0% found this document useful (0 votes)
25 views6 pages

NG Odu Odp1 Ari2 070411 - 1.1 - Ifr - 20220909

Uploaded by

mariam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views6 pages

NG Odu Odp1 Ari2 070411 - 1.1 - Ifr - 20220909

Uploaded by

mariam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

TotalEnergies EP Nigeria Limited

TECHNICAL SERVICES DIRECTORATE


ENGINEERING, CONSTRUCTION & PROJECTS
OML 100 FLARE REDUCTION PROJECT

The document relates to: SMR-100-20-002 - OML100 FLARE REDUCTION PROJECT


Document Title ODP1 - Instrument Datasheets Flow Indicating Tranmitter Page 1 of 6
Rev. Rev. Date St
Document Reference nbr. NG-ODU-ODP1-ARI2-070411 Sector ODP1 Discipline INS
1.1 9-Sep-22 IFR
Site OML100 (ODUDU & FSO UNITY). Syst/Unit NX_NAP Doc Type DTS

Flow Indicating Transmitter


Datasheet

INTERNAL REVIEW
This Documents is…..

Approved Code 1

Approved with Comments Code 2

Rejected Code 3
Date & Signature

Remarks:

1.1 9-Sep-22 Issued for Review W. Ahmed A.Olajide Y.Alege


1.0 12-Aug-22 Issued for Review I.Ajao A.Olajide Y.Alege
Rev. Date Description Issued by Reviewed by Approved by
This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.
TotalEnergies EP Nigeria Limited
TECHNICAL SERVICES DIRECTORATE Engineering,
Construction &
ENGINEERING, CONSTRUCTION & PROJECTS Projects Division
OML 100 FLARE REDUCTION PROJECT
ODP1 - Instrument Datasheets Flow Indicating Tranmitter page: 2/6
Rev. Status Rev. Date SMR/SOR/SIN nbr.
ECP ref. number NG-ODU-ODP1-ARI2-070411 1.1 IFR 9-Sep-22 SMR-100-20-002
Discipline INS Doc. Type DTS (Syst.) Unit NX_NAP

Instr.
S/N DTS number TYPE Class Rev. Remarks
Tag

1 3 Flow Transmitter - Ultrasonic FT-220 1.1

2 4 Flow Transmitter - Ultrasonic FT-230 1.1

3 5 Flow Transmitter - Turbine FT-741 1.1

4 6 Flow Transmitter - Turbine FT-742 1.1

Note 1:

Note 2 :

Note 3:

Note 4 :

Note 5 :

This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.
TotalEnergies EP Nigeria Limited Engineering,
TECHNICAL SERVICES DIRECTORATE Construction &
ENGINEERING, CONSTRUCTION & PROJECTS Projects Division
OML 100 FLARE REDUCTION PROJECT
16376657 The project is currently under leadership of…
SMR100-FRP ENGINEERING TEAM CONSTRUCTION TEAM CW & SURVEY TEAM X PROJECT TEAM

ODP1 - Instrument Datasheets Flow Indicating Tranmitter page: 3/6

COMPANY Rev. Status Rev. Date Discipline INS


NG-ODU-ODP1-ARI2-070411
ref. number: 1.1 IFR 9-Sep-22 Doc. Type DTS
CONTRACTOR ref: - - - (Syst.) Unit NX_NAP
DATASHEET Nbr: PID reference nbr:
NG-ODU-ODP1-ARI2-070411 NG-ODU-ODP1-ARI2-010211

