0% found this document useful (0 votes)
91 views16 pages

30RAM Catalog

The document discusses a modular air-cooled chiller unit from Carrier. The unit uses air as a cold source and water as a refrigerant carrier. It has basic modules that can be combined for different capacities ranging from 66kW to 2080kW. The unit has features like intelligent defrosting, air volume management, energy management, and various safety protections.

Uploaded by

Bellatcha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
91 views16 pages

30RAM Catalog

The document discusses a modular air-cooled chiller unit from Carrier. The unit uses air as a cold source and water as a refrigerant carrier. It has basic modules that can be combined for different capacities ranging from 66kW to 2080kW. The unit has features like intelligent defrosting, air volume management, energy management, and various safety protections.

Uploaded by

Bellatcha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

30RAM

MODULAR AIR-COOLED CHILLER


Turn To The Experts
Inheriting a rich legacy of innovation including inventing modern
air-conditioning, Carrier has been a global leader in innovations
for Heating Ventilation Air Conditioning (HVAC) and refrigeration
solutions. Carrier is a part of UTC Climate, Controls & Security,
a unit of United Technologies Corp., a leading provider to the
aerospace and building systems industries worldwide.

With a broad portfolio of advanced technical patent awards,


our global R&D center in Shanghai develops innovative heat,
ventilation and air-conditioning (HVAC) solutions.

In 1998, Time magazine named


Dr. Carrier oneof its 20 most
influential builders and titans of
the 20thcentury.
PRODUCT NOMENCLATURE

The modular air-cooled chiller (heat pump) unit is a central air conditioning using the air as cold & heat source and the
water as refrigerant carrier, which can be integrated with various air side units such as fan coil unit, air handling unit to
form a central air conditioning system. With 115 years of experience in R&D,design and application, Carrier constantly
launches new environment-friendly modular units, which improves the structures, systems and programs based on
original products, and designs special series of comfortable and technological units. The environment-friendly modular
unit has complete functions and various specifications, with basic modules of any combination available for different
models, including 66kW, 100kW, 130kW, and at most 8 modules can be connected in parallel, providing combination
products of 66kW- 2080kW. The unit is easy to install, with a system without cooling water, with simple pipelines, mod -
erate cost, short construction period,allowing staged investment, widely applied in such commercial, industrial and civil
buildings as villas, hotels,hospitals, office buildings, restaurants, supermarkets, movie theaters.

30RAM 201

201: Specification code


30RAM : Modular air-cooled chiller

3
R410A CLASSICAL MODULAR UNIT
The new generation of X series environment-friendly modular air-cooled unit is based on years of experience
in R&D and design, which is greatly improved in aspects of the structure,system and microcomputer control
technology, providing wider operation range of refrigeration and heating, and higher adaptability to applica -
tions with requirements on comfort and technology. There are basic modules of any combination available
for different models, including 66kW, 100kW, 130kW, and at most 16 modules can be connected in parallel,
providing combination products of 66kW - 2080kW.

Excellent Capacity

Units of the same model or different models can be


combined freely. Each group can combine up to 8
modules.

Free master Module Design

Any single unit can operate as the master once con -


nected with the wired controller. It overcomes the
problem that the whole system would fai l to work
properly when the fixed master unit malfunctions.

4
Intelligent Defrosting Technology, Non-stop When Defrosting

The unit control system can determine whether defrosting is nec -


essary according to the ambient temperature in heating mode,
evaporating temperature and running time; when defrosting con -
ditions are met, the unit will automatically activate the defrosting
program to complete defrosting within a short time and provide
heating operation efficiency up to over 90% , ensuring the opti -
mum heating capacity and high EER.

Intelligent Air Volume Management

The shared duct system is adopted to greatly expand the operat -


ing range. The single-module unit can automatically increase or
reduce fans based on the ambient temperature to achieve opti -
mal matching between air volume and load and deliver outstand -
ing performance.

Intelligent Energy Management Technology

Unique intelligent energy regulation technology in multi-module


combination ensures that each module loads or unloads a refrig -
erant circuit before loading or unloading other refrigerant circuits
in the single module, thereby providing higher efficiency, stability
and IPLV.

Widely Operation Range

Low temperature cooling


5°C- 48°C
High temperature heating
-15°C- 48°C

5
Compact Design And Smaller Footprint

Unique and compact structure results in small size and occupied


area, significant reductions in installation space and cost; the unit
is compact and easy to install. A 130KW unit covers floor space
of only 2.42m2, a 50% reduction compared to its equivalents.

Reliable Hermetic Scroll Compressor

Unit adopt Reliable hermetic scroll compressor, which is high-ef -


ficient,energy saving and operates stablely, with low noise,slight
vibration and long service life.

