WP #46 Cooling Strategies For Ultra-High Density Racks and Blade Servers
WP #46 Cooling Strategies For Ultra-High Density Racks and Blade Servers
White Paper 46
Revision 7
by Neil Rasmussen
Contents
> Executive summary Click on a section to jump to it
Introduction 2
Rack power of 10 kW per rack or more can result from
the deployment of high density information technology Clearly defining power density in 2
equipment such as blade servers. This creates difficult the data center
cooling challenges in a data center environment where
the industry average rack power consumption is less Power and cooling requirements 6
than 2 kW. Five strategies for deploying ultra-high for the high-density enclosure
power racks are described, covering practical solutions Five strategies for deployment of 10
for both new and existing data centers. high-density enclosures and
blade servers
Value of compaction 15
Conclusion 17
Resources 19
white papers are now part of the Schneider Electric white paper library
produced by Schneider Electric’s Data Center Science Center
[email protected]
Cooling Strategies for Ultra-High Density Racks and Blade Servers
Introduction The power consumed by the equipment housed in a single rack enclosure can vary dramati-
cally. The average power consumed by an enclosure in a data center is about 1.7 kW, but
the maximum power that can be obtained by filling a rack with available high density servers,
such as blade servers, is over 20 kW. Such loads greatly exceed the power and cooling
design capabilities of the typical data center.
Data center operators have very little experience with enclosures drawing over 10 kW, but
recent trends suggest that many will be confronted with the need to install and provision
power and cooling for high density racks either singly or in groups.
The simple answer to this problem would be to provision a data center so that it is capable of
providing 20 kW of redundant power and cooling to every enclosure. Unfortunately, this is
simply not technically feasible or economically practical in almost any case. Making the
wrong choices when specifying a data center for high density operation can needlessly
increase the lifetime cost of the physical infrastructure by many times. The purpose of this
paper is to outline practical and effective strategies for deployment of high density enclosures
and blade servers.
First the concept of power density is reviewed. Next the actual power density values of
current and new data centers are examined. The practical approaches to achieving high
density are presented, along with their limitations and benefits. Finally, logical and practical
strategies for deploying high density computing are presented.
Clearly defining Very significant misunderstandings can occur when describing power density because the
meaning of the term “power density” is ambiguous. Power density is often expressed in
power density in Watts per square foot or Watts per enclosure. This simple description is sufficient when the
the data center power consumed by all enclosures is the same. However, in a real data center the power per
enclosure varies dramatically. In these real-world cases the power density measured at the
rack level, at the row level, and at the room level may all differ considerably. This variation in
the power density measured at the enclosure, row, and room has a significant impact on the
design of the power infrastructure support system, and has an even greater impact on the
design of the cooling system.
The difference in power density measured at the rack, row, and room levels is shown in
1
Figure 1 . In the figure, enclosures of 12 kW are installed in a typical room. In one case,
15% of the enclosures in the room draw 12 kW and the remainder draw, 1 kW. In the second
case, the same percent of enclosures draw 12 kW but they are clustered into a single row. In
the third case, all the enclosures in the room draw 12 kW. In each of these cases the peak
power density is the same at 12 kW per rack, which translates to 480 W / ft2 (5.2 kW / m2).
However, the row and the room power densities vary dramatically between the cases.
1
The rack and row densities in Figure 1 use a rack floor equivalent of 25 ft2. Commonly-used rack floor
equivalents vary from 25 to 30 ft2 (2.3- 2.8m2). For more about representing power density, see White
Paper 120, Guidelines for Specification of Data Center Power Density.
Figure 1
Power density in Watts per unit area, per rack, per
row, and per room for three room configurations
12 kW Rack 1 kW Rack
The difference between the rack, the row, and the room power densities reflected in Figure 1
are representative of realistic alternative installations. These differences significantly affect
the design of the power and cooling infrastructure. The total rating of the power system and
the cooling system is simply the sum total of the power consumed by the loads. This allows
the total size of the UPS and computer room air conditioners (CRACS) to be readily deter-
mined. The main problem related to the variation and the peak values of power density relate
to power and air distribution within the data center.
