0% found this document useful (0 votes)
8 views4 pages

3VL47401TF460AA0 Datasheet en

This document provides technical specifications for a Siemens 3VL4740-1TF46-0AA0 circuit breaker. It has a rated current of 160-400A, is rated for 415V AC 4-pole operation, and has an integrated overload and short-circuit protection unit.

Uploaded by

BOURICH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views4 pages

3VL47401TF460AA0 Datasheet en

This document provides technical specifications for a Siemens 3VL4740-1TF46-0AA0 circuit breaker. It has a rated current of 160-400A, is rated for 415V AC 4-pole operation, and has an integrated overload and short-circuit protection unit.

Uploaded by

BOURICH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Data sheet 3VL4740-1TF46-0AA0

circuit breaker VL400N standard breaking capacity Icu=55kA, 415V AC 4-pole, line
protection trip unit ETU20, LSI In=400A, rated current IR=160...400A, overload
protection, ISD=1.5 to 10xIR, II=11 xIN short-circuit protection N protected without
auxiliary release without auxiliary/alarm switch
Model
type of the driving mechanism motor drive No
design of the overcurrent release ETU20
General technical data
number of poles 4
size of the circuit-breaker 3VL4
mechanical service life (operating cycles) typical 20 000
electrical endurance (operating cycles) typical 10 000
utilization category A
performance class for circuit breaker N
reference code according to DIN 40719 extended according to Q
IEC 204-2 according to IEC 750
operating frequency maximum 120 1/s
Voltage
Rated operational voltage Ue max. 690 V

● insulation voltage rated value 800 V


● insulation voltage (Ui) at AC rated value 800 V
surge voltage resistance rated value 8 kV
operating voltage
● rated value maximum 690 V
● for main current circuit at AC at 50 Hz maximum 690 V
● for main current circuit at AC at 60 Hz maximum 690 V
● for main current circuit at DC maximum 500 V
Protection class
protection class IP IP20
protection function of the overcurrent release LSIN
Main circuit
operating frequency
● 1 rated value 50 Hz
● 2 rated value 60 Hz
Auxiliary circuit
number of CO contacts for auxiliary contacts 0
number of NC contacts for auxiliary contacts 0
number of NO contacts for auxiliary contacts 0
Suitability
suitability for use system/generator protection
Adjustable parameters
adjustable current response value current of the current- 160 A
dependent overload release initial value
Product details
product component
● trip indicator No
● auxiliary switch No
● voltage trigger No
● undervoltage release No
● undervoltage release with leading contact No
product extension optional motor drive Yes
Product function
product function

3VL47401TF460AA0 Subject to change without notice


3/30/2024
Page 1/4 © Copyright Siemens
● of thermal overload trip unit adjustable
● grounding protection No
● for neutral conductors short-circuit and overload proof Yes
● overload protection Yes
Short circuit
operating short-circuit current breaking capacity (Ics)
● at 240 V rated value 65 kA
● at 415 V rated value 55 kA
● at 500 V rated value 20 kA
● at 690 V rated value 8 kA
maximum short-circuit current breaking capacity (Icu)
● at 240 V rated value 65 kA
● at 415 V rated value 55 kA
● at 440 V rated value 35 kA
● at 480 V according to NEMA rated value 35 kA
● at 500 V rated value 25 kA
● at 600 V according to NEMA rated value 20 kA
● at 690 V rated value 15 kA
Connections
arrangement of electrical connectors for main current circuit front side
type of connectable conductor cross-sections for main contacts
● with flexible busbar 25 x 10
● solid 50 ... 300 mm²
● finely stranded with core end processing 50 ... 240 mm²
● stranded 50 ... 300 mm²
type of connectable conductor cross-sections for auxiliary
contacts
● solid 0.75 ... 1.5 mm²
● finely stranded with core end processing 0,75 ... 1.0 mm²
type of electrical connection for main current circuit screw-type terminals
Mechanical Design
height 279.5 mm
width 183.5 mm
depth 163.5 mm
fastening method fixed mounting
Environmental conditions
ambient temperature during operation
● minimum -25 °C
● maximum 70 °C
ambient temperature during storage
● minimum -40 °C
● maximum 80 °C
Approvals Certificates
General Product Approval

Confirmation KC

General Product Ap-


Test Certificates Marine / Shipping other
proval

Special Test Certific- Type Test Certific- Confirmation


ate ates/Test Report

Environment

3VL47401TF460AA0 Subject to change without notice


3/30/2024
Page 2/4 © Copyright Siemens
Environmental Con-
firmations

Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VL4740-1TF46-0AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3VL4740-1TF46-0AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VL4740-1TF46-0AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications

last modified: 10/6/2022

3VL47401TF460AA0 Subject to change without notice


3/30/2024
Page 3/4 © Copyright Siemens
3VL47401TF460AA0 Subject to change without notice
3/30/2024
Page 4/4 © Copyright Siemens

You might also like