Version 4
Released in September 2022
Dr.-Ing. habil. Jigou Liu Technologies GmbH & Co KG
Split Core Hall Effect DC Current Sensor CYHCT-C2TV
This Hall Effect current sensor is based on open loop principle and designed with a split core and a high
galvanic isolation between primary conductor and secondary circuit. It can be used for measurement of DC
current etc. The output of the transducer reflects the real wave of the current carrying conductor.
Product Characteristics Applications
Photovoltaic equipment
Excellent accuracy
Frequency conversion timing equipment
Very good linearity
Various power supply
Light in weight
Uninterruptible power supplies (UPS)
Less power consumption
Electric welding machines
Window structure
Numerical controlled machine tools
Electrically isolating the output of the transducer
Electrolyzing and electroplating equipment
from the current carrying conductor
Electric powered locomotive
No insertion loss
Microcomputer monitoring
Current overload capability
Electric power network monitoring
Electrical Data/Input
Primary Nominal Primary Current DC Output Voltage Part number
DC Current Ir (A) Measuring Range Ip(A) (V) (see application notes on page 4)
25A 0 ~ ±25A CYHCT-C2TV-U/B025A-xnC
30A 0 ~ ±30A CYHCT-C2TV-U/B030A-xnC
40A 0 ~ ±40A x=0: 0-4V ±1.0% CYHCT-C2TV-U/B040A-xnC
50A 0 ~ ±50A x=3: 0-5V ±1.0% CYHCT-C2TV-U/B050A-xnC
100A 0 ~ ±100A x=8: 0-10V ±1.0% CYHCT-C2TV-U/B100A-xnC
200A 0 ~ ±200A CYHCT-C2TV-U/B200A-xnC
300A 0 ~ ±300A CYHCT-C2TV-U/B300A-xnC
400A 0 ~ ±400A CYHCT-C2TV-U/B400A-xnC
500A 0 ~ ±500A CYHCT-C2TV-U/B500A-xnC
600A 0 ~ ±600A CYHCT-C2TV-U/B600A-xnC
(n=2, Vcc= +12VDC; n=3, Vcc =+15VDC; n=4, Vcc =+24VDC, U: unidirectional, B: bidirectional)
(Connector: Molex connector C=M; Phoenix Connector: C=P, Cable connection: C=S)
Supply Voltage: Vcc=+12V, +15V, +24V 5%
Current Consumption Ic < 25mA
Isolation Voltage 2.5kV, 50/60Hz, 1min
Output Voltage at Ir, TA=25°C: Vout =0- 4V, 0-5V, 0-10VDC
Output Impedance: Rout < 150
Load Resistor: RL > 10k
Accuracy
Accuracy at Ir, TA=25°C, X <1.0% FS
Linearity from 0 to Ir, TA=25°C, EL <1.0% FS
Electric Offset Voltage, TA=25°C, Voe <50mV
Magnetic Offset Voltage (Ir 0) Vom <20mV
Thermal Drift of Offset Voltage, Vot <±1.0mV/°C
Thermal Drift (-10°C to 50°C), T.C. < 0.1% /°C
Response Time at 90% of IP (f=1k Hz) tr < 1ms
Frequency Bandwidth (-3dB), fb = DC - 20 kHz
Markt Schwabener Str. 8 Tel.: +49 (0)8121 – 2574100
D-85464 Finsing Fax: +49 (0)8121– 2574101
Germany Email:
[email protected] http://www.cy-sensors.com
Version 4
Released in September 2022
Dr.-Ing. habil. Jigou Liu Technologies GmbH & Co KG
Case Material: PBT
Ambient Operating Temperature, TA = -25°C ~ +85°C
Ambient Storage Temperature, TS =-40°C ~ +100°C
PIN Definition and Dimensions
Current
direction
OFS
OFS GIN
GIN 端子 接线
+G OG
+ +24V
G 地
7.5 1(+):O 输出
Vcc
2(G):G GND
地
3(O): Output
4(G): GND
OFS: Offset Adjustment GIN: Gain Adjustment
Connection
Vcc: +12V, +15V, +24VDC
GND
CYHCT-
C2TV Output
Vo V
GND
o
Markt Schwabener Str. 8 Tel.: +49 (0)8121 – 2574100
D-85464 Finsing Fax: +49 (0)8121– 2574101
Germany Email:
[email protected] http://www.cy-sensors.com
Version 4
Released in September 2022
Dr.-Ing. habil. Jigou Liu Technologies GmbH & Co KG
Cable Connection
Red: Vcc: +12V, +15V, +24VDC
Blue: GND
CYHCT-
C2TV Yellow: Output
Vo V
Black: GND
o
Wire Arrangement:
Red: Vcc: +12V, +15V, +24VDC
Blue: GND (ground)
Yellow: Vo (Voltage output)
Black: GND (ground)
Notes:
1. Connect the terminals of power source, output respectively and correctly, never make wrong
connection.
