Rxyq 72 Mtju
Rxyq 72 Mtju
OPERATION MANUAL
MODEL
RXYQ72MTJU
RXYQ96MTJU
RXYQ144MTJU
RXYQ168MTJU
RXYQ192MTJU
REYQ72MTJU
REYQ96MTJU
REYQ144MTJU
REYQ168MTJU
REYQ192MTJU
Read these instructions carefully before installation.
Keep this manual in a handy place for future reference.
This manual should be left with the equipment owner.
00_CV_3P161360-3D.fm Page 2 Wednesday, April 12, 2006 5:25 PM
F
NOT
AVAILABLE
23
24
Figure 2 Figure 3
F F
F F F
Figure 8 Figure 9
Multi-flow
Ceiling Suspended
Wall Mounted
Figure 13 Figure 14
Figure 15
01_EN_3P161360-3D.fm Page 4 Thursday, April 13, 2006 9:46 AM
4
01_EN_3P161360-3D.fm Page 5 Thursday, April 13, 2006 9:46 AM
5
01_EN_3P161360-3D.fm Page 6 Thursday, April 13, 2006 9:46 AM
• Avoid placing the controller in a spot splashed • Do not wipe the controller operation panel with
with water. benzine, thinner, chemical dustcloth, etc.
Water coming inside the controller may cause an elec- The panel may get discolored or the coating peeled
tric leak or may damage the internal electronic parts. off. If it is heavily dirty, soak a cloth in water-diluted
• Do not operate the air conditioner when using neutral detergent, squeeze it well and wipe the
a room fumigation - type insecticide. panel clean. And wipe it with another dry cloth.
Failure to observe could cause the chemicals to become • Dismantling of the unit, treatment of the refrig-
deposited in the unit, which could endanger the health of erant, oil and eventual other parts, should be
those who are hypersensitive to chemicals. done in accordance with the relevant local and
• Do not turn off the power immediately after national regulations.
stopping operation.
Always wait at least five minutes before turning off
the power. Otherwise, water leakage and trouble
2. WHAT TO DO BEFORE OPERA-
may occur. TION
• The appliance is not intended for use by young This operation manual is for the following systems
children or infirm persons without supervision. with standard control. Before initiating operation,
• The remote controller should be installed in contact your Daikin dealer for the operation that cor-
such away that children cannot play with it. responds to your system type and mark.
• Consult with installation contractor for clean- If your installation has a customized control system,
ing the inside of the air conditioner. ask your Daikin dealer for the operation that corre-
Wrong cleaning may make the plastics parts bro- sponds to your system.
ken or cause failure of water leakage or electric
shock. Outdoor units (Refer to figure 1)
• Do not touch the air inlet or aluminium fin of COOL/HEAT selector Operation modes
the air conditioner. Inverter series
Otherwise, injury may be caused. heat pumps RXYQ series ❏ yes ❏ no
• Do not place objects in direct proximity of the Heat recovery series
outdoor unit and do not let leaves and other heat pumps REYQ series ❏ yes ❏ no
debris accumulate around the unit.
Leaves are a hotbed for small animals which can • Names and functions of parts (Refer to figure 1)
enter the unit. Once in the unit, such animals can 1. Outdoor unit
cause malfunctions, smoke or fire when making 2. Indoor unit
contact with electrical parts. 3. Remote controller
4. Inlet air
5. Outlet air
NOTE
6. COOL/HEAT selector
• Never press the button of the remote controller 7. BS (branch selector) unit
with a hard, pointed object. (figure 1 shows systems with changeover remote
The remote controller may be damaged. control switches)
• Never pull or twist the electric wire of the
remote controller. 3. REMOTE CONTROLLER AND
It may cause the unit to malfunction.
COOL/HEAT SELECTOR: NAME
• Do not place appliances which produce open
fire in places exposed to the air flow from the AND FUNCTION OF EACH
unit or under the indoor unit. It may cause SWITCH AND DISPLAY
incomplete combustion or deformation of the
unit due to the heat.
(Refer to figure 2 and 3)
• Arrange the drain hose to ensure smooth 1. On/off button
drainage. Incomplete drainage may cause wet- Press the button and the system will start. Press
ting of the building, furniture etc. the button again and the system will stop.
• Do not place the controller exposed to direct 2. Operation lamp (red)
sunlight. The lamp lights up during operation.
The LCD display may get discolored, failing to dis-
play the data.
6
01_EN_3P161360-3D.fm Page 7 Thursday, April 13, 2006 9:46 AM
7
01_EN_3P161360-3D.fm Page 8 Thursday, April 13, 2006 9:46 AM
8
01_EN_3P161360-3D.fm Page 9 Thursday, April 13, 2006 9:46 AM
Stopping the system • If the hot air rises to the ceiling, leaving the
area above the floor cold, we recommend
6 Press the on/off button once again.
using the circulator (the indoor fan for circu-
The operation lamp goes off and the system
lating air). Contact your dealer for details.
stops operation.