Note that the above descriptions of density are expressed in terms of total floor area, which
includes space such as aisles, which are needed but are in addition to the footprint area of
the enclosure. This is the most commonly used method to describe density and this termi-
nology will be used consistently throughout this paper. However, some literature, particularly
from computer OEMs, describes density in Watts per unit area where the area is restricted
the footprint of the enclosure. Such density numbers based on equipment footprint must be
adjusted downwards by approximately 75%.
ers, service personnel, and consulting engineers. The actual overall per-enclosure power
density value found agrees closely with the values found in recent surveys by the University
of California at Berkeley.
Table 1
Survey data regarding the design and actual
power density of data centers
90% of data
Characteristic Average across data Maximum example
centers are less
centers found
than
35 W / ft2 60 W / ft2 200 W / ft2
Design power density (0.38 kW / m2) (0.65 kW / m2) (2.15 kW / m2)
Note: enclosures include rack enclosure and equipment enclosures such as DASD and mainframe computers. Equipment larger than
a rack enclosure are counted as a number of rack enclosures equaling the same footprint
The data indicates that design power density for data centers is on average 35 W / ft2 (0.377
kW / m2) corresponding to 1.1 kW per enclosure if 30 ft2 (2.79 m2) per enclosure is assumed.
The finding that average per-enclosure actual power is greater than the design value is
possible because on average the design density of 35 W / ft2 (0.38 kW / m2) per enclosure is
not achieved. This occurs primarily because data centers are not fully populated with
enclosures. For example, a data center that has a design per-enclosure power density of 1.1
kW / enclosure at 30 ft2 (2.79 m2) 2 per enclosure may be able to power a per-rack power
density of 2.2 kW / enclosure if the enclosures are only using half of the available floor space.
Note that this data is for production environments only. Somewhat higher average and
maximum power density was found in development and test environments.
In Figure 2, the frequency distribution of per-rack power consumption based on survey data
is shown. 3 This provides additional insight into the drivers of power density. Each bar or bin
represents the percentage of racks exhibiting a power draw in the 500-Watt range up to the
2
Mitchell-Jackson, J.D., Koomey, J.G., Nordman, B., Blazek, M., Data Center Power Requirements:
Measurements From Silicon Valley, May 16, 2001. Master’s Thesis, Energy and Resources Group,
University of California. Berkeley, California.
3
This data is more difficult to obtain than the data in Table 1 because per-rack power measurement
instrumentation is not present in most data centers. In many cases the data had to be estimated by
taking the actual power data for a group of racks and then apportioning the power among the enclo-
sures using the extensive cross-vendor power consumption data maintained by Schneider Electric for
use in UPS sizing tools.
kW value indicated at the bottom of the bar. For example the 1.5 kW bar includes enclosures
with a power draw between 1 kW and 1.5 kW.
Note in Figure 2 that there are a substantial number of enclosures in a typical data center
that draw under 500 W. These enclosures include patch panels and racks with low-density
switches and low-density servers. Many of these racks also include substantial unused open
vertical space.
Note further in Figure 2 that the number of enclosures drawing power above 2 kW decreases
dramatically, and that the number of enclosures drawing more than 8 kW was insignificant.
25%
>90% of new
data centers
capability
20% Max Max
1U blade
% of Enclosures
serv er server
Figure 2 2003 actual data
15%
Average = 1.7kW
Frequency distribution of
actual rack power consumption,
showing relation to maximum 10%
possible rack configuration
5%
0%
5
5
5
5
5
.5
.5
5
5
5
5
5
.5
.5
.5
.5
.5
.5
1.
3.
5.
6.
7.
8.
9.
.
.
0.
2.
4.
10
11
13
15
17
18
19
12
14
16
Per Rack Power - kW
The next two lines represent the power densities that can be obtained by filling rack enclo-
sures with the highest density server products available today, which are 1U servers and
blade servers. These values greatly exceed the design values for new data centers and the
actual values of existing data centers. Although blade servers can exhibit higher power per
rack than 1U servers, it should be noted that at these power densities the blade servers
provide approximately twice the number of servers as 1U servers, suggesting that blade
servers draw approximately 40% less power per server than conventional 1U servers.