1 Tag Number 10-FT-220

2 P&ID No. NG-ODU-ODP1-ARI2-010211

3 Service Relief Gas

4 Line Number Piping Class Material 12" FH 1036 001 B01 B01 Carbon Steel

5 Line Size Schedule Thickness 12'' Sch, 20 6.35mm


GENERAL

6 NACE Requirement SIL Requirement MR0175 (a)

7 Area Classification Zone-2, Gr. IIA, T3

8 ATEX / IECEx Certification ATEX MARKING Ex II 2G / Ex "d"-IIB T3 Yes

9 Rating 150#

10 End connection(Welded/Flanged/Threaded) Flanged

11 Face (RF/RJ) RF

12 Fluid Phase Hydrocarbon Gas

13 Design Pressure barg 6


GENERAL

14 Minimal Inlet Meter run Minimal Outlet Meter run 5D 3D


o
15 Design Temp. Min. Design Temp. Max. C 55
PROCESS CONDITION

16 Pressure Min Nor m. Max. Barg 0.2


o
17 Temperature C 11.27

18 Viscosity Cp 0.01078

19 Mass Flow Rate Kg/hr 7552

20 Volumetric Flow Rate Am3/hr 7880


GAS

21 Density Kg/m3 0.9584

22 Compressiblity Factor Z 0.9968

23 Molecular Weight g/mol 18.62

24 Connection Type / Material Flanged RF / SS 1.4408 / CF3M

25 Cable Connection Cable Length (a) m (a)

26 Cable Inner Type Material Cable outer/ Material (a) (a)


SENSOR

27 Flow Velocity Min/Max Unit 0.18 /35 (a) m/s (a)

28 Principle of Operation Time of Flight

29 No. of Paths Multiple path

30 Meter Size 12"

31 Flow Calibration Flow Scale Max./Min m3/h (a) m/s (a)

32 Flow Accuracy Flow Repeatability % ± 0.5% of Reading % ± 0.25%

33 Enclousre Material Ingress Protection SS316L IP65 mini


ULTRASONIC FLOW TRANSMITTER

34 power supply/consump. Loop Supply Vm 24V DC Loop powered

35 Analog Output Frequqency Output mA 4-20mA

36 Local Display Unit Yes LCD Nm3/h

37 Intergrated/ Remote Transm. Cable Gland (a) M20


HART Protocol
38 Yes Version 6 or 7

39 Mounting Position Horizontal Orientation, Transmitter head up

40 Intrusive / Non-Intrusive Type Intrusive Type

41 Accuracy ± 0.5% of Reading

42 Repeatability ± 0.25%

43 Sunshade Yes
PURCH

44 Manufacturer Model Endress + Hauser Prosonic Flow G500


AS E

45 Purchase Order Number VTA


Note:
(a). Vendor to Advise VTC = Vendor to confirm

This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.
TotalEnergies EP Nigeria Limited Engineering,
TECHNICAL SERVICES DIRECTORATE Construction &
ENGINEERING, CONSTRUCTION & PROJECTS Projects Division
OML 100 FLARE REDUCTION PROJECT
16376657 The project is currently under leadership of…
SMR100-FRP ENGINEERING TEAM CONSTRUCTION TEAM CW & SURVEY TEAM X PROJECT TEAM

ODP1 - Instrument Datasheets Flow Indicating Tranmitter page: 4/6

COMPANY Rev. Status Rev. Date Discipline INS


NG-ODU-ODP1-ARI2-070411
ref. number: 1.1 IFR 9-Sep-22 Doc. Type DTS
CONTRACTOR ref: - - - (Syst.) Unit NX_NAP
DATASHEET Nbr: PID reference nbr:
NG-ODU-ODP1-ARI2-070411 NG-ODU-ODP1-ARI2-010211

1 Tag Number 10-FT-230

2 P&ID No. NG-ODU-ODP1-ARI2-010211

3 Service Relief Gas

4 Line Number Piping Class Material 6" FL 1036 002 B01 B01 Carbon Steel

5 Line Size Schedule Thickness 6'' STD 7.11mm


GENERAL

6 NACE Requirement SIL Requirement MR0175 (a)

7 Area Classification Zone-2, Gr. IIA, T3

8 ATEX / IECEx Certification ATEX MARKING Ex II 2G / Ex "d"-IIB T3 Yes

9 Rating 150#

10 End connection(Welded/Flanged/Threaded) Flanged

11 Face (RF/RJ) RF

12 Fluid Phase Hydrocarbon Gas

13 Design Pressure barg 5


GENERAL

14 Minimal Inlet Meter run Minimal Outlet Meter run 5D 3D


o
15 Design Temp. Min. Design Temp. Max. C 55
PROCESS CONDITION

16 Pressure Min Nor m. Max. Barg 0.1


o
17 Temperature C 19.44

18 Viscosity Cp 0.01095

19 Mass Flow Rate Kg/hr 80.31

20 Volumetric Flow Rate Am3/hr 78.33


GAS

21 Density Kg/m3 1.025

22 Compressiblity Factor Z 0.9962

23 Molecular Weight g/mol 22.32

24 Connection Type / Material Flanged RF / SS 1.4408 / CF3M

25 Cable Connection Cable Length (a) m (a)

26 Cable Inner Type Material Cable outer/ Material (a) (a)


SENSOR

27 Flow Velocity Min/Max Unit 0.18 /35 (a) m/s (a)

28 Principle of Operation Time of Flight

29 No. of Paths Multiple path

30 Meter Size 6"

31 Flow Calibration Flow Scale Max./Min m3/h (a) m/s (a)

32 Flow Accuracy Flow Repeatability % ± 0.5% of Reading % ± 0.25%

33 Enclousre Material Ingress Protection SS316L IP65 mini


ULTRASONIC FLOW TRANSMITTER

34 power supply/consump. Loop Supply Vm 24V DC Loop powered

35 Analog Output Frequqency Output mA 4-20mA

36 Local Display Unit Yes LCD Nm3/h

37 Intergrated/ Remote Transm. Cable Gland (a) M20


HART Protocol
38 Yes Version 6 or 7

39 Mounting Position Horizontal Orientation, Transmitter head up

40 Intrusive / Non-Intrusive Type Intrusive Type

41 Accuracy ± 0.5% of Reading

42 Repeatability ± 0.25%

43 Sunshade Yes
PURCH

44 Manufacturer Model Endress + Hauser Prosonic Flow G500


AS E

45 Purchase Order Number VTA


Note:
(a). Vendor to Advise VTC = Vendor to confirm

This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.
TotalEnergies EP Nigeria Limited Engineering,
TECHNICAL SERVICES DIRECTORATE Construction &
ENGINEERING, CONSTRUCTION & PROJECTS Projects Division
OML 100 FLARE REDUCTION PROJECT
16376657 The project is currently under leadership of…

