Product datasheet
Specifications
variable speed drive, Altivar
Machine ATV340, 5.5kW, heavy
duty, 400V, 3 phases
ATV340U55N4
Main
Range Of Product Altivar Machine ATV340
Product Or Component Type Variable speed drive
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Specific Application Machine
Variant Standard version
Mounting Mode Cabinet mount
Communication Port Protocol Modbus serial
Option Card Communication module, Profibus DP V1
Communication module, PROFINET
Communication module, DeviceNet
Communication module, CANopen
Communication module, EtherCAT
Network Number Of Phases 3 phases
Supply Frequency 50...60 Hz +/- 5 %
[Us] Rated Supply Voltage 380...480 V - 15...10 %
Nominal Output Current 12.7 A
Motor Power Kw 7.5 kW for normal duty
5.5 kW for heavy duty
Motor Power Hp 10 hp for normal duty
7 hp for heavy duty
Emc Filter Class C3 EMC filter integrated
Ip Degree Of Protection IP20
Complementary
Discrete Input Number 5
Discrete Input Type PTI programmable as pulse input: 0…30 kHz, 24 V DC (30 V)
DI1...DI5 safe torque off, 24 V DC (30 V), impedance: 3.5 kOhm
programmable
Number Of Preset Speeds 16 preset speeds
Discrete Output Number 2.0
Discrete Output Type Programmable output DQ1, DQ2 30 V DC 100 mA
Analogue Input Number 2
Analogue Input Type AI1 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12
bits
AI1 software-configurable temperature probe or water level sensor
AI1 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12
bits
AI2 software-configurable voltage: - 10...10 V DC, impedance: 31.5 kOhm, resolution
12 bits
10-Jun-2024 1
Analogue Output Number 1
Analogue Output Type Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10
bits
Software-configurable current AQ1: 0...20 mA impedance 500 Ohm, resolution 10
bits
Relay Output Number 2
Output Voltage <= power supply voltage
Relay Output Type Relay outputs R1A
Relay outputs R1C electrical durability 100000 cycles
Relay outputs R2A
Relay outputs R2C electrical durability 100000 cycles
Maximum Switching Current Relay output R1C on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1C on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Relay output R2C on resistive load, cos phi = 1: 5 A at 250 V AC
Relay output R2C on resistive load, cos phi = 1: 5 A at 30 V DC
Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Minimum Switching Current Relay output R1B: 5 mA at 24 V DC
Relay output R2C: 5 mA at 24 V DC
Physical Interface 2-wire RS 485
Connector Type 1 RJ45
Method Of Access Slave Modbus RTU
Transmission Rate 4.8 kbit/s
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
Transmission Frame RTU
Number Of Addresses 1…247
Data Format 8 bits, configurable odd, even or no parity
Type Of Polarization No impedance
4 Quadrant Operation Possible True
Asynchronous Motor Control Variable torque standard
Profile Optimized torque mode
Constant torque standard
Synchronous Motor Control Permanent magnet motor
Profile Reluctance motor
Pollution Degree 2 conforming to IEC 61800-5-1
Maximum Output Frequency 0.599 kHz
Acceleration And Deceleration Linear adjustable separately from 0.01...9999 s
Ramps S, U or customized
Motor Slip Compensation Adjustable
Automatic whatever the load
Can be suppressed
Not available in permanent magnet motor law
Switching Frequency 2...16 kHz adjustable
7...16 kHz with derating factor
Nominal Switching Frequency 4 kHz
Braking To Standstill By DC injection
Brake Chopper Integrated True
2 10-Jun-2024
Line Current 15.3 A at 380 V (normal duty)
12.2 A at 480 V (normal duty)
20.0 A at 380 V (heavy duty)
16.0 A at 480 V (heavy duty)
Line Current 20 A at 380 V without line choke (heavy duty)
16 A at 480 V without line choke (heavy duty)
15.3 A at 380 V with external line choke (normal duty)
12.2 A at 480 V with external line choke (normal duty)
11.6 A at 380 V with external line choke (heavy duty)
9.4 A at 480 V with external line choke (heavy duty)
Maximum Input Current 20.0 A
Maximum Output Voltage 480 V
Apparent Power 12.1 kVA at 480 V (normal duty)
13.3 kVA at 480 V (heavy duty)
Maximum Transient Current 18.2 A during 60 s (normal duty)
19.1 A during 60 s (heavy duty)
22.3 A during 2 s (normal duty)
22.9 A during 2 s (heavy duty)
Electrical Connection Screw terminal, clamping capacity: 4...6 mm² for DC bus
Screw terminal, clamping capacity: 0.2...2.5 mm² for control
