SCHEDULE - 2(A) : Supply and Mandatory Spare Parts : 220/132 KV Jadugoda Substation
Schedule of Quantity & Prices for
Design, Engineering, Supply, Installation, Testing & Commissioning of 220/132 KV Jadugoda Substation
Bid Inviting Authority: General Manager, Contracts & Materials, Multi Lateral Funding Project
NIT No. 708/PR/JUSNL/2023-24
Total Price (Rs.) GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty Unit Price (Rs.) GST Rate
without GST (Rs) with GST
(4x5) % (6x7) (6+8)
1 2 3 4 5 6 7 8 9
Part-A Electrical
A TRANSFORMER
A1 Power Transfomer
200 MVA Three phase power Transformer 220/132/33 KV Auto
Transformer Complete with all accessories, marshaling boxes,
1 Nos. 2 0 0 0
terminal connectors etc. with NIFPS with 10% additional
Transformer Oil of same quality
A2 LT TRANSFORMER
630 KVA 33/0.433KV LT SUBSTATION TRANSFORMER with
1 NOS 2 0 0 0
oil,accessories and terminal connectors with 10%extra oil.
B-1 220 kV EQUIPMENT
1 Circuit breaker (3 phase) 0 0 0
2500 A, 40 kA SF6 CB with support structure, marshalling boxes,
terminal connectors etc.(current rating shall be equal to the current
i) Set 8 0 0 0
rating for which the short cuircuit test reports shall be furnished.
(Spring- Spring Mechanism ) (spring- spring )
ISOLATORS (3 phase), with solid core insulators, marshalling
2 boxes, terminal connectors (Motor Operated) with moving contact
of HDEC copper only.
i) 1600 A, 40 kA with two earth switch (Double break Isolator) Set 9 0 0 0
ii) 1600 A, 40 kA with one earth switch (Double break Isolator) Set 8 0 0 0
1600 A, 40 kA without earth switch (Double break Isolator)
iii) Set 14 0 0 0
(Tandem arrangement)
iv) 2500 A, 40 kA with two earth switch (Double break Isolator) Nos. 2 0 0 0
CURRENT TRANSFORMER 5 Core (1 phase) WITH
3
MARSHALING BOXES TERMINAL CONNECTORS
1600-800-400-200/1-1-1-1-1 A, 120% extended current rating, 40
i) Nos. 27 0 0 0
kA, 0.2 class 5 core
220 KV CVT 4400 pF CVTs (1 phase) for phase to phase coupling
4 Nos. 21 0 0 0
with all accessories, terminal connectors etc.
5 216 kV Surge Arresters (1 phase) class-III with terminal connectors. Nos. 18 0 0 0
6 Portable discharge rods Nos. 6 0 0 0
B2 ERECTION HARDWARE (220 kV)
1.1 Erection Hardware (Without BPI)
Insulator strings antifog type & hardware, spacers, conductor (S),
Bus bar material, galvanised cable trays/ cable rack, bay MB,
Clamps, Connectors including, Junction box,PVC pipes for
0
equipment and lighting, all accessories etc. for the following (The
main I & main II buses shall be of quad Moose ACSR Conductor &
TBC as well as Bus Coupler will be of double Moose conductor.
220 kV, Double Main & Transfer bus type
i Line bay set 4 0 0 0
ii Transformer bay Set 2 0 0 0
iii TBC Set 1 0 0 0
iv BC Bay Set 1 0 0 0
Bus Extension for 10 Bays (one no each for main I, main II & trasfer
v Set 3 0 0 0
bus)
220 kV Solid Core, Bus post Insulators (including requirement for
1.2 Set 115 0 0 0
wave trap)
C1 132 kV EQUIPMENT
1 Circuit breaker (3 phase)
1600 A, 31.5 kA SF6 CB with support structure, marshalling boxes,
terminal connectors etc.(current rating shall be equial to the current
i) Set 7 0 0 0
rating for which the short cuircuit test reports shall be furnished.)
(Spring- Spring )
ISOLATORS (3 phase), with solid core insulators, marshaling
2 boxes, terminal connectors (Motor Operated) with moving contact
of HDEC copper only.
i) 1600 A, 31.5 kA with one earth switch (Double break Isolator) Set 6 0 0 0
ii) 1600A, 31.5 kA without earth switch (Double break Isolator) Set 8 0 0 0
1600 A, 31.5 kA without earth switch (Double break Isolator)
iii) Set 7 0 0 0
(Tandem arrangement)
2000 A, 31.5 kA without earth switch (Double break high level beam
iv) Set 2 0 0 0
mounted Isolator)
3 Portable discharge rods ( 1 phase) Nos. 6 0 0 0
4 Current Transformers 5 core (1 phase) 0
1200 -600-300-150/1-1-1-1-1 A, 5 core 0.2S class ,31.5 kA with
i) 120% extended current rating with marshalling boxes, terminal Nos. 21 0 0 0
connectors etc.
8800 pF CVTs (1 phase) with marshalling boxes, terminal
5 Nos. 15 0 0 0
connectors etc .
120 kV Surge arresters class-III ( 1 phase) with marshalling boxes,
6 Nos. 18 0 0 0
terminal connectors etc.
C2 0
1.1 ERECTION HARDWARE (132 kV) 0
Insulator strings antifog type & hardware, spacers, conductor (S),
Bus bar material, galvanised cable trays/Cable rack, bay MB,
Clamps, Connectors including, Junction box,PVC pipes for
0
equipment and lighting, all accessories etc. for the following (main
bus shall be of quad Moose conductor and transfer bus shall be
strung with double Moose conductor)
132 kV Main & Transfer bay 0
i Line bay Set 4 0 0 0
ii Transformer bay Set 2 0 0 0
iii TBC Bay Set 1 0 0 0
iv Bus for 8 bays (One for main bus & another for transfer bus) Set 2 0 0 0
1.2 132 kV Solid Core, Bus post Insulators for erection hardware Nos. 53 0 0 0
D 33 kV EQUIPMENT
1 Circuit Breaker (3 Phase)
1600 A, 25KA Vacume CB with support structure, marshalling
boxes, terminal connectors etc. (current rating shall be equail to the
i) Set 2 0 0 0
current rating for which the short circuit test report shall be
furnished) (Spring-Spring)
ISOLATORS (3 phase), with solid core insulators, marshalling
2 boxes, terminal connectors (Manually operated) with moving 0
contact of HDEC copper only.
i) 1600 A, 25 kA without earth switch (Double break Isolator) Set 2 0 0 0
ii) 1200A, Horn gap fuse ( 1 phase) Nos. 6 0 0 0
3 Current Transformers (1 phase) 0 0
600-300-150/1 A, 5 core 0.2 class 25 kA with 120% extended
i) Set 6 0 0 0
current rating with marshalling boxes terminal connectors
30 kV Surge arresters class 3 ( 1 phase) with marshalling boxes
4 Set 6 0 0 0
terminal connectors
5 33 kV Solid core Bus post Insulators for erection hardware Set 6 0 0 0
E LT Switchgear 0 0
i 415 V Main switch Board Set 2 0 0 0
415 V ACDB (no of feeders shall be asper the requirement of the
ii Set 2 0 0 0
project plus 20% extra feeders)
iii 415V MLDB Set 2 0 0 0
iv 415V Emergency LDB Set 2 0 0 0
250V DCDB (no of feeders shall be asper the requirement of the
v Set 2 0 0 0
project plus 20% extra feeders)
vi 48V DCDB Set 2 0 0 0
F CONTROL & RELAY PANELS 0
1 220 kV (Simplex panels) 0
Control Panel for two bays with All indicating meters/
1.1 multifunctions meters shall be communicable type with 0.2 class Nos. 4 0 0 0
accuracy.
1.2 a) CB relay panel with A/R Nos. 4 0 0 0
1.2 b) CB relay panel without A/R Nos. 4 0 0 0
Line protection panel with numerical distance protection relays and
earth fault / overcurrent relays complying to IEC 61850 Protocal
1.3 Nos. 4 0 0 0
with optical fiber ports sufficient DI/DO ports for scheme with
additional 6 DI/DO Ports for spare.
Transformer protection panel HV and LV sides) with numerical
differential protecton relays with earth fault/ over current relay
1.4 complying to IEC 61850 Protocal with optical fiber ports and Nos. 2 0 0 0
sufficient DI/DO for scheme with additional 6 DI/DO ports for
spare.
Bus Bar Protection Panel ( will be integrated type and will have min.
1.5 Set 1 0 0 0
4 zone with numerical type relay)
Transfer bus coupler panel with distance protection relay scheme
1.6 Nos 1 0 0 0
with all relays
1.7 Time synchonization eqp. Will have dual ethernet with RJ 45 port Set 1 0 0 0
2 132 kV (Simplex Panels) 0
2.1 132KV Control, Relay & Protection Panel (Simplex Types Panels) 0
a) CB panel with BCU (Line and Transfer coupler) Nos. 5 0 0 0
b) CB panel with BCU (Transformer) Nos. 2 0 0 0
132 KV line (with A/R) with numerical distance protection relays
and earth fault / overcurrent relays complying to IEC 61850 Protocal
C) with optical fiber ports sufficient DI/DO for scheme with additional Nos. 4 0 0 0
6 DI/DO for spare. All indicating meters/ multifunctions meters shall
be communicable type with 0.2 class accuracy.
132/33 KV Transformer (without A/R) with numerical differential
protection relays and earth fault / overcurrent relays complying to
D) Nos. 2 0 0 0
IEC 61850 Protocal with optical fiber ports sufficient DI/DO for
scheme with additional 6 DI/DO for spare.
132 kV TBC (with A/R) with numerical distance protection relays
and earth fault / overcurrent relays complying to IEC 61850 Protocal
E) with optical fiber ports sufficient DI/DO for scheme with additional Nos. 1 0 0 0
6 DI/DO for spare. All indicating meters/ multifunctions meters shall
be communicable type with 0.2 class accuracy.