NOTE
5-2 PROGRAM DRY OPERATION
• Do not turn off power immediately after the • The function of this operation is to decrease
unit stops. the humidity in your room with a minimum
• The system needs at least 5 minutes for the temperature decrease.
residual operation of drain pump. • The micro computer automatically deter-
Turning the power off immediately will cause mines temperature and fan speed.
water leak or trouble. • This function is not available if the room tem-
perature is 68°F or lower.
EXPLANATION OF HEATING OPERATION FOR SYSTEMS WITHOUT COOL/HEAT
• For general heating operation, it may take longer SELECTOR (Refer to figure 5)
to reach the set temperature than in cooling oper-
1 Press the operation mode selector button several
ation.
times and select “ ” (program dry operation).
We recommend starting the operation which was
used before using timer operation. 2 Press the on/off button
• The following operation is performed in order to The operation lamp lights up and the system
prevent the heating capacity from dropping or starts operation.
cold air from blowing. 3 Press the air flow direction adjust button. Refer
Defrost operation to the chapter “Adjusting the air flow direction”
• In heating operation, freezing of the outdoor for details.
unit coil increases. Heating capability 4 Press the on/off button once again.
decreases and the system goes into defrost The operation lamp goes off and the system
operation. stops operation.
• The indoor unit fan stops and the remote
controller displays “ ”. NOTE
• After maximum 10 minutes of defrost operation, • Do not turn off power immediately after the
the system returns to heating operation again. unit stops, but wait for at least 5 minutes.
Hot start • The system needs at least 5 minutes for the
• In order to prevent cold air from blowing out residual operation of drain pump.
Turning the power off immediately will cause
of an indoor unit at the start of heating oper-
water leak or trouble.
ation, the indoor fan is automatically
stopped. The display of the remote controller FOR SYSTEMS WITH COOL/HEAT SELECTOR
shows “ ”. (Refer to figure 8)
NOTE 1 Select cooling operation mode with the COOL/
• The heating capacity drops as the outside HEAT selector.
temperature falls. If this happens, use 2 Press the operation mode selector button sev-
another heating device together with the eral times and select “ ” (program dry
unit. (When using the appliances which pro- operation).
duce open fire together, ventilate a room
3 Press the on/off button
constantly.)
The operation lamp lights up and the system
Do not place appliances which produce
starts operation.
open fire in places exposed to the air flow
from the unit or under the unit. 4 Press the air flow direction adjust button. Refer
• It takes some time for the room to warm up to the chapter “Adjusting the air flow direction”
from the time the unit is started since the unit for details.
uses a hot-air circulatory system to warm 5 Press the on/off button once again.
the entire room. The operation lamp goes off and the system
stops operation.
9
01_EN_3P161360-3D.fm Page 10 Thursday, April 13, 2006 9:46 AM
10
01_EN_3P161360-3D.fm Page 11 Thursday, April 13, 2006 9:46 AM
5-5 SETTING THE MASTER REMOTE CON- 5-6 PRECAUTIONS FOR GROUP CON-
TROLLER (Refer to figure 10) TROL SYSTEM OR TWO REMOTE CON-
• When the system is installed as shown in figure TROLLER CONTROL SYSTEM
14 and 15, it is necessary to designate one of the This system provides two other control systems
remote controllers as the master remote control- beside individual control (one remote controller con-
ler. trols one indoor unit) system. Confirm which type of
FOR RXYQ SERIES (Refer to figure 14) your unit is the following system.
When one outdoor unit is connected with several • Group control system
indoor units. One remote controller controls up to 16 indoor
FOR REYQ SERIES (Refer to figure 15) units. All indoor units are equally set.
When one BS unit is connected with several indoor • Two remote controller control system
units. Two remote controllers control one indoor unit (in
• Only the master remote controller can select case of group control system, one group of indoor
heating, cooling or automatic (only REYQ series) units). The unit is individually operated.
operation.
• The displays of slave remote controllers show NOTE
“ ” (changeover under control) and they • Contact your Daikin dealer in case of chang-
automatically follow the operation mode directed ing the combination or setting of group con-
by the master remote controller. trol and two remote controller control
systems.
However, it is possible to changeover to program dry
operation with slave remote controllers if the system
is in cooling operation set by the master remote con- 6. OPTIMUM OPERATION
troller, and to changeover to fan only operation.