SMR100-FRP ENGINEERING TEAM CONSTRUCTION TEAM CW & SURVEY TEAM X PROJECT TEAM

ODP1 - Instrument Datasheets Flow Indicating Tranmitter page: 5/6


COMPANY Rev. Status Rev. Date Discipline INS
NG-ODU-ODP1-ARI2-070411
ref. number: 1.1 IFR 9-Sep-22 Doc. Type DTS
CONTRACTOR ref: - (Syst.) Unit 6X
DATASHEET Nbr: PID reference nbr:
NG-ODU-ODP1-ARI2-070411 NG-ODU-ODP1-ARI2-010211
1 Tag Number 10-FT-741
2 Service Nitrogen Purge Flow Measurement to ODP1 Flare Header
3 Equipment Function
4 Line Number / Piping Class / Material 1'' NG 1074 001 B01 B01 Carbon Steel
GENERAL 5 Pipe O.D. / Schedule / Thickness 33.4 mm XS 4.55 mm
6 Line Size 1"
7 Area Classification Zone-2, Gr. IIA, T3
8 NACE Requirement SIL Requirement MR0175 Note 2
9 ATEX / IECEx Certification ATEX MARKING Ex II 2G / Ex "d"-IIB T3 Yes
10 Process Fluid Fluid State Nitrogen Gas
11 Volume Flow Rate Am3/hr Mass Flow Rate Kg/hr 0.95 (HOLD 1) 2 (Note 1)
12 Inlet Pressure bar-g Min./Oper./Max. 0.5 0.7 1.0
o
13 Temperature C Min./Oper./Max. AMB 30 (HOLD 1) 40 (HOLD 1)
14 Base Spec. Gravity Oper. Spec. Gravity
PROCESS
15 Molecular Weight Viscosity @ Oper. cP 28.0 0.01 (HOLD 1)
CONDITIONS
16 Quality Superheat
17 Compressiblity Factor Z 0.99 (HOLD 1)
18 Percent Solids
19 Design Pressure / Temperature / Oper. Density 12 Barg 60oC (HOLD 1) 1.92 (HOLD 1)
20 Minimal Inlet Meter run Minimal Outlet Meter run 5D 3D
21 Element Type Flat Blade Turbine
22 Integrated flow straightener Yes
23 End Conn. Size & Type 1/2" RF Flanged
24 End Conn. Rating CL150
25 Nominal Flow Range m3/hr VTA
26 Accuracy ± 0.5% of Reading
27 Linearity % Repeatability % (VTA) ± 0.25%
28 K Factor (cycles per unit volume) VTA
29 Excitation VTA
30 Body Material 316L SS
31 Support Material 316L SS
METER 32 Shaft Material AISI 316 or 316L SS
33 Flange Material 316L SS
34 Rotor Material AISI 316 or 316L SS
35 Bearing Material Tungsten Carbide
36 Bearing Type Ball
37 Maximum Speed RPM VTA
38 Minimum Output Voltage VTA
39 Pick-Up Type & Quantity Magnetic, Two (2)
40 Ingress Protection IP65 minimum
41 Pressure Drop 0.21 - 0.34 Bar (VTC)
42 Temperature & Pressure Rating VTA
43 Over Speed Protection / Reverse Flow Protection / Shocks Protection Yes Yes Yes
44 Function Indicate, Transmit
45 Pre-Amplifier Yes
46 Mounting Remote on 2" Pipe, with 316 SS Bracket
47 Supply Voltage Electrical Connection 24V DC, Loop-powered M20 x 1.5
48 Scale Range VTA
49 Output Range SMm3/d VTA
OPTIONS
50 Temperature Compensation No
51 Preset Counter MFR. STD.
52 Strainer Size & Mesh Provided by Other
53 Totalizer No
54 Transmitter Housing Material / Output 316L SS / 4-20 mA, HART
55 Sunshade Yes
56 Manufacturer Faure Herman
57 Model No. VTA
PURCHASE
58 Purchase Order Num. VTA
59 Serial Number VTA
NOTES:
1) Maximum =13 kg/h (initial sweeping of air during start-up
2) VTA = Vendor to Advice
3) VTC = Vendor to Confirm

