TM Daikin 50Hz Asean

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views167 pages

TM Daikin 50Hz Asean

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 167

ASEAN

TECHNICAL MANUAL
Chilled Water Fan Coil Units
FWW, FWF, FWK(E), FWE, FWC, FUD Series

FWW FWF FWK(E)

FWE-E FWC-C FWC-FD

FUD FWC-G EC
FWC-G

TM-FCUW-STA7
Table of Contents

Table of Contents

Nomenclature......................................................................................................................1
Product Line-Up..............................................................................................................5
Application Information......................................................................................................7
Operating Limits.............................................................................................................7
Installation Guide............................................................................................................9
Sound Data.........................................................................................................................24
Sound Pressure Level..................................................................................................24
Sound Power Level......................................................................................................31
NC Curve......................................................................................................................38
Selection Process.............................................................................................................67
Fan Performance Curve...............................................................................................69
Engineering & Physical Data..........................................................................................106
Outlines & Dimensions...................................................................................................128
Wiring Diagrams..............................................................................................................149
Service & Maintenance...................................................................................................160
Troubleshooting..............................................................................................................161
Table of Contents

ii
Nomenclature

Nomenclature
FWW 02 L - A C E AB

Revision
AA: Revision 1
AB: Revision 2

Specification
E: Cooling Only
H: Cooling and Heating
Market
C: Export with CE Mark
E: Export without CE Mark
Power Supply
A: 220-240V/1Ph/50Hz
F: 380-415V/3Ph/50Hz
Product Series
L: L series (for FWW)
D: D series (for FWE)
E: E series (for FWE)
Size
02: 2 kW*
03: 3 kW*
Fan Coil Unit Type
FWW: Wall Mounted
FWE: Ceiling Convertible / Ceiling Exposed

FWK 06 E - A C C AA

Revision
AA: Revision 1
AB: Revision 2

Specification
C: AC Motor Cooling and Heating
D: DC Motor Cooling and Heating

Market
C: Export with CE Mark
E: Export without CE Mark
Power Supply
A: 220-240V/1Ph/50Hz
F: 380-415V/3Ph/50Hz
Product Series
C: C series (for FWF)
E: E series (for FWK/FWKE)
EH: EH series (for 4 Pipes FWK/FWKE)
Size
06: 6 kW*
08: 8 kW*
Fan Coil Unit Type
FWF: Ceiling Cassette (600x600)
FWK: Ceiling Cassette (900x900)
FWKE: Ceiling Cassette (900x900) DC Motor
Remark:
* : Capacity value under Nomenclature is an indication.
Please refer to Engineering and Physical Data for exact capacity value

1
Nomenclature

FWC 03 C - A C A A A

Revision
A: Revision 1
B: Revision 2

Water Pipe Connection


A: Right Piping
B: Left Piping

Controller
A: With Controller
N: Without Controller

Market
C: Export with CE Mark
E: Export without CE Mark

Power Supply
A: 220-240V/1Ph/50Hz
F: 380-415V/3Ph/50Hz
Product Series
C: C series
Size
03: 3 kW*
04: 4 kW*
Fan Coil Unit Type
FWC: Ceiling Concealed

FUD 20 B - F C N P A

Air Discharge Direction


A: Horizontal
B: Vertical
Water Pipe Connection
P: Right Piping
Q: Left Piping
Controller
N: Without Controller

Market
C: Export with CE Mark
E: Export without CE Mark
Power Supply
A: 220-240V/1Ph/50Hz
F: 380-415V/3Ph/50Hz

Product Series
B: B series

Size
20: 20 kW*
25: 25 kW*

Fan Coil Unit Type


FUD: Ducted Blower

Remark:
* : Capacity value under Nomenclature is an indication.
Please refer to Engineering and Physical Data for exact capacity value

2
Nomenclature

FWC 20 F D - A E 5 C R F A X A A

Revision
A: Revision 1
B: Revision 2

Insulation Material/Thickness
A: PE/Drain Pan
Standard;Return Air Plenum
Without Insulation
K: NBR/Drain Pan
Standard;Return Air Plenum
Without Insulation

Motor/Control Module/Wired
Controller
X: AC/Without Control Module/
Without Wired Controller

Drain Pan Material & Length


A: Coated Cold Rolled Steel &
Standard Length
D: Stainless Steel & Standard
Length

Filter
F: 8mm Saranet Filter
H: 1inch Aluminium Filter

Return Air Plenum & Filter


Removal
R: Rear Return & Side/Bottom
Filter Removal

Coil & Water Pipe Connection


C: 3 Row, Right Piping
D: 3 Row, Left Piping
E: 4 Row, Right Piping
F: 4 Row, Left Piping
External Static Pressure
5: 50Pa
8: 75-80Pa
Market
E: Export w/o Marking
Power Supply
A: 220-240V/1Ph/50Hz
Application
D: High ∆T (9°C)

Product Series
F: F series
Size
02: 200CFM*
03: 300CFM*
Fan Coil Unit Type
FWC: Ceiling Concealed

Remark:
* : Air Flow Rate value under Nomenclature is an indication.
Please refer to Engineering and Physical Data for exact capacity value
Note:
Please consult factory for customised enquiry.

3
Nomenclature

FWC 10 G - A E 5 C X X A X D A

Revision
A: Revision 1
B: Revision 2

Insulation Material/Thickness
D: PE (10mm)
G: P E (20mm)
K: NBR (10mm)
R: NBR (20mm)

Motor/Control Module/Wired
Controller
X: AC/Without Control Module/
Without Wired Controller
Drain Pan Material & Length
A: Galvanised Steel & Standard
Length
B: Galvanised Steel & Extended
100mm
D: Stainless Steel & Standard
Length
E: Stainless Steel & Extended
100mm

Filter
X: No Filter
H: 1’’ Aluminium Filter
F: 8mm Saranet Filter
A: 8mm Aluminium Filter

Return Air Plenum & Filter


Removal
X: Without Return Plenum &
Without Filter Removal
S: Rear Return & Side Filter
Removal

Coil & Water Pipe Connection


C: Right Piping
D: Left Piping

External Static Pressure


3: 30Pa
5: 50Pa
8: 75-80Pa
Market
E: Export w/o Marking
Power Supply
A: 220-240V/1Ph/50Hz
W: 220-240V/1Ph/50Hz and
220-240V/1Ph/60Hz
Product Series
G: G series
Size
10: 1000CFM*

Fan Coil Unit Type


FWC: Ceiling Concealed
Remark:
* : Air Flow Rate value under Nomenclature is an indication.
Please refer to Engineering and Physical Data for exact capacity value
Note:
Please consult factory for customised enquiry.

4
Nomenclature

Product Line-Up

Chilled Water Fan Coil Units

Classification

Air Discharge
Connection
Handset

Control

Filter
PCB

1 1/4” BSP Female Thread Adaptor


Model

1/2” BSP Female Thread Adaptor

3/4” BSP Female Thread Adaptor


Without Controller

Horizontal Flow
Auto Air Swing

Saranet Filter
UCW_W2.0*

Vertical Flow

Viledon R29
50WJWXX*

Convertible
BRC52A

BRC51A
W3DC*

Turbo

Quiet
W3*

FWW02L X X X X X X X
FWW03L X X X X X X X
FWW04L X X X X X X X
FWW05L X X X X X X X
FWW06L X X X X X X X
FWF02C X X X X X
FWF04C X X X X X
FWF05C X X X X X
FWK06E(H) X X X X X X
FWK08E(H) X X X X X X
FWK09E(H) X X X X X X
FWK11E(H) X X X X X X
FWK13E(H) X X X X X X
FWKE05E(H) X X X X X X X
FWKE08E(H) X X X X X X X
FWKE11E(H) X X X X X X X
FWE05E X X X X X X
FWE06E X X X X X X
FWE07E X X X X X X
FWE08E X X X X X X
FWE10E X X X X X X
FWE12E X X X X X X

5
Nomenclature

Classification

Connection

Air Return

Discharge
Handset

Control

Filter
PCB

Air
1 1/4” BSP Female Thread Adaptor
3/4” BSPT Female Thread Adaptor

3/4” BSP Female Thread Adaptor

1” BSPT Female Thread Adaptor


Model

Without Controller

Horizontal Flow
Auto Air Swing

Bottom Return

Saranet Filter
UCW_W2.0*

Vertical Flow

Rear Return

Viledon R29
50WJWXX*

Convertible

Convertible
BRC52A

BRC51A
W3DC*

Turbo

Quiet
W3*

FWC03C X X X X X X
FWC04C X X X X X X
FWC06C X X X X X X
FWC07C X X X X X X
FWC09C X X X X X X
FWC11C X X X X X X
FWC12C X X X X X X
FWC14C X X X X X X
FWC16C X X X X X X
FWC02FD** X X X X X X
FWC03FD** X X X X X X
FWC04FD** X X X X X X
FWC05FD** X X X X X X
FWC06FD** X X X X X X
FWC08FD** X X X X X X
FWC10FD** X X X X X X
FWC02G X X X X
FWC03G X X X X
FWC04G X X X X
FWC06G X X X X
FWC08G X X X X
FWC10G X X X X
FWC12G X X X X
FWC14G X X X X
FWC16G X X X X
FWC18G X X X X
FWC20G X X X X
FUD20B X X X X X
FUD25B X X X X X
FUD30B X X X X X
FUD40B X X X X X
* PCB naming
** Standard Model, optional items please refer to Nomenclature.

6
Application Information

Application Information
Model: FWW
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode Heating Mode
Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F
Minimum indoor Minimum indoor
19.0 / 66.2 14.0 / 57.2 15.0 / 59.0 -
temperature temperature
Maximum indoor Maximum indoor
32.0 / 89.6 23.0 / 73.4 27.0 / 80.6 -
temperature temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.

Model: FWF
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (2 Pipes) (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode Heating Mode
Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F
Minimum indoor Minimum indoor
19.0 / 66.2 14.0 / 57.2 15.0 / 59.0 -
temperature temperature
Maximum indoor Maximum indoor
32.0 / 89.6 23.0 / 73.4 27.0 / 80.6 -
temperature temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.

Model: FWK & FWKE


Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (2 Pipes) (Heating), 35°C ~ 70°C (4 Pipes) (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode Heating Mode
Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F
Minimum indoor Minimum indoor
16.0 / 60.8 11.0 / 51.8 16.0 / 60.8 -
temperature temperature
Maximum indoor Maximum indoor
32.0 / 89.6 23.0 / 73.4 30.0 / 86.0 -
temperature temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.

Model: FWE
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode Heating Mode
Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F
Minimum indoor Minimum indoor
19.0 / 66.2 14.0 / 57.2 15.0 / 59.0 -
temperature temperature
Maximum indoor Maximum indoor
32.0 / 89.6 23.0 / 73.4 27.0 / 80.6 -
temperature temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.

7
Application Information

Model: FWC-C
Operating Limits:
Thermal carrier : Water
Water temperature : 4 ~ 10°C (Cooling), 35°C ~ 50°C (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode Heating Mode
Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F
Minimum indoor Minimum indoor
19.0 / 66.2 14.0 / 57.2 15.0 / 59.0 -
temperature temperature
Maximum indoor Maximum indoor
32.0 / 89.6 23.0 / 73.4 27.0 / 80.6 -
temperature temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.

Model: FWC-FD
Operating Limits:
Thermal carrier : Water
Water temperature : 4 ~ 10°C (Cooling)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
19.0 / 66.2 14.0 / 57.2
temperature
Maximum indoor
32.0 / 89.6 23.0 / 73.4
temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.

Model: FWC-G (LSP & MSP) , FWC-G EC (LSP & MSP)


Operating Limits:
Thermal carrier : Water
Water temperature : 4 ~ 10°C (Cooling)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
19.0 / 66.2 14.0 / 57.2
temperature
Maximum indoor
32.0 / 89.6 23.0 / 73.4
temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.

Model: FUD
Operating Limits:
Thermal carrier : Water
Water temperature : 4 ~ 10°C (Cooling), 35°C ~ 70°C (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode Heating Mode
Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F
Minimum indoor Minimum indoor
19.0 / 66.2 14.0 / 57.2 15.0 / 59.0 -
temperature temperature
Maximum indoor Maximum indoor
32.0 / 89.6 23.0 / 73.4 27.0 / 80.6 -
temperature temperature
Ts: Dry bulb temperature. Th: Wet bulb temperature.

8
Application Information

Installation Guide
System Configuration
The standard controller board comes with a VALVE jumper and a HEAT jumper. The system can be
configured as the jumper selection listed below:
HEAT Jumper VALVE Jumper
Heatpump Mode & Valve Application √ √
Heatpump Mode & Valveless Application √ X
Cooling Mode & Valve Application X √
Cooling Mode & Valveless Application X X
√ Jumper Remained X Jumper Removed

Caution
Disconnect the power supply to the unit before attempting to connect the wiring

Valve, Heat and Fan Priority Setting

Model: FWW-L

BLACK
WHITE
BROWN

FM BLACK (LIVE)
RED (FAN CAP)
WHITE (NEUTRAL)
AS

N
CN_FAN CN_STP CN_FAN FB
VALVE

Heat Jumper

VALVE HEAT
L
CN_ID COIL

Valve Jumper
TH1

CN_PGRM CN_WIR CN_DSP

NOTATION
FM : FAN MOTOR
TH2
BLACK

AS : AIR SWING MOTOR


BLUE

BLUE

RED
G/Y

TH1 : INDOOR COIL THERMISTOR


TH2 : ROOM THERMISTOR DISPLAY BOARD
HEAT -WITH JUMPER FOR HEAT PUMP VALVE N1 N L
-WITHOUT JUMPER FOR COOLING ONLY
-WITH JUMPER FOR VALVE APPLICATION L
VALVE N POWER
-WITHOUT JUMPER FOR VALVELESS APPLICATION SUPPLY
FIELD WIRING E
WIRED
CONTROLLER
2/3 WAY VALVE (OPTIONAL)

9
Application Information

Model: FWF/FWK/FWE/FWC-C

CN_DRY

SLIENT

CVLV

WTP
HVLV
LOW
MED

AS
HI
N2 LIVE

SHED CO_DRAFT TFULL A_FRZ W_OPEN UNOCP


HTR
N1

CN_TW

M1
M2

E
M3

LV
VA
M4
CN_PGRM

HE
H_SEN C_SEN ROOM CN_WIR CN_STP CN_DSP

AT
Valve Jumper Heat Jumper Fan Priority Jumper

Jumper With Jumper (Default) Without Jumper


User set speed or lower fan if auto
Fan Priority Jumper Fan Stop when thermostat cat off
mode is selected
Heat Jumper For Heat pump For Cooling only
Valve Jumper For valve control For valveless control

4 pipes system controller board setting


Model : FWK-E(H) & FWKE-E(H)

CN_DRY
SLIENT

HVLV
CVLV
LOW

WTP
MED

AS
HI

LIVE
N2

L
CO_DRAFT TFULL A_FRZ W_OPEN UNOCP

HTR
N1

CN_TW
Model 1
M1
M2 Model 2
E
LV

M3 Model 3
VA

M4
CN_PGRM Model 4
SHED
HE

H_SEN C_SEN ROOM CN_WIR CN_STP CN_DSP


AT

10
Application Information

The standard controller board (W3) comes with a default setting for model selection.
Please select the model accordingly by using jumper.
System Model Function

2 Pipe M1 - Cooling or Heating


System Model 1
FCU
Mini Chiller (Cooling Only)
FCU

M2 - Cooling or Heating with Auxiliary Heater


Model 2
FCU
Mini Chiller (Cooling / Heating)
FCU

4 Pipe M3 - Cooling Only with Boiler


System Model 3

FCU Mini Chiller (Cooling Only)

FCU Boiler

M4 - Cooling or Heating with Boiler


Model 4

FCU Mini Chiller (Cooling / Heating)

FCU
Boiler

NOTE :
i) Auto Fan Mode is only applicable in Model 3 only. (Cooling only with Boiler)
ii) Fan mode is not available in valveless control.
iii) Wired handset has an indoor room sensor. Avoid locating the wired handset at isolated places where room
temperature reading will be inaccurate.

11
Application Information

Indoor Installation
Model: FWW-L
The indoor unit must be installed in such a way so as to prevent short circuit of the cool discharged air with
the hot return air. Please follow the installation clearance shown in the figure. Do not place the indoor unit
where there could be direct sunlight shining on it. Also, this location must be suitable for piping and drainage,
and be away from doors or windows.

Air flow

performance)
(Indoor)

(Space for
min. 75
min. 50 min. 50
(Space for Required space (Space for
maintenance) maintenance)

All dimensions are in mm

Air Purging
To prevent pump damage, the fan coil unit should not be energized until the coil and all water lines have
been purged of air.

The Air Vent located inside the casing. Removed the casing and connect hose to the air vent while doing
purging.

Ensure there is no water droplets go into the control box during purging process.

The water piping can be routed to the unit in a number of ways (left or right from the back of the unit), by
using the cut-out holes on the casing of the unit (see figure). Bend the pipes carefully to the required position
in order to align it with the holes. For the side and bottom, hold the bottom of the piping and then position it to
the required direction (see figure). The condensation drain hose can be taped to the pipes.

Right-side, right-back or right-bottom piping

Right-side piping
Right-back piping
Remove pipe port cover here
for right-side piping
Right-bottom
piping
Bind coolant pipe
Remove pipe port cover here and drain hose
for right-bottom piping together with
insulating tape.

Left-side, left-back or left-bottom piping


Remove pipe port
cover here for
left-side piping

Left-side piping
Remove pipe port cover here Left-back piping
for left-bottom piping
Left-bottom piping

12
Application Information

Mounting Installation Plate


Ensure that the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to
reinforce the wall with plates, beams or pillars.
Use the level gauge for horizontal mounting, and fix it with 5 suitable screws for FWW02/03/04L and 7
suitable screws for FWW05/06L.
In case the rear piping draws out, drill a hole 65mm in diameter with a cone drill, slightly lower on the outside
wall (see figure).

FWW02/03/04L Mounting plate FWW02/03/04L (ALTERNATIVE INSTALLATION PLATE)


Mounting plate

Mounting plate fixing screw Mounting plate


fixing screw

FWW05/06L
Mounting plate

Mounting plate fixing screw

Model: FWF/FWK/FWKE
1. Preliminary Site Survey
Be sure to read this manual before installing the air-conditioner indoor unit.
• Voltage supply fluctuation must not exceed +10% of rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply fluctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
• Do not exert pressure on the resin parts when opening the unit or when moving it after opening.
• Do not move the unit from packaging while moving, until it reaches the installation site. Use safe material
or protection plates when unpacking it or lifting it to avoid damage or scratches to the unit.
Beam

3m or more
1m or more

3m or more

0.5m or more 0.5m or more 0.5m or more

Obstacle
Floor

• Ensure a location where:


a) Drainage can be done easily.
b) Convenient for wiring and piping.
c) Which have enough space for installation and service work.
d) Where no risk of flammable gas leakage.
e) When free from any obstacles in path of cool air discharge and warm air return and must allow
spreading of air throughout the room (near the center of the room).
f) Must be provided clearance for indoor unit from the wall and obstacles as shown in figure below.
g) The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid
amplifying noise and vibration.
h) The installation place (hanging ceiling surface) must be assuring levelness and the height in the ceiling
is 350mm or more.
i) The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).

13
Application Information

Unit Installation
• Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fix the
hanging rod.
• The installation template is extended according to temperature and humidity. Check on dimensions in use.
• The dimensions of the installation template are the same as those of the ceiling opening dimensions.
• Before ceiling laminating work is completed, be sure to fit the installation template to the indoor unit.
NOTE
Be sure to discuss the ceiling drilling work with the installers concerned.

FWK/FWKE FWF

Ceiling Opening Site = 890mm 15.0 538.0 18.0


Hanging Rod Site = 790mm

38.0

580.0 ~ 610.0mm (Ceiling Board Opening)


88.0
Ceiling Opening Site = 890mm
Hanging Rod Site = 621mm
Unit size 820mm

505.0

448.0
Unit size 820mm

Unit 32.0 529.0 19.0

580.0 ~ 610.0mm (Ceiling Board Opening)


Piping Direction

Unit Hanging
• Confirm the pitch of the hanging rod.
• Hold the unit and hang it on the hanging rod with the nut and washer.
• Adjust the unit height to 35.0mm between the indoor unit bottom surface and the ceiling surface.
• Confirm with a level gauge that the unit is installed horizontally and tighten the nut and bolt to prevent unit
failing and vibration.
• Open the ceiling board along the outer edge of the paper installation template.

Indoor
Indoor Unit
Unit
Ceiling
Ceiling
Board
Board

35.0mm
35.0 mm

Drain Piping Work


• Drain pipe must be in downward gradient for smooth drainage.
• Avoid installing the drain pipe in up and down slope to prevent reversed water flow.
• During the drain pipe connection, be careful not to exert extra force on the drain connector at indoor unit.
• The outside diameter of the drain connection at the flexible drain hose is 20mm.
• Be sure to execute heat insulation (polyethylene foam with thickness more than 8.0mm) on the drain
piping to avoid the condensed water dripping inside the room.

Flexible Hose
Pipe Clamp
700.0mm
or less

Indoor
Unit

Panel Ceiling

14
Application Information

Drain Test
• Connect the main drain pipe to the flexible drain.
• Feed water from flexible drain hose to check the piping for leakage.
• When the test is completed, connect the flexible drain hose to the drain connector on the indoor unit.

Feed Water

Main Drain Pipe

Flexible Drain Hose

NOTE
This Indoor Unit uses a drain pump for condensed water drainage. Install the unit horizontally to prevent
water leakage or condensation around the air outlet.