Screw terminal, clamping capacity: 1.5...6 mm² for line side
Screw terminal, clamping capacity: 1.5...6 mm² for motor
Prospective Line Isc 22 kA
Base Load Current At High 12.7 A
Overload
Base Load Current At Low 16.5 A
Overload
Power Dissipation In W Natural convection: 134 W at 380 V, switching frequency 4 kHz (heavy duty)
Forced convection: 134 W at 380 V, switching frequency 4 kHz (heavy duty)
Natural convection: 164 W at 380 V, switching frequency 4 kHz (normal duty)
Forced convection: 164 W at 380 V, switching frequency 4 kHz (normal duty)
Electrical Connection DC bus: screw terminal 4...6 mm²/AWG 12...AWG 10
Control: screw terminal 0.2...2.5 mm²/AWG 24...AWG 12
Line side: screw terminal 1.5...6 mm²/AWG 14...AWG 10
Motor: screw terminal 1.5...6 mm²/AWG 14...AWG 10
With Safety Function Safely True
Limited Speed (Sls)
With Safety Function Safe Brake True
Management (Sbc/Sbt)
With Safety Function Safe False
Operating Stop (Sos)
With Safety Function Safe False
Position (Sp)
With Safety Function Safe False
Programmable Logic
With Safety Function Safe Speed False
Monitor (Ssm)
With Safety Function Safe Stop 1 True
(Ss1)
With Sft Fct Safe Stop 2 (Ss2) False
With Safety Function Safe Torque True
Off (Sto)
With Safety Function Safely False
Limited Position (Slp)
With Safety Function Safe False
Direction (Sdi)
10-Jun-2024 3
Protection Type Thermal protection: motor
Safe torque off: motor
Motor phase loss: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent: drive
Output overcurrent between motor phase and earth: drive
Output overcurrent between motor phases: drive
Short-circuit between motor phase and earth: drive
Short-circuit between motor phases: drive
Motor phase loss: drive
DC Bus overvoltage: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Input supply loss: drive
Exceeding limit speed: drive
Break on the control circuit: drive
Width 110.0 mm
Height 270.0 mm
Depth 234.0 mm
Net Weight 2.9 kg
Continuous Output Current 16.5 A at 4 kHz for normal duty
12.7 A at 4 kHz for heavy duty
Environment
Operating Altitude <= 3000 m with current derating above 1000m
Operating Position Vertical +/- 10 degree
Product Certifications UL
CSA
TÜV
EAC
CTick
Marking CE
Standards IEC 61800-3
IEC 61800-5-1
IEC 60721-3
IEC 61508
IEC 13849-1
UL 618000-5-1
UL 508C
Assembly Style With heat sink
Electromagnetic Compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to
IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Environmental Class (During Class 3C3 according to IEC 60721-3-3
Operation) Class 3S3 according to IEC 60721-3-3
Maximum Acceleration Under 70 m/s² at 22 ms
Shock Impact (During Operation)
Maximum Acceleration Under 5 m/s² at 9...200 Hz
Vibrational Stress (During
Operation)
Maximum Deflection Under 1.5 mm at 2...9 Hz
Vibratory Load (During Operation)
Permitted Relative Humidity Class 3K5 according to EN 60721-3
(During Operation)
Volume Of Cooling Air 76.0 m3/h
Type Of Cooling Forced convection
Overvoltage Category Class III
4 10-Jun-2024
Regulation Loop Adjustable PID regulator
Noise Level 46.6 dB
Pollution Degree 2
Ambient Air Transport -40…70 °C
Temperature
Ambient Air Temperature For -15…50 °C without derating (vertical position)
Operation 50…60 °C with derating factor (vertical position)
Ambient Air Temperature For -40…70 °C
Storage
Isolation Between power and control terminals
Packing Units
Unit Type Of Package 1 PCE
Number Of Units In Package 1 1
Package 1 Height 13.000 cm
Package 1 Width 37.000 cm
Package 1 Length 31.500 cm
Package 1 Weight 3.720 kg
Unit Type Of Package 2 P06
Number Of Units In Package 2 10
Package 2 Height 75.000 cm
Package 2 Width 60.000 cm
Package 2 Length 80.000 cm
Package 2 Weight 50.200 kg
10-Jun-2024 5
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Resource performance
Upgraded Components Available
Well-being performance
Mercury Free
Rohs Exemption Information Yes
Certifications & Standards
Reach Regulation REACh Declaration
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
China Rohs Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins
Circularity Profile End of Life Information
6 10-Jun-2024
Product datasheet ATV340U55N4
Dimensions Drawings
Dimensions
Views: Front - Left - Rear
10-Jun-2024 7
Product datasheet ATV340U55N4
Mounting and Clearance
Clearance
Dimensions in mm
X1 X2 X3
100 100 60
Dimensions in in.