F) Transformer ( CB relay Panel without A/R ) Nos. 2 0 0 0
3 33 KV CONTROL & RELAY PANELS 0
33 kV Panels (Duplex) 0
Control, Relay & Protection Panel for 0
Line with numerical type E.F & O/C relays complying to IEC 61850
a) Nos. 2 0 0 0
protocol
FOTE Fiber Optic Terminal Equipment based communication
system for all 220KV and 132KV Terminal lines including spare
G bay, approach cable, RTU Communication Modules, interfacing Lot 1 0 0 0
with SLDC (for speech + protection and for speech + data),
PDH/SDH etc all complete along with for GSS end
H BATTERIES (VRLA TYPE OF EXIDE MAKE)
1.1 250 V
a) 500 AH Sets. 2 0 0 0
1.2 48 V 0 0
a) 500 AH Sets. 2 0 0 0
I BATTERY CHARGER SYSTEM chloride 0
1.1 250 V, 60A/50A Float and float Cum Boost Charger Nos. 2 0 0 0
1.2 48 V, 60A/50A Float and float Cum Boost Charger Nos. 2 0 0 0
J FIRE PROTECTION SYSTEM 0
1.1 Portable Fire Extinguishers 0
a 4.5 Kg DCP Type Nos. 20 0 0 0
b 4.5 Kg CO2 Type Nos. 15 0 0 0
c 22.5 Kg CO2 type Nos. 10 0 0 0
d 12 Fire buckets with stand LS 5 0 0 0
Complete pumping arrangement for HVWS system & hydrant
system, complete with all piping, valves, fittings, etc. inside pump
1.2 Set 4 0 0 0
house. (Pump house separate from control room as well as water
storage tank to be constructed)
1.3 Smoke detection system with all accessories and fittings Set 3 0 0 0
Hydrant system with complete U/G & O/G piping & accessories etc.
(all items) out side the Pump House. Hydrant system shall cover the
1.4 Set 1 0 0 0
switchyard area, Transformers, control room, Stores etc. as per
tender specification.
Complete HVW spray system with complete O/G & U/G piping and
accessories etc. (all items) with all required materials and
1.5 LS 1 0 0 0
equipments out side the pump house for 150 MVA, 2
Nos,220/132/33 KV power transformers as per tender specification.
K ILLUMINATION SYSTEM
L CONTROL ROOM BUILDING:
1 Lighting Panel
a Lighting Panel (Indoor) Type ACP-1 as per Tech. Specification Nos. 2 0 0 0
b Lighting Panel (Indoor) Type DCP as per Tech. Specification Nos. 1 0 0 0
Total Price (Rs.) GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty Unit Price (Rs.) GST Rate
without GST (Rs) with GST
(4x5) % (6x7) (6+8)
1 2 3 4 5 6 7 8 9
Part-A Electrical
Lighting fixtures and receptacles (including accessories/ materials
etc. as per requirement like junction box, cable/wires, flexible
2
conduits (if required) from junction box to lighting fixtures,
mounting arrangements)
a Lighting fixture Type- F1 as per Tech. Specification Nos. 50 0 0 0
b Lighting fixture Type- FF: as per Tech. Specification Nos. 100 0 0 0
c Lighting fixture Type- IF: as per Tech. Specification Nos. 30 0 0 0
d Lighting fixture Type- FB: as per Tech. Specification Nos. 30 0 0 0
e Lighting fixture Type- PF: as per Tech. Specification Nos. 5 0 0 0
f 5/15 A, 240V: Indoor Receptacles 3 pin type (type RI) Nos. 20 0 0 0
g 15A, 240V: Out door receptacles 2 pole, 3 pin type (Type RO) Nos. 2 0 0 0
63A, 415V : Interlocked switch socket outdoor Receptacles (Type
h Nos. 2 0 0 0
RP)
3 Switchboards
Modular switch board with 4 nos. 5Amp. Switches and 1 no. 5/15
a Nos. 10 0 0 0
Amp. receptacles
b Modular switchboard with 6 nos. 5Amp. Switches Nos. 10 0 0 0
c Modular switchboard with 2 nos. 5Amp. Switches Nos. 10 0 0 0
d Modular switchboard with 6 nos. 32 Amp MCB Nos. 5 0 0 0
e Modular switchboard with 1 no. 32 Amp. MCB Nos. 5 0 0 0
4 Ceiling fans 0 0
a 1400 mm sweep with electronic step regulator Nos. 28 0 0 0
5 Exhaust fans (16') Indristrial Type Nos. 10 0 0 0
6 Wall mounted fans 400 mm sweep Nos. 2 0 0 0
7 Conduits & wires
Heavy duty PVC conduits as of 20/25/32 mm size complete with all
accessories for point wiring for Light points, Fans power points 5/15
a amps. With 2.5 sq.mm/4 mm2/6.0 mm2 copper for circuit wiring and LS 1 0 0 0
1.5 mm2 copper earth wire PVC insulated in green color including
wiring for submains i.e. wiring from Lighting panel to switch board.
Wiring from lighting panel to switch boards, from switchboard to
junction boxes for light points with 2.5/4.0/6.0 mm2 copper wire as
b LS 1 0 0 0
per technical specification, complete in all respect. 1.5 mm2 copper
wire (green) will be used for earthing inside conduits
c Telephone sockets
c.1 Single socket outlet comprising RJ-11 socket Nos. 10 0 0 0
c.2 Dual socket outlet comprising RJ-45 socket Nos. 5 0 0 0
c.3 EPAX (24/8) with 24 telephones Set 1 0 0 0
Junction boxes with 4 nos. of terminal blocks for indoor lighting
8 Nos. 2 0 0 0
excluding junction box supplied alongwith lighting fixture
Lighting Transformer 630 kVA, 33/0.433KV LT Transformer with
9 Nos. 2 0 0 0
oil , accessories and as per Tech. Specification.
10 Self supported aluminium ladder as per technical specification Nos. 3 0 0 0
11 Air Conditioning System (as per technical specification) 0
Air conditioning of control room building with high wall type 5 star
(a) Nos. 50 0 0 0
rated split air conditioner unit of 2 TR capacity with stabilizer
L ii FFPH Building 0
Lighting fixtures and receptacles (including accessories/ materials
etc. as per requirement like junction box, cable/wires, flexible
1
conduits (if required) from junction box to lighting fixtures,
mounting arrangements)
a Lighting fixture Type- F1: as per Tech. Specification Nos. 25 0 0 0
b Lighting fixture Type- IF: as per Tech. Specification Nos. 7 0 0 0
c Lighting fixture Type- FB: as per Tech. Specification Nos. 12 0 0 0
d Lighting fixture Type- PF: as per Tech. Specification Nos. 3 0 0 0
e 5/15 A, 240V: Indoor Receptacles 3 pin type (type RI) Nos. 5 0 0 0
2 Switchboards
Modular switch board with 4 nos. 5Amp. Switches and 1 no. 5/15
a Nos. 7 0 0 0
Amp. receptacles
c Modular switchboard with 2 nos. 5Amp. Switches Nos. 5 0 0 0
3 Ceiling fans 0 0
a 1400 mm sweep with electronic step regulator Nos. 2 0 0 0
4 Exhaust fans (16') Indristrial Type Nos. 4 0 0 0
5 Wall mounted fans 400 mm sweep Nos. 4 0 0 0
6 Conduits & wires 0
Heavy duty PVC conduits as of 20/25/32 mm size complete with all
accessories for point wiring for Light points, Fans power points 5/15
a amps. With 2.5 sq.mm/4 mm2/6.0 mm2 copper for circuit wiring and LS 1 0 0 0
1.5 mm2 copper earth wire PVC insulated in green color including
wiring for submains i.e. wiring from Lighting panel to switch board.
Wiring from lighting panel to switch boards, from switchboard to
junction boxes for light points with 2.5/4.0/6.0 mm2 copper wire as
b Lot 1 0 0 0
per technical specification, complete in all respect. 1.5 mm2 copper
wire (green) will be used for earthing inside conduits
Junction boxes with 4 nos of terminal blocks for indoor lighting
7 Nos. 2 0 0 0
excuding junction box supplied alongwith lighting fixtures.
L. III Outdoor lighting (Switchyard and street lighting)
1 Lighting panel
a Lighting panel (Outdoor) Type ACP - 2 Nos. 8 0 0 0
b Lighting panel (Outdoor) Type ACP - 3 Nos. 3 0 0 0
Lighting fixtures and receptacles (including accessories/ materials
etc. as per requirement like junction box, cable/wires, flexible
2
conduits (if required) from junction box to lighting fixtures,
mounting arrangements)
a Lighting fixture Type- SF1: as per Tech. Specification Nos. 20 0 0 0
b Lighting fixture Type- SF2: as per Tech. Specification Nos. 30 0 0 0
c Lighting fixture Type- MP: as per Tech. Specification Nos. 6 0 0 0
d Lighting fixture Type- SC: as per Tech. Specification Nos. 35 0 0 0
e 15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO) Nos. 10 0 0 0
f 63A, 415V: Interlocked switch socket outdoor receptacles (Type RP) Nos. 10 0 0 0
3 Lighting poles Type A1 Nos. 50 0 0 0
4 Lighting poles Type E1 Nos. 20 0 0 0
5 Cart wheel mounted aluminium ladder as per Tech. Specification Nos. 1 0 0 0
L-IV Diesel Generator Set along with Control Panel (250 KVA) Set 1 0 0 0
Cables alongwith associated accessories like clamps, glands, lugs
M
and straight joints etc.
1.1 Power cables (XLPE) 1.1 kV
a 1C X 630 mm2 Lot 1 0 0 0
b 3.5C X 300 mm2 Lot 1 0 0 0
c 3.5C X 150 mm2 Lot 1 0 0 0
d 1C X 150 mm2 Lot 1 0 0 0
1.2 Power cables (PVC) 1.1 kV
a 3.5C X 70 mm2 Lot 1 0 0 0
b 3.5C X 35 mm2 Lot 1 0 0 0
c 4C X 16 mm2 Lot 1 0 0 0
d 4C X 6 mm2 Lot 1 0 0 0
e 2C X 6 mm2 Lot 1 0 0 0
1.3 Control cable (PVC) 1.1 kV 0
a 2C X 2.5 mm2 Lot 1 0 0 0
b 3C X 2.5 mm2 Lot 1 0 0 0
c 5C X 2.5 mm2 Lot 1 0 0 0
d 7C X 2.5 mm2 Lot 1 0 0 0
e 10C X 2.5 mm2 Lot 1 0 0 0
f 14C X 2.5 mm2 Lot 1 0 0 0
g 19C X 2.5 mm2 Lot 1 0 0 0
h 27C X 2.5 mm2 Lot 1 0 0 0
Materials for earthing mat with all materials and accessories as
well as spikes as per requirement of design as per IEEE
N standards for complete earthing of grid Sub-Station with the
followings. (The quantity is tentative and final quantity will
depend on actual design):-
40 mm MS rod for main earth mat including treated chemical type
1 MT 65 0 0 0
earthpits.
75x12 mm G.I Flats for risers for equipments, columns and
2 MT 55 0 0 0
structures
3 50x6 mm G.I flats for risers for all other equipments etc. MT 50 0 0 0
Materials for Earthing pits with supply of all earthing materials
4 LS 1 0 0 0
including base plate.
