E2 INTRODUCTION
E
E5 OUTRWALL®
E9 BRICK VENEER WALLS
E 10 FIRECLAD®
EXTERNAL WALLS
INTRODUCTION
The following USG Boral external wall systems are outlined
DESIGN OPTIONS
in this manual:
USG Boral OutRwall comprises a range of lightweight external
• OutRwall®
wall systems utilising fire resistant or non-fire resistant internal
• Brick Veneer linings and, if required, water- and fire-resistant plasterboard
• Fireclad®. linings between lightweight external cladding and wall frame.
USG Boral OutRwall external wall systems utilise lightweight OutRwall systems can be used with any type of approved
external cladding and plasterboard linings direct fixed to one lightweight external cladding.
or both sides of wall framing.
EXTERNAL CLADDING
Any type of approved external cladding fixed on battens.
MOISTURE BARRIER
Tyvek® HomeWrap membrane.
INSULATION
R2.5 Pink Wall Batts® glasswool by Fletcher Insulation.
SCREWS
Figure E1: OutRwall®
Refer to General Information – Materials section for
plasterboard screw types.
CAULKING
H.B. Fuller Firesound sealant.
» INTRODUCTION
INSTALLATION
Figure E2: Brick Veneer Wall
GENERAL
• Fire rated and acoustic systems must be installed strictly DESIGN OPTIONS
in accordance with USG Boral specifications in order to
achieve stated Fire Resistance Levels and acoustic ratings. USG Boral Brick Veneer wall systems are available in non-fire
rated or fire rated configurations up to FRL 120/120/120 from
• Refer to Timber Stud Walls and Junctions and Penetrations
one or both sides.
for installation specifications for fire rated timber framed
walls. Acoustic ratings have been provided for systems with 70mm
• Refer to OutRwall brochure for detailed system and 90mm studs. All acoustic ratings are based on 110mm
specifications. clay brick 170kg/m2 and 50mm gap between brick veneer
and internal framing.
• Timber framing must comply with AS 1684 Timber
framed construction.
MATERIALS
JOINTING AND FINISHING
PLASTERBOARD LININGS
• Stop and finish face layers of internal linings with the
• 10mm SHEETROCK Brand Wall Board
appropriate USG Boral jointing system (refer to USG Boral
Plasterboard Installation Manual). Joints and junctions in • 10mm Regular plasterboard
inner layers of multiple layer systems are not required to • 13mm Firestop plasterboard
be stopped. • 16mm Firestop plasterboard.
• Paper tape must be used in fire rated and wet area systems.
BRICK VENEER
CAULKING • Non-fire rated Brick Veneer (min 110mm clay brick 170kg/m2)
Perimeter gaps and penetrations in fire rated and acoustic • FRL 60/60/60 Brick Veneer
systems must be caulked with an approved sealant (refer
• FRL 90/90/90 Brick Veneer
to Junctions and Penetrations).
• FRL 120/120/120 Brick Veneer.
» INTRODUCTION
INSTALLATION
Refer to USG Boral Fireclad brochure for installation
instructions and details.
Rw
40-44 45-49 50-54 OUTRWALL
Rw +Ctr
1x10mm R2.5 GW
OWT.1B REGULAR
Nil
Wall Batts
27 24 27 24 2.9
1x10mm R2.5 GW
OWT.1C WET AREA
Nil
Wall Batts
28 24 28 24 2.9
SYSTEM DESCRIPTION
Internal Lining: 1x10mm R2.5 GW
OWT.1D FIBEROCK
Nil
Wall Batts
30 26 30 26 2.9
1x10mm non fire
resistant lining
Framing: Timber Studs * R2.5 GW Wall Batts - R2.5 Pink Wall Batts® glasswool by Fletcher Insulation.
Insulation: Refer to table
External Lining:
Nil
External Cladding:
Lightweight External
Cladding on battens over
Tyvek® HomeWrap membrane.
1x13mm 1x13mm
R2.5 GW
OWT30.1B WET AREA WET AREA
Wall Batts
41 33 41 34 3.2
FIRESTOP FIRESTOP
* R2.5 GW Wall Batts - R2.5 Pink Wall Batts® glasswool by Fletcher Insulation.
SYSTEM DESCRIPTION
Internal Lining:
1x13mm fire resistant pbd
Framing: Timber Studs
Insulation: Refer to table
External Lining:
1x13mm fire/water
resistant pbd
External Cladding:
Lightweight External
Cladding on battens over
Tyvek® HomeWrap membrane.