Model: FWE05/06/07E
Standard Mounting
• Ensure that the overhead supports are strong enough to hold the weight of the unit.
• Position the hanger rods (wall mounting bracket for floor standing), and check for its alignment with the
unit.
• Also, check that the hangers are secured and the base of the fan coil unit is leveled in both horizontal
directions, taking into account the gradient for drainage flow as recommended in Figure A.

Figure A 10mm or more

Please ensure that the following steps are taken:


• Check the gradient for drainage flow as recommended in Figure A.
• Provide clearance for easy servicing and optimal air flow as shown in Figure B.
• The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm
return air.
• Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit must be a large distance away from the door.

Figure B
Min 500.0mm

Min
300.0mm Min 250.0mm

Utensils, Furnitures Or Built-In


Architectural Features Must Not
Protrude More Than 250.0mm
Ceiling Type

15
Application Information

Model: FWE08/10/12E
Standard Mounting
Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger
rods (wall mounting bracket for floor standing), and check for its alignment with the unit. Also, check that
the hangers are secured and the base of the fan coil unit is leveled in both horizontal directions, taking into
account the gradient for drainage flow as recommended in Figure A.

Figure A

10.0mm or less
10.0mm or more
Please ensure that the following steps are taken:
• Unit installation should be tilted at least 10mm as recommended in Figure A.
• The drain pipe slope shall be kept at least 1:100.
• Provide clearance for easy servicing and optimal air flow as shown in Figure B.
• The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm
return air.
• Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit must be a large distance away from the door.
Figure B
Nut
Hanger Bracket
Washer
Ceiling
10mm

Washer
500mm or more

Indoor Unit
2300mm or more

250mm or less Drainage Pipe


Nut

Utensils, furnitures or built-in


architectural features must not
protrude more than 250mm

Floor

300mm
(Min.)

1m or more
400mm or more

Floor Standing Type

16
Application Information

Model: FWC-C
The indoor unit must be installed such that there is no short circuit of the cool discharge. Respect the
installation clearance. Do not put the indoor unit where there is direct sunlight on unit. The location is suitable
for piping and drainage and it must have a large distance between a door and unit.
Ceiling Concealed Mounting
• Use the hanger supplied with the unit.
• Make sure that the ceiling is sufficiently strong to withstand the weight.

Field supply
Insulation material See
(field supply) Detail A
Air inlet side
Washer for hanger bracket
Air outlet side (attached)

Tighten
Aluminium tape Aluminium tape
(field supply) (field supply) Detail A

Provide clearance for servicing ease and optimal air flow as shown in the diagram.

300mm
or more
10mm

300mm* or more Ceiling

2300mm or more

Floor

* Can be smaller than 300mm if ceiling is removable.

Ceiling Concealed Drain Piping Work


10mm (0.39")

Bottom of
the unit
Sla
nt

or more or more

Drain
100 100

trap

Insulate securely Do not leave in water Unit : mm

• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused
by leaks and condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
• Ensure the drain pipe is securely insulated.
• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit
compared to the outside atmospheric pressure when the unit is operating. The drain trap is to avoid
possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is
smooth.
• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.

17
Application Information

Model: FWC-FD
The indoor unit must be installed such that there is no short circuit of the cool discharge. Respect the
installation clearance. Do not put the indoor unit where there is direct sunlight on unit. The location is suitable
for piping and drainage and it must have a large distance between a door and unit.
Ceiling Concealed Mounting
• Use the hanger supplied with the unit.
• Make sure that the ceiling is sufficiently strong to withstand the weight.

Insulation material See Detail A


(field supply)
Air inlet side
Air outlet side

Aluminium tape
(field supply)
Aluminium tape
(field supply)

Provide clearance for servicing ease and optimal air flow as shown in the diagram.

300mm
or more
10mm

300mm* or more Ceiling

2300mm or more
Floor

* Can be smaller than 300mm if ceiling is removable.

Ceiling Concealed Drain Piping Work

Bottom of
the unit
Sl a
10mm (0.39")

or more or more
nt

Drain
100 100

trap

Insulate securely Do not leave in water


Unit : mm

• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused
by leaks and condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
• Ensure the drain pipe is securely insulated.
• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit
compared to the outside atmospheric pressure when the unit is operating. The drain trap is to avoid
possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.
• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.

18
Application Information

Model: FWC-G (MSP , LSP)


The indoor unit must be installed such that there is no short circuit of the cool discharge. Respect the
installation clearance. Do not put the indoor unit where there is direct sunlight on unit. The location is suitable
for piping and drainage and it must have a large distance between a door and unit.
Ceiling Concealed Mounting
• Use the hanger supplied with the unit.
• Make sure that the ceiling is sufficiently strong to withstand the weight.

Provide clearance for servicing ease and optimal air flow as shown in the diagram.

Ceiling Concealed Drain Piping Work

• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused
by leaks and condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
• Ensure the drain pipe is securely insulated.
• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit
compared to the outside atmospheric pressure when the unit is operating. The drain trap is to avoid
possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.
• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.

19
Application Information

Model: FWC-G EC (MSP , LSP)


The indoor unit must be installed such that there is no short circuit of the cool discharge. Respect the
installation clearance. Do not put the indoor unit where there is direct sunlight on unit. The location is suitable
for piping and drainage and it must have a large distance between a door and unit.
Ceiling Concealed Mounting
• Use the hanger supplied with the unit.
• Make sure that the ceiling is sufficiently strong to withstand the weight.

Provide clearance for servicing ease and optimal air flow as shown in the diagram.

DO NOT HOLD THE BLOWER WHILE


LIFTING AND INSTALLING THE UNIT.

20
Application Information

Ceiling Concealed Drain Piping Work

• The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused
by leaks and condensation.
• For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the flow.
• Ensure the drain pipe is securely insulated.
• It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit
compared to the outside atmospheric pressure when the unit is operating. The drain trap is to avoid
possibility of splashes or an odor.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Conduct a water drainage test after the installation is completed. Make sure that the drainage flow is smooth.
• In humid environments, use an extra drain pan to cover the entire area of the indoor unit.

Important
INSULATION THROUGH OUT CHILLED WATER PIPING
CORK TAPE FULLY INSTALLED

SEE VIEW FROM BOTTOM

SEE VIEW A

INSULATION MUST COVER ALL


THE DRAIN PIPE

VIEW A
DRAIN PIPE INSULATE SECURELY

VIEW FROM BOTTOM

21
Application Information

Model: FUD
Mounting
Ensure that the overhead supports are strong enough to hold the unit’s weight. Position hanger rods and
check for alignment with the unit. Check that hangers are secure and that the base of fan-coil unit is level
in the two horizontal directions, taking into account the gradient recommended for drainage flow as shown.
Check the gradient recommended for drainage flow as follow.

10

FUD20/25B

500mm

300mm
300mm

500mm

300mm

* for free return of air

Provide clearance for servicing and optimal air flow as shown in the diagram.
The indoor unit must be installed such that there is no short circuit of cool discharge with air discharge.
Respect the installation clearance.
FUD 30/40B (Horizontal)
800.0

800.0 800.0

FUD 30/40B (Vertical)


800.0

800.0
800.0

1000.0

All dimensions in mm

22
Application Information

Others
The controller board of 4 pipes system (W3) comes with other dry contact options.

UNOCP A_FRZ W_OPEN TFULL


Unoccupied Mode
COMP
Anti Freeze Mode

Window Open Mode

TRANSFORMER

SHED
i) Unoccupied Mode
If the dry contact is closed, the Unoccupied mode is activated and vice versa. When Timer On is active,
system goes back to Occupied mode.
ii) Anti Freeze Mode
Anti Freeze operation has the highest priority among all unit operation. Anti Freeze operation will be
activated only if dry contact is closed and vice versa.
iii) Window Open Mode
If the dry contact is closed, Window Open Mode will be activated on the fan coil unit which is connected and
vice versa.
Note: The dry contact connection point can be connected with individual fan coil unit only. It cannot be connected
parallel with other fan coil units.

Cable Size
Model Unit FWE / FWF / FWK / FWW
Power supply cable size* mm2 1.5
Number of wire 3
Recommended fuse* A 2

Model Unit FWC03C FWC04C FWC06C FWC07C


Power supply cable size* mm2 1.5 1.5 1.5 1.5
Number of wire 3 3 3 3
Recommended fuse* A 1 1 1 2

Model Unit FWC09C FWC11/12/14/16C FWC02/03/04/05FD FWC06/08FD


Power supply cable size* mm2 1.5 1.5 1.5 1.5
Number of wire 3 3 5 5
Recommended fuse* A 3 5 1 2

Model Unit FWC10FD FWC-G FUD20/25B FUD30/40B


Power supply cable size* mm2 1.5 1.0 1.5 1.5
Number of wire 5 5 3 4
Recommended fuse* A 3 6 10 10

Important: * These values are for information only. They should be checked and selected to comply local
or national codes and regulations. They are also subjected to the type of installation and size of
conductor

23
Sound Data

Sound Data
Sound Pressure Level
1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 31 32 33 28 26 14 6 34 28
FWW02L Med 25 29 28 24 19 9 5 29 22
Low 20 26 24 20 11 8 6 25 18
High 30 33 33 32 28 17 8 35 31
FWW03L Med 26 29 30 27 21 11 7 30 25
Low 19 25 25 21 14 6 6 25 19
High 41 39 39 38 36 26 14 42 38
FWW04L Med 38 36 37 34 32 22 10 39 33
Low 30 30 31 28 23 12 7 32 26
High 37 38 38 39 33 22 11 42 38
FWW05L Med 33 35 35 35 29 17 8 38 34
Low 29 33 32 31 23 12 7 34 30
High 42 42 42 42 40 31 21 46 42
FWW06L Med 37 38 39 38 34 24 13 42 37
Low 34 35 36 35 30 20 9 39 34
Microphone position: 1m in front and 0.8m below the vertical centre line of the unit.

1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 44 45 40 36 26 19 10 42 35
FWF02C Med 40 38 34 28 19 9 7 35 29
Low 37 32 27 20 14 7 7 29 21
High 48 48 44 39 31 27 15 45 39
FWF04C Med 42 42 36 30 22 13 7 38 31
Low 39 36 28 20 15 6 6 30 23
High 52 51 46 41 34 31 19 48 41
FWF05C Med 44 43 39 33 26 18 8 40 33
Low 41 39 35 28 22 11 7 36 30
Microphone position: 1.4m below the face center of the air return of the unit.

24
Sound Data

1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 44 43 42 35 29 23 15 42 37
FWK06E(H) Med 40 40 38 30 23 16 14 38 33
Low 35 34 32 23 15 10 14 32 26
High 48 47 45 39 34 28 17 46 40
FWK08E(H) Med 44 42 42 34 28 21 10 42 37
Low 39 37 36 26 19 10 6 35 31
High 49 48 46 42 37 35 22 48 41
*FWK09E(H) Med 44 44 42 36 32 27 14 43 37
Low 41 39 37 31 26 17 8 38 32
High 51 49 49 45 37 36 24 50 45
*FWK11E(H) Med 48 46 47 40 33 31 18 47 43
Low 44 42 43 35 28 23 10 43 38
High 53 54 50 47 39 38 28 52 46
*FWK13E(H) Med 49 48 47 43 36 35 25 49 43
Low 46 45 44 39 32 30 22 45 39
Microphone position: 1.4m/*1.5m below the face center of the air return of the unit.

1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 39 39 37 28 18 11 6 37 32
Med 36 33 31 20 8 6 6 31 25
FWKE05E(H)
Low 28 26 23 12 4 5 6 23 16
Quiet 21 17 13 6 4 5 6 16 -
High 49 47 46 40 34 33 20 47 41
Med 46 43 42 35 29 24 12 42 37
*FWKE08E(H)
Low 44 39 37 28 20 12 7 37 32
Quiet 41 32 30 20 9 6 7 31 24
High 53 50 50 45 38 36 25 51 46
Med 49 45 46 40 33 30 17 46 41
*FWKE11E(H)
Low 42 40 41 33 26 19 8 41 36
Quiet 39 34 34 25 14 7 6 34 29
Microphone position: 1.4m/*1.5m below the face center of the air return of the unit.

1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 39 46 43 40 35 29 23 45 39
FWE05E Med 34 40 37 33 27 20 15 38 32
Low 32 38 35 30 24 16 17 36 30
High 42 48 45 43 38 32 26 48 42
FWE06E Med 38 43 42 38 33 26 18 43 37
Low 35 40 38 33 28 20 11 39 33
High 43 49 47 45 40 34 28 49 44
FWE07E Med 40 47 44 41 36 30 23 46 40
Low 36 42 39 36 30 23 16 41 35
High 41 46 44 44 42 35 28 48 43
*FWE08E Med 41 45 42 43 41 33 26 47 42
Low 38 44 39 40 37 29 24 44 39
High 44 49 46 48 47 40 33 52 48
*FWE10E Med 40 44 42 43 41 31 24 47 42
Low 39 44 41 42 40 31 24 46 41
High 48 51 49 47 44 41 31 52 47
*FWE12E Med 45 48 47 45 43 38 28 50 44
Low 44 47 46 44 41 37 28 49 43
Microphone position: 1m in front of the unit and 0.8m/*1m below the air discharge opening.

25
Sound Data

1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 43 35 35 30 26 18 13 36 30
FWC03C Med 43 34 34 28 25 17 12 35 29
Low 42 31 31 27 22 14 9 33 25
High 46 40 40 33 29 21 17 40 35
FWC04C Med 45 38 38 31 27 18 14 38 33
Low 40 33 33 26 21 11 9 33 28
High 47 41 43 35 31 24 19 42 38
FWC06C Med 47 41 41 34 31 23 18 41 36
Low 47 39 39 33 29 21 16 40 34
High 48 41 40 35 31 24 19 41 35
FWC07C Med 47 39 39 34 29 22 17 40 34
Low 44 35 35 30 25 17 12 36 30
High 50 45 43 42 37 31 26 46 41
FWC09C Med 45 40 40 38 32 26 20 42 37
Low 42 36 37 33 28 22 15 38 32
High 54 47 47 45 39 35 29 49 44
FWC12C Med 49 42 43 41 35 31 24 45 40
Low 45 39 41 37 30 26 18 41 36
High 54 49 49 48 43 37 32 52 47
FWC14C Med 53 47 46 47 40 35 29 50 46
Low 51 45 44 44 36 32 26 47 43
High 55 49 49 50 44 37 33 53 49
FWC16C Med 53 46 47 47 39 34 28 50 46
Low 51 43 44 43 35 30 24 47 42
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

26
Sound Data

1/1 Octave Sound Pressure Level (dB, reference 20mPa) Overall Noise
Model Speed
125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA) Criteria
High 41 37 38 38 30 23 13 40 37
FWC02FD Med 43 36 37 37 28 21 12 39 36
Low 39 35 34 33 24 16 5 36 32
High 41 41 39 35 32 26 18 40 34
FWC03FD Med 41 40 38 35 31 25 17 39 34
Low 41 38 37 34 29 23 15 37 33
High 43 41 40 37 33 26 18 41 36
FWC04FD Med 45 41 39 36 32 25 16 40 35
Low 45 38 36 33 28 20 9 37 32
High 44 42 43 38 34 29 20 42 38
FWC05FD Med 43 42 42 38 34 28 20 41 37
Low 41 40 40 36 31 25 15 39 35
High 45 44 44 41 34 28 21 45 40
FWC06FD Med 46 44 44 41 34 28 20 44 40
Low 45 42 42 38 31 26 16 41 37
High 52 49 46 47 36 28 21 47 46
FWC08FD Med 51 47 46 46 35 27 20 46 45
Low 50 43 44 45 33 25 17 45 44
High 51 47 46 45 39 32 23 48 44
FWC10FD Med 51 48 46 44 38 31 22 47 44
Low 49 45 44 43 36 29 19 45 42
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

Model 1/1 Octave Sound Pressure Level (dB, reference 20mPa) Overall Noise
Speed
(LSP) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA) Criteria
High 41 33 29 25 17 10 9 31 23
FWC02G Med 35 28 24 19 9 8 8 26 0
Low 29 23 18 12 8 8 7 20 0
High 36 34 29 28 18 11 9 32 26
FWC03G Med 28 27 23 19 9 8 8 25 0
Low 26 20 16 15 8 8 8 20 0
High 40 36 32 30 23 16 9 35 29
FWC04G Med 35 31 27 25 16 9 8 29 23
Low 27 24 19 13 9 9 8 21 0
High 45 40 35 32 28 22 13 38 31
FWC06G Med 43 36 32 29 25 19 11 35 28
Low 40 30 28 25 18 10 8 30 23
High 45 41 37 33 28 20 12 39 32
FWC08G Med 41 37 32 27 21 12 11 34 26
Low 35 29 25 18 11 10 10 26 0
High 47 44 38 35 30 22 16 41 34
FWC10G Med 45 39 35 30 24 15 9 37 30
Low 44 33 27 22 15 8 8 31 25
High 47 43 40 37 32 23 15 42 36
FWC12G Med 44 40 37 34 28 19 9 39 33
Low 41 36 33 30 23 12 8 35 29
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

27
Sound Data

Model 1/1 Octave Sound Pressure Level (dB, reference 20mPa) Overall Noise
Speed
(MSP) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA) Criteria
High 37 36 34 30 23 15 5 35 29
FWC03G Med 32 30 28 24 16 5 5 29 22
Low 24 22 20 12 7 7 6 20 -
High 37 37 36 32 28 21 12 37 31
FWC04G Med 32 31 30 26 20 12 5 31 24
Low 25 22 22 15 8 5 5 22 -
High 46 41 39 36 30 24 15 41 35
FWC06G Med 41 37 37 32 25 18 9 37 32
Low 38 32 31 25 17 9 4 31 25
High 47 43 41 38 32 26 15 43 37
FWC08G Med 43 38 36 32 25 17 6 37 31
Low 37 31 30 24 16 6 5 30 24
High 48 44 42 39 33 26 18 44 38
FWC10G Med 47 41 38 34 28 20 10 40 33
Low 43 33 32 26 18 7 5 33 26
High 48 44 43 39 33 26 18 44 38
FWC12G Med 43 40 39 35 29 21 12 40 34
Low 40 38 36 32 24 15 6 37 31
High 52 46 47 41 36 31 26 47 43
FWC14G Med 48 42 43 36 31 26 19 43 38
Low 41 35 35 28 23 15 7 35 30
High 55 48 47 42 38 34 28 48 43
FWC16G Med 50 42 44 38 33 28 21 44 39
Low 43 36 38 29 25 17 7 37 33
High 57 51 46 42 38 34 30 49 41
FWC18G Med 55 45 42 38 36 29 24 45 39
Low 52 39 35 30 26 20 13 39 35
High 55 52 49 43 38 36 31 50 45
FWC20G Med 52 48 44 39 35 31 26 46 39
Low 46 39 37 31 26 20 13 38 32
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

28
Sound Data

Model 1/1 Octave Sound Pressure Level (dB, reference 20mPa) Overall Noise
Speed
EC (LSP) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA) Criteria
High 41 33 29 25 17 10 9 31 23
FWC02G Med 35 28 24 19 9 8 8 26 0
Low 29 23 18 12 8 8 7 20 0
High 36 34 29 28 18 11 9 32 26
FWC03G Med 28 27 23 19 9 8 8 25 0
Low 26 20 16 15 8 8 8 20 0
High 40 36 32 30 23 16 9 35 29
FWC04G Med 35 31 27 25 16 9 8 29 23
Low 27 24 19 13 9 9 8 21 0
High 45 40 35 32 28 22 13 38 31
FWC06G Med 43 36 32 29 25 19 11 35 28
Low 40 30 28 25 18 10 8 30 23
High 45 41 37 33 28 20 12 39 32
FWC08G Med 41 37 32 27 21 12 11 34 26
Low 35 29 25 18 11 10 10 26 0
High 47 44 38 35 30 22 16 41 34
FWC10G Med 45 39 35 30 24 15 9 37 30
Low 44 33 27 22 15 8 8 31 25
High 47 43 40 37 32 23 15 42 36
FWC12G Med 44 40 37 34 28 19 9 39 33
Low 41 36 33 30 23 12 8 35 29
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

Model 1/1 Octave Sound Pressure Level (dB, reference 20mPa) Overall Noise
Speed
EC (MSP) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA) Criteria
High 37 36 34 30 23 15 5 35 29
FWC03G Med 32 30 28 24 16 5 5 29 22
Low 24 22 20 12 7 7 6 20 0
High 37 37 36 32 28 21 12 37 31
FWC04G Med 32 31 30 26 20 12 5 31 24
Low 25 22 22 15 8 5 5 22 0
High 46 41 39 36 30 24 15 41 35
FWC06G Med 41 37 37 32 25 18 9 37 32
Low 38 32 31 25 17 9 4 31 25
High 47 43 41 38 32 26 15 43 37
FWC08G Med 43 38 36 32 25 17 6 37 31
Low 37 31 30 24 16 6 5 30 24
High 48 44 42 39 33 26 18 44 38
FWC10G Med 47 41 38 34 28 20 10 40 33
Low 43 33 32 26 18 7 5 33 26
High 48 44 43 39 33 26 18 44 38
FWC12G Med 43 40 39 35 29 21 12 40 34
Low 40 38 36 32 24 15 6 37 31
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

