Sensor
Input ranges (nominal ± 10 V/100 k
• Short-circuit protection Yes
ranges)/input resistance ± 20 mA/50 • Short-circuit current max. 40 mA
Permissible input voltage Current output
for voltage input • Idle voltage max. 13.1 V
(destruction limit) ± 18 V Connection of actuators
Permissible input current for
• For voltage output
current input (destruction
3-wire connection Possible
limit) ± 40 mA
4-wire connection
Connection of signal (measuring line) Not possible
sensors
• For current output
• For voltage 2-wire connection Possible
measurement Possible
Status, Interrupts, Diagnostics
• For current Interrupts
measurement
As 2-wire-transducer Possible • End-of-cycle interrupt Yes, can be set
As 4-wire-transducer Possible
• Diagnostic interrupt Yes, can be set
• For resistance
measurement Possible 1)
1) When supplied via analog outputs with a
constant current
Order Number
6ES7 961-3AA00-0AC0
Characteristics
The IF 961-CT1 interface submodule is used for connecting incremental encoders.
It has the following characteristics:
• Connection with RS422 or 24 V signals
• 4 digital inputs (START, STOP, SET, RESET), isolated
• 2 digital outputs (Q1, Q2), isolated
Introduction
This section contains an overview of the functionality of the IF 961-CT1 interface
submodule.
This functionality is achieved using the relevant driver software.
Comparison Values
You can store two comparison values on the submodule assigned to the two
outputs of the submodule. If the counter status reaches one of the comparison
values, the relevant output can be set to initiate control sequences directly in the
process.
Initial Value
You can specify an initial value (load value) for the IF 961-CT1. The counter is then
set to the initial value when a signal is present at the 24 V digital input on the
submodule.
Gate Functions
The count can be started and stopped in dependence on other events via gate
functions.
The IF 961-CT1 interface submodule has two gate functions:
• A software gate controlled via the program.
• A hardware gate controlled via the digital inputs of the interface submodule.
Interrupts
The IF 961-CT1 can initiate an interrupt when comparison values are reached or in
the event of overflow, underflow, or zero pass of the counter.
Diagnostic Interrupt
The IF 961-CT1 can initiate a diagnostic interrupt for the following events:
• Missing or incorrect counter module parameters
• Hardware interrupt lost
• Signal A, B, or N faulty
Additional Information
You will find more information about the interface submodule IF 961-CT1 in /108/,
IF 961-CT1 Counter Function Module, Programming and Parameter Assignment
Manual.
Addressing
The IF 961-CT1 interface submodule is addressed with the M7-300/400-reserved
I/O address area (starting from C000H).
Interrupt Request
The interface submodule supplies an interrupt request (IRQa).
You can define the assignment of the IRQa interrupt request to the relevant
processor interrupt request in the BIOS setup.
Submodule ID
The IF 961-CT1 interface submodule has the submodule ID 03H.
Technical Specifications
The IF 961-CT1 interface submodule receives its supply voltage from the M7-400
programmable modules or from the M7-300/400 expansion modules. The current
consumption given in the technical specifications is the consumption required for
dimensioning the power supply, that is, the current consumption is referenced to
24 V in the M7-300 and to 5 V in the M7-400.
Order Numbers
You can use the IF 964-DP interface submodule with order number
6ES7 964-2AA00-0AB0 (up to 07/99) in the M7-400.
You can use the IF 964-DP interface submodule with order number
6ES7 964-2AA01-0AB0 (as of 07/99) in the S7-400 and in the M7-400.
Characteristics
The IF 964-DP interface submodule is used for connecting distributed I/O via
“PROFIBUS DP”. The submodule has an isolated RS485 interface. The maximum
transmission rate is 12 Mbps.
The permissible cable length depends on the transmission rate and the number of
nodes. In the case of a point-to-point connection with a speed of 12 Mbps, a cable
length of 100 m is possible, and with a speed of 9.6 Kbps a cable length of
1,200 m is possible.
The system can be expanded to 125 stations.
Note
Even in an S7-400 CPU you may remove or insert the IF 964-DP interface
submodule only if it is off circuit.