Sub- Station galvanized Steel structure (220 kV, 132 KV ) (The
O quantity is tentative and final quantity will depend on actual
design):-
1 Lattice structure with fasteners etc. MT 470 0 0 0
2 Standard structure for equipment support (other than CB) MT 210 0 0 0
P Mandatory spares (As per Tech, Specification) 0
1 220/132 kV, 200 MVA Transformer LS 1 0 0 0
2 220 kV CB LS 1 0 0 0
3 132 kV CB LS 1 0 0 0
4 220 kV Isolator LS 1 0 0 0
5 132 kV Isolator LS 1 0 0 0
6 220 kV CT, 1600A, 120% extended current rating Nos. 3 0 0 0
7 220 kV CT, 1600A, 150% extended current rating Nos. 3 0 0 0
8 132 kV CT, 1200A, 120% extended current rating Nos. 3 0 0 0
9 132 KV CT 600A 120% extended Nos. 3 0 0 0
10 220 kV CVT, 4400 pF Nos. 3 0 0 0
11 132 kV CVT, 8800 pF Nos. 3 0 0 0
12 216 kV surge arrester Nos. 3 0 0 0
13 120 kV surge arrester Nos. 3 0 0 0
14 C&R Panels LS 1 0 0 0
15 PLCC LS 0 0 0 0
16 Batteries (250V & 48V) LS 1 0 0 0
17 Battery Charger (250 V & 48 V) LS 1 0 0 0
18 DG Set LS 1 0 0 0
19 LT Switchgear LS 1 0 0 0
20 Fire fighting System LS 1 0 0 0
21 Erection Hardware LS 1 0 0 0
22 Illumination LS 1 0 0 0
Maintenance & Testing equipment for CB and transformer
Q comprising of the following equipments:(As per Tech
Specification)
BDV Test kit (2.5/4 mm) - 100 KV Microprocessor based (Reputed
1 No. 1 0 0 0
Make)
Mobile switchyard equipment testing van(Having all equipments
2 from single OEM, they should function in integerated way No. 1 0 0 0
altogether)
3 Digital multimeter (3½ digit) No. 1 0 0 0
4 Oil sampling bottle (Stainless steel) No. 2 0 0 0
5 Portable SF6 gas refilling device No. 1 0 0 0
6 Dew point kit for SF6 gas. (Reputed make) No. 1 0 0 0
7 SF6 gas evacuating, filtering and drying plant No. 1 0 0 0
Transformer oil filtration plant (4 KL / Hr. capacity) complete with
8 No. 1 0 0 0
all accessories
9 Circuit breaker analyser (reputed make) No. 1 0 0 0
10 Primary current injection kit (reputed make) No. 1 0 0 0
11 Secondary current injection kit No 1 0 0 0
12 Relay operation timer (reputed make) No. 1 0 0 0
13 Selective level meter No. 1 0 0 0
14 Selective level generator No. 1 0 0 0
Distance to fault locator (off line) with Signature Analyzer
15 Set 1 0 0 0
System suitable for 66 KV to 400 KV EHT line.
16 Tongue tester/ Clamp meter (Range 10-1000A) Nos 1 0 0 0
17 Tongue tester (Range 10mA-10A) Nos 1 0 0 0
18 Thermovision Camera High end (640 x 480 Pixel) Nos 1 0 0 0
19 DC Earth Fault Locator Nos 1 0 0 0
R Galvanised Cable Racks as per design requirement. MT 25 0 0 0
Sub- Station automation system comprising of necessary
equipments & materials wth networking and interfacing,
complete in all respect (Break up of item to be given by
S LS 1 0 0 0
contractor in technical data sheet with Part-I of the
tender)whereever applicable, the communication protocol shall
be preferably IEC61850 along with system furniture etc.
T Overhead shielding
Overhead shielding against lightning by galvanized steel wires and
i. fittings as per requirement and design (excluding lighting cum LS 1 0 0 0
lightning mast)
ii. Lighting cum lightning masts as per design Sets. 6 0 0 0
Total Price (Rs.) GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty Unit Price (Rs.) GST Rate
without GST (Rs) with GST
(4x5) % (6x7) (6+8)
1 2 3 4 5 6 7 8 9
Part-A Electrical
U
29.1 Air condltioning (2Ton)System as per technical Specification.
a Switchyard panel Room
i 220 KV (2 nos.) Nos 4 0 0 0
ii 132 KV (3 nos.) Nos 6 0 0 0
TOTAL 0.00 0.00 0.00
Bidder Name :
Bidder Signature:
NOTE
1. All rates and prices shall be specified in Rs. only in accordance with ITB 18
2. a). The bid price for (i) the items for which quantities have been indicated as lump sum or lot or set and/or (ii) where the quantities are to be estimated by the Bidder shall remain constant unless
there is change made in the Scope of Work by Employer and / or for price variation relating to price adjustment provisions. The quantities and unit prices (i) subsequently arrived while
approving the Bill of Quantities (BOQ) /Billing breakup of lump sum quantities/lot/Set and/or (ii) estimated by the bidder shall be for on account payment purpose only. In case additional quantities,
over and above the quantities BOQ/billing breakup and /or estimated by the bidder, are required for successful completion of the scope of work as per Technical Specification, the Bidder shall
execute additional quantities of these items for which no additional payment shall be made over and above the lump sum bid price. In case quantities of these items supplied at site are in excess
of that required for successful completion of scope of work, such additional quantities shall be the property of the bidders and they shall be allowed to take back the same from the site for
which no deduction from the lump sum bid price shall be made. Further, in case actual requirement of quantities for successful completion of scope of work is less than the quantities identified in the
approved BOQ /billing breakup and/or estimated by the bidder, the lump sum bid price shall remain unchanged and no deduction shall be made from the lump sum price due to such reduction of
quantities.
b) Items for whicch no rate or price has been entered in, will not be paid for by the employer when executed and shall be deemed covered by the other rates and prices in the Bill of Quantities.
3. Bidder to consider the GST rate as applicable.
4. For all main Equipment (Transformer, Current Transformer, CVT/VT. Surge Arrestor, Circuit Breaker,Isolator,Cable,etc.) to be procured, Contractor shall provide Type Test Certificate conducted
within last 5-yrs.
Design Services : 220/132 KV Jadugoda Substation & 2 Nos of 132 KV Bays at 132/33 KV Grid Substation Dhalbhumgarh
Schedule of Quantity & Prices for
Design, Engineering, Supply, Installation, Testing & Commissioning of 220/132 KV Jadugoda Substation & 2 Nos of 132 KV Bays at
132/33 KV Grid Substation Dhalbhumgarh
Bid Inviting Authority: General Manager, Contracts & Materials, Multi Lateral Funding Project
NIT No. 708/PR/JUSNL/2023-24
Total Price
Unit Price GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty (Rs.) without GST Rate
(Rs.) (Rs) with GST
GST
(4x5) % (6x7) (6+8)
1 2 3 4 5 6 7 8 9
DESIGN ENGINEERING charges shall be considered as included in the other schedules. Separate payment shall not be done
Design, Engineering(220/132 KV Jadugoda Substation
1 & 2 Nos of 132 KV Bays at 132/33 KV Grid Substation LOT 1 0.00 0.00 0.00
Dhalbhumgarh)
TOTAL 0.00 0.00 0.00
Bidder Name :
Bidder Signature:
NOTE
1. All rates and prices shall be specified in Rs. only in accordance with ITB 18
2. Bidder to consider the GST rate as applicable.
SCHEDULE - 4(A) :Installation & other Services : 220/132 KV Jadugoda Substation
Schedule of Quantity & Prices for
Design,Engineering, Supply, Installation, Testing & Commissioning of 220/132 KV Jadugoda Substation
Bid Inviting Authority: General Manager, Contracts & Materials, Multi Lateral Funding Project
NIT No. 708/PR/JUSNL/2023-24
Transport & Transport &
Total Price (Rs.) GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty Unit Price (Rs.) GST Rate Insurance Insurance with
without GST (Rs) with GST
without GST GST
(4x5) % (6x7) (6+8+10)
1 2 3 4 5 6 7 8 9 10 11
Part-A Electrical
A TRANSFORMER
A1 Power Transfomer
200 MVA Three phase power Transformer 220/132/33 KV Auto
Transformer Complete with all accessories, marshaling boxes,
1 Nos. 2 0 0 0
terminal connectors etc. with NIFPS with 10% additional
Transformer Oil of same quality
A2 LT TRANSFORMER 0 0 0
630 KVA 33/0.433KV LT SUBSTATION TRANSFORMER with
1 NOS 2 0 0 0
oil,accessories and terminal connectors with 10%extra oil.
B-1 220 kV EQUIPMENT 0 0 0
1 Circuit breaker (3 phase) 0 0 0
2500 A, 40 kA SF6 CB with support structure, marshalling boxes,
terminal connectors etc.(current rating shall be equal to the current
i) Set 8 0 0 0
rating for which the short cuircuit test reports shall be furnished.
(Spring- Spring Mechanism ) (spring- spring )
ISOLATORS (3 phase), with solid core insulators, marshalling
2 boxes, terminal connectors (Motor Operated) with moving contact 0 0 0
of HDEC copper only.
i) 1600 A, 40 kA with two earth switch (Double break Isolator) Set 9 0 0 0
ii) 1600 A, 40 kA with one earth switch (Double break Isolator) Set 8 0 0 0
1600 A, 40 kA without earth switch (Double break Isolator)
iii) Set 14 0 0 0
(Tandem arrangement)
iv) 2500 A, 40 kA with two earth switch (Double break Isolator) Nos. 2 0 0 0
CURRENT TRANSFORMER 5 Core (1 phase) WITH
3 0 0 0
MARSHALING BOXES TERMINAL CONNECTORS
1600-800-400-200/1-1-1-1-1 A, 120% extended current rating, 40
i) Nos. 27 0 0 0
kA, 0.2 class 5 core
220 KV CVT 4400 pF CVTs (1 phase) for phase to phase coupling
4 Nos. 21 0 0 0
with all accessories, terminal connectors etc.
5 216 kV Surge Arresters (1 phase) class-III with terminal connectors. Nos. 18 0 0 0
6 Portable discharge rods Nos. 6 0 0 0
B2 ERECTION HARDWARE (220 kV) 0 0 0
1.1 Erection Hardware (Without BPI) 0 0 0
Insulator strings antifog type & hardware, spacers, conductor (S),
Bus bar material, galvanised cable trays/ cable rack, bay MB,
Clamps, Connectors including, Junction box,PVC pipes for
0 0 0
equipment and lighting, all accessories etc. for the following (The
main I & main II buses shall be of quad Moose ACSR Conductor &
TBC as well as Bus Coupler will be of double Moose conductor.