29
Sound Data

1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 57 50 47 44 40 35 24 50 43
FUD20B Med 57 46 44 40 35 30 17 46 41
Low 48 42 41 35 30 24 6 42 36
High 57 53 50 50 44 40 31 54 49
FUD25B Med 55 51 49 48 42 38 28 52 47
Low 54 50 48 46 40 35 25 50 45
FUD30B High 57 55 56 53 51 46 38 58 53
FUD40B High 57 55 56 53 51 46 38 58 53
Microphone position: 1m in front of the unit and center of the unit.
1m away from every side of the unit and 1m above floor level

30
Sound Data

Sound Power Level


1/1 Octave Sound Power Level (dB, reference 1pW) Overall
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)
High 40 43 44 41 36 23 19 48
FWW02L Med 39 40 40 37 29 20 28 41
Low 38 37 35 32 21 16 23 36
High 48 45 46 44 38 28 20 48
FWW03L Med 48 41 42 40 32 18 19 44
Low 45 37 38 35 24 14 18 39
High 48 50 52 51 46 38 26 55
FWW04L Med 45 47 49 47 41 32 22 50
Low 43 42 44 41 34 22 18 45
High 50 51 53 51 42 33 20 55
FWW05L Med 47 49 50 48 38 27 17 51
Low 45 46 47 44 33 22 17 47
High 53 55 55 55 50 40 26 59
FWW06L Med 48 51 52 50 42 33 21 54
Low 45 48 50 47 38 29 18 51
Measured In Reverberation Chamber

1/1 Octave Sound Power Level (dB, reference 1pW) Overall


Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)
High 53 56 49 43 35 28 21 52
FWF02C Med 47 49 42 35 26 20 19 45
Low 43 44 36 27 19 14 19 39
High 56 58 55 50 42 38 29 56
FWF04C Med 50 51 48 41 32 26 20 49
Low 47 49 45 37 27 20 19 45
High 56 58 55 50 42 38 29 56
FWF05C Med 50 51 48 41 32 26 20 49
Low 47 49 45 37 27 20 19 45
Measured In Reverberation Chamber

1/1 Octave Sound Power Level (dB, reference 1pW) Overall


Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)
High 53 54 52 45 35 31 19 52
FWK06E(H) Med 50 51 48 39 29 23 17 47
Low 46 45 42 32 22 14 17 41
High 58 58 55 48 39 37 25 55
FWK08E(H) Med 53 53 51 43 33 29 18 51
Low 49 48 45 36 28 21 17 45
High 59 61 56 51 43 44 31 58
FWK09E(H) Med 54 55 52 46 38 36 23 53
Low 50 50 47 40 32 26 17 47
High 60 60 58 54 45 45 33 59
FWK11E(H) Med 57 57 56 50 41 40 26 56
Low 53 53 51 44 35 32 19 51
High 64 66 61 55 48 48 37 62
FWK13E(H) Med 59 60 57 52 44 44 32 58
Low 56 56 54 48 40 38 25 55
Measured In Reverberation Chamber

31
Sound Data

1/1 Octave Sound Power Level (dB, reference 1pW) Overall


Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)
High 49 50 45 36 26 20 19 46
Med 46 44 39 28 16 15 18 40
FWKE05E(H)
Low 38 40 32 22 14 15 20 34
Quiet 33 38 24 15 10 14 18 30
High 59 58 56 50 42 42 30 67
Med 54 54 51 44 37 34 23 52
FWKE08E(H)
Low 57 55 45 37 29 22 25 49
Quiet 50 44 39 29 17 15 19 40
High 63 60 58 53 45 46 34 59
Med 60 55 54 48 40 40 27 55
FWKE11E(H)
Low 58 50 49 41 34 29 20 49
Quiet 53 45 42 33 22 16 19 43
Measured In Reverberation Chamber

1/1 Octave Sound Power Level (dB, reference 1pW) Overall


Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)
High 51 58 55 52 47 41 35 62
FWE05E Med 47 52 49 45 39 32 27 55
Low 44 50 47 42 36 28 29 53
High 54 60 58 55 50 44 38 63
FWE06E Med 50 55 54 50 45 38 30 59
Low 47 52 20 45 40 32 23 56
High 55 61 59 57 52 46 41 66
FWE07E Med 52 59 56 53 48 42 35 62
Low 48 54 52 48 42 35 28 58
High 62 65 60 59 55 50 43 64
FWE08E Med 58 63 57 57 52 46 39 61
Low 56 60 54 54 48 42 34 58
High 65 66 61 60 56 50 44 65
FWE10E Med 59 63 58 57 51 45 39 61
Low 57 60 55 54 48 41 34 58
High 61 66 61 61 56 52 45 65
FWE12E Med 60 64 60 58 54 48 41 63
Low 57 63 57 56 51 45 40 61
Measured In Reverberation Chamber

32
Sound Data

1/1 Octave Sound Power Level (dB, reference 1pW) Overall


Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)
High 57 54 52 52 51 46 44 57
FWC03C Med 54 51 50 49 48 43 39 54
Low 51 48 47 46 44 39 35 51
High 60 58 57 56 54 48 44 61
FWC04C Med 56 55 54 53 50 44 40 58
Low 51 50 49 48 44 37 34 52
High 63 62 61 61 59 55 51 65
FWC06C Med 61 61 59 60 58 53 49 64
Low 57 56 56 56 53 48 44 60
High 63 62 61 62 59 56 53 66
FWC07C Med 61 60 59 60 57 53 50 64
Low 58 57 56 57 54 49 47 61
High 65 66 68 69 65 63 60 73
FWC09C Med 61 62 64 65 61 58 55 69
Low 56 58 60 61 57 53 49 64
High 65 68 70 72 68 66 64 76
FWC12C Med 65 65 67 68 64 62 59 72
Low 59 61 63 64 60 59 54 68
High 67 69 71 72 69 66 64 76
FWC14C Med 66 66 69 69 66 63 61 73
Low 63 64 66 67 62 60 57 70
High 69 70 72 74 71 69 68 78
FWC16C Med 69 68 70 71 67 65 63 75
Low 64 65 67 67 63 61 59 71
Measured In Reverberation Chamber

33
Sound Data

1/1 Octave Sound Power Level (dB, reference 1pW) Overall


Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)
High 56 59 59 55 50 45 38 61
FWC02FD Med 57 58 58 54 49 44 37 60
Low 54 54 54 50 44 38 31 56
High 59 61 60 57 55 50 42 63
FWC03FD Med 59 61 59 56 53 48 40 62
Low 58 59 58 54 51 45 38 60
High 59 61 61 58 54 49 42 64
FWC04FD Med 60 60 60 57 53 48 41 63
Low 60 56 56 53 49 42 34 59
High 61 62 63 60 57 52 46 66
FWC05FD Med 60 62 62 60 57 52 45 66
Low 57 58 59 57 53 47 39 62
High 63 65 65 62 56 51 46 67
FWC06FD Med 62 64 64 61 55 51 45 66
Low 58 60 61 57 51 46 39 63
High 66 66 65 62 58 53 47 68
FWC08FD Med 67 65 64 61 57 52 47 67
Low 64 65 63 60 55 49 44 65
High 66 67 67 64 61 56 50 70
FWC10FD Med 65 66 67 64 60 55 49 69
Low 63 64 64 62 57 52 46 67
Measured In Reverberation Chamber

Model 1/1 Octave Sound Power Level (dB, reference 1pW) Overall
Speed
(LSP) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA)
High 61 52 54 54 47 41 32 57
FWC02G Med 53 49 51 50 42 35 29 53
Low 47 45 46 44 35 26 21 47
High 56 55 57 57 51 47 37 60
FWC03G Med 55 51 52 51 45 39 28 55
Low 49 43 44 41 33 24 23 45
High 58 58 59 59 54 49 40 62
FWC04G Med 55 55 56 55 49 43 33 58
Low 47 47 47 44 37 28 21 48
High 60 60 60 59 54 51 44 63
FWC06G Med 59 58 58 57 52 48 40 61
Low 54 54 54 53 46 42 33 56
High 60 60 60 58 53 49 41 62
FWC08G Med 57 56 56 55 48 43 34 58
Low 50 50 50 47 39 32 25 51
High 62 62 62 61 57 53 46 65
FWC10G Med 59 59 60 59 53 48 41 62
Low 54 54 55 54 47 41 31 57
High 64 62 62 61 56 52 44 65
FWC12G Med 61 60 60 58 52 48 40 62
Low 58 56 57 54 48 42 33 58
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

34
Sound Data

Model 1/1 Octave Sound Power Level (dB, reference 1pW) Overall
Speed
(MSP) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA)
High 55 55 58 58 53 48 40 61
FWC03G Med 50 51 53 52 47 41 32 56
Low 44 43 45 41 34 27 27 46
High 58 58 59 58 54 50 43 62
FWC04G Med 54 54 55 54 49 44 36 58
Low 47 45 47 45 37 30 27 48
High 60 60 62 61 56 52 45 65
FWC06G Med 57 58 60 59 53 48 41 62
Low 54 54 56 55 48 42 34 58
High 61 62 62 62 57 52 45 65
FWC08G Med 57 58 59 58 52 47 39 61
Low 52 51 53 51 43 37 30 54
High 61 63 64 65 60 55 49 68
FWC10G Med 58 60 61 61 56 51 43 64
Low 53 54 56 55 49 42 34 58
High 73 65 65 64 59 55 50 68
FWC12G Med 65 61 61 61 56 50 42 64
Low 61 58 59 58 52 46 37 61
High 68 70 69 68 63 62 60 72
FWC14G Med 66 65 65 64 59 56 52 68
Low 59 55 58 55 50 45 38 59
High 72 72 69 68 64 63 61 73
FWC16G Med 70 68 66 64 60 59 55 69
Low 58 58 58 56 52 48 42 60
High 71 73 72 71 66 65 63 75
FWC18G Med 68 69 69 67 62 60 58 71
Low 63 62 62 60 55 52 48 64
High 71 73 73 72 67 66 65 76
FWC20G Med 68 70 70 68 62 62 60 72
Low 61 62 62 60 55 52 48 64
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

35
Sound Data

Model 1/1 Octave Sound Power Level (dB, reference 1pW) Overall
Speed
EC (LSP) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA)
High 61 52 54 54 47 41 32 57
FWC02G Med 53 49 51 50 42 35 29 53
Low 47 45 46 44 35 26 21 47
High 56 55 57 57 51 47 37 60
FWC03G Med 55 51 52 51 45 39 28 55
Low 49 43 44 41 33 24 23 45
High 58 58 59 59 54 49 40 62
FWC04G Med 55 55 56 55 49 43 33 58
Low 47 47 47 44 37 28 21 48
High 60 60 60 59 54 51 44 63
FWC06G Med 59 58 58 57 52 48 40 61
Low 54 54 54 53 46 42 33 56
High 60 60 60 58 53 49 41 62
FWC08G Med 57 56 56 55 48 43 34 58
Low 50 50 50 47 39 32 25 51
High 62 62 62 61 57 53 46 65
FWC10G Med 59 59 60 59 53 48 41 62
Low 54 54 55 54 47 41 31 57
High 64 62 62 61 56 52 44 65
FWC12G Med 61 60 60 58 52 48 40 62
Low 58 56 57 54 48 42 33 58
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

Model 1/1 Octave Sound Power Level (dB, reference 1pW) Overall
Speed
EC (MSP) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA)
High 55 55 58 58 53 48 40 61
FWC03G Med 50 51 53 52 47 41 32 56
Low 44 43 45 41 34 27 27 46
High 58 58 59 58 54 50 43 62
FWC04G Med 54 54 55 54 49 44 36 58
Low 47 45 47 45 37 30 27 48
High 60 60 62 61 56 52 45 65
FWC06G Med 57 58 60 59 53 48 41 62
Low 54 54 56 55 48 42 34 58
High 61 62 62 62 57 52 45 65
FWC08G Med 57 58 59 58 52 47 39 61
Low 52 51 53 51 43 37 30 54
High 61 63 64 65 60 55 49 68
FWC10G Med 58 60 61 61 56 51 43 64
Low 53 54 56 55 49 42 34 58
High 73 65 65 64 59 55 50 68
FWC12G Med 65 61 61 61 56 50 42 64
Low 61 58 59 58 52 46 37 61
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).

36
Sound Data

1/1 Octave Sound Power Level (dB, reference 1pW) Overall


Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)
High 68 67 72 70 65 65 57 74
FUD20B Med 64 64 68 65 61 59 51 69
Low 61 60 63 60 56 53 43 65
High 71 71 74 74 70 70 63 78
FUD25B Med 70 69 73 72 68 68 60 76
Low 67 67 71 69 65 64 56 73
FUD30B High 75 76 75 72 69 65 60 77
FUD40B High 75 76 75 72 69 65 60 77
Measured In Reverberation Chamber

37
Sound Data

NC Curve

FWW02L
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
NC-50
NC-45
40 NC-40
NC-35
H
30 NC-30
M
L NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWW03L
70

60
Sound pressure level (dB, ref 20µPa)

NC-55

50 NC-50
NC-45

40 NC-40
NC-35
H
30 M NC-30

L NC-25

20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

38
Sound Data

FWW04L
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
NC-50
NC-45
40 H NC-40
M NC-35
30 L NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWW05L
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 NC-50

NC-45
40 H NC-40

M NC-35
30
L
NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

39
Sound Data

FWW06L
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 NC-50
NC-45
H
40 NC-40
M
NC-35
L
30 NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWF02C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 NC-50
NC-45
40 H NC-40
NC-35
M
30 NC-30
L
NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

40
Sound Data

FWF04C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55

50 NC-50
NC-45
H
40 NC-40
M NC-35

30 NC-30
L NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWF05C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
NC-50
H NC-45
40
M NC-40
NC-35
L
30 NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

41
Sound Data

FWK06E(H)
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
NC-50
NC-45
40 H NC-40
M NC-35

30 L NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWK08E(H)
70

60
Sound pressure level (dB, ref 20µPa)

NC-55

50 NC-50

H NC-45
40 M NC-40
NC-35
L
30 NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

42
Sound Data

FWK09E(H)
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
NC-50
H
NC-45
40 M
NC-40
L NC-35
30 NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWK11E(H)
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 NC-50
H
M NC-45
40 L NC-40

NC-35
30 NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

43
Sound Data

FWK13E(H)
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 H NC-50
M NC-45
40 L NC-40
NC-35
30 NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWKE05E(H)
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
NC-50

NC-45
40
NC-40
H NC-35
30 M NC-30

20
L NC-25

NC-20
Q
10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

44
Sound Data

FWKE08E(H)
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
NC-50

H NC-45
40 M NC-40
L NC-35
30
Q NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWKE11E(H)
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
H NC-50

M NC-45
40
L NC-40

NC-35
30
Q
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

45
Sound Data

FWE05E
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWE06E
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

46
Sound Data

FWE07E
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWE08E
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60
NC-60
NC-55
50 NC-50
H
NC-45
40 M
NC-40
L
NC-35
30
NC-30
NC-25
20
NC-20

10

125 250 500 1000 2000 4000 8000


Octave-band frequency (Hz)

47
Sound Data

FWE10E
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60
NC-60
NC-55
50 H NC-50
M NC-45
40 L NC-40
NC-35
30
NC-30
NC-25
20
NC-20

10

125 250 500 1000 2000 4000 8000


Octave-band frequency (Hz)

FWE12E
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60
NC-60
NC-55
50 H
NC-50
M
L NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20

10

125 250 500 1000 2000 4000 8000


Octave-band frequency (Hz)

48
Sound Data

FWC03C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 NC-50
NC-45
40 NC-40

H NC-35

30 M NC-30
L
NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC04C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55

50 NC-50
NC-45
40 NC-40
H
NC-35
M
30 L NC-30

NC-25

20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

49
Sound Data

FWC06C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
NC-50
H NC-45
40 M NC-40
L
NC-35
30 NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC07C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 NC-50

NC-45
40 H NC-40

M NC-35
30 L NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

50
Sound Data

FWC09C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 NC-50

H NC-45
40 NC-40
M
NC-35
L
30 NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC12C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50
H NC-50
NC-45
M
40
NC-40
L
NC-35
30 NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

51
Sound Data

FWC14C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 H NC-50
M
NC-45
L
40 NC-40

NC-35
30 NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC16C
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 H
NC-50
M
NC-45
40 L
NC-40
NC-35
30 NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

52
Sound Data

FWC02FD
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC03FD
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

53
Sound Data

FWC04FD
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC05FD
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

54
Sound Data

FWC06FD
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC08FD
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

55
Sound Data

FWC10FD
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC02G (LSP) / FWC02G EC (LSP)

80
Sound Pressure Level (dB,reference 20mPa)

70 NC-70

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

56
Sound Data

FWC03G (LSP) / FWC03G EC (LSP)

80
Sound Pressure Level (dB,reference 20mPa)

70 NC-70

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC04G (LSP) / FWC04G EC (LSP)

80
Sound Pressure Level (dB,reference 20mPa)

70 NC-70

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

57
Sound Data

FWC06G (LSP) / FWC06G EC (LSP)

80
Sound Pressure Level (dB,reference 20mPa)

70 NC-70

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC08G (LSP) / FWC08G EC (LSP)

80
Sound Pressure Level (dB,reference 20mPa)

70 NC-70

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

58
Sound Data

FWC10G (LSP) / FWC10G EC (LSP)

80
Sound Pressure Level (dB,reference 20mPa)

70 NC-70

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC12G (LSP) / FWC12G EC (LSP)

80
Sound Pressure Level (dB,reference 20mPa)

70 NC-70

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

59
Sound Data

FWC03G (MSP) / FWC03G EC (MSP)


80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC04G (MSP) / FWC04G EC (MSP)


80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

60
Sound Data

FWC06G (MSP) / FWC06G EC (MSP)


80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC08G (MSP) / FWC08G EC (MSP)


80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

61
Sound Data

FWC10G (MSP) / FWC10G EC (MSP)


80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC12G (MSP) / FWC12G EC (MSP)


80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

62
Sound Data

FWC14G (MSP)
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC16G (MSP)
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

63
Sound Data

FWC18G (MSP)
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FWC20G (MSP)
80

70 NC-70
Sound pressure level (dB, ref 20µPa)

NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40

NC-35
30
NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

64
Sound Data

FUD20B
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
50 NC-50
H
NC-45
M
40 NC-40
L NC-35

30 NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FUD25B
70

60
Sound pressure level (dB, ref 20µPa)

NC-55
H
50 NC-50
M
L NC-45
40 NC-40
NC-35

30 NC-30

NC-25

20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

65
Sound Data

FUD30B
70

60
Sound pressure level (dB, ref 20µPa)

H
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30 NC-30

NC-25
20
NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

FUD40B
70

60
Sound pressure level (dB, ref 20µPa)

H
NC-55
50 NC-50

NC-45
40 NC-40

NC-35
30 NC-30

NC-25
20 NC-20

10

0
125 250 500 1000 2000 4000 8000

Octave-band frequency (Hz)

66
Selection Process

Selection Process
Fan Performance Chart

Example 1 :
The following are the design requirements for FUD30B unit:
Model: FUD30B
Supply Air Quantity = 4200 CFM
External Static Pressure = 180 Pa
Step 1: From the fan curve (at 4200 CFM),
Standard operating system;
Total Static Pressure = 320 Pa
Internal Static Pressure = 171 Pa
External Static Pressure = 149 Pa
External Static Pressure of 149 Pa did not fulfill the design requirements.
Step 2: Therefore at 4200 CFM and 180 Pa External static pressure,
Total Static Pressure = 171 + 180 Pa
= 351 Pa
Step 3: From the fan curve, the design requirement calls for RPM about 800, whereas the unit can only deliver
RPM about 760 under the same CFM. Therefore, it is necessary to resize the pulley sizes.
From the table:
Motor pulley = 80 mm
Blower pulley = 160 mm
Motor RPM = 1405
In order to obtain 800 RPM, we recalculate the new blower pulley as:
(while maintaining the motor pulley)
Db = 80 x (1405/800)
= 140.5 mm
The nearest pulley size will be a diameter of 140mm
Recheck, with Db = 140mm
Blower pulley = 1405 x (80/140)
= 803
We thus need to change the blower pulley from 160mm to 140mm in order to obtain the higher operating
static pressure.
Step 4: When the pulley is changed, the V-belt length must be rechecked. We have for horizontal air throw
configuration:
V-belt length, L = 2C + 1.57 (Db + Dm)
= (2 x 340) + 1.57 (80 + 140)
= 1025.4mm
We thus can use a belt with a length of 1030mm
where, C = distance between the centres of the two pulleys
Db = diameter of blower pulley
Dm = diameter of motor pulley
Step 5: From the fan curve, we can also notice that the motor power input has increased. At the new operating
point, the power is approximately 1.25 kW.
By applying a safety factor of 1.2 to account for losses, we calculate that the motor power input requirement
should be = 1.25 x 1.2 = 1.5 kW
Thus, the existing motor is still sufficient to drive the blower with the smaller 140mm pulley.
Summary:
i) Fan motor kW = 1.5 kW
ii) Blower pulley diameter = 140 mm
iii) V-belt size = 1030 mm

67
Selection Process

The following table summarizes the pulley data, motor size used for the FUD series, as manufactured:
Motor Blower Pulley Center V-Belt V-Belt
Motor Motor Distance, C Length Length
Pulley Pulley
Model Size Speed
Diameter Diameter Horizontal Vertical Horizontal Vertical
kW RPM mm mm mm mm mm mm
FUD30B 1.5 1405 80 160 340 350 1060 1080
FUD40B 1.5 1405 80 160 340 350 1060 1080

Example 1:

FUD30B

RPM
500

1.5 kW

450 900

400

350
800
1.1 kW
Standard
Point
Total Static Pressure (Pa)