Additional Information
You can find information on “PROFIBUS DP” in the following technical overviews
or manuals:
• Technical overview Distributed I/O in SIMATIC S7 and M7
• Manuals on the DP masters, for example, S7-300 Programmable Controller or
S7-400, M7-400 Programmable Controllers for the PROFIBUS-DP interface of
the S7-300
• Manuals on the DP slaves, for example, ET 200M Distributed I/O Device or
ET 200C Distributed I/O Device
• The manual on the network components SINEC L2/L2FO Network Manual,
such as bus connectors, RS 485 repeaters
• Manuals on STEP 7
X1 connector
There is a 9-pin sub D socket connector on the frontside of the submodule for
plugging in the connecting cable. See Table 15-45 for the pin assignments.
Intermediate Memory
The IF 964-DP interface submodule provides (intermediate) storage of the data in
the dual-port RAM. The size of the memory and its address can be assigned via
the driver used.
Protected Mode: 1 out of 8 areas of 512 Kbytes in the address area
C0 00 00H bis FF FF FFH.
Note
The memory address must not collide with other system addresses. The
IF 964-VGA interface submodule, for example, occupies the addresses from
C 00 00H to C 7F FFH.
Interrupt Request
The interrupt line of the interface submodule is switched with a processor interrupt
per software parameter assignment.
Interrupt Request
The interrupt line of the interface submodule is permanently assigned to the
processor interrupt.
Submodule ID
The IF 964-DP interface submodule has the submodule ID 8CH.
Technical Specifications
The IF 964-DP interface submodule receives its supply voltage in the S7-400 from
the central processing unit and in the M7-400 from the programmable modules or
from the expansion modules. The current consumption given in the technical
specifications is the consumption required for dimensioning the power supply, that
is, the current consumption is referenced to 24 V in the M7-300 and to 5 V in the
M7-400.
Mechanical Configuration
Caution
! The synchronization submodule contains a laser system and is classified as a
“CLASS 1 LASER PRODUCT” according to IEC 825-1. To ensure you use this
submodule correctly, read the operating instructions carefully and keep them for
future reference. If you incur problems with this model, inform your nearest
“authorized Siemens representative.” To avoid direct contact with the laser beam,
do not open the housing.
max. 500m
Technical Specifications
Technical Specifications
Supply voltage supplied from the CPU
Current consumption 0.5 A
Submodule ID 0x85
Power losses 2.5 W
Dimensions W x H x D (mm) 18.2 x 67 x 97
Weight 0.080 kg
Chapter Overview
Further information
You will find further information on the following processing times in the S7-400
Instruction List. It lists all the STEP 7 instructions that can be processed by the
relevant CPUs, together with their execution times and all the SFCs/SFBs
integrated in the CPUs and the IEC functions that can be called in STEP 7,
together with their processing times.
In this chapter you will learn about the composition of the cycle time and how you
can calculate the cycle time.
Time-Sharing Model
Cyclic program scanning, and thus also processing of the user program, is
performed in time slices. So that you can better appreciate these processes, we
will assume in the following that each time slice is exactly 1 ms long.
Process Image
The process signals are read or written prior to program scanning so that a
consistent image of the process signals is available to the CPU for the duration of
cyclic program scanning. Then the CPU does not directly access the signal
modules during program scanning when the address area ”inputs” (I) and ”outputs”
(O) are addressed, but addresses instead the internal memory area of the CPU on
which the image of the inputs and outputs is located.
Step Process
1 The operating system starts the scan cycle monitoring time.
2 The CPU writes the values from the process-image output table in the
output modules.
3 The CPU reads out the status of the inputs at the input modules and
updates the process-image input table.
4 The CPU processes the user program in time slices and performs the
operations specified in the program.
Step Process
5 At the end of a cycle, the operating system executes pending tasks,
such as the loading and clearing of blocks.
6 The CPU then goes back to the beginning of the cycle after the
configured minimum cycle time, as necessary, and starts cycle time
monitoring again.
Cycle time
PII
User program
SCC (OS)
Operating sys.
User program
CCycle time
Communications
Factors Remark
Transfer time for the
process-image output table
... see Table 16-3
(PIQ) and the process-image
input table (PII)
User program processing ... is calculated from the execution times of the different
time instructions (see S7-400 Instruction List). For a special
characteristic of the CPU 417-4H refer to Table 16-5.