220 kV, Double Main & Transfer bus type 0 0 0
i Line bay set 4 0 0 0
ii Transformer bay Set 2 0 0 0
iii TBC Set 1 0 0 0
iv BC Bay Set 1 0 0 0
Bus Extension for 10 Bays (one no each for main I, main II & trasfer
v Set 3 0 0 0
bus)
220 kV Solid Core, Bus post Insulators (including requirement for
1.2 Set 115 0 0 0
wave trap)
C1 132 kV EQUIPMENT 0 0 0
1 Circuit breaker (3 phase) 0 0 0
1600 A, 31.5 kA SF6 CB with support structure, marshalling boxes,
terminal connectors etc.(current rating shall be equial to the current
i) Set 7 0 0 0
rating for which the short cuircuit test reports shall be furnished.)
(Spring- Spring )
ISOLATORS (3 phase), with solid core insulators, marshaling
2 boxes, terminal connectors (Motor Operated) with moving contact 0 0 0
of HDEC copper only.
i) 1600 A, 31.5 kA with one earth switch (Double break Isolator) Set 6 0 0 0
ii) 1600A, 31.5 kA without earth switch (Double break Isolator) Set 8 0 0 0
1600 A, 31.5 kA without earth switch (Double break Isolator)
iii) Set 7 0 0 0
(Tandem arrangement)
2000 A, 31.5 kA without earth switch (Double break high level beam
iv) Set 2 0 0 0
mounted Isolator)
3 Portable discharge rods ( 1 phase) Nos. 6 0 0 0
4 Current Transformers 5 core (1 phase) 0 0 0
1200 -600-300-150/1-1-1-1-1 A, 5 core 0.2S class ,31.5 kA with
i) 120% extended current rating with marshalling boxes, terminal Nos. 21 0 0 0
connectors etc.
8800 pF CVTs (1 phase) with marshalling boxes, terminal
5 Nos. 15 0 0 0
connectors etc .
120 kV Surge arresters class-III ( 1 phase) with marshalling boxes,
6 Nos. 18 0 0 0
terminal connectors etc.
C2 0 0 0
1.1 ERECTION HARDWARE (132 kV) 0 0 0
Insulator strings antifog type & hardware, spacers, conductor (S),
Bus bar material, galvanised cable trays/Cable rack, bay MB,
Clamps, Connectors including, Junction box,PVC pipes for
0 0 0
equipment and lighting, all accessories etc. for the following (main
bus shall be of quad Moose conductor and transfer bus shall be
strung with double Moose conductor)
132 kV Main & Transfer bay 0 0 0
i Line bay Set 4 0 0 0
ii Transformer bay Set 2 0 0 0
iii TBC Bay Set 1 0 0 0
iv Bus for 8 bays (One for main bus & another for transfer bus) Set 2 0 0 0
1.2 132 kV Solid Core, Bus post Insulators for erection hardware Nos. 53 0 0 0
D 33 kV EQUIPMENT 0 0 0
1 Circuit Breaker (3 Phase) 0 0 0
1600 A, 25KA Vacume CB with support structure, marshalling
boxes, terminal connectors etc. (current rating shall be equail to the
i) Set 2 0 0 0
current rating for which the short circuit test report shall be
furnished) (Spring-Spring)
ISOLATORS (3 phase), with solid core insulators, marshalling
2 boxes, terminal connectors (Manually operated) with moving 0 0 0
contact of HDEC copper only.
i) 1600 A, 25 kA without earth switch (Double break Isolator) Set 2 0 0 0
ii) 1200A, Horn gap fuse ( 1 phase) Nos. 6 0 0 0
3 Current Transformers (1 phase) 0 0 0
600-300-150/1 A, 5 core 0.2 class 25 kA with 120% extended
i) Set 6 0 0 0
current rating with marshalling boxes terminal connectors
30 kV Surge arresters class 3 ( 1 phase) with marshalling boxes
4 Set 6 0 0 0
terminal connectors
5 33 kV Solid core Bus post Insulators for erection hardware Set 6 0 0 0
E LT Switchgear 0 0 0
i 415 V Main switch Board Set 2 0 0 0
415 V ACDB (no of feeders shall be asper the requirement of the
ii Set 2 0 0 0
project plus 20% extra feeders)
iii 415V MLDB Set 2 0 0 0
iv 415V Emergency LDB Set 2 0 0 0
250V DCDB (no of feeders shall be asper the requirement of the
v Set 2 0 0 0
project plus 20% extra feeders)
vi 48V DCDB Set 2 0 0 0
F CONTROL & RELAY PANELS 0 0 0
1 220 kV (Simplex panels) 0 0 0
Control Panel for two bays with All indicating meters/
1.1 multifunctions meters shall be communicable type with 0.2 class Nos. 4 0 0 0
accuracy.
1.2 a) CB relay panel with A/R Nos. 4 0 0 0
1.2 b) CB relay panel without A/R Nos. 4 0 0 0
Line protection panel with numerical distance protection relays and
earth fault / overcurrent relays complying to IEC 61850 Protocal
1.3 Nos. 4 0 0 0
with optical fiber ports sufficient DI/DO ports for scheme with
additional 6 DI/DO Ports for spare.
Transformer protection panel HV and LV sides) with numerical
differential protecton relays with earth fault/ over current relay
1.4 complying to IEC 61850 Protocal with optical fiber ports and Nos. 2 0 0 0
sufficient DI/DO for scheme with additional 6 DI/DO ports for
spare.
Bus Bar Protection Panel ( will be integrated type and will have min.
1.5 Set 1 0 0 0
4 zone with numerical type relay)
Transfer bus coupler panel with distance protection relay scheme
1.6 Nos 1 0 0 0
with all relays
1.7 Time synchonization eqp. Will have dual ethernet with RJ 45 port Set 1 0 0 0
2 132 kV (Simplex Panels) 0 0 0
2.1 132KV Control, Relay & Protection Panel (Simplex Types Panels) 0 0 0
a) CB panel with BCU (Line and Transfer coupler) Nos. 5 0 0 0
b) CB panel with BCU (Transformer) Nos. 2 0 0 0
132 KV line (with A/R) with numerical distance protection relays
and earth fault / overcurrent relays complying to IEC 61850 Protocal
C) with optical fiber ports sufficient DI/DO for scheme with additional Nos. 4 0 0 0
6 DI/DO for spare. All indicating meters/ multifunctions meters shall
be communicable type with 0.2 class accuracy.
132/33 KV Transformer (without A/R) with numerical differential
protection relays and earth fault / overcurrent relays complying to
D) Nos. 2 0 0 0
IEC 61850 Protocal with optical fiber ports sufficient DI/DO for
scheme with additional 6 DI/DO for spare.
132 kV TBC (with A/R) with numerical distance protection relays
and earth fault / overcurrent relays complying to IEC 61850 Protocal
E) with optical fiber ports sufficient DI/DO for scheme with additional Nos. 1 0 0 0
6 DI/DO for spare. All indicating meters/ multifunctions meters shall
be communicable type with 0.2 class accuracy.
F) Transformer ( CB relay Panel without A/R ) Nos. 2 0 0 0
3 33 KV CONTROL & RELAY PANELS 0 0 0
33 kV Panels (Duplex) 0 0 0
Control, Relay & Protection Panel for 0 0 0
Line with numerical type E.F & O/C relays complying to IEC 61850
a) Nos. 2 0 0 0
protocol
FOTE Fiber Optic Terminal Equipment based communication
system for all 220KV and 132KV Terminal lines including spare
G bay, approach cable, RTU Communication Modules, interfacing Lot 1 0 0 0
with SLDC (for speech + protection and for speech + data),
PDH/SDH etc all complete along with for GSS end
H BATTERIES (VRLA TYPE OF EXIDE MAKE) 0 0 0
1.1 250 V 0 0 0
a) 500 AH Sets. 2 0 0 0
1.2 48 V 0 0 0
a) 500 AH Sets. 2 0 0 0
I BATTERY CHARGER SYSTEM chloride 0 0 0
1.1 250 V, 60A/50A Float and float Cum Boost Charger Nos. 2 0 0 0
1.2 48 V, 60A/50A Float and float Cum Boost Charger Nos. 2 0 0 0
J FIRE PROTECTION SYSTEM 0 0 0
1.1 Portable Fire Extinguishers 0 0 0
a 4.5 Kg DCP Type Nos. 20 0 0 0
b 4.5 Kg CO2 Type Nos. 15 0 0 0
c 22.5 Kg CO2 type Nos. 10 0 0 0
d 12 Fire buckets with stand LS 5 0 0 0
Complete pumping arrangement for HVWS system & hydrant
system, complete with all piping, valves, fittings, etc. inside pump
1.2 Set 4 0 0 0
house. (Pump house separate from control room as well as water
storage tank to be constructed)
1.3 Smoke detection system with all accessories and fittings Set 3 0 0 0
Hydrant system with complete U/G & O/G piping & accessories etc.
(all items) out side the Pump House. Hydrant system shall cover the
1.4 Set 1 0 0 0
switchyard area, Transformers, control room, Stores etc. as per
tender specification.
Complete HVW spray system with complete O/G & U/G piping and
accessories etc. (all items) with all required materials and
1.5 LS 1 0 0 0
equipments out side the pump house for 150 MVA, 2
Nos,220/132/33 KV power transformers as per tender specification.
K ILLUMINATION SYSTEM 0 0 0
L CONTROL ROOM BUILDING: 0 0 0
1 Lighting Panel 0 0 0
a Lighting Panel (Indoor) Type ACP-1 as per Tech. Specification Nos. 2 0 0 0
b Lighting Panel (Indoor) Type DCP as per Tech. Specification Nos. 1 0 0 0
Transport & Transport &
Total Price (Rs.) GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty Unit Price (Rs.) GST Rate Insurance Insurance with
without GST (Rs) with GST
without GST GST
(4x5) % (6x7) (6+8+10)
1 2 3 4 5 6 7 8 9 10 11
Part-A Electrical
Lighting fixtures and receptacles (including accessories/ materials
etc. as per requirement like junction box, cable/wires, flexible
2 0 0 0
conduits (if required) from junction box to lighting fixtures,
mounting arrangements)
a Lighting fixture Type- F1 as per Tech. Specification Nos. 50 0 0 0
b Lighting fixture Type- FF: as per Tech. Specification Nos. 100 0 0 0
c Lighting fixture Type- IF: as per Tech. Specification Nos. 30 0 0 0
d Lighting fixture Type- FB: as per Tech. Specification Nos. 30 0 0 0
e Lighting fixture Type- PF: as per Tech. Specification Nos. 5 0 0 0
f 5/15 A, 240V: Indoor Receptacles 3 pin type (type RI) Nos. 20 0 0 0
g 15A, 240V: Out door receptacles 2 pole, 3 pin type (Type RO) Nos. 2 0 0 0
63A, 415V : Interlocked switch socket outdoor Receptacles (Type
h Nos. 2 0 0 0
RP)
3 Switchboards 0 0 0
Modular switch board with 4 nos. 5Amp. Switches and 1 no. 5/15
a Nos. 10 0 0 0
Amp. receptacles
b Modular switchboard with 6 nos. 5Amp. Switches Nos. 10 0 0 0
c Modular switchboard with 2 nos. 5Amp. Switches Nos. 10 0 0 0
d Modular switchboard with 6 nos. 32 Amp MCB Nos. 5 0 0 0
e Modular switchboard with 1 no. 32 Amp. MCB Nos. 5 0 0 0
4 Ceiling fans 0 0 0
a 1400 mm sweep with electronic step regulator Nos. 28 0 0 0
5 Exhaust fans (16') Indristrial Type Nos. 10 0 0 0
6 Wall mounted fans 400 mm sweep Nos. 2 0 0 0
7 Conduits & wires 0 0 0
Heavy duty PVC conduits as of 20/25/32 mm size complete with all
accessories for point wiring for Light points, Fans power points 5/15
a amps. With 2.5 sq.mm/4 mm2/6.0 mm2 copper for circuit wiring and LS 1 0 0 0
1.5 mm2 copper earth wire PVC insulated in green color including
wiring for submains i.e. wiring from Lighting panel to switch board.