• Most enclosures in data centers operate at a power below the design value for the data
center
• High density computing equipment is not actually installed at the maximum density that
it is capable of achieving
• Power density values that are routinely talked about in the popular press are not
achieved by any significant number of current or impending data centers.
For purposes of this paper, the term “high density” will refer to enclosures of over 3 kW,
where the 3 kW value corresponds to the upper limit of the range of the average cooling
capability of current data centers.
Power and An example of a very high density enclosure would be a blade server installation consisting of
six 7U blade server frames in a 42U rack, with each blade chassis consuming 3 kW for a total
cooling power requirement of 18 kW. This means that 18 kW of power must be provided to the
requirements for enclosure, and that 18 kW of cooling must be provided to the enclosure. A system of this
type would typically be considered a mission-critical system and both power and cooling
the high-density redundancy would be required.
enclosure
Power requirement
From the power standpoint, this six-chassis blade system would most likely require (24) 20 A
power supply circuits at either 208 V or 230 V, assuming a typical four-wire configuration for
each dual-path chassis. The cabling associated with this circuitry is bulky and would
normally need to be run overhead to prevent the creation of airflow blockages under the
raised floor (if a raised floor is used). This is particularly true if there were a number of such
enclosures located near each other. Alternatively, if a raised floor is used the depth of the
raised floor could be increased to accommodate the wiring. In either case, substantial
additional wiring must be installed, which can be complicated and expensive if the data
center is operational. With these methods it is possible to provide redundant power to an
ultra-high density rack.
Cooling requirement
Cooling an ultra-high density enclosure is a much more difficult problem than providing
power. The blade server system described above would require approximately 2,500 cfm
(cubic feet per minute) (1,180 L/s) of cool air at the intake (based on a common value of 20°F
[11°C] exhaust air temperature rise) and would exhaust the same amount of heated air from
the rear of the enclosure. The equipment will draw this volume of air whether or not the
cooling system can provide it. If the room is not capable of providing this quantity of cool air
to the enclosure, then the enclosure will draw in its own hot exhaust air (or the exhaust air of
neighboring equipment) and eventually overheat. There are four key elements needed to
achieve the required cooling performance:
Each of these functions is very difficult to achieve. The difficulties of each of these are
addressed in the following sections.
substantially increased, and the spacing between racks substantially increased in order to
arrange for 8 vented tiles per enclosure. This is not feasible in a typical data center.
Figure 3 shows the rack enclosure cooling capacity as a function of effective cool airflow.
Effective cool airflow accounts for cool air leakage through the raised floor which is typically
about 25% of the total air supplied by the cooling units. While the rack cooling capacity rises
with increasing airflow, the figure shows that higher rack cooling capacities become more
difficult to attain. Cold aisle containment can increase rack cooling capacity up to about 10
kW / rack. Note that the cooling capacity of the raised floor is higher for blade servers than
for typical IT equipment. This is due to the fact that blade servers require, on average, 40%
less airflow for the same power when compared with typical IT equipment.
Figure 3
Available rack enclosure cooling capacity as a Contained aisle
function of effective cool airflow
12
Typical Perf tile With Grate tile Extreme
Capability Effort
10
Rack Power (kW)
8
Blade Servers
Standard IT Equipment
2
0
0 100 200 300 400 500 600 700 800 900 1000
[47.2] [94.4] [141.6] [188.8] [236.0] [283.2] [330.4] [377.6] [424.8] [471.9]
Figure 3 indicates that achieving airflow to a single rack above 300 cfm (142 L/s) requires
special effort including careful raised floor design, CRAC placement, air leakage, and the
control of under-floor airflow obstacles such as pipes, conduits, and cabling. Achieving
airflow above 500 cfm (236 L/s) requires the use of special floor tiles designed as open metal
grates. This could provide up to 700 cfm (330 L/s) per floor tile in a typical data center.