2. Two potentiometers can be adjusted, only if necessary, by turning slowly to the required accuracy with
a small screwdriver.
3. The best accuracy can be achieved when the window is fully filled with bus-bar (current carrying
conductor).
4. The in-phase output can be obtained when the direction of current of current carrying conductor is the
same as the direction of arrow marked on the transducer
Markt Schwabener Str. 8 Tel.: +49 (0)8121 – 2574100
D-85464 Finsing Fax: +49 (0)8121– 2574101
Germany Email:
[email protected] http://www.cy-sensors.com
Version 4
Released in September 2022
Dr.-Ing. habil. Jigou Liu Technologies GmbH & Co KG
Application Notes
1) Part number CYHCT-C2TV-U/BxxxA-xnC
U: unidirectional input current; B: bidirectional input current; xxx: current value; x: output voltage (x=0: 0-4V
±1.0%; x=3: 0-5V ±1.0%; x=8: 0-10V ±1.0%); n: power supply (n=2, Vcc= +12VDC; n=3, Vcc =+15VDC;
n=4, Vcc =+24VDC,); C: Connector (Molex connector C=M; Phoenix Connector: C=P)
Example 1: CYHCT-C2TV-U100A-32M Hall Effect DC Current sensor with
Output signal: 0 – 5V DC
Power supply: +12V DC
Rated input current: 0 - 100A DC (unidirectional)
Connector: Molex connector
Example 2: CYHCT-C2TV-B100A-84P Hall Effect DC Current sensor with
Output signal: 0 – 10V DC
Power supply: +24V DC
Rated input current: -100A - 0 - +100A DC (bidirectional)
Connector: Phoenix connector
2) Relation between Input current and output signal
Current Sensor CYHCT-C2TV-U100A-32M
Input current (A) Output voltage Vo (V)
0 0
25 1.25
50 2.5
75 3.75
100 5
Current Sensor CYHCT-C2TV-B100A-84P
Input current (A) Output voltage Vo (V)
-100 0
-75 1.25
-50 2.5
-25 3.75
0 5
25 6.25
50 7.5
75 8.75
100 10
Markt Schwabener Str. 8 Tel.: +49 (0)8121 – 2574100
D-85464 Finsing Fax: +49 (0)8121– 2574101
Germany Email:
[email protected] http://www.cy-sensors.com
Version 4
Released in September 2022
Dr.-Ing. habil. Jigou Liu Technologies GmbH & Co KG
DIN Rail Adapter CY-DRA88
The DIN Rail Adapter CY-DRA88 is designed for mounting the sensor on 35mm DIN Rail. It has
the size 70 x 24 x 23mm. The height from bottom to mounting surface is 14.8mm.
14.8
35.5
Markt Schwabener Str. 8 Tel.: +49 (0)8121 – 2574100
D-85464 Finsing Fax: +49 (0)8121– 2574101
Germany Email:
[email protected] http://www.cy-sensors.com
Version 4
Released in September 2022
Dr.-Ing. habil. Jigou Liu Technologies GmbH & Co KG
Mounting of Sensors
Sensor with Molex Connector
(The distance between the bottom und the middle of hole is 54.8mm)
Sensor with Phoenix Connector
(The distance between the bottom und the middle of hole is 54.8mm)
Markt Schwabener Str. 8 Tel.: +49 (0)8121 – 2574100
D-85464 Finsing Fax: +49 (0)8121– 2574101
Germany Email:
[email protected] http://www.cy-sensors.com