Wiring from lighting panel to switch boards, from switchboard to
junction boxes for light points with 2.5/4.0/6.0 mm2 copper wire as
b LS 1 0 0 0
per technical specification, complete in all respect. 1.5 mm2 copper
wire (green) will be used for earthing inside conduits
c Telephone sockets 0 0 0
c.1 Single socket outlet comprising RJ-11 socket Nos. 10 0 0 0
c.2 Dual socket outlet comprising RJ-45 socket Nos. 5 0 0 0
c.3 EPAX (24/8) with 24 telephones Set 1 0 0 0
Junction boxes with 4 nos. of terminal blocks for indoor lighting
8 Nos. 2 0 0 0
excluding junction box supplied alongwith lighting fixture
Lighting Transformer 630 kVA, 33/0.433KV LT Transformer with
9 Nos. 2 0 0 0
oil , accessories and as per Tech. Specification.
10 Self supported aluminium ladder as per technical specification Nos. 3 0 0 0
11 Air Conditioning System (as per technical specification) 0 0 0
Air conditioning of control room building with high wall type 5 star
(a) Nos. 50 0 0 0
rated split air conditioner unit of 2 TR capacity with stabilizer
L ii FFPH Building 0 0 0
Lighting fixtures and receptacles (including accessories/ materials
etc. as per requirement like junction box, cable/wires, flexible
1 0 0 0
conduits (if required) from junction box to lighting fixtures,
mounting arrangements)
a Lighting fixture Type- F1: as per Tech. Specification Nos. 25 0 0 0
b Lighting fixture Type- IF: as per Tech. Specification Nos. 7 0 0 0
c Lighting fixture Type- FB: as per Tech. Specification Nos. 12 0 0 0
d Lighting fixture Type- PF: as per Tech. Specification Nos. 3 0 0 0
e 5/15 A, 240V: Indoor Receptacles 3 pin type (type RI) Nos. 5 0 0 0
2 Switchboards 0 0 0
Modular switch board with 4 nos. 5Amp. Switches and 1 no. 5/15
a Nos. 7 0 0 0
Amp. receptacles
c Modular switchboard with 2 nos. 5Amp. Switches Nos. 5 0 0 0
3 Ceiling fans 0 0 0
a 1400 mm sweep with electronic step regulator Nos. 2 0 0 0
4 Exhaust fans (16') Indristrial Type Nos. 4 0 0 0
5 Wall mounted fans 400 mm sweep Nos. 4 0 0 0
6 Conduits & wires 0 0 0
Heavy duty PVC conduits as of 20/25/32 mm size complete with all
accessories for point wiring for Light points, Fans power points 5/15
a amps. With 2.5 sq.mm/4 mm2/6.0 mm2 copper for circuit wiring and LS 1 0 0 0
1.5 mm2 copper earth wire PVC insulated in green color including
wiring for submains i.e. wiring from Lighting panel to switch board.
Wiring from lighting panel to switch boards, from switchboard to
junction boxes for light points with 2.5/4.0/6.0 mm2 copper wire as
b Lot 1 0 0 0
per technical specification, complete in all respect. 1.5 mm2 copper
wire (green) will be used for earthing inside conduits
Junction boxes with 4 nos of terminal blocks for indoor lighting
7 Nos. 2 0 0 0
excuding junction box supplied alongwith lighting fixtures.
L. III Outdoor lighting (Switchyard and street lighting) 0 0 0
1 Lighting panel 0 0 0
a Lighting panel (Outdoor) Type ACP - 2 Nos. 8 0 0 0
b Lighting panel (Outdoor) Type ACP - 3 Nos. 3 0 0 0
Lighting fixtures and receptacles (including accessories/ materials
etc. as per requirement like junction box, cable/wires, flexible
2 0 0 0
conduits (if required) from junction box to lighting fixtures,
mounting arrangements)
a Lighting fixture Type- SF1: as per Tech. Specification Nos. 20 0 0 0
b Lighting fixture Type- SF2: as per Tech. Specification Nos. 30 0 0 0
c Lighting fixture Type- MP: as per Tech. Specification Nos. 6 0 0 0
d Lighting fixture Type- SC: as per Tech. Specification Nos. 35 0 0 0
e 15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO) Nos. 10 0 0 0
f 63A, 415V: Interlocked switch socket outdoor receptacles (Type RP) Nos. 10 0 0 0
3 Lighting poles Type A1 Nos. 50 0 0 0
4 Lighting poles Type E1 Nos. 20 0 0 0
5 Cart wheel mounted aluminium ladder as per Tech. Specification Nos. 1 0 0 0
L-IV Diesel Generator Set along with Control Panel (250 KVA) Set 1 0 0 0
Cables alongwith associated accessories like clamps, glands, lugs
M 0 0 0
and straight joints etc.
1.1 Power cables (XLPE) 1.1 kV 0 0 0
a 1C X 630 mm2 Lot 1 0 0 0
b 3.5C X 300 mm2 Lot 1 0 0 0
c 3.5C X 150 mm2 Lot 1 0 0 0
d 1C X 150 mm2 Lot 1 0 0 0
1.2 Power cables (PVC) 1.1 kV 0 0 0
a 3.5C X 70 mm2 Lot 1 0 0 0
b 3.5C X 35 mm2 Lot 1 0 0 0
c 4C X 16 mm2 Lot 1 0 0 0
d 4C X 6 mm2 Lot 1 0 0 0
e 2C X 6 mm2 Lot 1 0 0 0
1.3 Control cable (PVC) 1.1 kV 0 0 0
a 2C X 2.5 mm2 Lot 1 0 0 0
b 3C X 2.5 mm2 Lot 1 0 0 0
c 5C X 2.5 mm2 Lot 1 0 0 0
d 7C X 2.5 mm2 Lot 1 0 0 0
e 10C X 2.5 mm2 Lot 1 0 0 0
f 14C X 2.5 mm2 Lot 1 0 0 0
g 19C X 2.5 mm2 Lot 1 0 0 0
h 27C X 2.5 mm2 Lot 1 0 0 0
Materials for earthing mat with all materials and accessories as
well as spikes as per requirement of design as per IEEE
N standards for complete earthing of grid Sub-Station with the 0 0 0
followings. (The quantity is tentative and final quantity will
depend on actual design):-
40 mm MS rod for main earth mat including treated chemical type
1 MT 65 0 0 0
earthpits.
75x12 mm G.I Flats for risers for equipments, columns and
2 MT 55 0 0 0
structures
3 50x6 mm G.I flats for risers for all other equipments etc. MT 50 0 0 0
Materials for Earthing pits with supply of all earthing materials
4 LS 1 0 0 0
including base plate.
Sub- Station galvanized Steel structure (220 kV, 132 KV ) (The
O quantity is tentative and final quantity will depend on actual 0 0 0
design):-
1 Lattice structure with fasteners etc. MT 470 0 0 0
2 Standard structure for equipment support (other than CB) MT 210 0 0 0
R Galvanised Cable Racks as per design requirement. MT 25 0 0 0
Sub- Station automation system comprising of necessary
equipments & materials wth networking and interfacing,
complete in all respect (Break up of item to be given by
S LS 1 0 0 0
contractor in technical data sheet with Part-I of the
tender)whereever applicable, the communication protocol shall
be preferably IEC61850 along with system furniture etc.
T Overhead shielding 0 0 0
Overhead shielding against lightning by galvanized steel wires and
i. fittings as per requirement and design (excluding lighting cum LS 1 0 0 0
lightning mast)
ii. Lighting cum lightning masts as per design Sets. 6 0 0 0
U CIVIL WORKS (as per specification) 0 0 0
Foundation works for all equipments & structures including
CUM 6500 0 0 0
1 transformers (furnish schedule)
Supply and placement of Reinforcement steel MT 350 0 0 0
Concrete road (including all crossings) as per approved drawing
2 0 0 0
including reinforcement and concrete
a Road 5.5 Mtr. Wide RM 500 0 0 0
b Road 3.75 Mtr. Wide RM 1300 0 0 0
Construction of new cable trenches including all types of crossing,
3 RM 2600 0 0 0
cable trench covers (RCC) as per design.
All civil works as per drawing and specification for the following
4 0 0 0
buildings (Complete with finishing):
Construction of complete Control Room Building (double storied )
of requisite size , with floors as per specification, Aluminium doors
a) and windows, glass panels, lavatory, provision for lifting heavy sqm 550 0 0 0
equipment to first floor, collapsible gate, grills, water storage tank
etc. as per tender specification.
b) Ventillation System LS 1 0 0 0
c) FF cum PH building with Water tank for fire fighting. LS 1 0 0 0
d) Parking Shed Suitable for 10 light vehicle Sq. M 150 0 0 0
Rain water harvesting including reinforcement and concrete as per
5 LS 1 0 0 0
drawing.
Construction of complete water drainage system with drain inside
i. switchyard area, water sump. supply and installation of 3HP LS 1 0 0 0
dewatering pumps
ii Supplying & erection dewatering pumps 0 0 0
(a) 5 HP Nos. 2 0 0 0
(b) 0.5 HP Nos. 2 0 0 0
Water supply arrangement (from borewell to fire water tank & other
6 0 0 0
use.)
6”dia deep tube well (Deep Boring) complete with piping for water
i LS/ Lot 2 0 0 0
supply (Incld. overhead PVC Tank 1000Ltr x 02 Nos.Min.)