300

250 700

200
600

150
Internal Static
Pressure with air filter

100

Internal Static
Pressure w/o air filter
50

0
3500 4000 4500 5000 CFM

1652 1800 2000 2200 2360 L/S

Air Flow

68
Fan Performance Chart

Fan Performance Chart


Fan Performance Curve

FWC03C

Pa mmAq
69 7

LOW MEDIUM HIGH


59 6

49 5
External Static Pressure

39 4

29 3

20 2

10 1

0 0
200 250 300 350 400 450 CFM
340 400 450 500 550 600 650 700 765 CMH

Air Flow

69
Fan Performance Chart

FWC04C

Pa mmAq
69 7

59 6

LOW MEDIUM HIGH

49 5
External Static Pressure

39 4

29 3

20 2

10 1

0 0
300 350 400 450 500 550 600 650 700 750 800 CFM
510 600 700 800 900 1000 1100 1200 1300 1360 CMH

Air Flow

70
Fan Performance Chart

FWC06C

Pa mmAq
69 7

HIGH

59 6 MEDIUM

LOW

49 5
External Static Pressure

39 4

29 3

20 2

10 1

0 0
550 600 650 700 750 800 850 900 950 CFM
935 1000 1100 1200 1300 1400 1500 1615 CMH

Air Flow

71
Fan Performance Chart

FWC07C

Pa mmAq
69 7

59 6
LOW MEDIUM HIGH

49 5
External Static Pressure

39 4

29 3

20 2

10 1

0 0
450 500 550 600 650 700 750 800 850 900 950 CFM
765 900 1000 1100 1200 1300 1400 1500 1615 CMH

Air Flow

72
Fan Performance Chart

FWC09C

Pa mmAq
177 18
HIGH

157 16
MEDIUM

LOW
137 14

118 12
External Static Pressure

98 10

78 8

59 6

39 4

20 2

0 0
400 600 800 1000 1200 1400 CFM
680 900 1100 1300 1500 1700 1900 2100 2380 CMH

Air Flow

73
Fan Performance Chart

FWC11C

Pa mmAq
177 18

HIGH
157 16

MEDIUM
137 14

LOW

118 12
External Static Pressure

98 10

78 8

59 6

39 4

20 2

0 0
900 1000 1100 1200 1300 1400 1500 CFM
1530 1700 1900 2100 2300 2550 CMH

Air Flow

74
Fan Performance Chart

FWC12C

Pa mmAq
177 18
HIGH

MEDIUM

157 16
LOW

137 14

118 12
External Static Pressure

98 10

78 8

59 6

39 4

20 2

0 0
600 700 800 900 1000 1100 1200 1300 1400 1500 CFM
1020 1200 1400 1600 1800 2000 2200 2400 2550 CMH

Air Flow

75
Fan Performance Chart

FWC14C

Pa mmAq
177 18
HIGH

MEDIUM
LOW
157 16

137 14

118 12
External Static Pressure

98 10

78 8

59 6

39 4

20 2

0 0
900 1000 1100 1200 1300 1400 1500 1600 1700 1800 CFM
1530 1700 1900 2100 2300 2500 2700 2900 3060 CMH

Air Flow

76
Fan Performance Chart

FWC16C
Pa mmAq
177 18
HIGH

MEDIUM
157 16

LOW

137 14

118 12
External Static Pressure

98 10

78 8

59 6

39 4

20 2

0 0
1000 1200 1400 1600 1800 2000 CFM
1700 1900 2100 2300 2500 2700 2900 3200 3400 CMH

Air Flow

77
Fan Performance Chart

FWC02FD

100

90

80

70
External Static Pressure (Pa)

60

HIGH

50
MEDIUM

40

LOW
30

20

10

0
50 100 150 200 250 300 350 400
Airflow (CFM)

78
Fan Performance Chart

FWC03FD

100

90

80

70
External Static Pressure (Pa)

60

HIGH

50
MEDIUM

LOW
40

30

20

10

0
150 200 250 300 350 400 450

Air Flow (CFM)

79
Fan Performance Chart

FWC04FD

100

90

80

70
External Static Pressure (Pa)

60

HIGH

50 MEDIUM

40 LOW

30

20

10

0
150 200 250 300 350 400 450 500 550 600 650 700

Air Flow (CFM)

80
Fan Performance Chart

FWC05FD

100

90

80
HIGH
MEDIUM

70
External Static Pressure (Pa)

60 LOW

50

40

30

20

10

0
150 200 250 300 350 400 450 500 550 600 650 700

Air Flow (CFM)

81
Fan Performance Chart

FWC06FD

100

90

80
HIGH
MEDIUM

70
External Static Pressure (Pa)

60 LOW

50

40

30

20

10

0
300 350 400 450 500 550 600 650 700 750 800 850 900

Air Flow (CFM)

82
Fan Performance Chart

FWC08FD

100

90

80 HIGH

MEDIUM

70

LOW
External Static Pressure (Pa)

60

50

40

30

20

10

0
500 550 600 650 700 750 800 850 900 950 1000 1050 1100

Air Flow (CFM)

83
Fan Performance Chart

FWC10FD

100

90

80 HIGH

MEDIUM
70

LOW
External Static Pressure (Pa)

60

50

40

30

20

10

0
700 750 800 850 900 950 1000 1050 1100 1150 1200

Air Flow (CFM)

84
Fan Performance Chart

85
Fan Performance Chart

86
Fan Performance Chart

87
Fan Performance Chart

88
Fan Performance Chart

89
Fan Performance Chart

90
Fan Performance Chart

91
Fan Performance Chart

FWC03G (MSP) / FWC03G EC(MSP)


100 0.40

90
0.35

HIGH
80

0.30

70

External Static Pressure (in wg)


External Static Pressure (Pa)

0.25
60

MEDIUM

50 0.20

40
0.15

30

LOW
0.10

20

0.05
10

0 0.00
50 100 150 200 250 300 350 400 450 CFM
2 4 6 8 10 12 CMM

2059-004 Air Flow

92
Fan Performance Chart

FWC04G (MSP) / FWC04G EC(MSP)


100 0.40

90 0.36

HIGH
80 0.32

70 0.28

External Static Pressure (in wg)


External Static Pressure (Pa)

60 0.24
MEDIUM

50 0.20

40 0.16

30 0.12
LOW

20 0.08

10 0.04

0 0.00
100 150 200 250 300 350 400 450 500 550 600 CFM
3 4 6 8 10 12 14 16 17 CMM

2059-005 Air Flow

93
Fan Performance Chart

FWC06G (MSP) / FWC06G EC(MSP)


100 0.40

90 0.36

HIGH
80 0.32

70 0.28

MEDIUM

External Static Pressure (in wg)


External Static Pressure (Pa)

60 0.24

50 0.20

LOW
40 0.16

30 0.12

20 0.08

10 0.04

0 0.00
250 300 350 400 450 500 550 600 650 700 750 CFM
7 8 10 12 14 16 18 20 21 CMM

2059-006 Air Flow

94
Fan Performance Chart

FWC08G (MSP) / FWC08G EC(MSP)


100 0.40

90 0.36

HIGH
80 0.32

70 0.28

External Static Pressure (in wg)


External Static Pressure (Pa)

60 0.24
MEDIUM

50 0.20

40 0.16

LOW

30 0.12

20 0.08

10 0.04

0 0.00
300 400 500 600 700 800 900 1000 1100 CFM
9 10 15 20 25 30 31 CMM

2059-007 Air Flow

95
Fan Performance Chart

FWC10G (MSP) / FWC10G EC(MSP)


100 0.40

90 0.36

HIGH
80 0.32

70 0.28

External Static Pressure (in wg)


External Static Pressure (Pa)

MEDIUM
60 0.24

50 0.20

LOW
40 0.16

30 0.12

20 0.08

10 0.04

0 0.00
400 500 600 700 800 900 1000 1100 1200 1300 CFM
12 15 20 25 30 36 CMM

2059-008 Air Flow

96
Fan Performance Chart

97
Fan Performance Chart

FWC14G (MSP)
120 0.48

110
0.44

100 HIGH

0.40

90

0.36
80

External Static Pressure (in wg)


External Static Pressure (Pa)

0.32
70
MEDIUM

60 0.28

50
0.24

40
LOW
0.20

30

0.16
20

LOWER LIMIT 0.12


10

0 0.08
600 800 1000 1200 1400 1600 1800 CFM
17 20 25 30 35 40 45 51 CMM

2059-010 Air Flow

98
Fan Performance Chart

FWC16G (MSP)
120 0.48

110
0.44

100 HIGH

0.40

90

0.36
80

External Static Pressure (in wg)


External Static Pressure (Pa)

0.32
70
MEDIUM

60 0.28

50
0.24

40

LOW
0.20

30

0.16
20

LOWER LIMIT 0.12


10

0 0.08
600 800 1000 1200 1400 1600 1800 2000 CFM
17 20 25 30 35 40 45 50 56 CMM

2059-011 Air Flow

99
Fan Performance Chart

FWC18G (MSP)
120 0.48

110
0.44

HIGH
100
0.40

90

0.36
80

External Static Pressure (in wg)


External Static Pressure (Pa)

0.32
70
MEDIUM

60 0.28

50
0.24

40
LOW
0.20

30

0.16
20

0.12
10 LOWER LIMIT

0 0.08
800 1000 1200 1400 1600 1800 2000 2200 CFM
23 25 30 35 40 45 50 55 60 62 CMM

2059-012 Air Flow

100
Fan Performance Chart

FWC20G (MSP)
120 0.48

110 0.44

HIGH
100 0.40

90 0.36

80 0.32

External Static Pressure (in wg)


External Static Pressure (Pa)

70 0.28

MEDIUM
60 0.24

50 0.20

40 0.16

LOW
30 0.12

20 0.08

10 0.04
LOWER LIMIT

0 0.00
800 1000 1200 1400 1600 1800 2000 2200 2400 CFM
23 25 30 35 40 45 50 55 60 65 68 CMM

2059-013 Air Flow

101
Fan Performance Chart

FUD20B

Pa mmAq
137 14

LOW MEDIUM HIGH


118 12

98 10
External Static Pressure

78 8

59 6

39 4

20 2

0 0
0 500 1000 1500 2000 2500 3000 CFM
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5100 CMH

Air Flow

102
Fan Performance Chart

FUD25B

Pa mmAq
137 14

118 12

LOW MEDIUM HIGH

98 10
External Static Pressure

78 8

59 6

39 4

20 2

0 0
2000 2500 3000 3500 4000 CFM
3400 4000 4500 5000 5500 6000 6500 6800 CMH

Air Flow

103
Fan Performance Chart

FUD30B

RPM
500

1.5 kW

450 900

400

350
800
1.1 kW
Standard
Point
Total Static Pressure (Pa)

300

250 700

200
600

150
Internal Static
Pressure with air filter

100

Internal Static
Pressure w/o air filter
50

0
3500 4000 4500 5000 CFM

1652 1800 2000 2200 2360 L/S

Air Flow

104
Fan Performance Chart

FUD40B

RPM
500

900

1.5 kW

400

800
Total Static Pressure (Pa)

300

700
1.1 kW Standard
Point

200

Internal Static
Pressure with filter
100

0
4000 4200 4400 4600 4800 5000 CFM
1890 1990 2090 2180 2280 2360 L/s

Air Flow

2055-013 Rev1

105
Engineering & Physical Data

Engineering & Physical Data


Engineering Data - Chilled Water Fan Coil Unit
MODEL FWW02L FWW03L FWW04L FWW05L FWW06L
Btu/h 8300 9200 11300 15500 18000
NOMINAL COOLING CAPACITY
W 2430 2700 3310 4540 5280
Btu/h 6300 6900 9000 11700 14000
NOMINAL SENSIBLE COOLING CAPACITY
W 1850 2020 2640 3430 4100
NOMINAL HEATING CAPACITY Btu/h 11000 12000 15000 20500 25000
(ENTERING WATER TEMP. = 50°C) W 3220 3520 4400 6010 7330
NOMINAL TOTAL INPUT POWER W 31 32 42 53 72
NOMINAL RUNNING CURRENT A 0.19 0.20 0.21 0.29 0.34
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE AUTOMATIC LOUVER (UP & DOWN)
CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
HIGH CFM 260 280 370 510 620
MEDIUM CFM 230 250 320 450 520
AIR FLOW
LOW CFM 200 220 260 390 460
QUIET CFM 180 190 240 360 440
USGPM 1.85 2.03 2.51 3.43 4.01
NOMINAL WATER FLOW RATE
litres/min 7.00 7.68 9.50 13.00 15.18
HEAD LOSS (COOLING) kPa 34 24 31 30 36
HEAD LOSS (HEATING) : 50°C kPa 29 20 25 27 33
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.68 0.74 0.97 0.83 1.01
SOUND PRESSURE LEVEL (H/M/L) dBA 34 / 29 / 25 / 24 35 / 30 / 25 / 24 42 / 39 / 32 / 29 42 / 38 / 34 / 32 46 / 42 / 39 / 37
UNIT DIMENSION HXWXD mm 288 x 800 x 206 310 x 1065 x 224
PACKING DIMENSION HXWXD mm 344 x 874 x 274 386 x 1136 x 314
UNIT WEIGHT kg 9 14
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 12.70 BSP FEMALE THREAD ADAPTOR
TYPE CROSS FLOW FAN
DRIVE DIRECT
HIGH RPM 1030 1050 1310 1035 1250
FAN SPEED MEDIUM RPM 890 910 1150 920 1070
FAN
LOW RPM 760 780 955 825 970
INDOOR UNIT

HIGH % 26.70 24.20 21.00 21.60 20.90


FAN EFFICIENCY MEDIUM % 25.30 22.70 22.10 21.70 22.20
LOW % 24.80 21.60 22.80 23.10 22.80
TYPE SILICON-CONTROLLED RECTIFIER (SCR)
INDEX OF PROTECTION (IP) IP20 IP44
INSULATION GRADE E
HIGH W 31 32 42 53 72
RATED INPUT
MEDIUM W 29 31 37 47 68
POWER
LOW W 25 29 33 42 60
HIGH A 0.19 0.20 0.21 0.29 0.34
RATED RUNNING
FAN MOTOR MEDIUM A 0.18 0.20 0.20 0.26 0.32
CURRENT
LOW A 0.17 0.19 0.19 0.25 0.31
STARTING CURRENT A 0.40 0.40 0.40 0.30 0.43
MOTOR OUTPUT W 18 18 18 26 30
HIGH % 27.40 29.00 44.00 36.50 48.00
MOTOR
MEDIUM % 19.30 21.00 36.00 29.00 36.00
EFFICIENCY
LOW % 13.00 15.00 22.50 24.00 29.00
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.18 0.18 0.18 0.29 0.29
ROW 2
WATER VOLUME litre 0.52 0.58 0.58 0.95 0.95
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 2
CASING COLOUR WHITE

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

106
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


MODEL FWF02C FWF04C FWF05C
Btu/h 8500 14000 15500
NOMINAL COOLING CAPACITY
W 2490 4100 4540
Btu/h 6500 10000 11500
NOMINAL SENSIBLE COOLING CAPACITY
W 1910 2930 3370
NOMINAL HEATING CAPACITY Btu/h 12000 16000 18000
(ENTERING WATER TEMP. = 50°C) W 3520 4690 5280
NOMINAL TOTAL INPUT POWER W 63 64 79
NOMINAL RUNNING CURRENT A 0.28 0.28 0.35
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
HIGH CFM 380 400 440
AIR FLOW MEDIUM CFM 290 310 330
LOW CFM 230 220 280
USGPM 2.03 3.43 3.57
NOMINAL WATER FLOW RATE
litres/min 7.68 12.98 13.51
HEAD LOSS (COOLING) kPa 19.3 26.9 28.8
HEAD LOSS (HEATING) : 50°C kPa 16.8 23.9 26.5
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.74 0.74 0.82
SOUND PRESSURE LEVEL (H/M/L) dBA 42 / 35 / 29 45 / 38 / 30 48 / 40 / 36
UNIT DIMENSION - (WITH PANEL) HXWXD mm 250 x 570 x 570 (295 x 640 x 640)
PACKING DIMENSION - (PANEL) HXWXD mm 316 x 630 x 630 (126 x 700 x 726)
UNIT WEIGHT (UNIT + PANEL) kg 15 + 3 17 + 3 17 + 3
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
TYPE TURBO FAN
DRIVE DIRECT
HIGH RPM 725 810 900
FAN SPEED MEDIUM RPM 565 630 700
FAN
LOW RPM 460 480 610
INDOOR UNIT

HIGH % 38.30 46.90 25.90


FAN EFFICIENCY MEDIUM % 35.10 45.40 32.30
LOW % 46.70 46.10 21.50
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
HIGH W 63 64 79
RATED INPUT POWER MEDIUM W 51 58 73
LOW W 46 52 69
HIGH A 0.28 0.28 0.35
RATED RUNNING
FAN MOTOR MEDIUM A 0.23 0.25 0.32
CURRENT
LOW A 0.21 0.24 0.31
STARTING CURRENT A 0.32 0.30 0.47
MOTOR OUTPUT W 17 23 28
HIGH % 32.20 44.50 49.20
MOTOR EFFICIENCY MEDIUM % 20.50 23.60 24.00
LOW % 12.30 11.20 14.80
POLES 6
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.24 0.25 0.25
ROW 1 2 2
WATER VOLUME litre 0.43 0.83 0.83
AIR TYPE WASHABLE SARANET FILTER
FILTER
QUALITY QUANTITY pc 1
CASING COLOUR WHITE

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

107
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


MODEL FWK06E FWK08E FWK09E FWK11E FWK13E
Btu/h 21000 25000 30000 38000 43000
NOMINAL COOLING CAPACITY
W 6150 7330 8790 11140 12600
Btu/h 16700 19200 22300 27400 31000
NOMINAL SENSIBLE COOLING CAPACITY
W 4890 5630 6540 8030 9090
NOMINAL HEATING CAPACITY Btu/h 28000 33600 38300 45500 52000
(ENTERING WATER TEMP. = 50°C) W 8210 9850 11230 13340 15240
NOMINAL TOTAL INPUT POWER W 95 126 167 186 227
NOMINAL RUNNING CURRENT A 0.44 0.55 0.74 0.85 1.03
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
HIGH CFM 750 860 890 1000 1140
MEDIUM CFM 620 700 720 840 1000
AIR FLOW
LOW CFM 480 540 570 680 840
QUIET CFM 320 380 420 540 700
USGPM 4.71 5.59 6.69 8.45 9.60
NOMINAL WATER FLOW RATE
litres/min 17.83 21.17 25.29 31.94 36.29
HEAD LOSS (COOLING) kPa 20 37 22 44 53
HEAD LOSS (HEATING) : 50°C kPa 19 33 19 38 47
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.92 1.05 1.13 1.02 1.17
SOUND PRESSURE LEVEL (H/M/L/Q) dBA 42 / 38 / 32 / 23 46 / 42 / 35 / 27 48 / 43 / 38 / 30 50 / 47 / 43 / 33 52 / 49 / 45 / 39
UNIT DIMENSION - (WITH PANEL) HXWXD mm 265 x 820 x 820 (340 x 990 x 990) 300 x 820 x 820 (375 x 990 x 990)
PACKING DIMENSION - (PANEL) HXWXD mm 341 x 916 x 916 (125 x 1020 x 1020) 376 x 916 x 916 (125 x 1020 x 1020)
UNIT WEIGHT (UNIT + PANEL) kg 26 + 4 26 + 4 28 + 4 32 + 4 32 + 4
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
TYPE TURBO FAN
DRIVE DIRECT
HIGH RPM 530 600 660 710 800
FAN SPEED MEDIUM RPM 450 500 550 610 710
FAN
LOW RPM 360 400 450 510 610
INDOOR UNIT

HIGH % 57.10 60.50 65.00 58.30 55.70


FAN EFFICIENCY MEDIUM % 60.50 62.10 63.00 57.20 65.40
LOW % 58.20 63.30 52.70 58.40 61.60
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
HIGH W 95 126 167 186 227
RATED INPUT
MEDIUM W 79 103 109 151 176
POWER
LOW W 67 89 86 118 144
HIGH A 0.44 0.55 0.74 0.85 1.03
RATED RUNNING
FAN MOTOR CURRENT MEDIUM A 0.40 0.45 0.49 0.71 0.82
LOW A 0.36 0.39 0.39 0.57 0.69
STARTING CURRENT A 0.44 0.71 0.89 1.02 1.28
MOTOR OUTPUT W 30 45 65 80 110
HIGH % 35.20 37.70 30.80 40.30 48.50
MOTOR EFFICIENCY MEDIUM % 25.60 25.20 24.10 31.00 40.60
LOW % 15.60 14.60 21.50 23.20 30.90
POLES 8 6
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.39 0.39 0.37 0.46 0.46
ROW 2 2 3 3 3
WATER VOLUME litre 1.36 1.34 1.97 2.35 2.35
AIR TYPE WASHABLE SARANET FILTER
FILTER
QUALITY QUANTITY pc 1
CASING COLOUR WHITE

