FWC-F - IM - en - 07 - Installation Manuals - English
FWC-F - IM - en - 07 - Installation Manuals - English
MANUAL
Models
FWC02AAFNMV1
FWC03AAFNMV1
FWC04AAFNMV1
FWC05AAFNMV1
FWC06AAFNMV1
OUTLINE AND DIMENSIONS
English
Indoor Unit: FWC02AAFNMV1 / FWC03AAFNMV1 / FWC04AAFNMV1 / FWC05AAFNMV1 /
FWC06AAFNMV1
B C F
D E H
G
J
A
I
K
Model A B C D E F G H I J K
FWC02AAFNMV1 820 820 363 335 28 930 930 642 622 555 555
FWC03AAFNMV1 820 820 363 335 28 930 930 642 622 555 555
FWC04AAFNMV1 820 820 363 335 28 930 930 642 622 555 555
FWC05AAFNMV1 820 820 363 335 28 930 930 642 622 555 555
FWC06AAFNMV1 820 820 363 335 28 930 930 642 622 555 555
ACCESS VALVE 1
ACCESS VALVE 2
WATER OUTLET 2
WATER INLET 2
WATER INLET 1
WATER OUTLET 1
Note:
• Water Inlet 1* must couple with Water Outlet 1 and Access Valve 1. (*1 connection to chiller)
• Water Inlet 2* must couple with Water Outlet 2 and Access Valve 2. (*2 connection to Boiler)
• Valve cap of Access Valve 1 is painted red for indentification.
• All union joints are to be screwed in together with an “O” -ring. Apply Teflon white tape on the screw threads to ensure
leak proof joints.
• Secure all screw connection tightly to prevent leakage.
1
SAFETY PRECAUTIONS
! WARNING ! CAUTION
• Installation and maintenance should be performed by Please take note of the following important points when
qualified persons who are familiar with local code and installing.
regulation, and experienced with this type of appliance. • Ensure that te drainage piping is connected properly.
• All field wiring must be installed in accordance with the If the drainage piping is not connected properly, it may
national wiring regulation. cause water leakage which will dampen the furniture.
• Ensure that the rated voltage of the unit corresponds to • Ensure that the unit’s panel is closed after service or
that of the name plate before commencing wiring work
installation.
according to the wiring diagram.
• The unit must be GROUNDED to prevent possible hazard Unsecured panels will cause the unit to operate noisily.
due to insulation failure. • Air swing connector and LED wire connector shall be
• All electrical wiring must not touch the water piping or inside the control box.
any moving parts of the fan motors.
• Confirm that the unit has been switched OFF before • Sharp edges and coil surfaces are potential locations which
installing or servicing the unit. may cause injury hazards. Avoid from being in contact
• Risk of electric shock, can cause injury or death. with these places.
Disconnect all remain electric power supplies before
• Before turning off the power supply set the remote
servicing.
• DO NOT pull out the power cord when the power is ON. controller’s ON/OFF switch to the “OFF” position to
This may cause serious electrical shocks which may result prevent the nuisance tripping of the unit. If this is not done,
in the fire hazards. the unit’s fans will start turning automatically when power
• Keep the indoor and outdoor units, power cable and resumes, posing a hazard to service personnel or the user.
transmission wiring, at least 1m from TVs and radios, to • Do not operate any heating apparatus too close to the air
prevent distorted pictures and static. {Depending on the conditioner unit. This may cause the plastic panel to melt or
type and source of the electrical waves, static may be heard deform as a result of the excessive heat.
even when more than 1m away}. • Ensure the color of wires of the outdoor unit and the
terminal markings are same to the indoors respectively.
• IMPORTANT : DO NOT INSTALL OR USE THE AIR
CONDITIONER UNIT IN A LAUNDRY ROOM.
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not
be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant,
of oil and of other parts must be done by a qualified installer in accordance with relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this
product is disposed of correctly, you will help to prevent potential negative consequences for the environment and
human health. Please contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local
and national legislation.
2
INSTALLATION OF THE INDOOR UNIT
English
1. Preliminary Site Survey
Beam
Max. 0.3 m
Min. 1.0 m
Obstacle
Floor
• Electrical supply and installation is to conform to local authority’s (e.g. National Electrical Board) codes and regulations.