7.5 H.P. motor and pump set with associated piping, construction of
ii LS/ Lot 2 0 0 0
Pump house for water supply purposes
iii Hand pump with separate boring with 1.5” pipe LS/ Lot 1 0 0 0
7 Septic tank and soak pit complete as per the drawing Lot 2 0 0 0
8 Construction of sand pits 15' X 10' X 5' size with sand. LS 4 0 0 0
Complete work of Construction of store shed (100ftX30ft). With
9 Two MS galvanized racks to be provided each of 5ft. wide, 20ft long LS 1 0 0 0
and 9ft height with minimum three rows
Construction of room for DG set of requisite size (Minimum 6m X
10 LS 1 0 0 0
6m)
Construction of Transformer oil soak pit as per drawing and CBIP
11 LS 2 0 0 0
recommendation
12 Soil investigation, contour mapping, layout details etc. LS 1 0 0 0
Land cleaning incl. cutting shrubs & bushes, leveling, anti-weed
13 LS 1 0 0 0
treatment,
Providing antiweed treatment and laying of plain cement concrete
14 Sq. M 25000 0 0 0
1:4:8 before stone chips filling.
15 Stone/gravel spreading in switchyard excluding PCC Sq. M 25000 0 0 0
Transport & Transport &
Total Price (Rs.) GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty Unit Price (Rs.) GST Rate Insurance Insurance with
without GST (Rs) with GST
without GST GST
(4x5) % (6x7) (6+8+10)
1 2 3 4 5 6 7 8 9 10 11
Part-A Electrical
Chain link fencing of switchyard (galvanized wires and angles) with
16 requisite foundation work, necessary earthing and paintng with LS 1 0 0 0
Aluminium paint of standard quality.
Construction of 5.5 meter RCC approach road from main road up to
17 LS 1 0 0 0
switchyard gate with culvert etc (Max. 200 mtr.)
Supply of Godrej make furniture for control room and office in
charge of Grid Sub-station & computers ( 02 desktops with scanner
18 LS 1 0 0 0
and printer & 01 laptop) (Minimum 25 nos. of chairs, 5 tables and 5
steel Almirahs)
19 Landscaping of the area with plantation, lawn etc. LS 1 0 0 0
20 Boundary Wall 0 0 0
20.1 RCC framed masonary wall 8feet height with barbared wire fencing R.M. 1600 0 0 0
Painting of boundary wall with weather free paint of standard and
20.2 LS 1 0 0 0
approved make.
Boundary wall Gate (as per approved drawing) suitable for heavy
20.3 Nos 2 0 0 0
vehicle movements.
20.4 Site Leveling work including Contour Survey 0 0 0
a Earthwork in cutting & filling within S/S Boundary. CuM 20800 0 0 0
b Earthwork in filling within S/S with borrowed earth. CuM 4400 0 0 0
Land development, earthfilling after contour mapping, land
grading, land cleaning incl. cutting of shrubs & bushes, levelling,
21 antiweed treatment, - upto FGL= HFL+ 300mm (as per requirment) LS 1 0 0 0
and Construction of expanded metal fencing and barbed wire and
painting (as per specification)
Watering system for all treated earth pits including laying of
22 LOT 1 0 0 0
necessary pipes, valves, storage tank, etc.
Design & Construction of 01 block consisting of 06 flat multistorey
(G+2) building with two bed room quarter for staff with Electrical
23 M2 470 0 0 0
wiring, water supply & Sanitary installation all complete as per
approved drawing & design.
Design & Construction of 01 Block consisting of 06 flat multistorey
(G+2) building with three bed room quarter for officer with
24 M2 518 0 0 0
Electrical wiring, water supply & Sanitary installation all complete
as per approved drawing & design.
Construction of Fully furnished Guest House including all basic
25 M2 200 0 0 0
amenities and furnitures
Construction of dormetory fully furnished Dormetary including all
26 basic amenities and furnitures suitable for 10 persons (Security M2 150 0 0 0
Guards)
Construction of dormetory fully furnished Dormetary including all
27 basic amenities and furnitures suitable for 10 persons (Maintenance M2 100 0 0 0
Gangs)
Design & Construction of 3.5 Mtr. wide PCC Road for colony area
28 M2 700 0 0 0
with all complete as per approved drawing and design.
29 Switchyard panel room 0 0 0
(i) 220 KV (2 nos) L.S. 1 0 0 0
(ii) 132 KV (3 nos) L.S. 1 0 0 0
29.1 Air condltioning (2 Ton)System as per technical Specification. 0 0 0
a Switchyard panel Room 0 0 0
i 220 KV (2 nos.) Nos 4 0 0 0
ii 132 KV (3 nos.) Nos 6 0 0 0
Security Room (Size-6Mtrx3Mtr) along with septic tank and soak
pit(2 Mtr x 1.5Mtr) as per drawing complete (excluding exavation,
30 Nos. 1 0 0 0
PCC, RCC & reinforcement steel, which shall be measured and paid
seperately)
TOTAL 0.00 0.00 0.00 0.00 0.00
Bidder Name :
Bidder Signature:
NOTE
1. All rates and prices shall be specified in Rs. only in accordance with ITB 18
2. a). The bid price for (i) the items for which quantities have been indicated as lump sum or lot or set and/or (ii) where the quantities are to be estimated by the Bidder shall remain constant unless there is change made in the Scope of
Work by Employer and / or for price variation relating to price adjustment provisions. The quantities and unit prices (i) subsequently arrived while approving the Bill of Quantities (BOQ) /Billing breakup of lump sum quantities/lot/Set
and/or (ii) estimated by the bidder shall be for on account payment purpose only. In case additional quantities, over and above the quantities BOQ/billing breakup and /or estimated by the bidder, are required for successful completion of
the scope of work as per Technical Specification, the Bidder shall execute additional quantities of these items for which no additional payment shall be made over and above the lump sum bid price. In case quantities of these items
supplied at site are in excess of that required for successful completion of scope of work, such additional quantities shall be the property of the bidders and they shall be allowed to take back the same from the site for which no
deduction from the lump sum bid price shall be made. Further, in case actual requirement of quantities for successful completion of scope of work is less than the quantities identified in the approved BOQ /billing breakup and/or
estimated by the bidder, the lump sum bid price shall remain unchanged and no deduction shall be made from the lump sum price due to such reduction of quantities.
b) Items for whicch no rate or price has been entered in, will not be paid for by the employer when executed and shall be deemed covered by the other rates and prices in the Bill of Quantities.
3. Bidder to consider the GST rate as applicable.
4. For all main Equipment (Transformer, Current Transformer, CVT/VT. Surge Arrestor, Circuit Breaker,Isolator,Cable,etc.) to be procured, Contractor shall provide Type Test Certificate conducted within last 5-yrs.
SCHEDULE-5 : Grand Summary : Design, Engineering, Supply, Installation, Testing & Commissioning of
220/132 KV Substation at Jadugoda & 2 Nos of 132 KV Bays at 132/33 KV Grid Substation Dhalbhumgarh
along with Dismantalling works
Schedule of Quantity & Prices for
Design, Engineering, Supply, Installation, Testing & Commissioning of 220/132 KV Substation at Jadugoda &
2 Nos of 132 KV Bays at 132/33 KV Grid Substation Dhalbhumgarh along with Dismantalling works
Bid Inviting Authority: General Manager, Contracts & Materials, Multi Lateral Funding Project
NIT No. 708/PR/JUSNL/2023-24
Amount (in Rs.)
Sl. No. Description
Total
Total Supply Price excluding GST (Rs.)-Schedule No. 2(A) &
1 2(B) 0.00
Total Erection, Transport and Insurance price along with
2 dismantalling excluding GST (Rs.)-Schedule No. 4(A), 4(B), 4(C) 0.00
Grand Total 0.00
Bidder Name :
Bidder Signature :
NOTE
1. All rates and prices shall be specified in Rs. only in accordance with ITB 18
2. a). The bid price for (i) the items for which quantities have been indicated as lump sum or lot or set and/or (ii) where the quantities are to be
estimated by the Bidder shall remain constant unless there is change made in the Scope of Work by Employer and / or for price variation relating to
price adjustment provisions. The quantities and unit prices (i) subsequently arrived while approving the Bill of Quantities (BOQ) /Billing breakup of
lump sum quantities/lot/Set and/or (ii) estimated by the bidder shall be for on account payment purpose only. In case additional quantities, over and
above the quantities BOQ/billing breakup and /or estimated by the bidder, are required for successful completion of the scope of work as per Technical
Specification, the Bidder shall execute additional quantities of these items for which no additional payment shall be made over and above the lump sum
bid price. In case quantities of these items supplied at site are in excess of that required for successful completion of scope of work, such
additional quantities shall be the property of the bidders and they shall be allowed to take back the same from the site for which no deduction from the
lump sum bid price shall be made. Further, in case actual requirement of quantities for successful completion of scope of work is less than the
quantities identified in the approved BOQ /billing breakup and/or estimated by the bidder, the lump sum bid price shall remain unchanged and no
deduction shall be made from the lump sum price due to such reduction of quantities.
b) Items for whicch no rate or price has been entered in, will not be paid for by the employer when executed and shall be deemed covered by the other
rates and prices in the Bill of Quantities.
3. Bidder to consider the GST rate as applicable.
SCHEDULE-6 : Recommended Spare Parts : 220/132 KV Substation at Jadugoda & 2 Nos of 132 KV Bays at 132/33 KV Grid
Substation Dhalbhumgarh
Schedule of Quantity & Prices for
Design, Engineering, Supply, Installation, Testing & Commissioning of 220/132 KV Substation at Jadugoda & 2 Nos of 132
KV Bays at 132/33 KV Grid Substation Dhalbhumgarh
Bid Inviting Authority: General Manager, Contracts & Materials, World Bank Funded Project
NIT No. 708/PR/JUSNL/2023-24
Total Price
GST Amount Total Price
Sl. No. Item Description Unit Qty Unit Price (Rs.) (Rs.) without GST Rate
(Rs) (Rs.) with GST
GST
(4x5) % (6x7) (6+8)
1 2 3 4 5 6 7 8 9
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
Total 0.00 0.00 0.00
Bidder Name :
Bidder Signature :
NOTE
1. All rates and prices shall be specified in Rs. only in accordance with ITB 18
2. This schedule will not be included for bid evaluation purpose.
3. Bidder to consider the GST rate as applicable.
SCHEDULE - 2(B) : Supply and Mandatory Spare Parts : 2 Nos of 132 KV Bays at 132/33 KV Grid Substation Dhalbhumgarh
Schedule of Quantity & Prices for
Design, Engineering, Supply, Installation, Testing & Commissioning of 2 Nos of 132 KV Bays at 132/33 KV Grid Substation Dhalbhumgarh
Bid Inviting Authority: General Manager, Contracts & Materials, Multi Lateral Funding Project
NIT No. 708/PR/JUSNL/2023-24
Total Price (Rs.) GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty Unit Price (Rs.) GST Rate
without GST (Rs) with GST
(4x5) % (6x7) (6+8)
1 2 3 4 5 6 7 8 9
Part-A Electrical
A 132KV Bays
A-1 Circuit Breaker
1250A, 31.5 KA SF6 CB with support Structure. Marshalling boxes,
terminal connectors etc.(current rating shall be equal to the current
rating for which the short circuit test reports shall be furnished) Nos. 2 0 0 0
(spring-spring)
A-2 Current Transformer
132KV CTs 1 Ph 600-300-150/1A, 5 core 120% thermal rating,
31.5KA with 120% extended current rating with marshalling boxes, Nos. 6 0 0 0
terminals connectors etc., Accuracy Class 0.2S
A-3 Isolators (3 phase), with solid core insulators marshalling boxes,
terminal connectors(motor operated) with moving contact of HDEC
copper only
a Isolator without E/S, 3 Ph, 1250A 31.5KA Double Break set 5 0 0 0
b Isolator with one E/S, 3Ph, 1250A 31.5 KA Double Break set 2 0 0 0
A-4 132KV, 8800pF, 10KA 3-winding, single Phase Feeder CVT
(accuracy class 0.2S) with marshalling boxes, terminals connectors Nos. 6 0 0 0
etc.