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

108
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


MODEL FWK06EH FWK08EH FWK09EH FWK11EH FWK13EH
Btu/h 16400 18500 24600 29600 31300
NOMINAL COOLING CAPACITY
W 4800 5430 7210 8670 9160
Btu/h 14487 16108 19922 23991 25790
NOMINAL SENSIBLE COOLING CAPACITY
W 4250 4720 5840 7030 7560
NOMINAL HEATING CAPACITY Btu/h 30300 33400 40500 51100 54900
(ENTERING WATER TEMP. = 70°C) W 8870 9800 11880 14990 16100
NOMINAL TOTAL INPUT POWER W 95 126 167 186 227
NOMINAL RUNNING CURRENT A 0.44 0.55 0.74 0.85 1.03
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
HIGH CFM 750 860 890 1000 1140
MEDIUM CFM 620 700 720 840 1000
AIR FLOW
LOW CFM 480 540 570 680 840
QUIET CFM 320 380 420 540 700
USGPM 3.65 4.14 5.46 6.56 6.96
NOMINAL WATER FLOW RATE (COOLING)
litres/min 13.83 15.67 20.67 24.83 26.33
USGPM 3.35 3.70 4.49 5.68 6.12
NOMINAL WATER FLOW RATE (HEATING)
litres/min 12.67 14.00 17.00 21.50 23.17
HEAD LOSS (COOLING) kPa 25 31 27 31 35
HEAD LOSS (HEATING) : 70°C kPa 30 37 38 45 51
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.92 1.05 1.13 1.02 1.17
SOUND PRESSURE LEVEL (H/M/L/Q) dBA 42 / 38 /32 / 23 46 / 42 / 35 / 27 48 / 43 / 38 / 30 50 / 47 / 43 / 33 52 / 49 / 45 / 39
UNIT DIMENSION - (WITH PANEL) HXWXD mm 265 x 820 x 820 (340 x 990 x 990) 300 x 820 x 820 (385 x 990 x 990)
PACKING DIMENSION - (PANEL) HXWXD mm 341 x 916 x 916 (125 x 1020 x 1020) 376 x 916 x 916 (125 x 1020 x 1020)
UNIT WEIGHT (UNIT + PANEL) kg 26 + 4 26 + 4 28 + 4 32 + 4 32 + 4
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
TYPE TURBO FAN
DRIVE DIRECT
HIGH RPM 530 600 660 710 800
FAN SPEED MEDIUM RPM 450 500 550 610 710
INDOOR UNIT

FAN
LOW RPM 360 400 450 510 610
HIGH % 57.10 60.50 65.00 58.30 55.70
FAN EFFICIENCY MEDIUM % 60.50 62.10 63.00 57.20 65.40
LOW % 58.20 63.30 52.70 58.40 61.60
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
HIGH W 95 126 167 186 227
RATED INPUT
MEDIUM W 79 103 109 151 176
POWER
LOW W 67 89 86 118 144
HIGH A 0.44 0.55 0.74 0.85 1.03
FAN MOTOR RATED RUNNING
MEDIUM A 0.40 0.45 0.49 0.71 0.82
CURRENT
LOW A 0.36 0.39 0.39 0.57 0.69
STARTING CURRENT A 0.44 0.71 0.89 1.02 1.28
MOTOR OUTPUT W 30 45 65 80 110
HIGH % 35.20 37.70 30.80 40.30 48.50
MOTOR
MEDIUM % 25.60 25.20 24.10 31.00 40.60
EFFICIENCY
LOW % 15.60 14.60 21.50 23.20 30.90
POLES 8 6
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.39 0.39 0.37 0.46 0.46
ROW 2 2 3 3 3
WATER VOLUME litre 1.36 1.34 1.97 2.35 2.35
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1
CASING COLOUR WHITE

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
70°C (4 Pipes System)
LEAVING WATER TEMPERATURE 12°C 60°C (4 Pipes System)
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

109
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


FWKE05E FWKE08E
MODEL
HIGH MEDIUM LOW QUIET HIGH MEDIUM LOW QUIET
Btu/h 20100 15900 11900 8200 30000 24700 19800 15200
NOMINAL COOLING CAPACITY
W 5900 4650 3500 2400 8800 7250 5800 4550
Btu/h 15400 11700 8700 5800 21900 18500 14500 11000
NOMINAL SENSIBLE COOLING CAPACITY
W 4510 3440 2540 1710 6430 5410 4260 3220
NOMINAL HEATING CAPACITY Btu/h 24200 19800 15200 11300 38200 30400 23900 18400
(ENTERING WATER TEMP. = 50°C) W 7100 5800 4450 3300 11200 8900 7000 5400
FAN INPUT POWER W 37 19 12 7 90 50 26 17
NOMINAL RUNNING CURRENT A 0.26 0.19 0.13 0.11 0.74 0.43 0.28 0.19
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
AIR FLOW CFM 620 470 350 220 890 720 560 420
USGPM 4.52 3.56 2.68 1.84 6.74 5.55 4.44 3.41
NOMINAL WATER FLOW RATE
litres/min 17.10 13.48 10.15 6.96 25.51 21.02 16.81 12.90
HEAD LOSS (COOLING) kPa 24 15 10 5 20 14 9 7
HEAD LOSS (HEATING) : 50°C kPa 21 13 8 4 18 12 8 5
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.76 0.57 0.43 0.27 1.13 0.92 0.71 0.54
SOUND PRESSURE LEVEL dBA 37 31 23 16 47 42 37 31
UNIT DIMENSION - (WITH PANEL) HXWXD mm 265 x 820 x 820 (340 x 990 x 990)
PACKING DIMENSION - (PANEL) HXWXD mm 341 x 916 x 916 (125 x 1020 x 1020)
UNIT WEIGHT (UNIT + PANEL) kg 26 + 4 28 + 4
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
TYPE TURBO FAN
INDOOR UNIT

DRIVE DIRECT
FAN
FAN SPEED RPM 450 360 280 200 660 550 440 350
FAN EFFICIENCY % 50.3 51.3 37.4 22.0 51.9 52.6 49.6 40.5
TYPE BRUSHLESS DIRECT CURRENT
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE E
RATED RUNNING CURRENT A 0.26 0.19 0.13 0.11 0.74 0.43 0.28 0.19
FAN MOTOR
STARTING CURRENT A N/A N/A
MOTOR OUTPUT W 70 70
MOTOR EFFICIENCY % 70.0 70.0 70.0 70.0 75.0 75.0 75.0 75.0
POLES 8
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.39 0.37
ROW 2 3
WATER VOLUME litre 1.36 1.97
AIR TYPE WASHABLE SARANET FILTER
FILTER
QUALITY QUANTITY pc 1
CASING COLOUR WHITE

NOTE:
A) BASED ON EUROVENT CONDITIONS
B) ADDITIONAL 10W IS REQUIRED FOR CONDENSATE DRAIN PUMP
C) SOUND PRESSURE LEVEL IS TESTED AS PER JIS STANDARD AS BELOW:
FWKE05E(H) MODEL - 1.4M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
FWKE08/11E(H) MODEL - 1.5M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

110
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


FWKE11E
MODEL
HIGH MEDIUM LOW QUIET
Btu/h 40100 33100 26800 21000
NOMINAL COOLING CAPACITY
W 11750 9700 7850 6150
Btu/h 28600 23800 18900 14600
NOMINAL SENSIBLE COOLING CAPACITY
W 8370 6970 5540 4270
NOMINAL HEATING CAPACITY Btu/h 46700 39100 31600 24100
(ENTERING WATER TEMP. = 50°C) W 13700 11450 9250 7050
FAN INPUT POWER W 120 83 39 23
NOMINAL RUNNING CURRENT A 0.95 0.55 0.35 0.21
POWER SOURCE V/Ph/Hz 220-240/1/ 50
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL

AIR FLOW CFM 1060 870 680 510


USGPM 9.00 7.43 6.01 4.71
NOMINAL WATER FLOW RATE
litres/min 34.06 28.12 22.76 17.83
HEAD LOSS (COOLING) kPa 41 30 22 15
HEAD LOSS (HEATING) : 50°C kPa 37 26 20 12
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.08 0.89 0.70 0.52
SOUND PRESSURE LEVEL dBA 51 46 41 34
UNIT DIMENSION - (WITH PANEL) HXWXD mm 300 x 820 x 820 (375 x 990 x 990)
PACKING DIMENSION - (PANEL) HXWXD mm 376 x 916 x 916 (125 x 1020 x 1020)
UNIT WEIGHT (UNIT + PANEL) kg 32 + 4
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
TYPE TURBO FAN
INDOOR UNIT

DRIVE DIRECT
FAN
FAN SPEED RPM 750 630 510 400
FAN EFFICIENCY % 55.6 55.5 49.6 49.4
TYPE BRUSHLESS DIRECT CURRENT
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE E
RATED RUNNING CURRENT A 0.95 0.55 0.35 0.21
FAN MOTOR
STARTING CURRENT A N/A
MOTOR OUTPUT W 100
MOTOR EFFICIENCY % 75.0 75.0 75.0 75.0
POLES 8
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.46
ROW 3
WATER VOLUME litre 2.35
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1
CASING COLOUR WHITE

NOTE:
A) BASED ON EUROVENT CONDITIONS
B) ADDITIONAL 10W IS REQUIRED FOR CONDENSATE DRAIN PUMP
C) SOUND PRESSURE LEVEL IS TESTED AS PER JIS STANDARD AS BELOW:
FWKE05E(H) MODEL - 1.4M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
FWKE08/11E(H) MODEL - 1.5M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

111
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


FWKE05EH FWKE08EH
MODEL
HIGH MEDIUM LOW QUIET HIGH MEDIUM LOW QUIET
Btu/h 15000 12300 9600 6800 24600 20800 17100 13300
NOMINAL COOLING CAPACITY
W 4400 3600 2800 2000 7200 6100 5000 3900
Btu/h 13100 10200 7600 5300 19600 16600 13000 9900
NOMINAL SENSIBLE COOLING CAPACITY
W 3850 2990 2240 1560 5750 4850 3810 2910
NOMINAL HEATING CAPACITY Btu/h 26100 21700 17200 12800 38200 32800 27300 21800
(ENTERING WATER TEMP. = 70°C) W 7650 6350 5050 3750 11200 9600 8000 6400
FAN INPUT POWER W 37 19 12 7 90 50 26 17
NOMINAL RUNNING CURRENT A 0.26 0.19 0.13 0.11 0.74 0.43 0.28 0.19
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
AIR FLOW CFM 620 470 350 220 890 720 560 420
USGPM 3.39 2.76 2.14 1.53 5.50 4.67 3.83 2.99
NOMINAL WATER FLOW RATE (COOLING)
litres/min 12.75 10.44 8.12 5.80 20.87 17.68 14.49 11.31
USGPM 2.95 2.43 1.93 1.44 4.27 3.68 3.06 2.45
NOMINAL WATER FLOW RATE (HEATING)
litres/min 11.09 9.20 7.31 5.44 16.23 13.91 11.58 9.28
HEAD LOSS (COOLING) kPa 18 13 9 5 19 15 10 6
HEAD LOSS (HEATING) : 70°C kPa 22 16 10 7 32 25 18 13
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.76 0.57 0.43 0.27 1.13 0.92 0.71 0.54
SOUND PRESSURE LEVEL dBA 37 31 23 16 47 42 37 31
UNIT DIMENSION - (WITH PANEL) HXWXD mm 265 x 820 x 820 (340 x 990 x 990)
PACKING DIMENSION - (PANEL) HXWXD mm 341 x 916 x 916 (125 x 1020 x 1020)
UNIT WEIGHT (UNIT + PANEL) kg 26 + 4 28 + 4
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
INDOOR UNIT

TYPE TURBO FAN


DRIVE DIRECT
FAN
FAN SPEED RPM 450 360 280 200 660 550 440 350
FAN EFFICIENCY % 50.3 51.3 37.4 22.0 51.9 52.6 49.6 40.5
TYPE BRUSHLESS DIRECT CURRENT
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE E
RATED RUNNING CURRENT A 0.26 0.19 0.13 0.11 0.74 0.43 0.28 0.19
FAN MOTOR
STARTING CURRENT A N/A N/A
MOTOR OUTPUT W 70 70
MOTOR EFFICIENCY % 70.0 70.0 70.0 70.0 75.0 75.0 75.0 75.0
POLES 8
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.39 0.37
ROW 2 3
WATER VOLUME litre 1.36 1.97
AIR TYPE WASHABLE SARANET FILTER
FILTER
QUALITY QUANTITY pc 1
CASING COLOUR WHITE

NOTE:
A) BASED ON EUROVENT CONDITIONS
B) ADDITIONAL 10W IS REQUIRED FOR CONDENSATE DRAIN PUMP
C) SOUND PRESSURE LEVEL IS TESTED AS PER JIS STANDARD AS BELOW:
FWKE05E(H) MODEL - 1.4M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
FWKE08/11E(H) MODEL - 1.5M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
70°C (4 Pipes System)
LEAVING WATER TEMPERATURE 12°C 60°C (4 Pipes System)
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

112
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


FWKE11EH
MODEL
HIGH MEDIUM LOW QUIET
Btu/h 30700 26400 22200 17700
NOMINAL COOLING CAPACITY
W 9000 7750 6500 5200
Btu/h 24500 20700 16700 13300
NOMINAL SENSIBLE COOLING CAPACITY
W 7170 6060 4900 3890
NOMINAL HEATING CAPACITY Btu/h 53400 46200 39100 31900
(ENTERING WATER TEMP. = 70°C) W 15650 13550 11450 9350
FAN INPUT POWER W 120 83 39 23
NOMINAL RUNNING CURRENT A 0.95 0.55 0.35 0.21
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
AIR FLOW CFM 1060 870 680 510
USGPM 6.91 5.93 4.98 3.98
NOMINAL WATER FLOW RATE (COOLING)
litres/min 26.09 22.47 18.84 15.07
USGPM 5.99 5.19 4.38 3.58
NOMINAL WATER FLOW RATE (HEATING)
litres/min 22.68 19.64 16.60 13.55
HEAD LOSS (COOLING) kPa 32 24 19 12
HEAD LOSS (HEATING) : 50°C kPa 52 39 30 21
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.08 0.89 0.70 0.52
SOUND PRESSURE LEVEL dBA 51 46 41 34
UNIT DIMENSION - (WITH PANEL) HXWXD mm 300 x 820 x 820 (375 x 990 x 990)
PACKING DIMENSION - (PANEL) HXWXD mm 376 x 916 x 916 (125 x 1020 x 1020)
UNIT WEIGHT (UNIT + PANEL) kg 32 + 4
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
INDOOR UNIT

TYPE TURBO FAN


DRIVE DIRECT
FAN
FAN SPEED RPM 750 630 510 400
FAN EFFICIENCY % 55.6 55.5 49.6 49.4
TYPE BRUSHLESS DIRECT CURRENT
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE E
RATED RUNNING CURRENT A 0.95 0.55 0.35 0.21
FAN MOTOR
STARTING CURRENT A N/A
MOTOR OUTPUT W 100
MOTOR EFFICIENCY % 75.0 75.0 75.0 75.0
POLES 8
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.46
ROW 3
WATER VOLUME litre 2.35
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1
CASING COLOUR WHITE

NOTE:
A) BASED ON EUROVENT CONDITIONS
B) ADDITIONAL 10W IS REQUIRED FOR CONDENSATE DRAIN PUMP
C) SOUND PRESSURE LEVEL IS TESTED AS PER JIS STANDARD AS BELOW:
FWKE05E(H) MODEL - 1.4M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
FWKE08/11E(H) MODEL - 1.5M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
70°C (4 Pipes System)
LEAVING WATER TEMPERATURE 12°C 60°C (4 Pipes System)
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

113
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


MODEL FWE05E FWE06E FWE07E FWE08E FWE10E FWE12E
Btu/h 15500 20300 21000 25000 34000 47000
NOMINAL COOLING CAPACITY
W 4540 5950 6150 7330 9960 13770
Btu/h 12700 15400 16150 19250 25500 32900
NOMINAL SENSIBLE COOLING CAPACITY
W 3720 4510 4730 5640 7470 9640
NOMINAL HEATING CAPACITY Btu/h 19500 25000 28000 35000 47000 59000
(ENTERING WATER TEMP. = 50°C) W 5720 7330 8210 10260 13770 17290
NOMINAL TOTAL INPUT POWER W 86 135 160 148 197 225
NOMINAL RUNNING CURRENT A 0.38 0.67 0.79 0.65 0.87 0.99
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE AUTOMATIC LOUVER (UP & DOWN)
CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
HIGH CFM 520 580 640 840 1120 1230
AIR FLOW MEDIUM CFM 460 530 560 750 980 1090
LOW CFM 406 490 460 660 860 990
USGPM 3.43 4.49 4.67 5.77 7.71 10.17
NOMINAL WATER FLOW RATE
litres/min 12.98 17.00 17.68 21.85 29.19 38.53
HEAD LOSS (COOLING) kPa 27 48 57 36 50 67
HEAD LOSS (HEATING) : 50°C kPa 24 42 50 32 45 58
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.91 1.02 1.12 1.50 1.63 1.50
SOUND PRESSURE LEVEL (H/M/L) dBA 45 / 38 / 36 48 / 43 / 39 49 / 46 / 41 48/47/44 52/47/46 52/50/49
UNIT DIMENSION HXWXD mm 212 x 1090 x 630 259 x 1320 x 635 259 x 1538 x 635 259 x 1786 x 635
PACKING DIMENSION HXWXD mm 297 x 1197 x 740 348 x 1393 x 734 348 x 1612 x 734 348 x 1860 x 734
UNIT WEIGHT kg 27 41 46 53
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 12.70 BSP FEMALE THREAD ADAPTOR 19.05 BSP FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
HIGH RPM 1220 1300 1400 1235 1300 1310
FAN SPEED MEDIUM RPM 990 1100 1200 1120 1170 1170
FAN
LOW RPM 890 930 1000 1010 1090 1050
INDOOR UNIT

HIGH % 30.2 27.6 14.9 46.0 45.2 39.1


FAN
MEDIUM % 34.9 26.7 15.8 47.1 46.5 42.6
EFFICIENCY
LOW % 34.7 27.1 20 50.0 46.4 42.9
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
RATED HIGH W 86 135 160 148 197 225
INPUT MEDIUM W 58 97 113 138 169 190
POWER LOW W 51 83 91 126 153 173
RATED HIGH A 0.38 0.67 0.79 0.65 0.87 0.99
FAN RUNNING MEDIUM A 0.26 0.45 0.52 0.61 0.74 0.84
MOTOR CURRENT LOW A 0.23 0.39 0.44 0.55 0.67 0.76
STARTING CURRENT A 1.10 1.20 1.30 1.15 1.54 1.88
MOTOR OUTPUT W 50 65 70 92 118 149
HIGH % 51.0 49.4 54.9 53.5 57.7 56.2
MOTOR
MEDIUM % 36.5 37.5 42.0 40.2 47.4 43.3
EFFICIENCY
LOW % 30.2 26.2 29.4 29.7 40.7 33.5
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL FACE AREA m2 0.27 0.26 0.32 0.38
FIN
ROW 3 4
WATER VOLUME litre 1.41 1.23 1.48 2.37
AIR TYPE WASHABLE SARANET FILTER
FILTER
QUALITY QUANTITY pc 2 3 3 4
CASING COLOUR LIGHT GREY

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

114
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


MODEL FWC03C FWC04C FWC06C FWC07C
Btu/h 9900 11600 18000 22500
NOMINAL COOLING CAPACITY
W 2900 3400 5280 6590
Btu/h 7000 8120 12600 15750
NOMINAL SENSIBLE COOLING CAPACITY
W 2050 2380 3690 4620
NOMINAL HEATING CAPACITY Btu/h 11500 15000 23000 29000
(ENTERING WATER TEMP. = 50°C) W 3370 4400 6740 8500
NOMINAL TOTAL INPUT POWER W 89 140 168 182
NOMINAL RUNNING CURRENT A 0.40 0.65 0.77 0.86
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
HIGH CFM 300 510 700 730
AIR FLOW MEDIUM CFM 285 490 675 660
LOW CFM 260 400 640 580
EXTERNAL STATIC PRESSURE Pa 49 / 44 / 36 49 / 42 / 28 49 / 45 / 41 49 / 43 / 30
USGPM 2.20 2.60 4.05 5.06
NOMINAL WATER FLOW RATE
litres/min 8.33 9.84 15.33 19.15
HEAD LOSS (COOLING) kPa 10.5 24.0 20.1 32.4
HEAD LOSS (HEATING) : 50°C kPa 8.8 20.3 17.0 27.6
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.23 1.68 1.88 1.70
SOUND PRESSURE LEVEL (H/M/L) dBA 36 / 35 / 33 40 / 38 / 33 42 / 41 / 40 41 / 40 / 36
UNIT DIMENSION HXWXD mm 267 x 702 x 351 267 x 842 x 351 267 x 1002 x 351 267 x 1137 x 351
PACKING DIMENSION HXWXD mm 376 x 951 x 541 376 x 1091 x 541 376 x 1251 x 541 376 x 1386 x 541
UNIT WEIGHT kg 18 22 24 26
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
HIGH RPM 1282 1385 1369 1348
FAN SPEED MEDIUM RPM 1221 1279 1331 1270
FAN
LOW RPM 1117 1078 1263 1072
INDOOR UNIT

HIGH % 38.70 42.90 39.70 36.20


FAN EFFICIENCY MEDIUM % 40.70 51.90 47.50 38.10
LOW % 43.00 50.30 48.90 39.10
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
HIGH W 89 140 168 182
RATED INPUT
MEDIUM W 86 128 165 175
POWER
LOW W 78 127 163 163
HIGH A 0.40 0.65 0.77 0.86
RATED RUNNING
FAN MOTOR MEDIUM A 0.39 0.59 0.76 0.83
CURRENT
LOW A 0.35 0.59 0.75 0.77
STARTING CURRENT A 0.73 1.66 1.22 1.86
MOTOR OUTPUT W 38 72 80 90
HIGH % 47.90 49.70 56.40 57.50
MOTOR
MEDIUM % 42.40 39.60 50.90 48.40
EFFICIENCY
LOW % 33.50 24.80 44.10 30.40
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 9.52
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.11 0.14 0.18 0.20
ROW 3
WATER VOLUME litre 0.90 1.20 1.40 1.60
AIR TYPE WASHABLE SARANET FILTER
FILTER
QUALITY QUANTITY pc 1
CASING COLOUR WITHOUT PAINT