However, the use of these grilles dramatically alters the under-floor pressure gradients and
impacts the airflow in surrounding regions. The uniformity and predictability of the cooling
capacity can be impacted by these effects, creating undesirable and unpredictable cooling
capacity limits.
It is often suggested that increasing the depth of the raised floor will correct various problems,
including the uniformity of the cooling capacity. To study this problem Schneider Electric
used computational fluid dynamics (CFD) to simulate the effects of changing the raised floor
depth in typical designs. Some important results of this research are shown in Figure 4.
This data shows that the cooling capacity has a variation which is related to the depth of the
raised floor. As expected, the variation in cooling capacity per tile decreases as the raised
floor depth is increased.
However, there are two surprising findings. First, this data is relatively unaffected by the
magnitude of the airflow. That is, the variation of tile cooling capacity is controlled by the
floor design geometry, and relatively unaffected by the magnitude of the airflow. The second
surprising finding is that the airflow variation becomes extremely large when open-grate floor
tiles are used. For example, with a two-foot (0.61 m) raised floor the variation could be on
the order of 30% for a standard perforated tile, but 230% for a grate-type tile. In fact, in the
case of the grate-type tile, the airflow in some cases reverses and tiles draw air downward
instead of supplying it to the IT equipment.
Variations in tile airflow are undesirable but some averaging and sharing of airflow do take
place within the data center; for this reason, individual tile airflow variations of 30% should be
considered acceptable. However, the huge variations shown for grate-tiles in Figure 4 are
not acceptable since a fraction of rack locations would not receive sufficient cooling capacity.
Note further that increasing the raised floor depth is beneficial but still does not correct the
problem for any feasible floor depth. Therefore, while the occasional use of a grate-type tile
may be helpful, this data suggests that the use of such tiles is not an effective way to
increase the overall power density capability of a data center.
350%
Max % Tile Airflow Variation
300%
250%
Figure 4 56% Open Tiles (grate)
200%
Airflow variations as a function of
raised floor depth, for two
150%
different tile types
100%
25% Open Tiles (perforated)
50%
0%
1 2 3 4 5 6
[0.30] [0.61] [0.91] [1.22] [1.52]
Up to 30%
Floor Plenum Depth (feet) [meters] variation is
considered
acceptable
Even when an “extreme” cooling design is implemented, Figure 3 indicates that 3 to 4 grate-
type tiles would be needed to cool a hypothetical 18 kW rack enclosure. However, the typical
data center layout provides only 1 floor tile per rack enclosure. When this data is combined
with the airflow variation data of Figure 4, it suggests that conventional data center layout
Related resource with one vented tile per rack simply cannot cool racks of over approximately 6 kW per
White Paper 135 rack over a sustained area. This value could increase to as much as 10kW per rack over a
Hot Aisle vs. Cold Aisle sustained area when used with a hot or cold aisle containment system. For more information
Containment on containment see White Paper 135, Hot Aisle vs. Cold Aisle Containment.
Remove 2,500 cfm (1,180 L/s) of hot exhaust air from the enclosure
There are three ways to return air back to the cooling system: through the room, through a
duct or through the ceiling plenum. Ideally the hot exhaust air from the equipment would be
taken directly back to the cooling system without the opportunity to mix with the surrounding
air or be drawn into the intakes of equipment. This requires an unobstructed and direct return
path. For reference, carrying 2,500 cfm (1,180 L/s) in a 12” (30 cm) round duct requires an
air velocity of 35 miles per hour (56 km/hr). A high open ceiling with a bulk air return centrally
located at a high point is one means of providing this function. However, many data centers
depend on having the return air carried by return ductwork or a suspended ceiling plenum,
and many rely on bulk air return across the room underneath a ceiling which is only a few feet
higher than the enclosures. These cases represent technical challenges to the design.
The availability of return air capability at a specific rack enclosure is limited just as the supply
is limited. Like the supply side, attempts to provide more than about 400 cfm (189 L/s) return
air capability per rack over a sustained area requires specialized engineering to assure that
the system has the required performance and redundancy.
Keep the hot exhaust air away from the equipment air intake
The shortest supply path for air to reach the IT equipment air intake is the recirculation path
from the equipment’s own exhaust. An essential part of data center design is that the cool air
supply and hot exhaust return paths dominate this undesired recirculation path. This
becomes particularly challenging for high density environments, as the high airflow velocities
Related resource must overcome the resistances of the air distribution and return systems. Blanking panels,
White Paper 49 described later in this paper, are an effective solution for recirculation within the rack. This
Avoidable Mistakes that and other types of recirculation are covered in more detail in White Paper 49, Avoidable
Compromise Cooling Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms.
Performance in Data
Centers and Network Rooms
When the operating power density of conventional data centers is increased, the flow of air in
the plenum areas increases and the fundamental assumptions about the operation of the
shared-plenum system begin to break down. Turning off an individual CRAC unit can
radically alter the local airflow velocities within the plenum. The airflow at an individual floor
tile may even reverse, drawing air down into the floor as a result of the Venturi effect. The
operation of the cooling system under fault conditions becomes less predictable as power
density increases. For this reason high density installations are frequently simulated using
numerical simulation methods (computational fluid dynamics – CFD) to establish the pres-
ence of redundancy.
assure uninterrupted cooling. This necessity of having the cooling system on the UPS is a
major cost driver and a major barrier to deployment of high density computing.
Five strategies There are five basic ways to deploy high density enclosures and blade servers:
for deployment 1. Load spreading. Provide the room with the capability to power and cool to an average
of high-density value below the peak enclosure value, and spread out the load of any proposed enclo-
sures whose load exceeds the design average value by splitting the equipment among
enclosures and multiple rack enclosures.
blade servers 2. Rules-based borrowed cooling. Provide the room with the capability to power and cool
to an average value below the peak enclosure value, and use rules to allow high den-
sity racks to borrow adjacent underutilized cooling capacity.
3. Supplemental cooling. Provide the room with the capability to power and cool to an
average value below the peak enclosure value, and use supplemental cooling equip-
ment as needed to cool racks with a density greater than the design average value
4. Dedicated high-density areas. Provide the room with the capability to power and cool
to an average value below the peak enclosure value, provide a special limited area
within the room that has high cooling capacity, and limit the location of high density
enclosures to that area.
5. Whole-room cooling. Provide the room with the capability to power and cool any and
every rack to the peak expected enclosure density
Each of these approaches is discussed in turn along with its advantages and disadvantages.
This is the most popular solution for incorporating high-density equipment into today’s data
centers. Fortunately, 1U servers and blade servers do not need to be installed closely
spaced in the same enclosure, and can be spread out across multiple racks. By splitting
equipment among racks no rack need ever exceed the design power density and conse-
quently cooling performance is predictable.
Related resource Note that spreading out equipment among multiple racks leaves a sizable amount of unused
White Paper 44 vertical space within the racks. This space must be filled with blanking panels to prevent
Improving Rack Cooling degradation of cooling performance as described in White Paper 44, Improving Rack Cooling
Performance Using Blanking Performance Using Blanking Panels. An example of a modular snap-in blanking panel
Panels designed to seal racks is shown in Figure 5.
Figure 5
Example of a modular snap-in
rack blanking panel designed for
mass deployment in data
centers for airflow control (APC Detail of snap-in feature
# AR8136BLK)
The need to spread high density equipment over multiple racks is often driven by other
factors besides cooling. Delivery of the required number of power or data feeds to the rack
may not be feasible or practical, and in the case of 1U servers the bulk of wiring in the rear of
the enclosure may significantly block air or even prevent the closure of the rear doors.
This free solution is often practiced but rarely documented. This approach takes advantage
of the fact that some racks draw less power than the average design value. The cooling
delivery and return capacity that was available to the underutilized enclosures is available to
other enclosures in the same vicinity. A simple rule like “do not locate high density racks
near each other” has some beneficial effect, but more sophisticated rules can be put in place
that can reliably and predictably permit enclosures to be cooled to over twice the average
design value. These rules can be established by policy and compliance verified through the
monitoring of power consumption at the rack level. This function can be automated by a
management system, such as the ISX Manager from Schneider Electric. Automation of this
function will become essential as newer IT equipment is introduced which has power
consumption that varies with time.
An example of an effective rule, which could be implemented under this method, is provided
in Figure 6. This rule would be applied to new equipment deployments to establish that the
equipment can be deployed within the capacity of the cooling system. Under this rule,
cooling capacity not utilized by the immediately adjacent enclosures is available for cooling a
rack of equipment, which allows the peak enclosure power density to exceed the average
room cooling power by up to a factor of 3 if the cooling capacity of the adjacent enclosures is
not utilized. In typical data centers, this can be a very effective way to implement high
density enclosures because there are frequently neighboring enclosures that are not utilizing
the available cooling capacity.
This solution normally requires that the installation be planned in advance to be able to utilize
supplemental cooling equipment when and where needed. When a room has been planned
in this way, a variety of techniques can be used to supplement rack cooling. These include:
• Installation of specialty (grate-type) floor tiles or fans to boost the cool air supply from
the CRAC to an enclosure
• Installation of specialty return ducts or fans to scavenge the hot exhaust air from an
enclosure for return to the CRAC
• Installation of special racks or rack mounted cooling devices with the capability to pro-
vide the required cooling directly at the rack
Related resource These methods are the subject of discussion in White Paper 55, Rack Air Distribution
White Paper 55 Architecture for Mission Critical Facilities. These methods are only recently becoming
Rack Air Distribution available and are not deployed in significant numbers of data centers today. However, they
Architecture for Mission offer significant flexibility and with proper planning do not need to be purchased and installed
Critical Facilities until needed.
This approach requires prior knowledge of the fraction of high density enclosures, and the
ability to segregate those enclosures into a special area, and under these constraints can
achieve optimal space utilization. Unfortunately, prior knowledge of the fraction of high
density enclosures is not typically available. Therefore, this option is not available to many
users.
When a special area for high density can be identified, special high density technologies can
be installed to deliver predictable power and cooling density to that area. When the power
density exceeds 10 kW per rack, the unpredictability of airflow becomes the dominant
problem. The technologies that solve this problem are based on the principle of shortening
the airflow path between the cooling system and the rack.
An example of a modular high density power and cooling system for a cluster of high density
racks is the InfraStruXure HD shown in Figure 7. This system integrates a cluster of IT racks
with a high density air conditioning system and high density power distribution system in a
pre-manufactured, pre tested unit.
Figure 7
Door access
Example of a modular power and to hot aisle
cooling system for a dedicated and rear of IT
high density area within a data equipment
center. Modules of 2-12 IT racks,
rated at 20 kW per rack.
All hot exhaust
Integral rack air is captured
air conditioner within chamber
and neutralized
Equipment
racks take in
ambient air Can operate
from front on hard floor
or raised floor
The system shown in Figure 7 consists of a hot-aisle / cold aisle layout of IT racks. The key
operating principle of this system is the capture of all of the hot IT equipment exhaust air by
enclosing the hot aisle, and then immediately cooling this air using a rack-based air condi-
tioner. The capture of the hot air combined with the short air path allow very high density
cooling and also cause the system to exhibit high efficiency. The performance of this system
is completely independent of the site (even in locations where only comfort air is available)
and can be installed without a raised floor.
Solutions based on co-locating high density racks and using special high density technology
are preferred when there is a requirement to keep the high density racks together. All other
feasible solutions require some degree of spreading out of the high density equipment.
This is conceptually the simplest solution but is never implemented because data centers
always have substantial variation in per-rack power and designing for the worst case is
consequently wasteful and cost prohibitive. Furthermore, to design for an overall rack power
density of over 6 kW per rack requires extremely complex engineering and analysis. This
approach would only be logical in an extreme situation.
Summary
The advantages and disadvantages of the five approaches to providing cooling to high
density enclosures are summarized in Table 2.
Table 2
Application of the five approaches to cooling high
density enclosures
No new equipment needed Limited to about 2X the design Existing data centers, when high
2 Borrowed cooling power density density equipment is a small
Essentially free in many cases
Uses more floor space fraction of the total load
Provide average cooling capability
with rules to allow borrowing of Requires enforcement of
underutilized capacity complex rules
High density where needed Limited to about 10 kW per New construction or renovations
3 Supplemental cooling and when needed enclosure Mixed environment
Provide average cooling capability Deferred capital costs Racks and room must be Location of high density
with provision for supplemental High efficiency designed in advance to support equipment is not known in
cooling equipment this approach advance
Good floor space utilization
Maximum density Need to plan a high density Density 10-25 kW per rack
4 High density area area in advance, or reserve
Optimal floor space utilization When there is a requirement to
space for it co-locate high density devices
Create a special high density row High density equipment does
or zone within the data center not need to be spread out Must segregate high density New construction or renovations
equipment
High efficiency
Handles all future scenarios Extreme capital and operating Rare and extreme cases of
5 Whole Room costs of up to 4X alternative large farms of high density
Provide high density cooling methods equipment with very limited
capability to every rack May result in extreme physical space
underutilization of expensive
infrastructure
Value of The previous sections identify a number of difficult cost, complexity, and reliability barriers
associated with high power density installations. These problems must be overcome to
compaction deploy high density in the data center. Yet the prevailing predictions in industry trade
publications are that compaction of data centers is inevitable and in process of occurring, due
to the associated cost and space saving benefits associated with compaction. However, the
data does not support these beliefs, and instead suggest that increasing compaction through
increasing density without a fundamental reduction in power consumption is not cost effec-
tive.
Figure 8 shows the data center area per kW as a function of the power density of IT equip-
ment. When the density of IT equipment is increased, the building area devoted to this
equipment falls as shown in the lower curve. However, there is no corresponding decrease in
the building area devoted to power and cooling infrastructure. After the power density passes
approximately 2.5 kW per rack the area consumed by the power and cooling equipment
actually exceeds the area of the IT equipment. The result is that compaction beyond
approximately 4-5 kW per rack does not actually result in any further reduction of the
total area.
50 [4.65]
45 [4.18]
Area in ft2 / kW [m2 / kW]
40 [3.72]
Total area of IT equipment + infrastructure
35 [3.25]
Figure 8
30 [2.79]
Data center area per kW of
capacity as a function of rack Area of power and cooling infrastructure [2.32]
power density 25
[1.86]
20
[1.39]
15
[0.93]
10
Area of IT equipment [0.46]
5
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Compaction density: kW Per Rack
An unstated and widely held belief that is a fundamental premise of compaction is that data
center costs are driven by area, so reducing area through compaction will reduce cost.
Figure 9 shows the lifetime total cost of ownership (TCO) of the data center as a function of
the power density of IT equipment. When the density of the IT equipment is increased, a
commonly expected result is that the TCO will decrease proportionally as show in the lower
curve in the figure. However, the reality is that 75% of data center TCO costs are driven by
power and only 25% of costs are driven by area. Furthermore, per-Watt costs increase with
increasing power density due to factors previously described. The consequence is that the
TCO costs do not decline significantly with increasing power density, but actually
increase after an optimum power density, which is on the order of 6 kW per enclosure.
100%
0%
0 2 4 6 8 10 12 14 16 18 20
Compaction: kW Per Rack
The benefits of increasing power density of IT equipment are small. However, there are
substantial benefits from reducing power consumption of IT equipment because, as the
previous sections show, both data center area and TCO are strongly affected by power
consumption. Table 3 shows how further reductions in IT equipment power consumption and
size affect data center area and TCO. Compared to the typical baseline case, reductions in
power consumption have a much greater benefit than proportional reductions in size.
Table 3
Data center area and TCO savings resulting from
reduction in IT equipment size and power consumption
Blade servers, because of their shared chassis infrastructure for power supplies and cooling
fans, do achieve a 20-40% reduction in electrical power consumption when compared with
conventional servers of equivalent computing power. This savings represents a significant
TCO savings because TCO is dominated by power related costs and not by IT space related
costs.
Contrary to popular belief, the primary TCO benefit related to Data Center Physical
Infrastructure for blade servers comes from their reduced power consumption, NOT
their reduced space consumption. Blade servers do not need to be installed at high
density to obtain these TCO benefits.
3) Choose a baseline power density for new The baseline power density should be selected to avoid significant waste
designs between 40 and 100 W / ft2 [0.4 – 1.1 kW / due to oversizing, and by keeping it below 100 W / ft2 (1.1 kW / m2) the
m2], with 80 W / ft2 [0.9 kW / m2] (2800 W / enclo- performance and redundancy capability becomes predictable.
sure average) being a practical value for most new
designs
4) When the fraction of high density loads is high When it is known in advance that an area of high density is needed, and
and predictable, establish and equip special high spreading the load out is not feasible. This can add significant cost, time,
density areas of 100-400 W / ft2 [1.1-4.3 kW / m2] and complexity to the data center design. These areas will use specialized
(3-12 kW per enclosure) within the data center cooling equipment and not the typical raised floor design.
The lowest cost and lowest risk option, but can consume considerable
7) Split equipment up that cannot be installed to space when there are more than a small fraction of high density loads.
meet the rules Many users who do not have significant area constraints choose this as
their primary strategy.
Conclusion The maximum rack power density exhibited by the latest generation of high density IT
equipment is approximately 10 times the average rack power density in existing data centers.
There are an insignificant number of rack enclosures operating in actual data centers
operating at even half of this maximum power density.
The current methods and layouts for data centers cannot practically provide the cooling
required by this high density equipment because of limitations of the air delivery and return
systems, and the difficulty of providing redundancy and uninterrupted cooling during genera-
tor switchover.
When the objective is to reduce data center area and reduce Total Cost of Ownership,
customers should focus on the purchase of IT equipment based on functionality provided per
Watt and ignore the physical size of the IT equipment. This unexpected conclusion results
because above 60 W / ft2 (0.6 kW / m2), power has a larger affect than does IT equipment
size on both TCO and area.
There are a variety of solutions that allow high density computing equipment to be effectively
deployed in conventional environments. While designing entire data centers for high density
remains impractical, data centers can support the limited installation of high density equip-
ment by using supplemental cooling systems, using rules to allow the borrowing of neighbor-
ing underutilized capacity, and finally by spreading the load among multiple enclosures.
When an installation is planned with a high percentage of high density enclosures, and it is
not feasible to spread out the equipment, the only alternative is to design to provide this
capability for all enclosures. Conventional raised floor designs will not provide sufficient
capacity or predictable performance for such systems and specialized rack / row / cluster
level cooling systems are needed.
Despite the discussions in the trade journals of data center design densities of 300-600 Watts
per square foot (3.2-6.5 kW / m2), achieving such densities remains impractical due to large
cost penalties and the difficulties in achieving high availability at these densities. Current
high availability, high performance data center designs are predictable and practical in the
range of 40 to 100 W / ft2 [0.4-1.1 kW / m2] (1.2 kW to 3 kW per rack average), with the
ability to accommodate occasional loads of up to 3X the design value by taking advantage of
load diversity and through the use of supplemental cooling devices.
Neil holds 19 patents related to high-efficiency and high-density data center power and cooling
infrastructure, and has published over 50 white papers related to power and cooling systems,
many published in more than 10 languages, most recently with a focus on the improvement of
energy efficiency. He is an internationally recognized keynote speaker on the subject of high-
efficiency data centers. Neil is currently working to advance the science of high-efficiency,
high-density, scalable data center infrastructure solutions and is a principal architect of the APC
InfraStruXure system.
Prior to founding APC in 1981, Neil received his bachelors and masters degrees from MIT in
electrical engineering, where he did his thesis on the analysis of a 200MW power supply for a
tokamak fusion reactor. From 1979 to 1981 he worked at MIT Lincoln Laboratories on flywheel
energy storage systems and solar electric power systems.