Factory Automation Cable
CE-531XXSB
CE H05VVC4V5-K(0.5∼2.5Ý)
A05VVC4V5-K(4∼25Ý)
UL AWM 2587(0.5∼6Ý)
CCC 227 IEC 74(RVVYP)(0.5∼2.5Ý) Features
■ Global-standard cables designed to CE&CCC (equal to or less
Characteristics Radar Chart than 2.5Ý) &UL・cUL (equal to or less than 6Ý) & <PS>E (0.75-
4Ý) &GOST-R
Heat resistance
5
■ Oil resistant, heat resistant
(105℃), flexible, movable
■ Fine conductor
4
Cable carrier Oil resistance ■ Noise resistance (allowing effective use for cable connection
resistance 3
requiring protection against EMC)
2 ■ Low transfer impedance (250mΩ/m or less at 30MHz)
1
0
left/right
Noise
bending
resistance
Application
resistance
■ Internal/external cable connection to electrical equipment
■ Cable connection under oil environment
■ Wiring of the portion requiring noise resistance
45°left/right vibration
resistance Twist resistance
CE-531XXSB General VCTF Certification/Marking
※The characteristics of the cable indicated on the radar chart are intended for ※ ※ ※
use as a general guide for selecting the cable meeting your requirements.
※The cable is subject to limitation of applicable sizes for each relevant standard. For
details, refer to“Applicable Range”for each standard in [Technical Data] given below.
Technical Data
CE UL・cUL CCC Electrical Appliance and Material Safety Law<PS>E
0.5∼2.5Ý:H05VVC4V5-K
Cable Type AWM style 2587 227 IEC 74
(RVVYP) VCTF
4∼25Ý :A05VVC4V5-K
Voltage Rating 300/500V 600V 300/500V 300V
Temperature Rating 70℃ 90℃ 70℃ 75℃
Test Voltage AC2000V・15min AC3000V・1min AC2000V・5min AC2000V・1min
Flame Resistance IEC 60332-1 VW-1, FT1 IEC 60332-1 60°inclination
CENELEC HD 21.13 UL 758 GB5023.7 Electrical Appliance and
Applicable Standard
IEC 60227-7 CAN/CSA-C22.2 No210.2 IEC 60227-7 Material Safety Law
0.5∼6Ý 0.5-2.5Ý, only types designed for
Applicable Range All sizes 0.75∼4Ý
(20∼10AWG) insulator identification by numbering
Electrical Characteristics
Nominal Cross-Sectional Number of Cores Allowable Current(A)
Item
Area(Ý)(AWG) 2∼31 2 3 4 5 6 7 8 10 12 15 21 25 31
0.5 (20) 39.0 10 9 8 7 7 7 7 6 6 5 5 5 4
0.75(19) 26.0 13 11 10 9 9 9 8 8 7 7 6 6 5
1 (18) 19.5 15 13 12 11 11 10 10 9 9 8 7 7 6
1.5 (16) 13.3 20 17 15 14 14 13 13 12 11 10 9 9 8
Conductor Resistance 2.5 (14) 7.98 27 23 21 20 19 18 18 16 15 14 13 12 11
(20℃)
Ω/Ü or below 4 (12) 4.95 36 31 28 26 25 24
6 (10) 3.30 47 40 36 34 32 31
10 1.91 67 57 51 48 45 43
16 1.21 89 76 68
●Allowable Current (A) for the cable is based on calculation under aerial one-cable installation at ambient temperature
25 0.780 118 101 91
of 30℃, not representing a guaranteed value.
0.5(20)∼1.5(16) 50 Allowable current for the cable at ambient temperature above 30℃ is to be determined by multiplying the current
Insulation Resistance 2.5(14)∼4(12) 40 value by the appropriate current reduction factor specified in the following table for the ambient temperature.
(20℃) ●The Allowable current values are those calculated by JCS197, but not guaranteed.
MΩÜ or above 6(10)∼10 30
16∼25 20 ( For details on Allowable current of the cable when used in Europe, refer to the applicable standard
− IEC60364-5 (Electrical installation of building − Part 5: Selection and erection of electrical
equipment − Section 523: Current-carrying capacities in wiring system).