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

115
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


MODEL FWC09C FWC11C FWC12C FWC14C FWC16C
Btu/h 24800 38000 37000 44700 51800
NOMINAL COOLING CAPACITY
W 7270 11140 10840 13100 15180
Btu/h 19700 29800 29300 35100 40900
NOMINAL SENSIBLE COOLING CAPACITY
W 5770 8730 8590 10290 11990
NOMINAL HEATING CAPACITY Btu/h 32800 49200 48000 54900 65300
(ENTERING WATER TEMP. = 50°C) W 9610 14420 14070 16090 19140
NOMINAL TOTAL INPUT POWER W 345 504 442 427 531
NOMINAL RUNNING CURRENT A 1.50 2.28 1.93 1.86 2.32
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE DUCTED
CONTROL
OPERATION WIRED REMOTE CONTROL
HIGH CFM 830 1250 1240 1340 1550
AIR FLOW MEDIUM CFM 760 1130 1100 1220 1400
LOW CFM 710 1040 1020 1190 1300
EXTERNAL STATIC PRESSURE Pa 167 / 128 / 88 118 / 108 / 88 128 / 88 / 39 157 / 137 / 108 157 / 137 / 98
USGPM 5.55 8.59 8.28 10.04 11.62
NOMINAL WATER FLOW RATE
litres/min 21.01 32.51 31.34 38.00 43.98
HEAD LOSS (COOLING) kPa 14.0 39.0 23.0 38.0 51.0
HEAD LOSS (HEATING) : 50°C kPa 11.0 37.0 19.0 33.0 48.0
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.41 1.75 1.83 1.54 1.52
SOUND PRESSURE LEVEL (H/M/L) dBA 46 / 42 / 38 51 / 48 / 45 49 / 45 / 41 52 / 50 / 47 53 / 50 / 47
UNIT DIMENSION HXWXD mm 384 x 917 x 462 316 x 1225 x 559 384 x 1003 x 462 384 x 1287 x 462 384 x 1487 x 462
PACKING DIMENSION HXWXD mm 415 x 1126 x 631 355 x 1461 x 727 415 x 1245 x 631 415 x 1497 x 631 415 x 1701 x 631
UNIT WEIGHT kg 42 47 44 50 56
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSP FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
HIGH RPM 1230 1381 1260 1284 1303
FAN SPEED MEDIUM RPM 1093 1268 1097 1203 1215
FAN
LOW RPM 937 1169 913 1108 1067
INDOOR UNIT

HIGH % 37.20 46.00 42.20 43.70 41.70


FAN EFFICIENCY MEDIUM % 39.50 49.10 42.90 47.30 43.30
LOW % 41.60 44.50 44.30 48.70 43.40
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20 IP21 IP22 IP20 IP20
INSULATION GRADE B
HIGH W 345 504 442 427 531
RATED INPUT
MEDIUM W 304 380 384 388 466
POWER
LOW W 270 338 342 373 413
HIGH A 1.50 2.28 1.93 1.86 2.32
RATED RUNNING
FAN MOTOR MEDIUM A 1.34 1.72 1.69 1.69 2.02
CURRENT
LOW A 1.21 1.53 1.54 1.63 1.81
STARTING CURRENT A 2.43 2.77 3.18 3.50 4.90
MOTOR OUTPUT W 310 470 355 373 500
HIGH % 60.80 63.10 63.80 63.00 68.00
MOTOR
MEDIUM % 47.40 60.80 47.50 58.60 59.60
EFFICIENCY
LOW % 34.80 53.00 32.30 49.40 46.10
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 9.52
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.28 0.34 0.32 0.41 0.48
ROW 3 3 3 3 3
WATER VOLUME litre 2.20 2.70 2.60 3.30 3.80
AIR TYPE WASHABLE SARANET FILTER
FILTER
QUALITY QUANTITY pc 2
CASING COLOUR WITHOUT PAINT

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

116
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


MODEL FWC02FD FWC03FD FWC04FD FWC05FD
Btu/h 6600 8700 12100 14000
NOMINAL COOLING CAPACITY
W 1930 2550 3550 4100
Btu/h 5400 6300 9500 9600
NOMINAL SENSIBLE COOLING CAPACITY
W 1580 1850 2780 2810
NOMINAL TOTAL INPUT POWER W 92 108 131 151
NOMINAL RUNNING CURRENT A 0.42 0.50 0.58 0.66
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 280 310 450 460
AIR FLOW MEDIUM CFM 270 300 430 450
LOW CFM 220 280 360 400
EXTERNAL STATIC PRESSURE (H/M/L) Pa 53 / 50 / 34 53 / 50 / 44 55 / 50 / 40 78 / 75 / 60
USGPM 0.84 1.06 1.50 1.72
NOMINAL WATER FLOW RATE
litres/min 3.17 4.00 5.67 6.50
HEAD LOSS (COOLING) kPa 24.9 20.8 17.2 31.2
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.20 1.33 1.25 1.28
SOUND PRESSURE LEVEL (H/M/L) dBA 40 / 39 / 36 40 / 39 / 37 41 / 40 / 37 42 / 41 / 39
UNIT DIMENSION HXWXD mm 247 x 552 x 619 247 x 552 x 870
PACKING DIMENSION HXWXD mm 320 x 630 x 737 320 x 630 x 987
UNIT WEIGHT kg 16 17 23 24
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSPT FEMALE TREAD ADAPTOR
TYPE CENTRIFUGAL
DRIVE DIRECT
QUANTITY 1 1 2 2
HIGH RPM 1265 1379 1290 1389
FAN FAN SPEED MEDIUM RPM 1232 1356 1245 1369
LOW RPM 1107 1290 1115 1290
INDOOR UNIT

HIGH % 40.4 37.5 40.0 36.4


FAN EFFICIENCY MEDIUM % 40.8 39.4 41.1 38.6
LOW % 41.9 42.8 40.1 42.9
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 1 1 1 1
HIGH W 92 108 131 151
RATED INPUT
MEDIUM W 86 100 124 131
POWER
LOW W 68 84 105 102
HIGH A 0.42 0.50 0.58 0.66
FAN MOTOR RATED RUNNING
MEDIUM A 0.38 0.44 0.54 0.58
CURRENT
LOW A 0.30 0.37 0.46 0.49
STARTING CURRENT A 0.68 1.08 1.08 1.41
MOTOR OUTPUT W 36 71 71 100
HIGH % 37.0 45.9 53.3 53.6
MOTOR EFFICIENCY MEDIUM % 35.1 44.0 48.1 52.0
LOW % 28.2 40.0 34.4 46.0
POLES 4 4 4 4
MATERIAL COPPER
TUBE
DIAMETER mm 7
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.11 0.11 0.17 0.17
ROW 3 4 3 4
WATER VOLUME litre 0.38 0.63 0.72 0.96
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 2
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 24°C DB / 18°C WB
ENTERING WATER TEMPERATURE 5.5°C
LEAVING WATER TEMPERATURE 14.5°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

117
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


MODEL FWC06FD FWC08FD FWC10FD
Btu/h 17000 24500 28500
NOMINAL COOLING CAPACITY
W 4980 7180 8350
Btu/h 11800 17000 20200
NOMINAL SENSIBLE COOLING CAPACITY
W 3460 4980 5920
NOMINAL TOTAL INPUT POWER W 192 265 321
NOMINAL RUNNING CURRENT A 0.95 1.28 1.57
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 570 820 940
AIR FLOW MEDIUM CFM 560 800 920
LOW CFM 500 750 840
EXTERNAL STATIC PRESSURE (H/M/L) Pa 77 / 75 / 61 78 / 75 / 66 78 / 75 / 67
USGPM 2.11 3.04 3.52
NOMINAL WATER FLOW RATE (COOLING)
litres/min 8.00 11.50 13.33
HEAD LOSS (COOLING) kPa 18.7 25.0 19.4
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.24 1.29 1.22
SOUND PRESSURE LEVEL (H/M/L) dBA 45 / 44 / 41 47 / 46 / 45 48 / 47 / 45
UNIT DIMENSION HXWXD mm 247 x 552 x 1060 247 x 552 x 1390 247 x 552 x 1600
PACKING DIMENSION HXWXD mm 320 x 630 x 1177 320 x 630 x 1507 320 x 630 x 1717
UNIT WEIGHT kg 28 38 45
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSPT FEMALE TREAD ADAPTOR
TYPE CENTRIFUGAL
DRIVE DIRECT
QUANTITY 2 3 4
HIGH RPM 1415 1430/1403 1422
FAN FAN SPEED MEDIUM RPM 1395 1415/1388 1402
LOW RPM 1283 1336/1337 1322
INDOOR UNIT

HIGH % 33.7 40.9 31.0


FAN EFFICIENCY MEDIUM % 38.1 45.9 32.3
LOW % 36.9 45.7 38.4
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 1 2 2
HIGH W 192 265 321
RATED INPUT
MEDIUM W 178 242 297
POWER
LOW W 149 201 253
HIGH A 0.95 1.28 1.57
FAN MOTOR RATED RUNNING
MEDIUM A 0.79 1.06 1.31
CURRENT
LOW A 0.65 0.88 1.11
STARTING CURRENT A 2.65 2.65/1.08 2.65
MOTOR OUTPUT W 150 150/71 150
HIGH % 58.5 54.6/40.1 60.2
MOTOR EFFICIENCY MEDIUM % 53.6 48.6/39.4 56.7
LOW % 41.4 43.9/38.1 44.9
POLES 4 4 4
MATERIAL COPPER
TUBE
DIAMETER mm 7
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.22 0.30 0.36
ROW 4 4 4
WATER VOLUME litre 1.22 1.67 1.95
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 2 3 3
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 24°C DB / 18°C WB
ENTERING WATER TEMPERATURE 5.5°C
LEAVING WATER TEMPERATURE 14.5°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

118
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


Low Static Pressure (LSP)
MODEL FWC02G FWC03G FWC04G FWC06G
Btu/h 6000 9000 12000 18000
NOMINAL COOLING CAPACITY
W 1760 2640 3520 5280
Btu/h 5000 7000 9700 14400
NOMINAL SENSIBLE COOLING CAPACITY
W 1470 2050 2840 4220
NOMINAL TOTAL INPUT POWER W 53 61 81 116
NOMINAL RUNNING CURRENT A 0.23 0.27 0.36 0.50
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 200 300 400 600
AIR FLOW MEDIUM CFM 160 220 305 500
LOW CFM 130 150 200 385
EXTERNAL STATIC PRESSURE (H/M/L) Pa 30/19/12 30/16/7 30/18/7 30/21/13
USGPM 1.32 2.00 2.66 3.99
NOMINAL WATER FLOW RATE
litres/min 5.00 7.57 10.09 15.13
HEAD LOSS (COOLING) kPa 7 20 25 34
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.26 1.17 1.56 1.99
SOUND PRESSURE LEVEL (H/M/L) dBA 31/26/20 32/25/20 35/29/21 38/35/30
UNIT DIMENSION HXWXD mm 251X630X461 251X774X461 251X774X461 251X874X461
PACKING DIMENSION HXWXD mm 595X836X284 595x984x284 595x984x284 595x1084x284
UNIT WEIGHT kg 11.00 14.50 15.00 17.50
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSPT FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
QUANTITY 1 2 2 2
HIGH RPM 985 970 1070 1300
FAN FAN SPEED MEDIUM RPM 800 740 870 1120
LOW RPM 655 540 610 940
INDOOR UNIT

HIGH % 34.2 34.8 32.5 33.4


FAN EFFICIENCY MEDIUM % 36.7 36.1 34.6 34.1
LOW % 40.4 39.6 39.0 35.5
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 1 1 1 1
HIGH W 53 61 81 116
RATED INPUT POWER MEDIUM W 30 39 57 91
LOW W 19 21 30 67
HIGH A 0.23 0.27 0.36 0.50
FAN MOTOR RATED RUNNING
MEDIUM A 0.13 0.17 0.25 0.39
CURRENT
LOW A 0.08 0.09 0.13 0.29
STARTING CURRENT A 0.27 0.37 0.47 0.97
MOTOR OUTPUT W 15 21 32 70
HIGH % 28.20 28.60 38.70 54.80
MOTOR EFFICIENCY MEDIUM % 24.40 19.00 27.20 40.70
LOW % 19.00 11.90 15.80 29.10
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.08 0.12 0.12 0.14
ROW 3
WATER VOLUME litre 0.28 0.45 0.45 0.62
AIR TYPE OPTION (WASHABLE SARANET FILTER OR ALUMINIUM MESH FILTER)
FILTER
QUALITY QUANTITY pc 2
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 27°C DB / 19°C WB
ENTERING WATER TEMPERATURE 7°C
LEAVING WATER TEMPERATURE 12°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

119
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


Low Static Pressure (LSP)
MODEL FWC08G FWC10G FWC12G
Btu/h 24000 30000 36000
NOMINAL COOLING CAPACITY
W 7030 8790 10550
Btu/h 19100 23400 27900
NOMINAL SENSIBLE COOLING CAPACITY
W 5600 6860 8180
NOMINAL TOTAL INPUT POWER W 159 202 241
NOMINAL RUNNING CURRENT A 0.72 0.90 1.05
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 800 1000 1200
AIR FLOW MEDIUM CFM 650 805 975
LOW CFM 465 600 810
EXTERNAL STATIC PRESSURE (H/M/L) Pa 30/19/10 30/18/11 30/20/13
USGPM 5.33 6.66 7.99
NOMINAL WATER FLOW RATE
litres/min 20.18 25.22 30.26
HEAD LOSS (COOLING) kPa 38 42 38
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.69 2.11 2.05
SOUND PRESSURE LEVEL (H/M/L) dBA 39/34/26 41/37/31 42/39/35
UNIT DIMENSION HXWXD mm 251x1264x461 251x1264x461 251x1514x461
PACKING DIMENSION HXWXD mm 595x1437x284 595x1473x284 595x1724x284
UNIT WEIGHT kg 26 26 30
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSPT FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
QUANTITY 3 3 4
HIGH RPM 1140 1275 1220
FAN FAN SPEED MEDIUM RPM 950 1035 1010
LOW RPM 710 805 835
INDOOR UNIT

HIGH % 52.90 43.90 37.70


FAN EFFICIENCY MEDIUM % 53.60 51.20 33.90
LOW % 57.60 57.30 46.70
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 2 2 2
HIGH W 159 202 241
RATED INPUT POWER MEDIUM W 126 161 187
LOW W 81 115 148
HIGH A 0.72 0.90 1.05
FAN MOTOR RATED RUNNING
MEDIUM A 0.54 0.70 0.82
CURRENT
LOW A 0.35 0.50 0.65
STARTING CURRENT A 0.93 1.31 1.51
MOTOR OUTPUT W 74 109 122
HIGH % 44.00 54.20 51.90
MOTOR EFFICIENCY MEDIUM % 32.70 34.80 35.90
LOW % 20.80 21.40 25.20
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.22 0.22 0.28
ROW 3
WATER VOLUME litre 0.90 1.04 1.29
AIR TYPE OPTION (WASHABLE SARANET FILTER OR ALUMINIUM MESH FILTER)
FILTER
QUALITY QUANTITY pc 3 3 4
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 27°C DB / 19°C WB
ENTERING WATER TEMPERATURE 7°C
LEAVING WATER TEMPERATURE 12°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

120
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


Medium Static Pressure (MSP)
MODEL FWC03G FWC04G FWC06G FWC08G FWC10G
Btu/h 9000 12000 18000 24000 30000
NOMINAL COOLING CAPACITY
W 2640 3520 5280 7030 8790
Btu/h 7000 9700 14400 19100 23400
NOMINAL SENSIBLE COOLING CAPACITY
W 2050 2840 4220 5600 6860
NOMINAL TOTAL INPUT POWER W 61 87 130 184 235
NOMINAL RUNNING CURRENT A 0.27 0.38 0.58 0.81 1.03
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 300 400 600 800 1000
AIR FLOW MEDIUM CFM 220 305 500 650 805
LOW CFM 150 200 385 465 600
EXTERNAL STATIC PRESSURE (H/M/L) Pa 50/32/15 50/32/15 50/35/20 50/33/17 50/33/18
USGPM 2.00 2.66 3.99 5.33 6.66
NOMINAL WATER FLOW RATE
litres/min 7.57 10.09 15.13 20.18 25.22
HEAD LOSS (COOLING) kPa 20 25 34 38 42
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.17 1.56 1.99 1.69 2.11
SOUND PRESSURE LEVEL (H/M/L) dBA 35/29/20 37/31/22 41/37/31 43/37/30 44/40/33
UNIT DIMENSION HXWXD mm 251X774X461 251X774X461 251X874X461 251X1264X461 251X1264X461
PACKING DIMENSION HXWXD mm 595X984X284 595X984X284 595X1084X284 595X1473X284 595X1473X284
UNIT WEIGHT kg 14.50 15.00 17.50 26.00 26.00
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSPT FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
QUANTITY 2 2 2 3 3
HIGH RPM 1115 1235 1350 1310 1405
FAN FAN SPEED MEDIUM RPM 900 990 1170 1080 1190
LOW RPM 645 715 935 830 930
INDOOR UNIT

HIGH % 35.90 36.30 33.50 39.00 36.00


FAN EFFICIENCY MEDIUM % 37.00 36.00 33.90 39.90 38.60
LOW % 38.70 37.00 35.40 40.40 39.60
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 1 1 1 2 2
HIGH W 61 87 130 184 235
RATED INPUT
MEDIUM W 43 66 106 143 176
POWER
LOW W 26 42 80 104 137
HIGH A 0.27 0.38 0.58 0.81 1.03
FAN MOTOR RATED RUNNING
MEDIUM A 0.19 0.29 0.47 0.63 0.77
CURRENT
LOW A 0.12 0.19 0.35 0.46 0.60
STARTING CURRENT A 0.34 0.53 0.91 1.27 2.09
MOTOR OUTPUT W 27 43 80 104 140
HIGH % 43.00 50.30 58.80 53.30 58.30
MOTOR EFFICIENCY MEDIUM % 28.60 32.10 46.40 36.40 43.50
LOW % 15.80 17.00 30.50 21.80 25.60
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.12 0.12 0.14 0.22 0.22
ROW 3
WATER VOLUME litre 0.45 0.45 0.62 0.90 1.04
TYPE OPTION (WASHABLE SARANET FILTER OR ALUMINIUM MESH FILTER)
AIR QUALITY FILTER
QUANTITY pc 2 2 2 3 3
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 27°C DB / 19°C WB
ENTERING WATER TEMPERATURE 7°C
LEAVING WATER TEMPERATURE 12°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

121
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


Medium Static Pressure (MSP)
MODEL FWC12G FWC14G FWC16G FWC18G FWC20G
Btu/h 36000 42000 48000 54000 60000
NOMINAL COOLING CAPACITY
W 10550 12310 14070 15830 17580
Btu/h 27900 33900 38200 43900 50000
NOMINAL SENSIBLE COOLING CAPACITY
W 8180 9940 11200 12870 14650
NOMINAL TOTAL INPUT POWER W 246 450 558 624 659
NOMINAL RUNNING CURRENT A 1.10 1.96 2.43 2.72 2.87
POWER SOURCE V/Ph/Hz 220-240/1/50
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 1200 1400 1600 1800 2000
AIR FLOW MEDIUM CFM 975 1130 1300 1445 1530
LOW CFM 810 825 905 1060 1075
EXTERNAL STATIC PRESSURE (H/M/L) Pa 50/33/23 75/48/24 75/48/24 75/48/25 75/45/22
USGPM 7.99 9.32 10.65 11.98 13.31
NOMINAL WATER FLOW RATE
litres/min 30.26 35.31 40.35 45.40 50.44
HEAD LOSS (COOLING) kPa 38 31 27 33 32
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 2.05 2.43 2.41 2.71 2.65
SOUND PRESSURE LEVEL (H/M/L) dBA 44/40/37 47/43/35 48/44/37 49/45/39 50/46/38
UNIT DIMENSION HXWXD mm 251X1514X461 363X1116X660 363X1254X660 363X1254X660 363X1394X660
PACKING DIMENSION HXWXD mm 595X1724X284 760X1331X395 760X1469X395 760X1469X395 760X1609X395
UNIT WEIGHT kg 30 34 37 38 41
CONDENSATE DRAIN SIZE mm 19.05
19.05 BSPT
PIPE CONNECTION mm FEMALE THREAD 25.4 BSPT FEMALE THREAD ADAPTOR
ADAPTOR
TYPE BLOWER
DRIVE DIRECT
QUANTITY 4 2 2 2 2
HIGH RPM 1320 1065 1115 1210 1220
FAN FAN SPEED MEDIUM RPM 1050 875 920 1000 1070
LOW RPM 965 675 690 740 875
INDOOR UNIT