V-Shaped Condenser

The v-shaped condenser has used an integral reinforcing metal


frame, internal thread and triple anti-frosting features (patented
design of open-window hydrophilic aluminum foil + bottom ele -
vated + one-way valve), providing higher structural stability and
corrosion resistance; with heat exchange efficiency improved
through full use of heat exchange area, low tendency to dust ac -
cumulation and frosting in winter, low loss of pressure, smoother
drainage and higher re liability.

Efficient Shell And Tube Heat Exchanger

The waterside efficient shell and internal thread heat exchanger


is of helical baffle type, with better heat transfer performance and
higher resistance to freezing than plate heat exchanger, lower
water resistance and lower requirements for water quality.

6
Saw-shaped Condenser Fan Blades

Compared to plastic impellers, the saw-shaped condenser


fan blade provide large air volume, high durability and high air
supply efficiency with low noise.

High Precision Electronic Expansion Valve

The electronic expansion valve achieves 480 regulating range,


supplemented by Carrier's patented precision throttle control
technology to realize dynamic matching in refrigerating sys -
tem, fully improve the optimum efficiency of each component
and ensure the optimum condition of system operation pres -
sure and temperature.

In House Engineered Microprocessor Control

Carrier control panel is fully upgraded based on original con -


trol panels with years of experience in R&D and design, which
combines more functions including phase sequence detec -
tion, current detection , RS-485 communication interface,
delivering stronger performance, utility, standardization, con -
venience and universality. The USB interface is also provided
to facilitate later-stage maintenance and upgrade of control
function. The panel is supplemented by Carrier developed
control program which offers full operation control and multi -
ple safety protection functions.

Multiple Protection Functions, Providing Safety And Reliable

The unit has multiple safety protection functions which en -


sure safety and stable operation of the unit and systems.
The water flow switch and multiple anti-freezing program
designs protect the unit and systems in an all-round way.

7
Specifications
Model 30RAM201 30RAM401
Power supply V-ph-Hz 380-3-50 380-3-50
Cooling Cooling capacity kW 66 130
Cooling power input kW 21.29 41.9
Cooling current A 37.9 75.5
Maximum power input kW 30.2 57.6
Maximum input current A 50 100
Starting current A 172 266.1
Energy regulation % 0-50-100 0-50-100
Compressor Type - Hermetic scroll compressor
Qty - 2 2
Evaporator Type - High-efficiency shell-and-tube heat excanger
Water flow m3/h 11.4 22.4
Water pressure drop kPa 45 45
Connection pipe
- DN65 (Flange)
dimension
Fan Qty - 2 2
Air flow m3/h 28000 48000
Current A 2.35 5.3
Power kW 1.13 2.2
Unit dimensions (L*W*H) mm 2200×860×2000 2200×1100×2205
Packaging dimensions (L*W*H) mm 2260×920×2000 2260×1160×2205
Net weight kg 570 850
Operating weight kg 630 950
Refrigerant Type - R410A R410A

Combined Capacity Parameter Table


Model and
modular 30RAM201 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
quantity
Cooling
kW 66 132 198 264 330 396 462 528 594 660 726 792 858 924 990 1056
capacity
m3/h 11.4 22.8 34.2 45.6 57 68.4 79.8 91.2 102.6 114 125.4 136.8 148.2 159.6 171 182.4
volume

Model and
modular 30RAM401 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
quantity
Cooling
kW 130 260 390 520 650 780 910 1040 1170 1300 1430 1560 1690 1820 1950 2080
capacity
m3/h 22.4 44.8 67.2 89.6 112 134.4 156.8 179.2 201.6 224 246.4 268.8 291.2 313.6 336 358.4
volume

Maximum Maximum
Compressor Main Board
Model Cooling capacity Circulation loop Combination Combination
Number Number
Number Capacity
30RAM201 66 2 2 1 16 1040

30RAM401 130 2 2 1 16 2080

1. Nominal cooling operating conditions:leaving water temperature 7°C, ambient temperature 35°C; Nominal heating operating conditions: leaving water
temperature 45°C ,outdoor dry bulb temperature 7°C, wet bulb temperature 6°C.
2. In actual use, the cooling/heating loss should be considered after the in stallation of the system piping, pumps, valve, dirt, etc. about 6%.
3. For other working conditions or capacity parameters, Please contact Carrier offices for cooling ambient condition under 5°C .
4. There will be no further notice if the parameters changes due to product optimization.
5. The units of the same model or different models can be combined freely. Each system can combine up to 16 modules.
6. The controllers need to be ordered separately, including wired controller, communication line, IOM, temperature sensor. Manufacturer reserves the
right to make changes to above specifications without prior notice, please refer to the factory configuration when purchasing.