Operating system scan time
... see Table 16-4
at scan cycle checkpoint
Increase in the cycle time You parameterize the maximum permissible cycle load
from communications due to communications in % in STEP 7 (Manual
Programming with STEP 7 Version 5.0). See Section 16.2.
Impact of interrupts on the Interrupt can interrupt the user program at any time.
cycle time ... see Sections 16.5 and 16.6, and also Table 16-6
Note
With CPUs produced prior to October 1998, updating of the process image of the
outputs takes place before the scan cycle checkpoint.
Figure 16-2 Formula for Calculation of the Transfer Time for the Process Image
Table 16-3 Data for Calculation of the Transfer Time for the Process Image
Table 16-4 Operating System Scan Time at the Scan Cycle Checkpoint
Table 16-5 User program processing time for the CPU 417-4H
OB10
A further reason for cycle times of different length is the fact that the execution
time of blocks (for example, OB 1) can vary on account of:
• Conditional instructions
• Conditional block calls
• Different program paths
• Loops, etc.
T cyc T wait
PCl16 OB40
PCl07 OB10
The actual cycle time is the sum of Tcyc and Twait. It is always greater than or equal
to Tmin.
User program
Component configurable
between 5 and 50%
Communications
Of the part remaining, the operating system of the S7-400 requires only a
negligibly small amount for internal tasks.
The CPU 417-4H is an exception: with this CPU the operating system component
is included in the factor shown in Table 16-5.
Cycle time
30 ms
You can set the communication load in this range
25 ms
20 ms
15 ms
10 ms
5 ms
0% 5% 10% 20% 30% 40% 50% 60%
Communication load
Notes
• Check the effects of a change of the value for the parameter “Cycle load due to
communications” in system operation.
• The communication load must be taken into account when you set the
maximum cycle time, since time errors will occur if it is not.
Recommendations
• If possible, apply the default value.
• Use a larger value only if the CPU is being used primarily for communication
purposes and the user program is non-time-critical.
• In all other cases select a smaller value.
Variation
The actual reaction time is somewhere between a shortest and a longest reaction
time. For configuring your system, you must always reckon with the longest
reaction time.
The shortest and longest reaction times are analyzed below so that you can gain
an impression of the variation of the reaction time.
Factors
The reaction time depends on the cycle time and on the following factors:
• Delay in the inputs and outputs
• Additional DP cycle times on the PROFIBUS-DP network
• Execution of the user program
Bus
17 ms
transit
time
7 ms
5 ms
4 ms
3 ms
2 ms Transmission rate:
12 Mbps
1 ms
Min. slave
interval
1 2 4 8 16 32 64 Number of DP slaves
If you are operating a PROFIBUS-DP network with more than one master, you
must take the DP cycle time into account for each master. In other words, perform
a separate calculation for each master and add the results together.
SCC (OS)
PIQ
Immediately before the PII is read in, the status of the input under
review changes. The change of input signal is also taken into account
PII in the PII.
The change of input signal is processed here by the user program.
Reaction time
User pro-
gram
SCC (OS)
The reaction of the user program to the change of input signal is output
here to the outputs.
PIQ
Calculation
The (shortest) reaction time is made up as follows:
• 1 × process image transfer time of the inputs +
• 1 × process image transfer time of the outputs +
• 1 × program processing time +
• 1 × operating system processing time at SCC +
• 2 × run time of the DP slave message frame (including processing in the DP
master) +
• Delay in the inputs and outputs
This is equivalent to the sum of the cycle time, DP run time and the delay in the
inputs and outputs.
SCC (OS)
Delay in the inputs
+ DP cycle time on the PROFIBUS-DP
PIQ
While the PII is being read in, the status of the input
under review changes. The change of input signal is no
PII
longer taken into account in the PII.
User pro-
gram
Reaction time
SCC (OS)
PIQ
Here the change of input signal is taken into account
PII in the PII.
The change of input signal is processed here by the
User pro-
user program.
gram
SCC (OS)
Calculation
The (longest) reaction time is made up as follows:
• 2 × process image transfer time of the inputs +
• 2 × process image transfer time of the outputs +
• 2 × operating system processing time +
• 2 × program processing time +
• 2 × run time of the DP slave message frame (including processing in the DP
master) +
• Delay in the inputs and outputs
This is equivalent to the sum of twice the cycle time and the delay in the inputs and
outputs plus twice the DP cycle time.