HIGH % 32.90 37.60 31.70 33.60 32.40


FAN EFFICIENCY MEDIUM % 30.10 38.60 35.00 34.50 40.30
LOW % 33.40 42.70 41.00 36.90 46.40
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION)
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 2 1 1 1 1
HIGH W 246 450 558 624 659
RATED INPUT
MEDIUM W 200 307 385 459 497
POWER
LOW W 158 173 214 295 313
HIGH A 1.10 1.96 2.43 2.72 2.87
FAN MOTOR RATED RUNNING
MEDIUM A 0.88 1.34 1.68 2.00 2.17
CURRENT
LOW A 0.70 0.76 0.95 1.31 1.40
STARTING CURRENT A 1.62 2.75 3.81 4.38 4.35
MOTOR OUTPUT W 146 248 342 418 446
HIGH % 58.80 53.20 53.30 62.10 59.80
MOTOR EFFICIENCY MEDIUM % 38.90 41.60 40.70 44.90 50.70
LOW % 33.10 29.70 26.70 27.70 37.20
POLES 4
MATERIAL COPPER
TUBE
DIAMETER mm 7.00 9.52
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.28 0.22 0.26 0.26 0.29
ROW 3
WATER VOLUME litre 1.29 2.00 2.32 2.32 2.63
TYPE OPTION ( WASHABLE SARANET FILTER OR ALUMINIUM MESH FILTER)
AIR QUALITY FILTER
QUANTITY pc 4 2 3 3 3
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 27°C DB/ 19°C WB
ENTERING WATER TEMPERATURE 7°C
LEAVING WATER TEMPERATURE 12°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

122
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit (EC Motor)


Medium Static Pressure (LSP)
MODEL FWC02G FWC03G FWC04G FWC06G
Btu/h 6000 9000 12000 18000
NOMINAL COOLING CAPACITY
W 1.76 2.64 3.52 5.28
Btu/h 5000 7000 9700 14400
NOMINAL SENSIBLE COOLING CAPACITY
W 1.47 2.05 2.84 4.22
NOMINAL TOTAL INPUT POWER W 19 30 43 80
NOMINAL RUNNING CURRENT A 0.20 0.29 0.40 0.69
POWER SOURCE V/Ph/Hz 220-240/1/50 & 208-230/1/60
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 200 300 400 600
AIR FLOW MEDIUM CFM 160 220 305 500
LOW CFM 130 150 200 385
EXTERNAL STATIC PRESSURE (H/M/L) Pa 30/19/12 30/16/7 30/18/7 30/21/13
USGPM 1.32 2.00 2.66 3.99
NOMINAL WATER FLOW RATE
litres/min 5.00 7.57 10.09 15.13
HEAD LOSS (COOLING) kPa 7 20 25 34
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.26 1.17 1.56 1.99
SOUND PRESSURE LEVEL (H/M/L) dBA 32/27/21 33/26/21 36/30/22 39/36/31
UNIT DIMENSION HXWXD mm 251x630x461 251x774x461 251x774x461 251x874x461
PACKING DIMENSION HXWXD mm 595x836x284 595x984x284 595x984x284 595x1084x284
UNIT WEIGHT kg 13 16 16 17.5
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSPT FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
QUANTITY 1 2 2 2
HIGH RPM 985 970 1070 1300
FAN FAN SPEED MEDIUM RPM 800 740 870 1120
LOW RPM 655 540 610 940
INDOOR UNIT

HIGH % 34.2 34.8 32.5 33.4


FAN EFFICIENCY MEDIUM % 36.7 36.1 34.6 34.1
LOW % 40.4 39.6 39.0 35.5
TYPE DC BRUSHLESS MOTOR
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 1
HIGH W 19 30 43 80
RATED INPUT
MEDIUM W 10 13 21 56
POWER
LOW W 6 6 9 30
HIGH A 0.20 0.29 0.40 0.69
FAN MOTOR RATED RUNNING
MEDIUM A 0.15 0.18 0.22 0.50
CURRENT
LOW A 0.12 0.13 0.14 0.30
STARTING CURRENT A 1.20 1.20 1.20 1.20
MOTOR OUTPUT W 120 120 120 120
HIGH % 71.5 77.9 79.9 81.1
MOTOR EFFICIENCY MEDIUM % 56.8 64.6 72.4 80.4
LOW % 38.3 44.1 56.4 76.4
POLES 10
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.08 0.12 0.12 0.14
ROW 3
WATER VOLUME litre 0.28 0.45 0.45 0.62
TYPE OPTION (WASHABLE SARANET FILTER OR ALUMINIUM MESH FILTER)
AIR QUALITY FILTER
QUANTITY pc 2
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 27°C DB / 19°C WB
ENTERING WATER TEMPERATURE 7°C
LEAVING WATER TEMPERATURE 12°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

123
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit (EC Motor)


Medium Static Pressure (LSP)
MODEL FWC08G FWC10G FWC12G
Btu/h 24000 30000 36000
NOMINAL COOLING CAPACITY
W 7.03 8.79 10.55
Btu/h 19100 23400 27900
NOMINAL SENSIBLE COOLING CAPACITY
W 5.60 6.86 8.18
NOMINAL TOTAL INPUT POWER W 100 142 163
NOMINAL RUNNING CURRENT A 0.87 1.18 1.35
POWER SOURCE V/Ph/Hz 220-240/1/50 & 208-230/1/60
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 800 1000 1200
AIR FLOW MEDIUM CFM 650 805 975
LOW CFM 465 600 810
EXTERNAL STATIC PRESSURE (H/M/L) Pa 30/19/10 30/18/11 30/20/13
USGPM 5.33 6.66 7.99
NOMINAL WATER FLOW RATE
litres/min 20.18 25.22 30.26
HEAD LOSS (COOLING) kPa 38 42 38
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.69 2.11 2.05
SOUND PRESSURE LEVEL (H/M/L) dBA 40/35/27 42/38/32 43/40/36
UNIT DIMENSION HXWXD mm 251x1264x461 251x1264x461 251x1514x461
PACKING DIMENSION HXWXD mm 595x1473x284 595x1473x284 595x1724x284
UNIT WEIGHT kg 26 26 29.5
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSPT FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
QUANTITY 3 3 4
HIGH RPM 1140 1275 1220
FAN FAN SPEED MEDIUM RPM 950 1035 1010
LOW RPM 710 805 835
INDOOR UNIT

HIGH % 52.9 43.9 37.7


FAN EFFICIENCY MEDIUM % 53.6 51.2 33.9
LOW % 57.6 57.3 46.7
TYPE DC BRUSHLESS MOTOR
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 2 2 2
HIGH W 100 142 163
RATED INPUT
MEDIUM W 60 84 102
POWER
LOW W 29 40 62
HIGH A 0.87 1.18 1.35
FAN MOTOR RATED RUNNING
MEDIUM A 0.58 0.77 0.89
CURRENT
LOW A 0.37 0.42 0.60
STARTING CURRENT A 2.40 2.40 2.40
MOTOR OUTPUT W 120 120 120
HIGH % 80.1 81.3 80.8
MOTOR EFFICIENCY MEDIUM % 77.1 78.6 79.5
LOW % 69.1 73.9 78.0
POLES 10
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.22 0.22 0.28
ROW 3
WATER VOLUME litre 0.90 1.04 1.29
TYPE OPTION (WASHABLE SARANET FILTER OR ALUMINIUM MESH FILTER)
AIR QUALITY FILTER
QUANTITY pc 3 3 4
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 27°C DB / 19°C WB
ENTERING WATER TEMPERATURE 7°C
LEAVING WATER TEMPERATURE 12°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

124
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit (EC Motor)


Medium Static Pressure (MSP)
MODEL FWC03G FWC04G FWC06G
Btu/h 9000 12000 18000
NOMINAL COOLING CAPACITY
W 2.64 3.52 5.28
Btu/h 7000 9700 14400
NOMINAL SENSIBLE COOLING CAPACITY
W 2.05 2.84 4.22
NOMINAL TOTAL INPUT POWER W 40 55 94
NOMINAL RUNNING CURRENT A 0.38 0.49 0.80
POWER SOURCE V/Ph/Hz 220-240/1/50 & 208-230/1/60
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 300 400 600
AIR FLOW MEDIUM CFM 220 305 500
LOW CFM 150 200 385
EXTERNAL STATIC PRESSURE (H/M/L) Pa 50/32/15 50/32/15 50/35/20
USGPM 2.00 2.66 3.99
NOMINAL WATER FLOW RATE
litres/min 7.57 10.09 15.13
HEAD LOSS (COOLING) kPa 20 25 34
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.17 1.56 1.99
SOUND PRESSURE LEVEL (H/M/L) dBA 35/29/20 37/31/22 41/37/31
UNIT DIMENSION HXWXD mm 251x774x461 251x774x461 251x874x461
PACKING DIMENSION HXWXD mm 595x984x284 595x984x284 595x1084x284
UNIT WEIGHT kg 16 16 17.5
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSPT FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
QUANTITY 2 2 2
HIGH RPM 1115 1235 1350
FAN FAN SPEED MEDIUM RPM 900 990 1170
LOW RPM 645 715 935
INDOOR UNIT

HIGH % 35.9 36.3 33.5


FAN EFFICIENCY MEDIUM % 37.0 36.0 33.9
LOW % 38.7 37.0 35.4
TYPE DC BRUSHLESS MOTOR
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 1 1 1
HIGH W 40 55 94
RATED INPUT
MEDIUM W 19 27 62
POWER
LOW W 9 11 34
HIGH A 0.38 0.49 0.80
FAN MOTOR RATED RUNNING
MEDIUM A 0.20 0.26 0.56
CURRENT
LOW A 0.13 0.16 0.32
STARTING CURRENT A 1.20 1.20 1.20
MOTOR OUTPUT W 120 120 120
HIGH % 75.0 76.4 81.5
MOTOR EFFICIENCY MEDIUM % 67.2 72.0 81.4
LOW % 54.1 59.3 77.8
POLES 10
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.12 0.12 0.14
ROW 3
WATER VOLUME litre 0.45 0.45 0.62
TYPE OPTION (WASHABLE SARANET FILTER OR ALUMINIUM MESH FILTER)
AIR QUALITY FILTER
QUANTITY pc 2 2 2
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 27°C DB / 19°C WB
ENTERING WATER TEMPERATURE 7°C
LEAVING WATER TEMPERATURE 12°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

125
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit (EC Motor)


Medium Static Pressure (MSP)
MODEL FWC08G FWC10G FWC12G
Btu/h 24000 30000 36000
NOMINAL COOLING CAPACITY
W 7.03 8.79 10.55
Btu/h 19100 23400 27900
NOMINAL SENSIBLE COOLING CAPACITY
W 5.60 6.86 8.18
NOMINAL TOTAL INPUT POWER W 120 170 189
NOMINAL RUNNING CURRENT A 1.02 1.38 1.54
POWER SOURCE V/Ph/Hz 220-240/1/50 & 208-230/1/60
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 800 1000 1200
AIR FLOW MEDIUM CFM 650 805 975
LOW CFM 465 600 810
EXTERNAL STATIC PRESSURE (H/M/L) Pa 50/33/17 50/33/18 50/33/23
USGPM 5.33 6.66 7.99
NOMINAL WATER FLOW RATE
litres/min 20.18 25.22 30.26
HEAD LOSS (COOLING) kPa 38 42 38
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 1.69 2.11 2.05
SOUND PRESSURE LEVEL (H/M/L) dBA 43/37/30 44/40/33 44/40/37
UNIT DIMENSION HXWXD mm 251x1264x461 251x1264x461 251x1514x461
PACKING DIMENSION HXWXD mm 595x1473x284 595x1473x284 595x1724x284
UNIT WEIGHT kg 26 26 29.5
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05 BSPT FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT
QUANTITY 3 3 4
HIGH RPM 1310 1405 1320
FAN FAN SPEED MEDIUM RPM 1080 1190 1050
LOW RPM 830 930 965
INDOOR UNIT

HIGH % 39.0 36.0 32.9


FAN EFFICIENCY MEDIUM % 39.9 38.6 30.1
LOW % 40.4 39.6 33.4
TYPE DC BRUSHLESS MOTOR
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
QUANTITY 2 2 2
HIGH W 120 170 189
RATED INPUT
MEDIUM W 68 101 126
POWER
LOW W 34 45 72
HIGH A 1.02 1.38 1.54
FAN MOTOR RATED RUNNING
MEDIUM A 0.63 0.89 1.09
CURRENT
LOW A 0.40 0.46 0.68
STARTING CURRENT A 2.40 2.40 2.40
MOTOR OUTPUT W 120 120 120
HIGH % 80.7 82.1 81.7
MOTOR EFFICIENCY MEDIUM % 78.6 80.7 80.9
LOW % 70.7 74.6 78.5
POLES 10
MATERIAL COPPER
TUBE
DIAMETER mm 7
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.22 0.22 0.28
ROW 3
WATER VOLUME litre 0.90 1.04 1.29
TYPE OPTION (WASHABLE SARANET FILTER OR ALUMINIUM MESH FILTER)
AIR QUALITY FILTER
QUANTITY pc 3 3 4
CASING COLOUR WITHOUT PAINT

MODE COOLING
ENTERING AIR TEMPERATURE 27°C DB / 19°C WB
ENTERING WATER TEMPERATURE 7°C
LEAVING WATER TEMPERATURE 12°C
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

126
Engineering & Physical Data

Engineering Data - Chilled Water Fan Coil Unit


MODEL FUD20B FUD25B FUD30B FUD40B
Btu/h 75600 95000 125000 150000
NOMINAL COOLING CAPACITY
W 22160 27840 36640 43960
Btu/h 53700 69400 90000 106500
NOMINAL SENSIBLE COOLING CAPACITY
W 15740 20340 26380 31210
NOMINAL HEATING CAPACITY Btu/h 78000 97500 138000 170000
(ENTERING WATER TEMP. = 50°C) W 22860 28580 40450 49820
NOMINAL TOTAL INPUT POWER W 760 1800 1620 1910
NOMINAL RUNNING CURRENT A 3.49 7.84 3.33 4.03
POWER SOURCE V/Ph/Hz 220-240/1/50 380-415/3/50
AIR DISCHARGE DUCTED
CONTROL
OPERATION WITHOUT CONTROLLER
HIGH CFM 2500 3200 4200 4600
AIR FLOW MEDIUM CFM 2100 3000 N/A N/A
LOW CFM 1750 2800 N/A N/A
EXTERNAL STATIC PRESSURE Pa 100 / 72 / 50 100 / 80 / 60 149* 149*
USGPM 16.90 21.10 27.70 33.30
NOMINAL WATER FLOW RATE
litres/min 64.00 80.00 105.00 126.00
HEAD LOSS (COOLING) kPa 34.5 42.0 48.8 53.3
HEAD LOSS (HEATING) : 50°C kPa 32.9 27.4 31.5 63.2
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 2.18 2.79 1.97 2.16
SOUND PRESSURE LEVEL dBA 50 / 46 / 42 54 / 52 / 50 58 58
UNIT DIMENSION HXWXD mm 572 x 1402 x 605 885 x 1540 x 850
PACKING DIMENSION HXWXD mm 762 x 1605 x 880 1154 x 1787 x 1188
UNIT WEIGHT kg 92 102 176 189
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 31.75 BSP FEMALE THREAD ADAPTOR
TYPE BLOWER
DRIVE DIRECT BELT
HIGH RPM 835 950 707 707
FAN SPEED MEDIUM RPM 720 885 N/A N/A
FAN
LOW RPM 620 805 N/A N/A
INDOOR UNIT

HIGH % 43.30 31.60 41.30 27.10


FAN EFFICIENCY MEDIUM % 43.20 35.00 N/A N/A
LOW % 45.40 38.20 N/A N/A
TYPE PERMANENT SPLIT CAPACITOR (INDUCTION) THREE PHASE INDUCTION
INDEX OF PROTECTION (IP) IP22
INSULATION GRADE B
HIGH W 760 1800 1620 1910
RATED INPUT
MEDIUM W 611 1620 N/A N/A
POWER
LOW W 478 1320 N/A N/A
HIGH A 3.49 7.84 3.33 4.03
RATED RUNNING
FAN MOTOR MEDIUM A 2.86 7.06 N/A N/A
CURRENT
LOW A 2.32 5.82 N/A N/A
STARTING CURRENT A 5.20 10.30 3.48 4.21
MOTOR OUTPUT W 375 500 1500 1500
HIGH % 58.30 41.00 77.20 79.70
MOTOR
MEDIUM % 42.50 36.60 N/A N/A
EFFICIENCY
LOW % 31.30 31.30 N/A N/A
POLES 6 4 4 4
MATERIAL COPPER
TUBE
DIAMETER mm 9.52
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m2 0.54 0.54 1.01 1.01
ROW 3 4 3 4
WATER VOLUME litre 4.53 6.27 8.14 11.63
TYPE WASHABLE SARANET FILTER VILEDON R29
AIR QUALITY FILTER
QUANTITY pc 2 3
CASING COLOUR IVORY WHITE

* The external static pressure for FUD30/40B above is inclusive of R29 filters whereby R29 filters contribute a pressre drop of 81Pa.

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27°C DB / 19°C WB 20°C DB
50°C (2 Pipes System)
ENTERING WATER TEMPERATURE 7°C
-
LEAVING WATER TEMPERATURE 12°C -
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

127
Outlines & Dimensions

Outlines & Dimensions


Indoor Unit
Model: FWW02/03/04/05/06L

THE MARK SHOWS PIPING DIRECTION


A

REAR REAR
LEFT RIGHT

C
TOP VIEW

NAME PLATE
SIGNAL RECEIVER
B

B
TERMINAL
BLOCK
WITH EARTH
INDOOR UNIT
TERMINAL
ON/OFF SWITCH SIDE VIEW
BOTTOM BOTTOM
ROOM TEMPERATURE
THERMISTOR (INSIDE)
LOUVER FRONT GRILLE FIXED SCREWS
(INSIDE)

FRONT VIEW

NOTE: PLEASE BASED ON ACTUAL INSTALLATION PLATE DESIGN IN THE UNIT FOR INSTALLATION PLATE
FWW02/03/04L DIMENSION REFERENCE AT PAGE 1&2.

Use tape measure as shown.


 Recommended mounting plate retention spots Position the end of a tape measure at 
(5 spots in all)

D E

F
F
B

Through the wall


hole Ø 65mm

G
G

H J K I
L M
A Drain hose position

Liquid pipe end Gas pipe end

INSTALLATION PLATE FWW02/03/04L

Dimension
A B C D E F G H I J K L M
Model
FWW02/03/04L 800 288 206 166 184 42 46 55 56 154 182 263 52

Note: Dimension in mm

128
Outlines & Dimensions

Model: FWW02/03/04/05/06L

 Recommended mounting plate retention spots


(5 spots in all)
D E

F
F

Through the wall


B

hole Ø 65mm

G
G

H J Drain hose position


L M K I
A

Liquid pipe end Gas pipe end

ALTERNATIVE INSTALLATION PLATE FWW02/03/04L

Dimension
A B C D E F G H I J K L M
Model
FWW02/03/04L 800 288 206 104 141 30 46 55 56 153 181 207 52

 Recommended mounting plate retention spots


(7 spots in all)

D E
F

F
B

Through the wall


hole Ø 65mm
G

H J Liquid pipe end Gas pipe end K I Drain hose position


L M
A

INSTALLATION PLATE FWW05/06L

Dimension
A B C D E F G H I J K L M
Model
FWW05/06L 1065 310 224 190 173 61 40 45 48 91 219 580 45

Note: Dimension in mm

129
Outlines & Dimensions

Model: FWF02/04/05C

H
640
408
G
F
364

408

K
364
D
E

SEE DETAIL A
25C0

DETAIL A
J
I

WATER OUTLET
WATER INLET
57B0

Dimension
A B C D E F G H I J K
Model

FWF02/04/05C 570 570 250 640 408 364 408 640 75 98 364

Note: Dimension in mm

130
Outlines & Dimensions

Model: FWK06/08/09/11/13E(H)

B
D
C
E
K
H

J
I
G

Dimension
A B C D E F G H I J K
Model

FWK06/08/09E(H) 820 820 340 300 40 990 990 627 627 607 430

FWK11/13E(H) 820 820 375 335 40 990 990 627 627 607 430

Note: Dimension in mm

131
Outlines & Dimensions

Model: FWKE05/08/11E(H)

G
J
I

H
F

K
D E
C
B

Dimension
A B C D E F G H I J K
Model

FWKE05/08E(H) 820 820 340 300 40 990 990 627 627 607 430

FWKE11E(H) 820 820 375 335 40 990 990 627 627 607 430

Note: Dimension in mm

132
Outlines & Dimensions

Model: FWE05/06/07E

G
DRAIN PIPE
F

WATER INLET

WATER OUTLET

N
D

M
E

C
DETAIL A
B H
I J
K

SEE DETAIL A

Dimension
A B C D E F G H I J K L M N
Model

FWE05/06/07E 800 1090 230 630 20 150 20 21 156 57 213 144 107 129

Mounting Bracket
A
C B
G

D
F
E
H

Dimension
A B C D E F G H
Model

FWE05/06/07E 1073 534 268 135 336 630 145 485

Note: Dimension in mm

133
Outlines & Dimensions

Model: FWE08/10/12E

C
B

D
G

F
E

Dimension
A B C D E F G
Model
FWE08E 1272 1088 74 1320 268 635 259

FWE10E 1490 1308 74 1538 268 635 259

FWE12E 1738 1556 74 1786 268 635 259

Mounting Bracket
A
B
C
D

H
F E

Dimension
A B C D E F G H
Model
FWE08E 1320 635 255 134 1222 49 148 120

FWE10E 1538 635 255 134 1440 49 148 120

FWE12E 1786 635 255 134 1688 49 148 120

Note: Dimension in mm

134
Outlines & Dimensions

Model: FWC03C

LEFT PIPING
D
H
150 31

10
51

I
L

J
M

I
150 31

10
N G
O 10
20
40
40

WATER OUTLET
131
Q

P
131

E
178

WATER INLET
133
39

36 40

10

F
63
C
B
A

RIGHT PIPING

D
H
31 150
10

51
K
I
J

L
I

31 150
10

G N
10 O
20

40
40

WATER OUTLET
131

Q
131
P
E

WATER INLET
133
178
40
36 40

10
F

C 63
B
A

Dimension
A B C D E F G H I J K L M N O P Q
Model
FWC03C 808 774 702 741 267 36 662 662 93 225 115 218 76 411 351 211 211