X1 X2 X3
3.94 3.94 2.36
8 10-Jun-2024
Product datasheet ATV340U55N4
Mounting Types
Mounting Type A: Side by Side IP20
Possible, at ambient temperature ≤ 50 °C (122 °F)
Mounting Type B: Individual IP20
a 50 mm (1.97 in.) from 50...60°C, no restriction below 50°C
10-Jun-2024 9
Product datasheet ATV340U55N4
Connections and Schema
Connections and Schema
Three-phase Power Supply with Upstream Breaking via Line Contactor Without Safety
Function STO
Connection diagrams conforming to standards ISO13849 category 1 and IEC/EN 61508 capacity SIL1, stopping
category 0 in accordance with standard IEC/EN 60204-1.
(1) Use relay output R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 : Line Contactor
Q2, Q3 : Circuit breakers
S1 : Pushbutton
S2 : Emergency stop
T1 : Transformer for control part
Three-phase Power Supply With Downstream Breaking via Switch Disconnector
10 10-Jun-2024
Product datasheet ATV340U55N4
(1) Use relay output R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
Q1 : Switch disconnector
Sensor Connection
It is possible to connect either 1 or 3 sensors on terminals AI1.
10-Jun-2024 11
Product datasheet ATV340U55N4
Control Block Wiring Diagram
(1) 24V supply (STO)
(2) STO - Safe Torque Off
(3) PTI - Pulse Train In
(4) PTO - Pulse Train Out
(5) Motor Encoder connection
(6) Digital outputs
(7) Digital inputs
(8) Analog output
(9) Analog input
(10) Differential Analog Input
(11) Ethernet port (only on Ethernet drive version)
SW1 : Sink/Source switch
R1A, R1B, R1C : Fault relay
R2A, R2C : Sequence relay
12 10-Jun-2024
Product datasheet ATV340U55N4
Digital Inputs Wiring
Digital Inputs: Internal Supply
Using DISUP Signal
In SRC position DISUP outputs 24 V. In SK position DISUP is connected to 0 V.
Digital Inputs: External Supply
Positive Logic, Source, European Style
Negative Logic, Sink, Asian Style
Digital Inputs: Internal supply
Negative Logic, Sink, Asian Style
10-Jun-2024 13
Product datasheet ATV340U55N4
14 10-Jun-2024
Product datasheet ATV340U55N4
Digital Outputs Wiring
Digital Outputs: Internal Supply
Positive Logic, Source, European Style, DQCOM to +24V
(1) Relay or valve
Negative Logic, Sink, Asian Style, DQCOM to 0V
(1) Relay or valve
Digital Outputs: External Supply
Positive Logic, Source, European Style, DQCOM to +24V
(1) Relay or valve
Negative Logic, Sink, Asian Style, DQCOM to 0V
10-Jun-2024 15
Product datasheet ATV340U55N4
(1) Relay or valve
16 10-Jun-2024
Product datasheet ATV340U55N4
Performance Curves
Open Loop Applications
1: Self-cooled motor: continuous useful torque
2: Force-cooled motor: continuous useful torque
3: Overtorque for 60 s maximum
4: Transient overtorque for 2 s maximum
5: Torque in overspeed at constant power
10-Jun-2024 17
Product datasheet ATV340U55N4
Closed Loop Applications
1: Self-cooled motor: continuous useful torque
2: Force-cooled motor: continuous useful torque
3: Overtorque for 60 s maximum
4: Transient overtorque for 2 s maximum
5: Torque in overspeed at constant power
18 10-Jun-2024