A-5 132KV, 3-winding, single phase potential Transformer (accuracy
Nos. 6 0 0 0
class 0.2S) with marshalling boxes, terminals connectors etc.
A-6 120KV LA (1Ph), Class III with marshalling boxes, terminals
Nos. 9 0 0 0
connectors etc.
A-8 132KV Solid core BPI Nos. 36 0 0 0
A-9 132KV grade 1xC 630sqmm XLPE insulated copper as per technical
km 0.50 0 0 0
specification .
A-10 Cable termination as per technical specification for interconnection
with overhead transmission line for 132kv cable (including support Nos. 12 0 0 0
insulators)
A-11 OPGW
UGFO Cabling
(a) 2/3/4 way joint box (48 Fiber) including coiling bracket as per
requirment for looping /coiling of 30 meters of cable as per technical Nos. 2 0 0 0
requirement
A-12 PLB HDPE pipe O.D 40mm including accessories as per technical
km 1 0 0 0
specification
A-13 FODP 48 F indoor type , rack mounted with FCPC Coupling and
Nos. 4 0 0 0
pigtails
A-14 Fiber optic approach Cable including Harware set (like ties,clips,
0 0 0
cleats, conduits, ducts supports, fittings.
(a) 24 Fibre (DWSM) KM 1 0 0 0
(b) Hardware set for 24 Fiber optic approach cable. set 2 0 0 0
A-15 Optical cards 0 0 0
(a) L4.2 NO. 4 0 0 0
A-16 Patch Cards (Lcto LC/FC/PC)type 10mtrs lenght no. 8 0 0 0
A-17 VOIP telephone with licence of existing exchange set 2 0 0 0
A-18 Erection Hardware (Insulator strings antifog type and
hardware, spacers, conductors(S), bus bar materials, cable trays,
bay MB, clamps, connectors including, Junction box, PVC pipes
for equipments and lighting, all accesories etc. for the
following(main bus shall be Quad moose conductor and transfer
shal be strung with double moose conductor) and hardware, 0 0 0
conductor/ Bus Bar Materials, CT/CVT JB, BMK, Equipments,
connectors, cable tray/ cable rack/ cable rack, Buried cable,
Trench and other miscellaneous items)
a 132KV Line Feeder Bay set 2 0 0 0
b BUS for five nos. Of Bays for Transfer BUS ( 2 bays for now and
set 1 0 0 0
three bays for future extension)
A19 Control & Relay Panels 0 0 0
a 132KV Line Duplex C&R Panel (with auto reclosure) with
numerical distance protection and earth fault/overcurrent relay
compiling to IEC 61850 protocol with optical fibre ports sufficient
DI/DO scheme with additional 6 DI/DO for Spare.All indicating Nos. 2 0 0 0
meters/multifunctions meters shall be communicable type with 0.5
class accuracy
B-1 BATTERIES, BATTERY CHARGER 0 0 0
a 48V DCDB set 1 0 0 0
B-2 BATTERIES (Dry Cell exide make) 0 0 0
a 48Volt 300AH set 1 0 0 0
B-3 BATTERY CHARGER 0 0 0
a 48 Volt, 30/20A Fload and Float cum Boost Charger set 1 0 0 0
C CABLES along with associated accessries like clamps, glands,
0 0 0
lugs and straight joints etc.
C-1 Power Cable (XLPE) 1.1KV 0 0 0
a 3.5C x 150 sq mm KM 1 0 0 0
b 3.5C x 95 sq mm KM 1 0 0 0
c 1C x 150 sq mm KM 2 0 0 0
C-2 Power Cable (PVC) 1.1KV 0 0 0
a 3.5 X 35 sq mm KM 2 0 0 0
b 4C x 16 sq mm KM 1 0 0 0
c 4C x 6 sq mm KM 1 0 0 0
d 2C x 6 sqmm KM 1 0 0 0
C-3 Control Cables (PVC) 1.1KV 0 0 0
a 2C x 2.5 sq mm KM 2 0 0 0
b 3C x 2.5 sq mm KM 1 0 0 0
c 5C x 2.5 sqmm KM 2 0 0 0
d 7C x 2.5 sq mm KM 1 0 0 0
e 10C x 2.5 sqmm KM 1 0 0 0
f 14C x 2.5 sq mm KM 1 0 0 0
g 19C x 2.5 sq mm KM 2 0 0 0
D 40mm MS rod for Main Earthmat MT 20 0 0 0
E Treated Earthpit Nos. 12 0 0 0
F Steel Structures 0 0 0
Galvanized Gantry structures, equipment support structure, riser for
Lot 1 0 0 0
earth mat and nuts & bolts with fasteners for 132KV
H MANDATORY SPARES Lot 1 0 0 0
TOTAL 0.00 0.00 0.00
Bidder Name :
Bidder Signature:
NOTE
1. All rates and prices shall be specified in Rs. only in accordance with ITB 18
2. a). The bid price for (i) the items for which quantities have been indicated as lump sum or lot or set and/or (ii) where the quantities are to be estimated by the Bidder shall remain constant unless
there is change made in the Scope of Work by Employer and / or for price variation relating to price adjustment provisions. The quantities and unit prices (i) subsequently arrived while
approving the Bill of Quantities (BOQ) /Billing breakup of lump sum quantities/lot/Set and/or (ii) estimated by the bidder shall be for on account payment purpose only. In case additional quantities,
over and above the quantities BOQ/billing breakup and /or estimated by the bidder, are required for successful completion of the scope of work as per Technical Specification, the Bidder shall
execute additional quantities of these items for which no additional payment shall be made over and above the lump sum bid price. In case quantities of these items supplied at site are in excess
of that required for successful completion of scope of work, such additional quantities shall be the property of the bidders and they shall be allowed to take back the same from the site for
which no deduction from the lump sum bid price shall be made. Further, in case actual requirement of quantities for successful completion of scope of work is less than the quantities identified in the
approved BOQ /billing breakup and/or estimated by the bidder, the lump sum bid price shall remain unchanged and no deduction shall be made from the lump sum price due to such reduction of
quantities.
b) Items for whicch no rate or price has been entered in, will not be paid for by the employer when executed and shall be deemed covered by the other rates and prices in the Bill of Quantities.
3. Bidder to consider the GST rate as applicable.
4. For all main Equipment (Transformer, Current Transformer, CVT/VT. Surge Arrestor, Circuit Breaker,Isolator,Cable,etc.) to be procured, Contractor shall provide Type Test Certificate conducted
within last 5-yrs.
SCHEDULE - 4(B) : Installation & other Services: 2 Nos of 132 KV Bays at 132/33 KV Grid Substation Dhalbhumgarh
Schedule of Quantity & Prices for
Design, Engineering, Supply, Installation, Testing & Commissioning of 2 Nos of 132 KV Bays at 132/33 KV Grid Substation Dhalbhumgarh
Bid Inviting Authority: General Manager, Contracts & Materials, Multi Lateral Funding Project
NIT No. 708/PR/JUSNL/2023-24
Transport & Transport &
Total Price (Rs.) GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty Unit Price (Rs.) GST Rate Insurance Insurance with
without GST (Rs) with GST
without GST GST
(4x5) % (6x7) (6+8+10)
1 2 3 4 5 6 7 8 9 10 11
Part-A Electrical
A 132KV Bays
A-1 Circuit Breaker
1250A, 31.5 KA SF6 CB with support Structure. Marshalling boxes,
terminal connectors etc.(current rating shall be equal to the current
rating for which the short circuit test reports shall be furnished) Nos. 2 0 0 0
(spring-spring)
A-2 Current Transformer 0 0 0
132KV CTs 1 Ph 600-300-150/1A, 5 core 120% thermal rating,
31.5KA with 120% extended current rating with marshalling boxes, Nos. 6 0 0 0
terminals connectors etc., Accuracy Class 0.2S
A-3 Isolators (3 phase), with solid core insulators marshalling boxes,
terminal connectors(motor operated) with moving contact of HDEC 0 0 0
copper only
a Isolator without E/S, 3 Ph, 1250A 31.5KA Double Break set 5 0 0 0
b Isolator with one E/S, 3Ph, 1250A 31.5 KA Double Break set 2 0 0 0
A-4 132KV, 8800pF, 10KA 3-winding, single Phase Feeder CVT
(accuracy class 0.2S) with marshalling boxes, terminals connectors Nos. 6 0 0 0
etc.
A-5 132KV, 3-winding, single phase potential Transformer (accuracy
Nos. 6 0 0 0
class 0.2S) with marshalling boxes, terminals connectors etc.
A-6 120KV LA (1Ph), Class III with marshalling boxes, terminals
Nos. 9 0 0 0
connectors etc.
A-8 132KV Solid core BPI Nos. 36 0 0 0
A-9 132KV grade 1xC 630sqmm XLPE insulated copper as per technical
km 0.50 0 0 0
specification .
A-10 Cable termination as per technical specification for interconnection
with overhead transmission line for 132kv cable (including support Nos. 12 0 0 0
insulators)
A-11 OPGW 0 0 0
UGFO Cabling 0 0 0
(a) 2/3/4 way joint box (48 Fiber) including coiling bracket as per
requirment for looping /coiling of 30 meters of cable as per technical Nos. 2 0 0 0
requirement
A-12 PLB HDPE pipe O.D 40mm including accessories as per technical
km 1 0 0 0
specification
A-13 FODP 48 F indoor type , rack mounted with FCPC Coupling and
Nos. 4 0 0 0
pigtails
A-14 Fiber optic approach Cable including Harware set (like ties,clips,
0 0 0
cleats, conduits, ducts supports, fittings.
