Product datasheet
Specifications
variable speed drive ATV320 -
7.5kW - 380...500V - 3 phase -
book
ATV320U75N4B
Main
Range Of Produc Altivar Machine ATV320
Product Or Component Type Variable speed drive
Product Specific Application Complex machines
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Variant Standard version
Format Of The Drive Book
Mounting Mode Wall mount
Communication Port Protocol Modbus serial
CANopen
Option Card Communication module, CANopen
Communication module, EtherCAT
Communication module, Profibus DP V1
Communication module, PROFINET
Communication module, Ethernet Powerlink
Communication module, EtherNet/IP
Communication module, DeviceNet
[Us] Rated Supply Voltage 380...500 V - 15...10 %
Nominal Output Current 17.0 A
Motor Power Kw 7.5 kW for heavy duty
Emc Filter Class C2 EMC filter integrated
Ip Degree Of Protection IP20
Complementary
Discrete Input Number 7
Discrete Input Type STO safe torque off, 24 V DC, impedance: 1.5 kOhm
DI1...DI6 logic inputs, 24 V DC (30 V)
DI5 programmable as pulse input: 0…30 kHz, 24 V DC (30 V)
Discrete Input Logic Positive logic (source)
Negative logic (sink)
Discrete Output Number 3
Discrete Output Type Open collector DQ+ 0…1 kHz 30 V DC 100 mA
Open collector DQ- 0…1 kHz 30 V DC 100 mA
Analogue Input Number 3
Analogue Input Type AI1 voltage: 0...10 V DC, impedance: 30 kOhm, resolution 10 bits
AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30 kOhm, resolution 10 bits
AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by
configuration), impedance: 250 Ohm, resolution 10 bits
Analogue Output Number 1
Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
Mar 18, 2024 1
Analogue Output Type Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10
bits
Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10
bits
Relay Output Type Configurable relay logic R1A 1 NO electrical durability 100000 cycles
Configurable relay logic R1B 1 NC electrical durability 100000 cycles
Configurable relay logic R1C
Configurable relay logic R2A 1 NO electrical durability 100000 cycles
Configurable relay logic R2C
Maximum Switching Current Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7
ms: 2 A at 250 V AC
Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7
ms: 2 A at 30 V DC
Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 250 V AC
Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 30 V DC
Minimum Switching Current Relay output R1A, R1B, R1C, R2A, R2C: 5 mA at 24 V DC
Method Of Access Slave CANopen
4 Quadrant Operation Possible True
Asynchronous Motor Control Voltage/frequency ratio, 5 points
Profile Flux vector control without sensor, standard
Voltage/frequency ratio - Energy Saving, quadratic U/f
Flux vector control without sensor - Energy Saving
Voltage/frequency ratio, 2 points
Synchronous Motor Control Vector control without sensor
Profile
Transient Overtorque 170…200 % of nominal motor torque
Maximum Output Frequency 0.599 kHz
Acceleration And Deceleration Linear
Ramps U
S
CUS
Ramp switching
Acceleration/deceleration ramp adaptation
Acceleration/deceleration automatic stop with DC injection
Motor Slip Compensation Automatic whatever the load
Adjustable 0...300 %
Not available in voltage/frequency ratio (2 or 5 points)
Switching Frequency 2...16 kHz adjustable
4...16 kHz with derating factor
Nominal Switching Frequency 4 kHz
Braking To Standstill By DC injection
Brake Chopper Integrated True
Line Current 26.5 A at 380 V (heavy duty)
18.7 A at 500 V (heavy duty)
Maximum Input Current 26.5 A
Maximum Output Voltage 500 V
Apparent Power 16.2 kVA at 500 V (heavy duty)
Network Frequency 50...60 Hz
Relative Symmetric Network 5%
Frequency Tolerance
Prospective Line Isc 22 kA
Base Load Current At High 17.0 A
Overload
Power Dissipation In W Fan: 229.0 W at 380 V, switching frequency 4 kHz
With Safety Function Safely True
Limited Speed (Sls)
2 Mar 18, 2024
With Safety Function Safe Brake False
Management (Sbc/Sbt)
With Safety Function Safe False
Operating Stop (Sos)
With Safety Function Safe False
Position (Sp)
With Safety Function Safe False
Programmable Logic
With Safety Function Safe Speed False
Monitor (Ssm)
With Safety Function Safe Stop 1 True
(Ss1)
With Sft Fct Safe Stop 2 (Ss2) False
With Safety Function Safe Torque True
Off (Sto)
With Safety Function Safely False
Limited Position (Slp)
With Safety Function Safe False
Direction (Sdi)
Protection Type Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overheating protection: drive
Short-circuit between motor phases: drive
Thermal protection: drive
Width 150 mm
Height 308.0 mm
Depth 232.0 mm
Net Weight 4.4 kg
Environment
Operating Position Vertical +/- 10 degree
Product Certifications CE
ATEX
NOM
GOST
EAC
RCM
KC
Marking CE
ATEX
UL
CSA
EAC
RCM
Standards IEC 61800-5-1
Electromagnetic Compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to
IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Environmental Class (During Class 3C3 according to IEC 60721-3-3
Operation) Class 3S2 according to IEC 60721-3-3
Maximum Acceleration Under 150 m/s² at 11 ms
Shock Impact (During Operation)
Maximum Acceleration Under 10 m/s² at 13...200 Hz
Vibrational Stress (During
Operation)
Maximum Deflection Under 1.5 mm at 2...13 Hz
Vibratory Load (During Operation)
Permitted Relative Humidity Class 3K5 according to EN 60721-3
(During Operation)
Mar 18, 2024 3
Volume Of Cooling Air 60 m3/h
Overvoltage Category III
Regulation Loop Adjustable PID regulator
Speed Accuracy +/- 10 % of nominal slip 0.2 Tn to Tn
Pollution Degree 2
Ambient Air Transport -25…70 °C
Temperature
Ambient Air Temperature For -10…50 °C without derating
Operation 50…60 °C with derating factor
Ambient Air Temperature For -25…70 °C
Storage
Packing Units
Unit Type Of Package 1 PCE
Number Of Units In Package 1 1
Package 1 Height 20.500 cm
Package 1 Width 27.200 cm
Package 1 Length 32.800 cm
Package 1 Weight 5.620 kg
Unit Type Of Package 2 P06
Number Of Units In Package 2 10
Package 2 Height 75.000 cm
Package 2 Width 60.000 cm
Package 2 Length 80.000 cm
Package 2 Weight 69.960 kg
4 Mar 18, 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Resource performance
Upgraded Components Available
Well-being performance
Mercury Free
Rohs Exemption Information Yes
Certifications & Standards
Reach Regulation REACh Declaration
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
China Rohs Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins
Circularity Profile End of Life Information
Mar 18, 2024 5
Product datasheet ATV320U75N4B
Dimensions Drawings
Dimensions
Right and Front View
6 Mar 18, 2024
Product datasheet ATV320U75N4B
Right and Front View with EMC Plate
Mar 18, 2024 7
Product datasheet ATV320U75N4B
8 Mar 18, 2024
Product datasheet ATV320U75N4B
Mounting and Clearance
Mounting and Clearance
(1) Minimum value corresponding to thermal constraints.
Mar 18, 2024 9
Product datasheet ATV320U75N4B
Connections and Schema
Connection Diagrams
Diagram with Line Contactor
Connection diagrams conforming to standards ISO13849 category 1 and IEC/EN 61508 capacity SIL1, stopping
category 0 in accordance with standard IEC/EN 60204-1.
(1) Line choke (if used)
(2) Fault relay contacts, for remote signaling of drive status
Diagram with Switch Disconnect
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping
category 0 in accordance with standard IEC/EN 60204-1.
10 Mar 18, 2024
Product datasheet ATV320U75N4B
(1) Line choke (if used)
(2) Fault relay contacts, for remote signaling of drive status
Mar 18, 2024 11
Product datasheet ATV320U75N4B
Control Connection Diagram in Source Mode
(1) Analog output
(2) Analog inputs
(3) Reference potentiometer (10 kOhm maxi)
(4) Digital inputs
12 Mar 18, 2024
Product datasheet ATV320U75N4B
Digital Inputs Wiring
The logic input switch (SW1) is used to adapt the operation of the logic inputs to the technology of the programmable
controller outputs.
Switch SW1 set to “Source” position and use of the output power supply for the DIs.
Switch SW1 set to “Source” position and use of an external power supply for the DIs.
Switch SW1 set to “Sink Int” position and use of the output power supply for the DIs.
Switch SW1 set to “Sink Ext” position and use of an external power supply for the DIs.
Mar 18, 2024 13
Product datasheet ATV320U75N4B
14 Mar 18, 2024
Product datasheet ATV320U75N4B
Performance Curves
Derating Curves
Derating curve for the nominal drive current (In) as a function of temperature and switching frequency (SF).
40 °C (104 °F) - Mounting type A, B and C
50 °C (122 °F) - Mounting type A, B and C
60 °C (140 °F) - Mounting type B and C
In : Nominal Drive Current
SF : Switching Frequency
Mar 18, 2024 15