The specified times are merely CPU processing times and apply, unless otherwise
stated, to signal modules in the central rack.
Course of Calculation
1. Using the Instruction List, determine the run time of the user program.
2. Calculate and add the transfer time for the process image. You will find guide
values for this in Table 16-3.
3. Add to it the processing time at the scan cycle checkpoint. You will find guide
values for this in Table 16-4.
4. CPU 417-4H: multiply the calculated value by the factor in Table 16-5.
The result you achieve is the cycle time.
5. Multiply the result by the following factor:
100
100 - “configured communication load in %”
6. Using the Instruction List, calculate the run time of the program sections that
hardware interrupts. Add to it the relevant value in Table 16-6.
Multiply this value by the factor in step 4.
Add this value to the theoretical cycle time as often as the interrupt is triggered,
or is likely to be triggered, during the during the cycle time.
The result you obtain is approximately the actual cycle time. Make a note of the
result.
Example Installation I
You have installed an S7-400 with the following modules in the central rack:
• One CPU 414-2
• Two digital input modules SM 421; DI 32×DC 24 V (4 byte each in PA)
• Two digital output modules SM 422; DO 32×DC 24 V/0.5A (4 byte each in PA)
User Program
According to the Instruction List, your user program has a run time of 15 ms.
Example Installation II
You have installed an S7-400 with the following modules:
• One CPU 414-2
• Four digital input modules SM 421; DI 32×DC 24 V (4 byte each in PA)
• Three digital output modules SM 422; DO 16×DC 24 V/2A (2 byte each in PA)
• Two analog input modules SM 431; AI 8×13 bit (not in PA)
• Two analog output modules SM 432; AO 8×13 bit (not in PA)
CPU Parameters
The CPU has been assigned parameters as follows:
• Cycle load due to communications: 40%
User Program
According to the Instruction List, the user program has a run time of 10.0 ms.
Note
The interrupt reaction times can be delayed by read and write jobs having a
maximum aggregate (approx. 460 byte).
When interrupts are transferred between a CPU and DP master, only a diagnostic
or hardware interrupt can be currently reported at any time from a DP line.
Calculation
Min. interrupt reaction time of the CPU Max. interrupt reaction time of the CPU
+ min. interrupt reaction time of the + max. interrupt reaction time of the
signal modules signal modules
+ DP cycle time on PROFIBUS-DP + 2 * DP cycle time on PROFIBUS-DP
Signal Modules
The hardware interrupt reaction time of the signal modules is made up as follows:
• Digital input modules
Hardware interrupt reaction time = internal interrupt processing time + input
delay
You will find the times in the data sheet of the digital input module concerned.
• Analog input modules
Hardware interrupt reaction time = internal interrupt processing time +
conversion time
The internal interrupt processing time of the analog input modules is negligible.
The conversion times can be taken from the data sheet of the analog input
module concerned.
The diagnostic interrupt reaction time of the signal modules is the time which
elapses between a diagnostics event being detected by the signal module and the
diagnostic interrupt being triggered by the signal module. This time is so small that
it can be ignored.
Calculation
The hardware interrupt reaction time for the example results from the following
times:
• Hardware interrupt reaction time of the CPU 416-2: approx. 0.35 ms
• Increase from communication in accordance with the formula shown in the
footnote of Table 16-9 :
100 s + 1000 s × 20% = 300 s = 0.3 ms
• Hardware interrupt reaction time of the SM 421; DI 16×UC 24/60 V:
– Internal interrupt processing time: 0.2 ms
– Input delay: 0.5 ms
• Since the signal modules are plugged into the central rack, the DP cycle time
on the PROFIBUS-DP is not relevant.
The hardware interrupt reaction time results from the sum of the listed times:
Hardware interrupt reaction time = 0.35 ms + 0.3 ms + 0.2 ms + 0.5 ms = approx.
1.35 ms.
This calculated hardware interrupt reaction time is the time from a signal being
applied across the digital input to the first instruction in OB 40.