• Voltage supply fluctuation must not exceed ±10% of rated voltage. Electricity supply lines must be independent of welding
transformers which can cause high supply fluctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
• The indoor unit must be installed in such that is free from any obstacles in path of cool air discharge and warm air return, and must
allow spreading of air throughout the room (near the center of the room)
• Provide clearance for the indoor unit from the wall and obstacles as shown in the figure.
• The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid amplifying noise and
vibration.
• The installation place (hanging ceiling surface) must be levelled and the height in the ceiling is 350mm or more.
• The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).
2. Unit Installation
890.0 mm (Ceiling Board Opening)
• Measure and mark the position for the hanging rod. Drill the hole for the
790.0 mm (Hanging Rod)
angle nut on the ceiling and fix the hanging rod.
3. Unit Hanging
• Confirm the pitch of the hanging rod.
• Hold the unit and hang it on the hanging rod with the nut and washer.
• Adjust the unit height to 35.0mm between the indoor unit bottom surface
and the ceiling surface.
• Confirm with a level gauge that the unit is installed horizontally and Indoor Unit
tighten the nut and bolt to prevent unit failing and vibration. Ceiling
• Open the ceiling board along the outer edge of the paper installation Board
template. 35.0 mm
3
5. Drain Test Feed Water
• Connect the main drain pipe to the flexible drain.
• Feed water from flexible drain hose to check the piping for leakage. Main Drain Pipe
• When the test is completed, connect the flexible drain hose to the drain
connector on the indoor unit.
Note: This Indoor Unit uses a drain pump for condensed water drainage Flexible Drain Hose
Install the unit horizontally to prevent water leakage or condensation
around the air outlet.
Gate Valve 3 Way Valve Gate Valve 2 Way Valve Gate Valve
7. Panel Installation
• Be sure to remove the installation template before installing the front panel.
• Open the air intake grille by pulling back the catchers and removing it together with
filter from panel.
• Install the front frame panel onto the indoor unit by 4 screws and tighten it completely
to prevent cool air leakage. OPEN
• Connect the LED wire and air swing wire to the indoor unit.
Note:
Install the front panel firmly to prevent cool air leakage which will cause condensation
and water dripping
LED Wire
From From
Front Control
Panel Box
Screw
4
ELECTRICAL WIRING CONNECTION
English
This is a proposed wiring connection. It may change subject to the chiller unit and must comply with local and national code and
regulations.
PART NO: 70034071317-02
FCU 1 FCU 2 FCU 3
HVLV CVLV L/L1 N/L2 N/L2 HVLV CVLV L/L1 N/L2 N/L2 HVLV CVLV L/L1 N/L2 N/L2
R
S
T
N
X1 X2 X3
G/Y
PUMP
WIRED
CONTROLLER
LED/IR RECEIVER
BLUE
LEVEL SWITCH
BLUE
POWER
SUPPLY
AUX.
CONTACT
BLACK
HTR
N
RED
BLACK
PURPLE
WHITE
ORANGE (FM)
PURPLE (FH)
BROWN (FL)
AIR SWING
G/Y
RED
MOTOR
BLACK
WHITE
RED BLACK
G/Y G/Y
RED
5
OPERATING RANGE
Operating Limits:
Thermal carrier : Water
Water temperature : 5 ~65°C
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode Heating Mode
Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F
Minimum indoor Minimum indoor
temperature 16.0 / 60.8 11.0 / 51.8 temperature 16.0 / 60.8 -
Maximum indoor Maximum indoor
temperature 32.0 / 89.6 23.0 / 73.4 temperature 30.0 / 86.0 -
Minimum outdoor Minimum outdoor
temperature 16.0 / 60.8 - temperature -5.0 / 23.0 -6.0 / 21.2
Maximum outdoor Maximum outdoor
temperature 46.0 / 114.8 - temperature 24.0 / 75.2 18.0 / 64.4
ACCESSORY PARTS
• The indoor unit is provided with air discharge and air intake “knock-out” hole for duct connection. However the connection of the
short duct for air discharge is possible on one side only.
• The use of short duct for air discharge will improve airflow distribution if there is an obstruction (such as a lighting fixture) or in
a long, narrow room or an L-shaped room. It is also use for air conditioning of two rooms simultaneously.