(a) 24 Fibre (DWSM) KM 1 0 0 0
(b) Hardware set for 24 Fiber optic approach cable. set 2 0 0 0
A-15 Optical cards 0 0 0
(a) L4.2 NO. 4 0 0 0
A-16 Patch Cards (Lcto LC/FC/PC)type 10mtrs lenght no. 8 0 0 0
A-17 VOIP telephone with licence of existing exchange set 2 0 0 0
A-18 Erection Hardware (Insulator strings antifog type and
hardware, spacers, conductors(S), bus bar materials, cable trays,
bay MB, clamps, connectors including, Junction box, PVC pipes
for equipments and lighting, all accesories etc. for the
following(main bus shall be Quad moose conductor and transfer
shal be strung with double moose conductor) and hardware, 0 0 0
conductor/ Bus Bar Materials, CT/CVT JB, BMK, Equipments,
connectors, cable tray/ cable rack/ cable rack, Buried cable,
Trench and other miscellaneous items)
a 132KV Line Feeder Bay set 2 0 0 0
b BUS for five nos. Of Bays for Transfer BUS ( 2 bays for now and
set 1 0 0 0
three bays for future extension)
A19 Control & Relay Panels 0 0 0
a 132KV Line Duplex C&R Panel (with auto reclosure) with
numerical distance protection and earth fault/overcurrent relay
compiling to IEC 61850 protocol with optical fibre ports sufficient
DI/DO scheme with additional 6 DI/DO for Spare.All indicating
Nos. 2 0 0 0
meters/multifunctions meters shall be communicable type with 0.5
class accuracy
B-1 BATTERIES, BATTERY CHARGER 0 0 0
a 48V DCDB set 1 0 0 0
B-2 BATTERIES (Dry Cell exide make) 0 0 0
a 48Volt 300AH set 1 0 0 0
B-3 BATTERY CHARGER 0 0 0
a 48 Volt, 30/20A Fload and Float cum Boost Charger set 1 0 0 0
C CABLES along with associated accessries like clamps, glands,
0 0 0
lugs and straight joints etc.
C-1 Power Cable (XLPE) 1.1KV 0 0 0
a 3.5C x 150 sq mm KM 1 0 0 0
b 3.5C x 95 sq mm KM 1 0 0 0
c 1C x 150 sq mm KM 2 0 0 0
C-2 Power Cable (PVC) 1.1KV 0 0 0
a 3.5 X 35 sq mm KM 2 0 0 0
b 4C x 16 sq mm KM 1 0 0 0
c 4C x 6 sq mm KM 1 0 0 0
d 2C x 6 sqmm KM 1 0 0 0
C-3 Control Cables (PVC) 1.1KV 0 0 0
a 2C x 2.5 sq mm KM 2 0 0 0
b 3C x 2.5 sq mm KM 1 0 0 0
c 5C x 2.5 sqmm KM 2 0 0 0
d 7C x 2.5 sq mm KM 1 0 0 0
e 10C x 2.5 sqmm KM 1 0 0 0
f 14C x 2.5 sq mm KM 1 0 0 0
g 19C x 2.5 sq mm KM 2 0 0 0
D 40mm MS rod for Main Earthmat MT 20 0 0 0
E Treated Earthpit Nos. 12 0 0 0
F Steel Structures 0 0 0
Galvanized Gantry structures, equipment support structure, riser for
Lot 1 0 0 0
earth mat and nuts & bolts with fasteners for 132KV
G Civil Works 0 0 0
a All Foundation (RCC/PCC) works for equipments, supports & sub-
Lot 1 0 0 0
station structure M-20 grade, RCC Cable trench with cover slab.
I Gravel filling in switchyard area including PCC and provision of
cement slurry. The gravel filling shall be done in the complete Lot 1 0 0 0
switchyard area.
J Soil Investigation Lot 1 0 0 0
E Land Development, excavation of foundation pits & cable trench,
earth filling, land grading , land cleaning including cutting of shrubes
and bushes levelling & Dressing, antiweed treatment including
earthfilling from borrow pits as per requirement and construction of
RCC retaining wall(from 132KV Transfer bus to 33KV Transfer Lot 1 0 0 0
bus), watering system for all treated earth pits including laying of
necessary pipes, valves etc., water drainage system (as per approved
drawing) as per site requirement.
L Control Room Building Extention 0 0 0
a) Construction of complete Control Room Building (double storied )
of requisite size , with floors as per specification, Aluminium doors
and windows, glass panels, lavatory, provision for lifting heavy sqm 50 0 0 0
equipment to first floor, collapsible gate, grills, water storage tank
etc. as per tender specification.
TOTAL 0.00 0.00 0.00 0.00 0.00
Bidder Name :
Bidder Signature:
NOTE
1. All rates and prices shall be specified in Rs. only in accordance with ITB 18
2. a). The bid price for (i) the items for which quantities have been indicated as lump sum or lot or set and/or (ii) where the quantities are to be estimated by the Bidder shall remain constant unless there is change made in the Scope of
Work by Employer and / or for price variation relating to price adjustment provisions. The quantities and unit prices (i) subsequently arrived while approving the Bill of Quantities (BOQ) /Billing breakup of lump sum quantities/lot/Set
and/or (ii) estimated by the bidder shall be for on account payment purpose only. In case additional quantities, over and above the quantities BOQ/billing breakup and /or estimated by the bidder, are required for successful completion of
the scope of work as per Technical Specification, the Bidder shall execute additional quantities of these items for which no additional payment shall be made over and above the lump sum bid price. In case quantities of these items
supplied at site are in excess of that required for successful completion of scope of work, such additional quantities shall be the property of the bidders and they shall be allowed to take back the same from the site for which no
deduction from the lump sum bid price shall be made. Further, in case actual requirement of quantities for successful completion of scope of work is less than the quantities identified in the approved BOQ /billing breakup and/or
estimated by the bidder, the lump sum bid price shall remain unchanged and no deduction shall be made from the lump sum price due to such reduction of quantities.
b) Items for whicch no rate or price has been entered in, will not be paid for by the employer when executed and shall be deemed covered by the other rates and prices in the Bill of Quantities.
3. Bidder to consider the GST rate as applicable.
4. For all main Equipment (Transformer, Current Transformer, CVT/VT. Surge Arrestor, Circuit Breaker,Isolator,Cable,etc.) to be procured, Contractor shall provide Type Test Certificate conducted within last 5-yrs.
SCHEDULE - 4(C) : Dismentalling work for : A) 2 Nos of 132 KV Bays b) 33 KV Bay & Substation galvanizd steel structure of railway bays at 132/33 KV Grid Substation
Dhalbhumgarh for termination of 132 KV New Jadugoda- Dhalbhumgarh Transmission Line at GSS Dhalbhumgarh
Schedule of Quantity & Prices for
Dismentalling work forA) 2 Nos of 132 KV Bays b) 33 KV Bay & Substation galvanizd steel structure of railway bays at 132/33 KV Grid Substation Dhalbhumgarh for
termination of 132 KV New Jadugoda- Dhalbhumgarh Transmission Line at GSS Dhalbhumgarh
Bid Inviting Authority: General Manager, Contracts & Materials, Multi Lateral Funding Project
NIT No. 708/PR/JUSNL/2023-24
Transport & Transport &
Total Price (Rs.) GST Amount Total Price (Rs.)
Sl. No. Item Description Unit Qty Unit Price (Rs.) GST Rate Insurance Insurance with
without GST (Rs) with GST
without GST GST
(4x5) % (6x7) (6+8+10)
1 2 3 4 5 6 7 8 9 10 11
A-1 TRANSFORMER
Removal from plinth/existing position and dragging of
1.1 transformer from its position to the point of loading (digging up Nos. 2 0 0 0
to 100feet)100feet-79510 ,After 200feet -422x200= 84400
315KVA,33/0.433KV LT , Sub station Transformer with terminal
1.2 connection Nos. 2 0 0 0
C-1 132 kV EQUIPMENT 0 0 0
1 Circuit breaker (3 phase) 0 0 0
1600 A, 31.5 kA SF 6 CB with support structure, marshalling boxes,
terminal connectors etc.(current rating shall be equial to the current
i) Nos. 2 0 0 0
rating for which the short cuircuit test reports shall be furnished.)
(Spring- Spring )
1250 A, 25 kA Vacume CB with support structure, marshalling
boxes, terminal connectors etc.(current rating shall be equial to the
ii) Nos. 2 0 0 0
current rating for which the short cuircuit test reports shall be
furnished.) (Spring- Spring )
ISOLATORS (3 phase), with solid core insulators, marshaling
2 boxes, terminal connectors (Motor Operated) with moving contact 0 0 0
of HDEC copper only.
i) 1600 A, 31.5 kA with one earth switch (Double break Isolator) Nos. 2 0 0 0
ii) 1250 A, 25 kA without earth switch (Double break Isolator) Nos. 2 0 0 0
3 Current Transformers 5 core (1 phase) 0 0 0
1200 -600-300-150/1-1-1-1-1 A, 5 core 0.2S class ,31.5 kA with
i) 120% extended current rating with marshalling boxes, terminal Nos. 2 0 0 0
connectors etc.
1600-300-150/1-1-1-1 A, 5 core 0.2S class ,25 kA with 120%
ii) extended current rating with marshalling boxes, terminal connectors Nos. 2 0 0 0
etc.
8800 pF CVTs (1 phase) with marshalling boxes, terminal
4 Nos. 3 0 0 0
connectors etc .
C – II 0 0 0
1.1 ERECTION HARDWARE (132 kV) 0 0 0
Insulator strings antifog type & hardware, spacers, conductor (S),
Bus bar material, galvanised cable trays/Cable rack, bay MB,
Clamps, Connectors including, Junction box,PVC pipes for
0 0 0
equipment and lighting, all accessories etc. for the following (main
bus shall be of quad Moose conductor and transfer bus shall be
strung with double Moose conductor)
132 kV Main & Transfer bay 0 0 0
i) Transformer bay Set 2 0 0 0
ii) 132 kV Solid Core, Bus post Insulators for erection hardware Nos. 4 0 0 0
O Sub- Station galvanized Steel structure (132 kV, 33 KV ) 0 0 0
1 Lattice structure with fasteners etc. MT 150 0 0 0
2 Standard structure for equipment support (other than CB) MT 50 0 0 0
TOTAL 0.00 0.00 0.00 0.00 0.00
Bidder Name :
Bidder Signature:
. Bidder to consider the GST rate as applicable.