Note: Dimension in mm

135
Outlines & Dimensions

Model: FWC04/06/07C

LEFT PIPING
D
H
DETAIL B FOR FWPMM6/7 DETAIL A FOR FWPMM4 R 31

10
WATER OUTLET WATER OUTLET 51

I
K
162

179
121

133
WATER INLET WATER INLET

J
61 60
84

I
M
R 31

10
SEE DETAIL A FOR FWPMM4 N G
SEE DETAIL B FOR FWPMM6/7 O
10
40

40
WATER INLET
131

131
Q

E
P
WATER OUTLET
36 40
40

10

F
C
B
A

RIGHT PIPING
D
H
31 R
10

DETAIL A FOR FWPMM4 DETAIL B FOR FWPMM6/7


51
I

WATER OUTLET
WATER OUTLET
J

WATER INLET
WATER INLET 162
179

121
133
I

60 61
31 R 84
10

N SEE DETAIL A FOR FWPMM4


O SEE DETAIL B FOR FWPMM6/7
10
40
40

WATER INLET
P

Q
131

131
E

WATER OUTLET
36 40

40

10
F

C
B
A

Dimension
A B C D E F G H I J K L M N O P Q R
Model

FWC04C 939 914 842 881 267 36 802 802 93 225 114 222 76 412 351 211 211 185

FWC06C 1108 1075 1002 1041 267 36 962 962 93 225 64 272 76 412 351 211 211 179

FWC07C 1243 1209 1137 1176 267 36 1097 1097 93 225 64 272 76 412 351 211 211 206

Note: Dimension in mm

136
Outlines & Dimensions

Model: FWC08/11C

LEFT PIPING
H
R 25

16
50

I
L

J
I
M
371 40

15
N G
O D
25
W

15
WATER OUTLET WATER INLET

P
S
160
Q

E
15
15
V
22

F
U C
T B
A

RIGHT PIPING
H
25 R
16

50
I

K
J

L
M
I

40 371
15

G N
D O
25
W
15

WATER INLET WATER OUTLET


P
S

160
Q
E

15

15
V
22
F

U
C T
B
A

Dimension
A B C D E F G H I J K L
Model
FWC08C 987 997 920 959 296 36 824 869 131 339 136 367

FWC11C 1292 1297 1225 1264 316 36 824 1174 119 401 147 394

Dimension
M N O P Q R S T U V W
Model
FWC08C 97 600 521 121 213 410 91 137 87 167 31

FWC11C 97 638 559 186 233 563 156 148 97 149 51

Note: Dimension in mm

137
Outlines & Dimensions

Model: FWC09/12/14/16C

LEFT PIPING D
H
R 25

15
50

I
L

J
M

I
N S 40
O G
60

40
WATER OUTLET WATER INLET

P
93
Q
188

E
40
15
59

15

F
U C
T B
A

RIGHT PIPING
D
H
25 R
15

50
I

K
L
J

M
I

40 S N
G O

60
40

WATER INLET WATER OUTLET


P
93

188
Q
E

40

15
V
59

15
F

C U
B T
A

Dimension
A B C D E F G H I J K L
Model
FWC09C 972 988 917 956 384 36 798 866 143 256 162 206

FWC12C 1088 1105 1033 1072 384 36 798 982 143 256 162 206

FWC14C 1342 1358 1287 1326 384 36 798 1236 143 256 159 209

FWC16C 1542 1558 1487 1526 384 36 798 1436 143 256 159 199

Dimension
M N O P Q R S T U V
Model
FWC09C 173 541 462 173 307 409 359 159 109 196

FWC12C 173 541 462 173 307 467 359 159 109 196

FWC14C 173 541 462 173 307 594 359 156 106 196

FWC16C 183 541 462 173 307 694 359 154 104 196

Note: Dimension in mm

138
Outlines & Dimensions

Model: FWC02/03/04/05/06/08/10FD

LEFT PIPING
KE
KD 31

321
552
183
140

48
KC 31
552 KB
129 129
20 183 19
71
143
87
186

247
31

125
317 32 KA
333

RIGHT PIPING
KE
31 KD
321
552
183

140
48

31 KC 552
KB 129
19 183 20
11
71
143
87
247

186
31

125
KA 32 317
333

Dimension
KA KB KC KD KE
Model
FWC02/03FD 619 477 437 440 501

FWC04/05FD 870 726 687 690 751

FWC06FD 1060 916 877 880 941

FWC08FD 1390 1246 1207 1210 1271

FWC10FD 1600 1456 1417 1420 1481

Note: Dimension in mm

139
Outlines & Dimensions

Model: FWC02G (LSP)

MOUNTING HOLE
198

(4 X 10.0 X 16.0)
CONDENSATE DRAIN (R3/4")
267

187
43
38 KE WATER OUT
66 KD 110 30 (3/4" BSPT FEMALE THREAD ADAPTOR)
26 KC 18 104

18
161 16
143 38

219
251
OUT

IN

27

82
132 WATER IN 148
KB (3/4" BSPT FEMALE THREAD ADAPTOR)
KA 461

Dimension
KA KB KC KD KE
Model
FWC02G 657 630 494 414 470

Note: Dimension in mm

140
Outlines & Dimensions

Model: FWC03/04/06G (MSP,LSP)

Dimension
KA KB KC KD KE
Model
FWC03/04G 801 774 638 558 614

FWC06G 901 874 738 658 714

Note: Dimension in mm

141
Outlines & Dimensions

Model: FWC08/10G (MSP,LSP)

Dimension
KA KB KC KD KE
Model
FWC08/10G 1289 1264 1048 1127 1103

Note: Dimension in mm

142
Outlines & Dimensions

Model: FWC12G (MSP,LSP)

. . . .
MOUNTING HOLE
I� I I / (4 X 10.0 X 16.0)

� ...

.!,[ ... ll CONDENSATE DRAIN (R3/4")
([) d

�v

0 0

'

=- . . . . . . ""'"

38 KE

66 KC 110 30
WATER OUT
104 3/4" BSPT FEMALE THREAD ADAPTOR
26 KD 18

0 0
00

;
V C')

ii
� �
C')

co

... - •

h
N
00
N

KB I 132 148
WATER IN
KA 3/4" BSPT FEMALE THREAD ADAPTOR
461

Dimension
KA KB KC KD KE
Model
FWC12G 1540 1514 1300 1378 1354

Note: Dimension in mm

143
Outlines & Dimensions

Model: FWC14/16/18/20G (MSP)

Dimension
KA KB KC KD KE
Model

FWC14GW 1142 1116 953 877 929

FWC16/18GW 1280 1254 1091 1015 1067

FWC20GW 1420 1394 1231 1155 1207

Note: Dimension in mm

144
Outlines & Dimensions

Model: FWC02/03/04/06/08/10/12G EC (LSP , MSP)

59 KG 59
12 KF 12

18 18
MOUNTING HOLE
(6 X 10.0 X 16.0)
142

CONDENSATE DRAIN (R3/4”)


187
43

38 KE 513
KD 110 30 WATER OUT
66 104 (3/4” BSPT FEMALE THREAD ADAPTOR)
26 KC 18 235 24

16

23
38
161
143
OUT

203
251
IN

82
27
KB 132 159

23
WATER IN
KA (3/4” BSPT FEMALE THREAD ADAPTOR)

Dimension
KA KB KC KD KE KF KG
Model
FWC02GW 657 630 494 414 470 508 414

FWC03/04GW 801 774 638 558 614 652 558

FWC06GW 901 874 738 658 714 752 658

FWC08/10GW 1289 1264 1127 1049 1103 1141 1047

FWC12GW 1540 1514 1378 1300 1354 1392 1298

Note: Dimension in mm

145
Outlines & Dimensions

Model: FUD20/25B

A
E B H

I
F F

J
NOTE:
FOR HORIZONTAL AIR DISCHARGE

K
G C G
V D V
Y X W W X Y
T L M N M L T
Z

Z
ZE
O
ZB

ZA

ZB
ZA
R
ZC

ZC
P

S
ZD

ZD
U U
Q

Z
Z

LEFT PIPING (OPTIONAL) RIGHT PIPING (STANDARD)

Dimension
A B C D E F G H I J K L M
Model
FUD20B 1402 1232 1462 1502 53 50 20 117 163 394 48 287 270
FUD25B 1402 1232 1462 1502 53 50 20 117 163 394 48 287 270

Dimension
N O P Q R S T U V W X Y Z
Model
FUD20B 288 177 295 65 302 103 33 72 761 60 605 96 35
FUD25B 288 177 295 65 289 103 33 72 761 60 605 96 35

Dimension
ZA ZB ZC ZD ZE
Model
FUD20B 537 437 572 100 132
FUD25B 537 437 572 100 145

Note: Dimension in mm

146
Outlines & Dimensions

Model: FUD30/40B (Horizontal Air Discharge)

A
E B H

I
F F

J
NOTE:
FOR HORIZONTAL AIR DISCHARGE
G C G

I
X D X
ZA Z Y Y Z ZA
T L M L T

S
S

U
N
Z
ZB

ZB
O
K

K
Q
P

R
ZC

ZC
W W
S

S
V V

LEFT PIPING (OPTIONAL) RIGHT PIPING (STANDARD)

Dimension
A B C D E F G H I J K L M
Model
FUD30B 1540 1370 1600 1640 53 50 20 117 48 754 885 533 474

FUD40B 1540 1370 1600 1640 53 50 20 117 48 754 885 533 474

Dimension
N O P Q R S T U V W X Y Z
Model
FUD30B 220 408 222 468 120 35 88 262 155 132 1040 60 850

FUD40B 220 408 222 468 120 35 88 262 155 132 1040 60 850

Dimension
ZA ZB ZC
Model
FUD30B 130 747 103

FUD40B 130 747 103

Note: Dimension in mm

147
Outlines & Dimensions

Model: FUD30/40B (Vertical Air Discharge)

A
E B H

I
N
F F

J
NOTE:

O
FOR VERTICAL AIR DISCHARGE

P
L M L

I
X G C G X
ZA Z D Z ZA
T T
Y

S
S

U
ZD
ZB

ZB
Z

ZD
K

K
R Q
ZC

ZC
W W
S

V V
LEFT PIPING (OPTIONAL) RIGHT PIPING (STANDARD)

Dimension
A B C D E F G H I J K L M
Model
FUD30B 1540 1370 1600 1640 53 50 20 117 48 754 885 533 474

FUD40B 1540 1370 1600 1640 53 50 20 117 48 754 885 533 474

Dimension
N O P Q R S T U V W X Y Z
Model
FUD30B 382 408 60 468 120 35 88 262 155 132 980 60 850

FUD40B 382 408 60 468 120 35 88 262 155 132 980 60 850

Dimension
ZA ZB ZC ZD
Model
FUD30B 130 747 103 945

FUD40B 130 747 103 945

Note: Dimension in mm

148
Wiring Diagrams

Wiring Diagrams
Model: FWW02/03/04/05/06L

FAN
DE
NG

MO
SWI

OFF
P
SLEE
BO

CEL
TUR

R
TIME

CAN
ET
QUI

CK
CLO
ON

CEL
CAN
POWER SUPPLY
220-240V/1Ph/50Hz

Model: FWF02/04/05C
NA
F
ED

GN
OM

IW
S
FF
O

PE
EL

OB
LE

S
RE

R
C

UT
NA

MI
C

TE
IU
Q
KC
OL
C

NO
LE
CN
AC

WIRED
CONTROLLER
(OPTIONAL)

POWER SUPPLY
220-240V/1Ph/50Hz

TO 2/3 WAY VALVE

Note: Please do not install using third party controller as this will affect the functionality of unit feature

149
Wiring Diagrams

Model: FWK06/08/09/11/13E

TO 2/3 WAY VALVE

L
POWER SUPPLY
N 220-240V/1Ph/50Hz
E

FAN
DE
ING

MO
SW

OFF
EP
BO

SLE

CEL
TUR

ER

CAN
TIM
IET
QU

CK
CLO
ON

CEL
CAN
WIRED
CONTROLLER
(OPTIONAL)

Note: Please do not install using third party controller as this will affect the functionality of unit feature

Model: FWK06/08/09/11/13EH

TO 2/3 WAY VALVE TO 2/3 WAY VALVE


(HEATING) (COOLING)
L
N
POWER SUPPLY
E
220-240V/1Ph/50Hz

FAN
DE
ING

MO
SW

OFF
EP
BO

SLE

CEL
TUR

ER

CAN
TIM
IET
QU

CK
CLO
ON

CEL
CAN

WIRED
CONTROLLER
(OPTIONAL)

Note: Please do not install using third party controller as this will affect the functionality of unit feature

150
Wiring Diagrams

Model: FWKE05/08E

WIRED
CONTROLLER
(OPTIONAL)
NA
F
ED

GN
OM

IW
S
FF
O

PE
EL

OB
LE

S
RE

R
C

UT
NA

MI
C

TE
IU
Q
KC
OL
C

NO
LE
C
NA
C

POWER SUPPLY
220-240V/1Ph/50Hz

TO 2/3 WAY VALVE

Note: Please do not install using third party controller as this will affect the functionality of unit feature

Model: FWKE11E

WIRED
CONTROLLER
(OPTIONAL)
NA
F
ED

GN
OM

IW
S
FF
O

PE
E

OB
LE

LS
RE

R
C

UT
NA

MI
C

TE
IU
Q
KC
OL
C

NO
LE
C
NA
C

POWER SUPPLY
220-240V/1Ph/50Hz

TO 2/3 WAY VALVE

Note: Please do not install using third party controller as this will affect the functionality of unit feature

151
Wiring Diagrams

Model: FWKE05/08EH

WIRED
CONTROLLER
(OPTIONAL)
NA
F
ED

GN
OM

IW
S
FF
O

PE
EL

OB
LE

S
RE

RU
C
NA

MI

T
C

TE
IU
Q
KC
OL
C

NO
LE
C
NA
C

POWER SUPPLY
220-240V/1Ph/50Hz

TO 2/3 WAY VALVE TO 2/3 WAY VALVE


(HEATING) (COOLING)

Note: Please do not install using third party controller as this will affect the functionality of unit feature

Model: FWKE11EH

WIRED
CONTROLLER
(OPTIONAL)
NA
F
ED

GN
O

IW
M

S
FF
O

PE
EL

OB
LE

S
RE

R
C

UT
NA

MI
C

TE
IU
Q
KC
OL
C

NO
LE
C
NA
C

POWER SUPPLY
220-240V/1Ph/50Hz

TO 2/3 WAY VALVE TO 2/3 WAY VALVE


(HEATING) (COOLING)

Note: Please do not install using third party controller as this will affect the functionality of unit feature

152
Wiring Diagrams

Model: FWE05/06/07E

WIRED
CONTROLLER
(OPTIONAL)
NA
F
ED

GN
OM

IW
S
FF
O

PE
EL

OB
LE

S
RE

RU
C
NA

T
IT
C

TE
IU
Q
KC
OL
C

NO
LE
C
NA
C

E POWER SUPPLY
N 220-240V/1Ph/50Hz
L
TO 2/3 WAY VALVE

Model: FWE08/10/12E

TO 2/3 WAY VALVE

L
POWER SUPPLY
N
220-240V/1Ph/50Hz
E

FAN
DE
ING

MO
SW

OFF
EP
BO

SLE

CEL
TUR

ER

CAN
TIM
IET
QU

CK
CLO
ON

CEL
CAN

WIRED
CONTROLLER
(OPTIONAL)

Note: Please do not install using third party controller as this will affect the functionality of unit feature

153
Wiring Diagrams

Model: FWC03/04/06/07C (With Controller)

WIRED
CONTROLLER
(OPTIONAL)

E
POWER SUPPLY
N 220-240V/1Ph/50Hz
L
TO 2/3 WAY VALVE

Model: FWC09/11/12/14/16C (With Controller)

WIRED
CONTROLLER
(OPTIONAL)

E POWER SUPPLY
N 220-240V/1Ph/50Hz
L
TO 2/3 WAY VALVE

154
Wiring Diagrams

Model: FWC03/04/06/07C (Without Controller)

Model: FWC09/11/12/14/16C (Without Controller)

155
Wiring Diagrams

Model: FWC02/03/04/05/06FD

Model: FWC08/10FD

156
Wiring Diagrams

Model: FWC02/03/04/06/14/16/18/20G

Model: FWC02/03/04/06/08/12G EC (LSP , MSP)

157
Wiring Diagrams

Model: FUD30/40B

Model: FUD20B

158
Wiring Diagrams

Model: FUD25B

159
Service & Maintenance

Service & Maintenance

Moving machinery and electrical power hazards. May cause severe personal injury or death.
Disconnect from main power supply before servicing equipment.

The unit is designed to give long life operation with minimum maintenance required. However, it should
be regularly checked and the following items should be given due attention.

Components Maintenance Procedures Recommended Schedule


Air Filter 1. Remove any dust adhering to the filter by using a At least once every 4 weeks.
(Indoor Unit) vacuum cleaner or wash in lukewarm water (below
40˚C) with a neutral cleaning detergent.
2. Rinse the filter well and dry before placing it back onto More frequently if necessary.
the unit.
3. Note: Never use gasoline, volatile substances or
chemicals to clean the filter.
Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping At least once every 4 weeks.
it with a soft cloth soaked in lukewarm water (below
40˚C) and a neutral detergent solution.
2. Note: Never use gasoline, volatile substances or More frequently if necessary.
chemicals to clean the indoor unit.
Condense Drain 1. Check the cleanliness and clean it if necessary. Every 3 months.
Pan & Pipe
Indoor Fan Check if there is any abnormal noise. When necessary.
Indoor Coil 1. Check and remove the dirt between the fins. Every month.
2. Check and remove any obstacles which hinder air
flowing into and out of the indoor unit.
Power Supply 1. Check the voltage and current of the indoor unit. Every 2 months.
2. Check the electrical wiring for any faulty contacts
caused by loose connections, foreign matters, etc.
Tighten the wires onto the terminal block if
necessary.
Fan Motor Oil All motors are pre-lubricated and sealed at factory. No maintenance required.

Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when
performing a leakage test or an air tight test. These gases could cause severe explosion and damage if
expose to high temperature and pressure.

160
Troubleshooting

Troubleshooting
Model Board
FWW02/03/04/05/06L 50WJW
FWF02/04/05C W2
FWK06/08/09/11/13E(H) W3
FWE08/10/12E
FWKE05/08/11E(H) W3DC
FWE05/06/07E W2
FWC02/03/04/06/07/08/09/11/12/14/16C W2
FWC02/03/04/06/08/10/12/14/16/18/20G No Controller
FUD20/25/30/40B No Controller

Self Diagnostic Table - 50WJW Board

Normal Operation/Fault Indication Action Error Code


COOL/HEAT
(GREEN/RED)

Cool mode - -
Green

Heat mode - -
Red
Timer on - -

Sleep mode on - -

Fan mode on - -

Dry mode on - -

Room air sensor contact


Call your dealer Blink E1
1 time Loose/Short

Indoor coil sensor open/short Call your dealer Blink E2


2 times

Pipe water temperature poor - Blink E4


3 times

Pipe water temperature bad - Blink E5


1 time

Hardware error (tact switch pin short) Call your dealer Blink E8
6 times

No feedback from indoor fan Call your dealer Blink E9


4 times

ON ON or OFF Blinking

161
Troubleshooting

Self Diagnostic Table – W2 Board


Error
Fault Indication COOL LED Action
Code
Check room sensor
Room sensor error (short/open) Blink 1 time E1 connection/change room air
sensor
Check pipe water sensor
Pipe water sensor error (short/open) Blink 2 times E2 connection/change pipe
water sensor
Clear the clogging at drain
Water pump error* Blink 6 times E6 pipe. If pump is not working,
change the pump
Check chiller condition
Pipe water temperature fault Blink 5 times E5
(not working or just started)
*Applicable to FWF model only.

Self Diagnostic Table – W3 Board


Event Power LED Timer LED Error Code
1. Room Sensor Open or Short Blink 1 time - Blink E1
2. Pipe Water sensor Open or Short Blink 2 times - Blink E2
3. Pipe Water Temperature poor Blink 3 times - Blink E4
4. Pipe Water Temperature bad/fault - Blink 1 time Blink E5
5. Water Pump Fault** - Blink 2 times Blink E6
Hardware Error (tact switch pin Short/M3 or M4
6. - Blink 6 times Blink E8
Mode with valveless section)
7. Window Open activated* Blink 6 times - -
8. Antifreeze mode activated* Blink 7 times - -
9. Load Shedding activated* Blink 8 times - -
*Only applicable for 4-pipes system.
**Applicable to FWK model only.

Self Diagnostic Table – W3DC Board


Event Power LED Timer LED Error Code
1. Room Sensor Open or Short Blink 1 time - Blink E1
2. Pipe Water sensor Open or Short Blink 2 times - Blink E2
3. Pipe Water Temperature poor Blink 3 times - Blink E4
4. Pipe Water Temperature bad/fault - Blink 1 time Blink E5
5. Water Pump Fault - Blink 2 times Blink E6
6. Window Open activated* Blink Cool 6 times - -
7. Antifreeze mode activated* Blink Cool 7 times - -
8. Load Shedding activated* Blink Cool 8 times - -
9. Hardware Error - Blink 6 times Blink E8
10. No feedback from indoor fan Blink Cool 4 times Blink E9
*Only applicable for 4-pipes system.