HOLDS:
1) To be confirmed with Nitrogen Generator Package vendor data

This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.
TotalEnergies EP Nigeria Limited Engineering,
TECHNICAL SERVICES DIRECTORATE Construction &
ENGINEERING, CONSTRUCTION & PROJECTS Projects Division
OML 100 FLARE REDUCTION PROJECT
16376657 The project is currently under leadership of…

SMR100-FRP ENGINEERING TEAM CONSTRUCTION TEAM CW & SURVEY TEAM X PROJECT TEAM

ODP1 - Instrument Datasheets Flow Indicating Tranmitter page: 6/6


COMPANY Rev. Status Rev. Date Discipline INS
NG-ODU-ODP1-ARI2-070411
ref. number: 1.1 IFR 9-Sep-22 Doc. Type DTS
CONTRACTOR ref: - (Syst.) Unit 6X
DATASHEET Nbr: PID reference nbr:
NG-ODU-ODP1-ARI2-070411 NG-ODU-ODP1-ARI2-010211
1 Tag Number 10-FT-742
2 Service Nitrogen Purge Flow Measurement to 6" FS 2015 B51
3 Equipment Function
4 Line Number / Piping Class / Material 1'' NG 1074 003 B01 B01 Carbon Steel
GENERAL 5 Pipe O.D. / Schedule / Thickness 33.4 mm XS 4.55 mm
6 Line Size 1"
7 Area Classification Zone-2, Gr. IIA, T3
8 NACE Requirement SIL Requirement MR0175 Note 2
9 ATEX / IECEx Certification ATEX MARKING Ex II 2G / Ex "d"-IIB T3 Yes
10 Process Fluid Fluid State Nitrogen Gas
11 Volume Flow Rate Am3/hr Mass Flow Rate Kg/hr 0.95 (HOLD 1) 2 (Note 1)
12 Inlet Pressure bar-g Min./Oper./Max. 0.5 0.7 1.0
o
13 Temperature C Min./Oper./Max. AMB 30 (HOLD 1) 40 (HOLD 1)
14 Base Spec. Gravity Oper. Spec. Gravity
PROCESS
15 Molecular Weight Viscosity @ Oper. cP 28.0 0.01 (HOLD 1)
CONDITIONS
16 Quality Superheat
17 Compressiblity Factor Z 0.99 (HOLD 1)
18 Percent Solids
19 Design Pressure / Temperature / Oper. Density 12 Barg 60oC (HOLD 1) 1.92 (HOLD 1)
20 Minimal Inlet Meter run Minimal Outlet Meter run 5D 3D
21 Element Type Flat Blade Turbine
22 Integrated flow straightener Yes
23 End Conn. Size & Type 1/2" RF Flanged
24 End Conn. Rating CL150
25 Nominal Flow Range m3/hr VTA
26 Accuracy ± 0.5% of Reading
27 Linearity % Repeatability % (VTA) ± 0.25%
28 K Factor (cycles per unit volume) VTA
29 Excitation VTA
30 Body Material 316L SS
31 Support Material 316L SS
METER 32 Shaft Material AISI 316 or 316L SS
33 Flange Material 316L SS
34 Rotor Material AISI 316 or 316L SS
35 Bearing Material Tungsten Carbide
36 Bearing Type Ball
37 Maximum Speed RPM VTA
38 Minimum Output Voltage VTA
39 Pick-Up Type & Quantity Magnetic, Two (2)
40 Ingress Protection IP65 minimum
41 Pressure Drop 0.21 - 0.34 Bar (VTC)
42 Temperature & Pressure Rating VTA
43 Over Speed Protection / Reverse Flow Protection / Shocks Protection Yes Yes Yes
44 Function Indicate, Transmit
45 Pre-Amplifier Yes
46 Mounting Remote on 2" Pipe, with 316 SS Bracket
47 Supply Voltage Electrical Connection 24V DC, Loop-powered M20 x 1.5
48 Scale Range VTA
49 Output Range SMm3/d VTA
OPTIONS
50 Temperature Compensation No
51 Preset Counter MFR. STD.
52 Strainer Size & Mesh Provided by Other
53 Totalizer No
54 Transmitter Housing Material / Output 316L SS / 4-20 mA, HART
55 Sunshade Yes
56 Manufacturer Faure Herman
57 Model No. VTA
PURCHASE
58 Purchase Order Num. VTA
59 Serial Number VTA
NOTES:
1) Maximum =13 kg/h (initial sweeping of air during start-up
2) VTA = Vendor to Advice
3) VTC = Vendor to Confirm

HOLDS:
1) To be confirmed with Nitrogen Generator Package vendor data

This document is the property of TOTAL and must not be reproduced, stored or disclosed without permission from COMPANY.

You might also like