OUTRWALL Rw
40-44 45-49 50-54
Rw +Ctr
1x16mm
1x10mm R2.5 GW
OWT60.1B REGULAR
WET AREA
Wall Batts
41 33 41 34 3.2
FIRESTOP
1x10mm 1x16mm
R2.5 GW
OWT60.1C WET AREA WET AREA
Wall Batts
41 33 41 34 3.2
BOARD FIRESTOP
1x16mm 1x16mm
R2.5 GW
OWT60.2B WET AREA WET AREA
Wall Batts
42 36 42 38 3.2
FIRESTOP FIRESTOP
* R2.5 GW Wall Batts - R2.5 Pink Wall Batts® glasswool by Fletcher Insulation.
† Refer to Timber Stud Walls section Table D1 for maximum vertical loads on load bearing fire rated walls.
SYSTEM DESCRIPTION
Internal Lining:
1x16mm fire resistant pbd
Framing:= Timber Studs
Insulation: Refer to table
External Lining:
1x16mm fire/water
resistant pbd
External Cladding:
Lightweight External
Cladding on battens over
Tyvek® HomeWrap membrane.
Rw
40-44 45-49 50-54 OUTRWALL
Rw +Ctr
2x16mm
1x10mm R2.5 GW
OWT90.1B REGULAR
WET AREA
Wall Batts
43 39 43 40 3.2
FIRESTOP
2x16mm
1x10mm R2.5 GW
OWT90.1C WET AREA
WET AREA
Wall Batts
43 39 43 40 3.2
SYSTEM DESCRIPTION FIRESTOP
Internal Lining:
1x10mm non fire
resistant lining
Framing: Timber Studs 2x16mm
1x10mm R2.5 GW
Insulation: Refer to table OWT90.1D FIBEROCK
WET AREA
Wall Batts
44 39 44 40 3.2
External Lining: FIRESTOP
2x16mm fire/water
resistant pbd
External Cladding: * R2.5 GW Wall Batts - R2.5 Pink Wall Batts® glasswool by Fletcher Insulation.
Lightweight External
Cladding on battens over
Tyvek® HomeWrap membrane.
1x16mm 2x16mm
R2.5 GW
OWT90.2B WET AREA WET AREA
Wall Batts
45 41 45 42 3.3
FIRESTOP FIRESTOP
* R2.5 GW Wall Batts - R2.5 Pink Wall Batts® glasswool by Fletcher Insulation.
† Refer to Timber Stud Walls section Table D1 for maximum vertical loads on load bearing fire rated walls.
SYSTEM DESCRIPTION
Internal Lining:
1x16mm fire resistant pbd
Framing: Timber Studs
Insulation: Refer to table
Internal Lining:
2x16mm fire/water
resistant pbd
External Cladding:
Lightweight External
Cladding on battens over
Tyvek® HomeWrap membrane.
OUTRWALL Rw
40-44 45-49 50-54
Rw +Ctr
2x13mm 2x13mm
R2.5 GW
OWT90.3B WET AREA WET AREA
Wall Batts
48 44 48 45 3.3
FIRESTOP FIRESTOP
* R2.5 GW Wall Batts - R2.5 Pink Wall Batts® glasswool by Fletcher Insulation.
† Refer to Timber Stud Walls section Table D1 for maximum vertical loads on load bearing fire rated walls.
SYSTEM DESCRIPTION
Internal Lining:
2x13mm fire resistant pbd
Framing: Timber Studs
Insulation: Refer to table
External Lining:
2x13mm fire/water
resistant pbd
External Cladding:
Lightweight External
Cladding on battens over
Tyvek® HomeWrap membrane.
Rw
40-44 45-49 50-54 BRICK VENEER WALLS
Rw +Ctr
MIN 30/30/30
LB 1x13mm R2.5 GW
BVT30.1A 30/30/30
BRICK VENEER
FIRESTOP Wall Batts
64 55 65 56 3.3
FRL
* R2.5 GW Wall Batts – R2.5 Pink Wall Batts® glasswool by Fletcher Insulation.
† Refer to Timber Stud Walls section Table D1 for maximum vertical loads on load bearing fire rated walls.
MIN 60/60/60
NLB 1x13mm R2.5 GW
BVS60.1A –/60/60
BRICK VENEER
FIRESTOP Wall Batts
64 55 65 56 3.3
FRL
* R2.5 GW Wall Batts – R2.5 Pink Wall Batts® glasswool by Fletcher Insulation.
FIRECLAD Rw
40-44 45-49 50-54
Rw +Ctr
FC ACOUSTIC RATINGS
90/90/90
3x13mm
FC90.1A from outside
FIRESTOP
Adds 61mm NA 37 0.5
only
120/120/120
3x16mm
FC120.1A from outside
FIRESTOP
Adds 70mm NA 38 0.5
only
SYSTEM DESCRIPTION
External Lining:
-- Steel cladding on battens
-- Tyvek Housewrap waterproofing membrane
-- Two or more layers of fire resistant pbd fixed
to girts.