Definition of “Reproducibility”
Time-delay interrupt:
The deviation with time from the first instruction of the interrupt OB being called to
the programmed interrupt time.
Watchdog interrupt:
The variation in the time interval between two successive calls, measures between
the first instruction of the interrupt OB in each case.
Reproducibility
Table 16-10 contains the reproducibility of time-delay and watchdog interrupts of
the CPUs.
Module Reproducibility
Time-Delay Interrupt: Watchdog Interrupt
CPU 412-1/-2 –770 s / +330 s –40 s / +40 s
CPU 414-2/-3 –770 s / +330 s –40 s / +40 s
CPU 416-2/-3 –770 s / +330 s –40 s / +40 s
CPU 417-4 –770 s / +330 s –40 s / +40 s
CPU 417-4H solo –750 s / +400 s –850 s / +850 s
CPU 417-4H redundant –500 s / +800 s –700 s / +700 s
These times apply only if the interrupt can be executed at this time and not, for
example, delayed by interrupts with higher priority or interrupts of identical priority
that have not yet been executed.
Order Number
Area of Application
The IM 463-2 interface module is used for distributed connection of S5 expansion
units to an S7-400.
You can use the IM 463-2 in the CR of the S7-400. In the S5 expansion unit, you
use an IM 314.
This allows you to connect the following S5 expansion units to an S7-400:
• EU 183U
• EU 185U
• EU 186U
• ER 701-2
• ER 701-3
Accordingly, you can use all digital and analog I/O modules suitable for these EUs
or ERs.
Basic Requirement
If you connect an S5 expansion unit to a CR of the S7-400 via an IM 463-2, the
SIMATIC S5 basic requirements concerning EMC, ambient conditions, etc., apply
for the overall system.
Note
In environments contaminated by radiated noise, you must apply the type 721
cable shield (see Installation Manual, Chapter 4).
Introduction
When you connect S5 expansion units to an S7-400 via the IM 463-2, there are
rules to observe with regard to cable length, maximum expansion, use of a
terminating connector and permissible potential differences.
Cable Length
The maximum cable length per IM 463-2 from the CR of the S7-400 to the last
S5 expansion unit is 600 m. You set the actual cable length at the IM 463-2
(see Section A.3).
Maximum Expansion
You can use up to four IM 463-2s in one S7-400 CR.
At each IM 463-2 interface (C1 and C2), you can connect up to four S5 expansion
units in a distributed configuration.
You can connect further EUs centrally to the EUs connected in the distributed
configuration.
Terminating Connector
You must terminate the IM 314 of the last EU in each chain with the
6ES5760-1AA11 terminating connector.
Introduction
All controls and indicators on the IM 463-2 are arranged on the front plate. The
following figure shows the arrangement of the controls and indicators.
X1 connector
C1 interface
X2 connector
C2 interface
LEDs
LED Meaning
LED EXTF (red) Lights up in the event of an external fault. Chain 1 or chain 2 has a
fault (power supply failed in the EU; terminating connector missing;
wire break, or interface selector switch wrongly set).
LED C1 (green) Chain 1 (via front connector X1, connection 1) is in order.
LED C2 (green) Chain 2 (via front connector X2, connection 2) is in order.
Front connector X1 Connector plug (output) for chain 1 and chain 2.
and X2 X1 = upper front connector; X2 = lower front connector
Warning
! Danger of data loss.
Changing the setting of the interface selector switch and the cable length selector
switch in RUN mode can result in loss of data.
Change the settings of these switches only in STOP mode of the CPU.
Introduction
To install an IM 463-2 in a CR of the S7-400, proceed in the same way as when
installing other S7-400 modules (see Installation Manual, Chapter 5).
To connect an IM 463-2, follow the steps outlined below:
1. Prepare the connecting cable.
2. Plug in the connecting cable.
3. Select the interface.
4. Select the cable length.
Introduction
To operate the IM 463-2, you must set on the IM 314 the S5 expansion unit used
and the address area of the S5 I/O modules.