8
Ambient Temperature °C
Leaving
Water 5 10 15 20 25 30 35 40 48
Temperature
°C Power Power Power Power Power Power Power Power Power
Cooling Cooling Cooling Cooling Cooling Cooling Cooling Cooling Cooling
input input input input input input input input input

5 1.06 0.72 1.08 0.73 1.09 0.71 1.09 0.78 1.04 0.84 0.99 0.90 0.93 0.97 0.87 1.01 0.80 1.08

7 1.14 0.75 1.16 0.76 1.17 0.74 1.16 0.81 1.11 0.87 1.06 0.93 1.00 1.00 0.94 1.04 0.87 1.11

9 1.21 0.78 1.23 0.79 1.24 0.77 1.23 0.84 1.18 0.90 1.13 0.96 1.07 1.03 1.01 1.07 0.94 1.14

12 1.28 0.81 1.30 0.82 1.31 0.80 1.30 0.87 1.25 0.93 1.20 0.99 1.14 1.06 1.08 1.10 1.01 1.17

15 1.35 0.84 1.37 0.85 1.38 0.83 1.37 0.90 1.32 0.96 1.27 1.02 1.21 1.09 1.15 1.13 1.08 1.20

Note: Above Correction Factor adapt to 30RHM201/301/401XH, 30RHM201HHE, 30RHM201XHR.

9
Example lifting schematic for 30RHM203

The maximun
Main power supply wiring Communication line
operating current
Model
Ground
(A) Phase line Netural line (RVVP) (A×B)
wire
Communication line between
Unit and remote controller is
30RAM201 50 16 10 16 four-Cords telephone wire,
Copper bar cross-sectional
area A×B shall not be less than
30 meters. Communication
square number of Main power
line between different units is
supply wire.
30RAM401 100 50 25 25 2-cords telephone wire, the

5 m.

1. The power supply is 380-415V/3N ~ /50Hz.


2. Q0 and Q1/Q2/Q3 is the circuit breaker. For circuit breaker, select D type.
3. Either Q0 and (Q1/Q2/Q3) can be choosen. Q1 /Q2/Q3 is more convenient for single unit maintenance.
4. During on-site installation, circuit breaker I wire I copper need to be selected according to reality, considering water pump and other load.
5. For installation of copper bar, see electric wiring diagram.
6. Copper bar isn't needed for less than two modules.
7. Terminal port is reserved in the factory, customers need to connect on job site.
8. The unit power supply wiring need to be provided by the user, the main power supply wiring must conform to the national standard of electric and
electric construction.
9. The recommended power wire specifications is 70 C
ࡈ PVC insulated cables in the insulation of the cable laid in the insulation wall, the ambient
ࡈ in the air, 20 C
temperature is (30 C ࡈ underground) when the selection of copper core cable specifications Take the IEC_60364-5-523 wire and cable
ampacity standard), if the actual installation conditions changes, please refer to service manual according to the manufacturer's specifications, wire and
wire laying conditions.
10. The selection of the power wire is closely related with local climate, soil characteristics, cable laying length. Such unit projects are usually designed
by the design institute and subjected to design institute.
11. Communication wire must use STP, prohibited to be mixed with strong electricity.

10
H

Top view

Example lifting schematic for 30RAM20 1

Chain

11
12
Full

13
30RHM201/301/401XH can not conduct the refrigeration when the environment temperature is lower than 5°C. In case
that it is necessary to conduct the cryogenic refrigeration, please indicate it on the purchase order.

14
DAILY MAINTENANCE

Air conditioners are equipment for air conditioning. The users are recommended to record routine operation date of
such equipment and provide regular maintenance.
Before initial service, it is required to check if terminal equipment and other components of the water system work
normally.
When the equipment is used, the following maintenance system is recommended:

Standard maintenance interval


Description of unit maintenance
Quarterly Semi-annual

1. Check if the power line (from the power distribution cabinet to the unit) is loosened or ƾ
damaged.

2. Check if there is any abnormal noise when the unit is in operation. Ɣ

3. Check if the air-side heat exchanger has to be cleaned (dust on the surface, impurities, etc.). Ɣ

he unit and immediately replace


ƾ Ɣ

Note: If necessary, the maintenance system before the equipment is put into service can apply. See Installation
Instructions for each model.

1. Maintenance to be implemented by users: Mandatory inspection items ---•; r ecommended inspection items---
2. Vulnerable parts necessary for maintenance shall be purchased by users from Carrier.
3. The maintenance intervals above are suitable for normal operation, and in case of operation in severe conditions, the interval can be adjusted as required.

15
www.carrier.com
The Manufacturer reserves the right to change any produt specifications without prior notices
Version : 30RAM-11/18
© All Rights Reserved Carrier