Possible Direction For Air Discharge And Air Intake Possible Opening Dimension For Duct Connection
Air Discharge Air Discharge
PCD Ø140
10 50 50 50 50 50 10
20
Ø100
90
70
20
115 20 115
119
109
Note:
• Avoid using the short duct on which the air discharge grille can be completely closed, to prevent evaporator freezing.
• In order to prevent condensation forming, be sure that there is sufficient thermal insulation and no leakage of cool air when
installing the short duct.
• Keep the introduction of fresh air intake within 20% of total air flow. Also provide a chamber and use a booster fan.
Sealing Material
• It is possible to seal one of the four air discharge outlet. (Sealing two or more air discharge outlet could cause a malfunction.)
• Remove the front panel and insert the sealing material into the air discharge outlet on the indoor unit to seal the air outlet.
• The sealing material is the same length as the longer air discharge outlet. If it is desired to seal the shorter air discharge outlet, cut
the sealing material to shorten it.
• Push the sealing material in about 10mm beyond the bottom surface of the indoor unit so that it does not touch the air louver.
• Be sure not to push the sealing material in any further than about 10mm.
6
INDICATOR LIGHTS
English
Remote Control
When there is infrared remote control operating signal, the signal receiver on indoor unit will made a <beep> for signal acceptance
confirmation.
Error Description Cool LED Error Indication
Room sensor error 1 blink E1
Pipe water sensor error 2 blinks E2
Water pump error 6 blinks E6
Pipe water temperature fault 5 blinks E5
*Window open activated 3 blinks -
*Antifreeze mode activated 7 blinks -
*Load shedding activated 8 blinks -
*Only applicable for 4-pipe system
COMP
TRANSFORMER
M3 Model 3
M4
Model 4
The standard controller board ( W 2.0 ) comes with a default setting for model selection :- Model 4. Please select the model accordingly
by using the jumper.
System Model Function
4 Pipe M3 - Cooling Only with Boiler
FCU Boiler
FCU Boiler
7
B) VALVE, HEAT AND FAN PRIORITY SELECTION
HTR
TRANSFORMER
With Jumper
Jumper Without Jumper
(Default)
Fan Priority Jumper User set speed or lower fan if auto Fan Stop when thermostat cut off
mode is selected
Heat Jumper For Heat pump For Cooling only
Valve Jumper For valve control For valveless control
C ) OTHERS
L
UNOCP A_FRZ W_OPEN TFULL
Unoccupied Mode
HTR
Anti Freeze Mode
TRANSFORMER
SHED
i) Unoccupied Mode
If the dry contact is closed , the Unoccupied mode is activated and vise versa. When Timer On is active, system goes back to Occupied
mode.
The dry contact connection points can be connected in parallel with other fan coil unit ( FCU ) boards. If the dry contact is closed,
Unoccupied mode will be activated on all the fan coil units which are connected in parallel as shown in figure above.
8
ii) Anti Freeze Mode
English
Anti Freeze operation has the highest priority among all unit operation. Anti Freeze operation will be activated only if dry contact is
closed and vice versa.
GLOBAL
SW SWITCH
Global Unoccupied, Global Window Open and Global Load Shedding operation could also be activated via the network communication
bus line by the master controller with or without the above connection. (Depends on availability for this feature.)
Note:
i) Auto Fan Mode is only applicable in model 3 only . ( Cooling only with Boiler ).
ii) Fan mode is not available in valveless control.
iii) Wired handset has an indoor room sensor. Avoid locating the wired handset at isolated places where room temperature reading
will be inaccurate.
OVERALL CHECKING
Note:
• The installation guide above covers only the fan coil unit. For installation of outdoor (mini chiller etc) please refer to the
installation guide for such unit.
• The installation of fan coil unit may vary according to the type of outdoor unit.
• Installation must be done by qualified personnel who is familiar with this type of product.
9
SERVICE AND MAINTENANCE
Indoor air filter 1. Remove any dust adhered on the filter by using a vacuum cleaner or At least once every
wash in lukewarm water (below 40ºC) with neutral cleaning detergent. 2 weeks.
2. Rinse the filter well and dry before placing it back into the unit. More frequently if necessary.
3. Do not use gasoline, volatile substances or chemical to clean the filter.
TROUBLESHOOTING
When any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit.
Check the following fault conditions and causes for some simple troubleshooting tips.
10
MEMO
Head office: Zandvoordestraat 300, B-8400 Oostende, Belgium
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/