X3 X1 X3 X1
3 2 1 3 2 1
BR 3 ••• BR 3 •• •
X4 X2 X4 X2
X3 X1
3 2 1
BR 3 • ••
X4 X2
*) Status as shipped
further EU 184U,
EU 187U (central)
S5 IM 300-3 S5 S5 IM 300-5
expansion unit expansion unit IM 300-3 expansion unit
S5 IM 312-3 S5 IM 312-5
expansion unit expansion unit
S7-400
IM 463-2 S5 IM 300-3 S5
expansion unit expansion unit IM 300-5
max. 600 m
To further S5 expansion units (distributed)
(max. 4 per IM 463-2)
ÍÍÍÍÍÍÍÍÍÍÍ ÍÍÍÍÍÍÍÍÍÍÍ
1 17 50 34
Introduction
The IM 314 of the last expansion unit of each chain is terminated with the
6ES5 760-1AA11 terminating connector.
The following table shows the pin assignments of the 760-1AA11 terminating
connector.
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
1 17
ÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ
Plug Connection
34
Plug Connection
28 8
29 9
26 6
27 7
48 4
47 5
44 2
45 3
42 24
43 25
38 22
1)
39 23
34 20
1)
35 21
36 18
1)
37 19
40 12
1)
41 13
48 10
2)
49 11
15 30
16 31
14
50
1) 100
2) 200
Other References
You will find a detailed description of the principle of assigning parameters to signal
modules in the user program and a description of the SFCs that can be used for
this purpose in the STEP 7 manuals.
Modifiable Parameters
You can change the parameters of data set 1 and transfer them to the signal
module with SFC55. This does not change the parameters set in the CPU. You
cannot change the parameters of data set 0 in the user program for the S7-400.
The sections below give you an overview of which parameters of a module class
are stored in data sets 0 and 1.
Parameters
Table B-1 contains all the parameters you can set for the digital input modules. You
can see from the list
• Which parameters you can change with STEP 7 and
• Which parameters you can change with SFC55 “WR_PARM”.
You can also transfer the parameters set with STEP 7 to the module using SFC56
and SFC57 (see STEP 7 manuals).
Note
If you want to enable a diagnostic interrupt in the user program in data set 1, you
must first enable the diagnostics in data set 0 using STEP 7.
7 6 0 Bit no.
Byte 0
7 6 5 4 3 2 1 0
Byte 1 Hardware interrupt
7 6 5 4 3 2 1 0
Byte 2 Hardware interrupt
7 6 5 4 3 2 1 0
Byte 3 Hardware interrupt
The following figure shows you the structure of data set 1 (bytes 4, 5, and 6) of the
parameters of the digital input modules.
You activate a parameter by setting the relevant bit to “1”.
7 6 5 4 3 2 1 0
Byte 4 Hardware interrupt
7 6 5 4 3 2 1 0
Byte 5 Substitute value*)
7 6 5 4 3 2 1 0
Byte 6 Substitute value*)
Parameters
Table B-2 contains all the parameters you can set for the digital output modules.
You can see from the list
• Which parameters you can change with STEP 7 and
• Which parameters you can change with SFC55 “WR_PARM”.
You can also transfer the parameters set with STEP 7 to the module using SFC56
and SFC57 (see STEP 7 manuals).
Note
If you want to enable a diagnostic interrupt in the user program in data set 1, you
must first enable the diagnostics in data set 0 using STEP 7.
7 6 0 Bit no.
Byte 0
7 6 5 4 3 2 1 0
Byte 1 Substitute value
7 6 5 4 3 2 1 0
Byte 2 Substitute value
7 6 5 4 3 2 1 0
Byte 3 Substitute value
7 6 5 4 3 2 1 0
Byte 4 Substitute value
Parameters
Table B-3 contains all the parameters you can set for the analog input modules.
You can see from the list
• Which parameters you can change with STEP 7 and
• Which parameters you can change with SFC55 “WR_PARM”.
You can also transfer the parameters set with STEP 7 to the module using SFC56
and SFC57 (see STEP 7 manuals).
Note
If you want to enable a diagnostic interrupt in the user program in data set 1, you
must first enable the diagnostics in data set 0 using STEP 7.
7 6 0 Bit no.
Byte 0
Note
The representation of the limit values and the reference temperature corresponds
to the analog value representation (see Chapter 6). Please observe the range
limits in each case when setting the limit values.