Observe the following precautions to ensure the
How to designate the master remote con- system operates properly.
troller
• Adjust the air outlet properly and avoid direct air
1 Press the operation mode selector button of flow to room inhabitants.
the current master remote controller for 4 sec- • Adjust the room temperature properly for a com-
onds. fortable environment. Avoid excessive heating or
The display showing “ ” (changeover cooling.
under control) of all slave remote controllers • Prevent direct sunlight from entering a room dur-
connected to the same outdoor unit or BS unit ing cooling operation by using curtains or blinds.
flashes. • Ventilate often.
2 Press the operation mode selector button of Extended use requires special attention to venti-
the controller that you wish to designate as the lation.
master remote controller. Then designation is • Do not leave doors and windows open. If the
completed. This remote controller is desig- doors and windows remain open, air will flow out
nated as the master remote controller and the of your room causing a decrease in the cooling or
display showing “ ” (changeover heating effect.
under control) vanishes. • Never place objects near the air inlet or the air
The displays of other remote controllers show outlet of the unit. It may cause deterioration in the
effect or stop the operation.
“ ” (changeover under control).
• Turn off the main power supply switch to the unit
when the unit is not used for longer periods of
time. If the switch is on, it uses electricity. Before
restarting the unit, turn on the main power supply
switch 6 hours before operation to ensure smooth
running. (Refer to the chapter “Maintenance” in
the indoor unit manual.)
11
01_EN_3P161360-3D.fm Page 12 Thursday, April 13, 2006 9:46 AM
• When the display shows “ ” (time to clean the 8. FOLLOWING SYMPTOMS ARE
air filter), ask a qualified service person to clean
the filters. (Refer to the chapter “Maintenance” in
NOT AIR CONDITIONER TROU-
the operation manual of indoor unit.) BLES
• Keep the indoor unit and remote controller at least
8-1 THE SYSTEM DOES NOT OPERATE
3.5ft. away from televisions, radios, stereos, and
other similar equipment. • The air conditioner does not start immediately
Failing to do so may cause static or distorted pic- when restarting or changing the operation
tures. mode.
• Do not use other heating devices directly beneath If the operation lamp lights, the system is in nor-
the indoor unit. mal condition.
If you do, they might get deformed by the heat. To prevent overloading of the compressor motor,
the air conditioner starts 5 minutes after it is
7. SEASONAL MAINTENANCE turned ON again in case it was turned OFF just
before.
7-1 AT THE BEGINNING OF THE SEASON • If “Centralized Control” is displayed on the
Check remote controller and pressing the operation
• Are the indoor and outdoor unit intake and outlet button causes the display to blink for a few
vents blocked? seconds.
Remove anything that might be blocking them. This indicates that the central device is controlling
the unit.
Clean the air filter and exterior.
The blinking display indicates that the remote
• After cleaning the air filter, be sure to put it back in
controller cannot be used.
the same position.
See the operation manual included with the • The system does not start immediately after
indoor unit for details on how to clean it. the power supply is turned on.
Wait 1 minute until the micro computer is pre-
Turn the power on.
pared for operation.
• When the power comes on, the characters in the
remote controller display appear. 8-2 IT STOPS SOMETIMES
(To protect the unit, turn the power on at least 6
• The remote controller display reads “U4” or
hours before operating it. This makes operation
“U5” and stops but then restarts after a few
smoother.)
minutes.
7-2 AT THE END OF THE SEASON This is because the remote control is intercepting
noise from electrical appliances other than the air
On a clear day, use fan operation for around half
conditioner, and this prevents communication
a day to thoroughly dry out the interior of the
between the units, causing them to stop.
unit.
Operation automatically restarts when the noise
• Refer to page 8 for details on fan operation.
goes away.
Turn off the power
• When the power is shut off, the characters in the 8-3 COOL/HEAT CANNOT BE CHANGED
remote controller display disappear. OVER
• When the power is on, the unit consumes up to • When the display shows “ ”
several dozen Watts of power. (changeover under control).
Turn off the power to conserve energy. It shows that this is a slave remote controller.
Clean the air filter and exterior. Refer to “Setting the master remote controller”.
• After cleaning the air filter, be sure to put it back in • When the COOL/HEAT selector is installed
the same position. and the display shows “ ”
See the operation manual included with the (changeover under control).
indoor unit for details on how to clean it. This is because cool/heat changeover is con-
trolled by the COOL/HEAT selector. Ask your
Daikin dealer where the remote control switch is
installed.
12
01_EN_3P161360-3D.fm Page 13 Thursday, April 13, 2006 9:46 AM
13
01_EN_3P161360-3D.fm Page 14 Thursday, April 13, 2006 9:46 AM
14
01_EN_3P161360-3D.fm Page 15 Thursday, April 13, 2006 9:46 AM
15
00_CV_3P161360-3D.fm Page 4 Wednesday, April 12, 2006 5:25 PM