)
JCS197… Japanese Electric Wire and Cable Makers’Association’s Standard“Allowable Current for Cabtyre Cable”
■ Current Reduction Factor Table
Ambient Temperature(℃) 30 35 40 45 50 55 60 65
Current Reduction Factor 1.00 0.94 0.87 0.79 0.71 0.61 0.5 0.35
87
Core Identification
Core identification system
Identification by
2cores− Identified by numbering in white color on black insulator surface
Number
3cores or more − Identified by numbering in white color on black insulator surface + green/yellow
(for Standard)
Identification by 2cores − Identified by brown and light blue
Color 3cores − Identified by brown, light blue and green/yellow
(for Custom Order) 4cores − Identified by brown, light blue, black and green/yellow
●Green/yellow: Yellow straight lines on green (in green/yellow color ratio of 60/40)
Cable Construction
Item Configuration
Conductor Soft annealed stranded copper
Insulator Heat resistant PVC
CE-531XXSB
Conductor stranding Circular
Core wrapping tape Tape wrap around cores if their number and size are 5 or above and 6Ý or above, respectively
Inner sheath Oil resistant/heat resistant PVC (black)
Shield Tin-plated soft annealed copper braid
Sheath Oil resistant/heat resistant PVC (light gray)
■ Example: 3 core (0.75Ý) 19AWG cable
Oil resistant/heat resistant PVC sheath
Soft annealed stranded copper conductor
CE-531XXSB KURAMO DEMKO H05VVC4V5-K 0.75Ý(19AWG)
1
KURAMO E162205-K AWM 2587 Ⅰ/Ⅱ A/B 90C 600V VW-1 FT1
VCTF <PS>E JET タイネツ 300V GOST-R LF
2
A045839 KURAMO 227 IEC 74(RVVYP)300/500V GB5023.7 0.75Ý
Braided shield
Heat resistant PVC insulator
Inner sheath
Cable Outside Diameter/Weight
Nominal cross-sectional area(Ý)<AWG> Number of cores
Conductor count/wire diameter 2 3 4 5 6 7 8 10 11 12 15 16 21 25 31
0.5 (48/0.12) 8.5 8.8 9.4 10.5 11.5 12.0 13.0 14.0 14.0 14.5 15.5 16.0 18.0 19.5 21.0
※ ※ ※ ※ ※ ※ ※ ※ ※ ※ ※ ※ ※ ※ ※
<20> 115 125 140 160 180 205 225 265 280 300 360 400 460 520 640
0.75(67/0.12) 8.8 9.2 10.0 11.0 12.0 12.5 13.5 14.5 14.5 15.5 16.5 17.0 19.0 20.5 22.5
※ ※ ※ ※ ※
<19> 120 135 155 185 200 230 255 300 300 350 410 430 530 640 790
1 (90/0.12) 9.2 9.8 10.5 12.0 12.5 13.5 14.5 15.5 15.5 16.5 17.5 18.0 20.5 23.0 24.0
<PS>E
※ ※ ※ ※ ※
<18> 130 150 180 210 230 270 300 360 365 390 470 485 630 810 950
1.5 (135/0.12) 10.5 11.0 12.0 13.5 14.5 15.5 16.5 18.0 18.5 19.0 20.5 21.0 25.0 26.0 28.0
※ ※ ※ ※ ※
<16> 165 200 230 275 305 350 395 480 500 510 620 680 850 1050 1400
UL AWM
2.5 (98/0.18) 12.0 12.5 14.0 16.0 17.0 18.5 19.5 21.5 21.5 22.0 24.0 24.5 28.0 30.5 32.5
※ ※ ※ ※ ※ ※ ※ ※ ※ ※
<14> 225 265 325 400 445 520 580 700 750 800 980 1100 1300 1550 1900
4 (75/0.26) 14.0 14.5 15.5 17.5 19.0 20.5
NFPA79
NFPA70
※ ※ ※
<12> 315 355 460 530 600 690
6 (112/0.26) 15.5 16.5 17.5 19.5 21.0 23.5
※ ※ ※ ※
<10> 340 435 550 640 730 950
cUL/CSA
19.0 20.0 22.0 24.0 26.5 29.0
10 (7/28/0.26) ※ ※ ※ ※ ※
560 700 870 1000 1150 1250
22.0 23.0 25.5
16 (7/28/0.32) ※ ※ ※
750 860 1150 Upper: Standard cable outside diameter(Approx.Ù)
CE
27.0 28.5 31.5 Lower: Approximate weight(è/Ü)
25 (7/44/0.32) ※ ※ ※
1350 1500 1950 ※ indicates specifications for custom order production.
CCC
GOST-R
88