B
Backup battery, 1-9
F
Fault LEDs, M7-400, CPUs, 13-6
L P
LBA mode, M7-400, 13-34
Parameter assignment, tool, 6-5, 6-25
LEDs, A-5
Parameters, 4-22
Limit value, 6-11
analog input modules, B-9
Loads, connecting, 6-30, 15-41
digital input modules, B-3
digital output modules, B-6
PARM_MOD, B-2
M Password, M7-400, 13-31
M7-400 Performance features, M7-400, CPUs, 13-2
ambient climatic conditions for use, 1-13 Permissible potential differences, A-3
main memory assignment, 13-40 PG cable, 12-2, 13-15
Main memory assignment, 13-40 Pin assignment, RS 485 repeater, 11-6
Maximum expansion, A-3 Process image updating, processing time, 16-4
Measured value sensors Process interrupt
connecting, 6-24 in the S7-400H system, 4-23
isolated, 6-24, 15-37 SM 321-7BH00, 4-23
non-isolated, 15-38 Processing time
Measuring range submodules, 6-2 process image updating, 16-4
settings, 6-4 user program, 16-4
Measuring ranges, analog input channels, 6-2 Protection class, 1-12
Memory assignment, M7-400, 13-40 Protection level, 4-16
Memory card, 8-2 setting, 4-16
Memory card, M7-400, CPUs, 13-8
Memory reset, operating sequence, 4-17
Q S
Quick memory test, 13-37 S5 modules, configuring, A-9
Scan cycle control, scan time, 16-6
Scan time
R operating system, 16-5
scan cycle control, 16-6
Rack
Secondary cache size, M7-400, 13-38
CR2, 2-7
Select boot sequence, M7-400, 13-36
ER1, 2-8
Select submodule, M7-400, 13-26
ER2, 2-8
Settling time, analog output, 6-28, 15-44
UR1, 2-3, 2-5
Setup fields, M7-400, 13-20
UR2, 2-3, 2-5
Setup page, M7-400
RAM card, 8-3
”Boot Options”, 13-36
Reaction time, 16-12
”Date/Time”, 13-32
calculation, 16-12
”Floppy/Card”, 13-35
calculation of, 16-14, 16-16
”Hard Disk”, 13-33
diagnostic interrupt, 16-24
”IF modules”, 13-25
hardware interrupt, 16-22
”Security”, 13-30
longest, 16-15
”System”, 13-38
parts, 16-12
”Timeout Function”, 13-29
reducing, 16-16
User Help, 13-24
shortest, 16-14
SFC55 WR_PARM, B-2
Read only, M7-400, 13-30
SFC56 WR_DPARM, B-2
Redundant mode, 3-5
SFC57 PARM_MOD, B-2
Redundant power supplies, 3-5
Shared destination, M7-400, 13-27
Reference junction, 6-9, 6-18
SIG destination, M7-400, 13-28
Reference temperature, 6-9
SIG source, M7-400, 13-28
Repeater. See RS 485 Repeater
Sign, analog value, 6-31
Resistance, 6-23
Smoothing, 6-9
Resistance thermometer, connections, 15-40
Spare parts, 12-1
Resolution, 6-31
Static parameters
Response time, analog output, 6-29, 15-44
of the AI, 6-5
RS 485 repeater, 11-1
of the AO, 6-25
appearance, 11-3
of the DI, 5-2
application, 11-2
Status LEDs, M7-400, CPUs, 13-6
definition, 11-2
Structure of thermocouples, 6-16
grounded, 11-4
Submodule IDs, interface submodule, 15-4
grounded operation, 11-4
rules on construction, 11-2
ungrounded, 11-4
ungrounded operation, 11-4
Oestliche Rheinbrueckenstr. 50
D-76181 Karlsruhe
Federal Republic of Germany
From:
Your Name: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Your Title: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Company Name: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Street: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
City, Zip Code _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Country: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Phone: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
r Automotive r Pharmaceutical
r Chemical r Plastic
r Electrical Machinery r Pulp and Paper
r Food r Textiles
r Instrument and Control r Transportation
r Nonelectrical Machinery r Other _ _ _ _ _ _ _ _ _ _ _
r Petrochemical
Please give each of the following questions your own personal mark within the range from 1 (very
good) to 5 (poor).
Additional comments:
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _