MANY0701A.GB - Technical Manual Metacentre EX Box
MANY0701A.GB - Technical Manual Metacentre EX Box
bar
TM
EX Box
Metacentre EX Box
Index
2.0 Introduction
2.1 Metacentre Connectivity
2.2 Basic Function
3.0 Installation
3.1 Guidelines
3.2 Location
3.3 Power Supply
3.4 RS485 Connection
3.5 Compressor Interface PCB
3.6 Pressure Sensor (Option)
3.7 Auxiliary Fault Inputs (Option)
3.8 Remote Output (Option)
4.0 Commissioning
4.1 Commissioning Procedure
4.2 Metacentre Management System
4.3 Menu Navigation
4.4 Menu Items and Settings
4.5 Diagnostics
5.0 Operation
5.1 User Interface
5.2 Display
5.3 Status Symbols
5.4 Indications
5.5 Compressor Identification
5.6 Operation
5.7 Power Failure Auto-Restart
5.8 Failure Modes
5.9 Compressor Fault
5.10 EX Box Fault
5.11 Pressure Sensor Fault
Page 1
Technical Manual
Never remove or tamper with safety devices, guards Do not paint the control facial or obscure any
or insulation materials fitted to the unit. indications, controls, instructions or warnings.
Page 2
Metacentre EX Box
Page 3
Technical Manual
3. Installation
28 L1
3.1 Guidelines X07
27 L2
26 RS485
It is recommended that installation and 25
commissioning be carried out by an authorised
and trained product supplier. Note: Polarity is important.
3.2 Location
RS485 data communications and other
The EX Box is wall mounting using low voltage signals can be subject to electrical
conventional screw fixings. The EX Box can interference. This potential can result in
be located remote from the compressor unit(s) intermittent malfunction or anomaly that is
but within 100m (330ft) cable length from each difficult to diagnose. To avoid this possibility
compressor (as applicable) and within 100m always use earth shielded cables, securely
(330ft) cable length from any pressure sensor bonded to a known good earth at one end. In
option (if applicable). addition, give careful consideration to cable
routing during installation.
3.3 Power Supply
1) Never route an RS485 data
A fused switching isolator must be installed to communications or low voltage signal cable
the main incoming power supply, external to alongside a high voltage 3-phase power
the EX Box. The isolator must be fitted with a supply cable. If it is necessary to cross the
fuse of the correct rating to provide adequate path of a power supply cable(s), always cross
protection to the power supply cable used (in at a right angle.
accordance with local electrical and safety
regulations). 2) If it is necessary to follow the route of power
supply cables for a short distance (for
example: from a compressor unit to a wall
XPM-TAC24
1 2 3 4 1 2 3 4
along a suspended cable tray) attach the
X04 RS485 or signal cable on the outside of an
earthed cable tray such that the cable tray
N L E E VOLTAGE SELECT
forms an earthed electrical interference shield.
X01 230Vac
N L E 1 2 3 4
3) Where possible, never route an RS485 or
X04
signal cable near to equipment or devices that
VOLTAGE SELECT may be a source of electrical interference (for
115Vac
example: 3-phase power supply transformer,
high voltage switchgear unit, frequency
inverter drive module, radio communications
Check the input voltage select link wires on antenna).
the EX Box power supply PCB, adjust if
necessary.
Page 4
Metacentre EX Box
Page 5
Technical Manual
The ‘i-PCB’ is fitted with a six-pin terminal C04 In instances where a convenient voltage signal
for compressor monitoring. The ‘i-PCB’ uses for a compressor ready condition is not
two inputs (Ready and Run) to determine available the ‘Ready’ input can be connected
compressor status. An Alarm input can be directly to a constant compressor control
used if compressor alarm indication is system power supply voltage (12V to 250Vac
available and required. The Alarm input is or dc). This will signal the EX Box that the
optional and is not necessary for system compressor is ready and available at all times
control. when power is applied to the compressor. The
EX has a built-in function to determine when a
Ready Input: compressor is not responding, or is in a
shutdown condition, regardless of a constant
The ‘Ready’ connection is intended to indicate ready signal. If the EX Box requests a
that the compressor is in a ‘started’ state, has compressor to run/load, but fails to detect a
no operational inhibiting fault condition and is RUN signal within 60 seconds, the EX Box will
ready to respond to EX Box regulation without regard the compressor as ‘not ready’ and
manual intervention. indicate the compressor as not available. If a
RUN signal is detected at any time, the EX
READY LAMP 0V
Box will automatically reset the compressor
+V ‘not ready’ condition and re-establish control.
+Vac
F1
Page 6
Metacentre EX Box
Page 7
Technical Manual
LOAD
SEQ LOAD Contacts :- SOLENOID
Relay Relay 250Vac/dc @ 5A
1&2 3 maximum
C03
NC
NO
C
NC
NO
OUT IN
24Vac
C02
NC
NO
C
NC
NO
OUT IN
C02
Page 8
Metacentre EX Box
COMPRESSOR CONTROLLER
INPUTS
Do not attempt to utilise the Load/Seq
‘Electronic Pressure Control’ (terminal C01)
and the ‘Pressure Switch Control’ (terminal
Remote Load Local/Remote C02) output connections at the same time.
or These two output functions are internally
Remote Load Enable connected and a short circuit condition and/or
Inputs Common
malfunction may result.
Note:
The ‘i-PCB’ connection examples shown in
this manual are intended to provide a guide for
the majority of compressor control systems in
C01
use. Some compressors have variations in
operation and/or function; consult your
SEQ
LOAD
C
Page 9
Technical Manual
Page 10
Metacentre EX Box
#1
Polarity is important.
Page 11
Technical Manual
Page 12
Metacentre EX Box
4. COMMISSIONING
4.1 Commissioning Procedure 4.2 Metacentre Management System
Carry out the following procedures before For each compressor connected to the
attempting to apply power and start. Metacentre management unit using an EX
Box, ensure the connection type for the
It is recommended that an authorised and compressor is defined as “I-485” (RS485
trained product supplier carry out network communication) in the Metacentre
commissioning. management system configuration.
L N E E VOLTAGE SELECT
1 2 3 4
L N E X04
1 2 3 4
VOLTAGE SELECT
115Vac
Example:
Compressor #1 = network address 3
General Checks: Compressor #2 = network address 4
Check and ensure all pressure sensor, ‘i-PCB’
and other connections are correctly installed The local EX Box reference numbers (#1 and
and secure. #2) have no meaning for Metacentre
management system identification and
Close the front panel of the EX Box and apply referencing; it is not important for compressors
power. to be connected to the EX Box in numerical
order or sequentially.
Page 13
Technical Manual
Display Item Structure: Access to page list displays higher than page
‘P00’ is restricted by access code. To access
All value, parameter or option selection menu mode pages press UP and DOWN
displays are grouped into menu lists. Items are together, an access code entry display is
assigned to a list according to type and shown and the first code character will flash.
classification. Items that can be used to select Use PLUS or MINUS to adjust the value of the
options or modify functions are assigned to first code character then press ENTER. The
‘menu mode’ lists. Items that a User may next code character will flash; use UP or
require to view during routine operation, DOWN to adjust then press ENTER. Repeat
detected pressure for example, are assigned for all four code characters.
to the normal operational mode list. Lists are
identified by page number; the normal User
display list is page ‘P00’. All parameters and
options are assigned to menu mode pages If the code number is less than 1000 then the
‘P01’ or higher. All Page ‘P00’ items are view first code character will be 0(zero). To return
only and cannot be adjusted. to a previous code character press ESCAPE.
When all four code characters have been set
Normal Operational Mode (Page P00): to an authorized code number press ENTER.
An invalid code will return the display to
At controller initialisation, all display elements normal operational mode; page ‘P00’.
and LED indicators are switched on for three
seconds, the display will then show the Access Code Timeouts:
software version code for a further 3 seconds
before initialisation is complete and the normal When in menu mode, if no key activity is
operating display (Page P0) is shown. In page detected for a period of time the display will
P00 ‘normal operational display mode’ the automatically reset to the normal operational
main display will continuously show the display; Page ‘P00’.
detected delivery pressure and the Item
display will show the first item of the ‘User’ Menu Mode Navigation:
menu. User menu ‘Items’ can be selected
using the Up or Down buttons at any time. In menu mode the main value display will flash
Pressing the Enter button will lock any and show the Page number. To select a page
selected Item display and inhibit return to the press UP or DOWN. For each page the
default display. When an Item display is locked display will show the first Item of the page list.
the lock key symbol will slow flash. To unlock To view a page list press ENTER, the Page
an Item display press Up or Down to view an number will stop flashing and the Item display
alternative Item display or press Reset or will flash. Press UP or DOWN to view the
Escape. No Item values, options or selected page list items. To select an Item
parameters can be adjusted in page ‘P00’. If a value for modification press ENTER, the Item
fault condition occurs the fault code becomes display will stop flashing and the Value display
the first list item and the display will will flash. The value or option can now be
automatically jump to display the fault code. modified by pressing UP(Plus) or
More than one active fault code item can exist DOWN(Minus). To enter a modified value or
at any one time. option in memory press ENTER; alternatively
the modification can be abandoned, and the
original setting maintained, by pressing
Page 0 Page 1
ESCAPE.
Page 2
Item 1 Value
Item 2 Value Page 3 Item 1 Value
Item 3 Value Item 2 Value
Page 4
Item 4 Value Item 3 Value
Item 5 Value Page 5 Item 4 Value
Item 6 Value Item 5 Value
Page 14
Metacentre EX Box
Page 0 Page 1
Page 2
Item 1 Value
Item 2 Value Page 3
Item 1 Value
Item 3 Value Item 2 Value
Page 4
Item 4 Value Item 3 Value
Item 5 Value Page 5 Item 4 Value
Item 6 Value Item 5 Value
Page 15
Technical Manual
Page 16
Metacentre EX Box
Note: The compressor network address Selects the display pressure units:
number must be unique; if two compressors
are assigned the same network address 0: bar (default)
number the Metacentre system will be 1: psi
disrupted. 2: kPa
‘i-PCB’ Alarm input configuration for Selects the function of the auxiliary relay
compressor #2. contact output R4.
As default the ‘i-PCB’ Alarm input (optional) Fno: Compressor Fault N/O
will generate an Alarm condition when voltage Energised if a compressor Alarm or
(12V to 250V) is applied to the Alarm input Trip fault is detected.
terminals (‘no’). Fnc: Compressor Fault N/C
De-energised if a compressor Alarm
This configuration can be changed so that a or Trip fault is detected.
constant voltage can be applied to the Alarm C1r: Compressor #1 Running
input terminals and an Alarm generated when Energised when compressor #1 is
the voltage is removed. (‘nc’). detected as running.
C2r: Compressor #2 Running
‘no’ (normally open) – default Energised when compressor #2 is
Alarm when voltage applied. detected as running.
‘nc’ (normally closed) Crr: Compressor Running
Alarm when voltage removed. Energised if compressor #1 and/or
compressor #2 is detected as running.
Set to default ‘no’ if not used. On: Metacentre ON
Energised when the Metacentre
management system is regulating to
D7: Auxiliary Input
achieve or maintain pressure (Off
when in standby or stopped).
Selects the function and operation of the
AC: Metacentre Active
‘Auxiliary Input’:
Energised when the Metacentre
management system is actively
Ano Alarm: (normally open) – default
maintaining control of compressors
Alarm when closed
inclusive of Standby (Off when
Anc Alarm: (normally closed)
stopped; unless management system
Alarm when open
set to force compressors offload when
Tno Trip: (normally open)
stopped)
Trip when closed
rPC: Remote Pressure Control
Tnc Trip: (normally closed)
Energised when in ‘Remote Mode’ –
Trip when open
Metacentre management system
control.
Set to default ‘Ano’ if not used.
Page 17
Technical Manual
4.4.4 Menu 4 – Comp#1 Pressure Sensor The compressor will be inhibited from loading
again until the detected pressure has reduced
P1 below the set limit, and remains below the set
limit, for longer than 10 seconds. If, after re-
loading, pressure exceeds the limit again, the
cycle is repeated.
#1 When pressure exceeds the set limit the
‘excess pressure symbol’ will flash in the
DP#1 appropriate compressor status display. This
indication will remain until manually reset.
The ‘Compressor #1’ pressure sensor (P1)
input is intended for monitoring the ‘delivery’ To deactivate adjust to 0(zero) – default.
pressure of compressor #1 prior to any
isolation valve and air treatment or other Po: Pressure Offset Calibration
potential air flow restriction that may cause a
pressure differential. The value can be adjusted between –1.5bar
(minus 1.5bar) and +1.5bar (-22 to +22psi).
PE: Pressure Sensor Option Enable Default = 0.0bar (0psi).
4-20mA auxiliary pressure sensor enable: The ‘offset’ value can be used for atmospheric
(0bar-g) calibration; expose the senor to
0: Disable (default) atmosphere and adjust until the display
1: Enable pressure shows 0(zero)bar. The main display
value will show the actual detected pressure
A compatible ‘4-20mA’ type pressure sensor when this menu item is selected.
must be connected to the EX Box compressor
#1 pressure sensor input. Note: For sensors with ‘minus’ offset values
any detected pressure below 0(zero)bar will
When enabled the pressure will be displayed be displayed, and transmitted on the network,
with compressor #1 status. as 0(zero)bar.
Page 18
Metacentre EX Box
4.4.5 Menu 5 – Comp#2 Pressure Sensor The compressor will be inhibited from loading
again until the detected pressure has reduced
P2 below the set limit, and remains below the set
limit, for longer than 10 seconds. If, after re-
loading, pressure exceeds the limit again, the
cycle is repeated.
#2
When pressure exceeds the set limit the
‘excess pressure symbol’ will flash in the
DP#2 appropriate compressor status display. This
indication will remain until manually reset.
The ‘Compressor #2’ pressure sensor (P2)
input is intended for monitoring the ‘delivery’ To deactivate adjust to 0(zero) – default.
pressure of compressor #2 prior to any
isolation valve and air treatment or other Po: Pressure Offset Calibration
potential air flow restriction that may cause a
pressure differential. The value can be adjusted between –1.5bar
(minus 1.5bar) and +1.5bar (-22 to +22psi).
PE: Pressure Sensor Option Enable Default = 0.0bar (0psi).
4-20mA auxiliary pressure sensor enable: The ‘offset’ value can be used for atmospheric
(0bar-g) calibration; expose the senor to
0: Disable (default) atmosphere and adjust until the display
1: Enable pressure shows 0(zero)bar. The main display
value will show the actual detected pressure
A compatible ‘4-20mA’ type pressure sensor when this menu item is selected.
must be connected to the EX Box compressor
#2 pressure sensor input. Note: For sensors with ‘minus’ offset values
any detected pressure below 0(zero)bar will
When enabled the pressure will be displayed be displayed, and transmitted on the network,
with compressor #2 status. as 0(zero)bar.
Page 19
Technical Manual
The ‘System’ pressure sensor (Ps) input is When the ‘System’ pressure sensor option is
intended for monitoring system, or ‘dry-side’ enabled, and the ‘broadcast system pressure’
pressure downstream of local air treatment or (SP) option is set to ‘1’, the EX Box will
other potential airflow restriction that may transmit the detected ‘System’ pressure on the
cause a pressure differential. network instead of the pressure from each
compressor; the individual compressor
P1 pressure(s), if enabled, will not be transmitted
on the network. This feature will enable the
Ps Metacentre management system to use the
system pressure value for advanced pressure
#1 control functions.
DP#1
0: Broadcast Comp. ‘Delivery’ pressure(s)
P2 1: Broadcast ‘System’ pressure (default)
Page 20
Metacentre EX Box
Digital Inputs:
Page 21
Technical Manual
The upper display will continuously show the 1: Compressor Not Available
‘network address’ number for the compressor 2: Auxiliary Trip input active
(Metacentre management system compressor
number); for example “C03” for compressor 3. 5.4 Indicators
The display symbols will show the status of the
compressor associated with the compressor Run Indicator (Green LED)
number. If the ‘’Compressor’ pressure function
is enabled the lower display value will show OFF No Compressor(s) Available
the detected ‘delivery’ pressure. ON Active
Page 22
Metacentre EX Box
EX Box
The design of some air compressor control
systems may inhibit automatic transfer of
1 2 3 4 pressure regulation control to local operation
mode. In this instance the compressor will not
continue production of compressed air –
The identification number will be unique for the consult the air compressor manual or your air
Metacentre system and may not be sequential compressor supplier / specialist for details
or follow the EX Box local reference numbers before installing the Metacentre / EX Box unit.
#1 and #2. The ‘compressor number’ display
item shows the system number for each 5.9 Compressor Fault
connected compressor.
If a compressor fault condition is detected the
To establish which compressor status display ‘status’ display associated with the
is associated with the compressor connected compressor will indicate a fault condition (see
to the EX Box as compressor #1 – press UP. Status Symbols). The EX Box ‘Fault’ indicator
The status displays do not wrap-around; the (10) will flash to attract attention. Compressor
status display at the top of the item menu list is fault conditions will also be communicated to
always compressor #1. the Metacentre management system
controller.
5.6 Operation
5.10 EX Box Fault Code E:0821
The EX Box is always active (started) and
cannot be stopped. The EX Box will The EX Box has one shutdown fault condition:
automatically switch between ‘Remote’, when
under Metacentre management system
control, or ‘Local’ mode.
Short Circuit Condition Detected,
Check all EX Box controller inputs and
5.7 Power Failure Auto-Restart
outputs.
The EX Box will always automatically start
If this fault condition occurs the EX Box will
when power is re-applied after a power supply
switch ‘off’ to ‘Local’ mode. The display will not
disruption or failure.
show any compressor number, status or
pressure; only the ‘Alarm’ and ‘Short Circuit’
5.8 Failure Modes
symbols will be displayed. The condition can
be reset when the fault is resolved; check all
If communications with the Metacentre
input and output connections and devices.
management system is disrupted, the EX Box
will switch to ‘Local’ mode and pressure
5.11 Pressure Sensor Fault (Option)
regulation control is automatically transferred
back to each compressor. The compressor(s)
If a pressure sensor fault is detected (if the
will continue to operate using the pressure
pressure sensor option is enabled) the EX Box
settings programmed or set in the individual
will indicate a compressor ‘Alarm’ condition
compressor controller(s).
and the associated pressure display will show
“- - - -“ dashes.
The EX Box will automatically switch back to
‘Remote’ mode when communications with the
The pressure communications ‘broadcast’ on
Metacentre management system are re-
the system network will be 0(zero)bar.
established, or the EX Box fault is reset.
The EX Box will continue to operate normally
without interruption.
Page 23
Technical Manual
Metacentre EX Box
24 14
24mm
Dimensions 291mm x 241mm x 152mm
Weight 6.5kg (14lb)
Mounting wall, 4 x screw fixings
Enclosure IP54, NEMA 12
Supply 230Vac +/- 10%
188mm 236mm
115Vac +/- 10%
Power 50VA
Temperature 0°C to 45°C (32°F to 112°F)
Humidity 30% to 90% RH
8mm Ø
non-condensing
286mm
Page 24
Metacentre EX Box
EX Box
S1-10-R4-333 +VDC
C001
Controller C002
29 30 31 32
Ai1 C009 L1
C003
C010 L2
X07
X05
+VDC C004 Multi485
Ai2 C005
L1
+VDC C006 L2
Ai3
27 28
C007
X06
C007 not used
A-GND
X06
C008
C008
Ao
21 22 23 24 25 26
C009 C006 - Ai3 4-20mA
RS485
L1
X07
X05
C003 + Pressure #2
8 7 6 5 4 3 2 1 C+
C011
C012 C002 - Ai1 4-20mA
C013 C001 + Pressure #1
C014
15 16 17 18 19 20
C015 C011 +C
X04
X04
C018
C018 Di7 Aux Fault #2
C019
not used
C019
C028
C029
C026
C027
13 14
C024 X03
C020
C025
R4 Aux Output
R3 R2 R1
C021
C011
X03
10k + 20VDC
8 9 10 11 12
C022 6
i-PCB 2
C015 Di4 Ready/Run 5
C023
C016 Di5 Alarm/Serv. 4
X02
C023 R3 LOAD
R4
2
C025
X01
C021 R1 SEQ 1
V2 7
2
C029
1
C032
10k + 20VDC 6
2 3 4 5 6
i-PCB 1
24Vac
XPM-TAC24
4
X01
C030
1
C031
- GND 3
N
E
E
L
C022 R2 LOAD 2
X01
0Vac
R1 SEQ 1
V1 1
C027
N
E
L
230Vac 10%
115Vac 10%
Page 25
Technical Manual
XPM-TAC24
BLUE BLACK
BROWN ORANGE
RED WHITE
GREEN VIOLET
1 2 3 4 X04
T3.15A T1.6A T1.6A T1.0A 1 2 3 4
115V
115V +-10%
IEC T1.0A FH1
5x20mm
1 2 3 4
X03 X02
2 1 2 X01
N L E E
24Vac/2 24Vac/1
earthed isolated NL E
Page 26
Metacentre EX Box
EX Commissioning Form
Customer Contact Customer Ref:
Comp #1 Manufacturer
3
Comp #1 Model/Type
bar m /min Comp #1 Working Pressure bar/psi
#1 kW VA Hz
Comp #1 Full Load Capacity m3/min
Comp #2 Manufacturer
bar m3/min Comp #2 Model/Type
#2 kW VA Hz Comp #2 Working Pressure bar/psi
Comp #2 Full Load Capacity m3/min
Page 27