Iec Testing Method
Iec Testing Method
The goal of this thesis is to provide a detailed understanding of the basic testing
process of electrical appliances at SGS Fimko, in accordance with the IEC 60335
standard. In addition, the thesis aims to analyze the differences between conducting
basic testing and a previous full testing of an appliance to determine if there are
significant differences in the results.
The project was conducted by gaining extensive knowledge of the IEC 60335
standard’s tests and doing basic testing in the laboratory to observe different
appliances safety performance. The most important tests and methods were listed to
this thesis according to past observations, on which of the tests matter to the safety
of the appliance.
After comparing chargers which had a full testing conducted, a conclusion was
reached. If an appliance which had full testing done, would had only basic testing
done, the result would not have changed. The primary reason for the lack of
significant difference between the full testing and basic testing of the appliance is
likely due to the nature of the testing that the appliance was subjected to. Appliances
that undergo full testing are often those that are being certified, and manufacturers
have a strong incentive to build these appliances in compliance with safety standards
to obtain the certification mark. However, for appliances that are subject to basic
testing by a safety authority, manufacturers may not have built them according to
European safety standards as they may sell the appliance globally and are not aimed
specifically at the internal market of the European Union.
Verrattaessa latureita, jolle oli suoritettu täysi testaus, tehtiin johtopäätös, että
jos laitteelle olisi tehty vain perustestaus, tulokset eivät olisi olleet erilaisia.
Tämän merkittävän eron puuttuminen perustestauksen ja täyden testauksen
välillä johtuu todennäköisesti siitä, millaisesta syystä testaus on laitteelle tehty.
Laitteet, jotka käyvät läpi täyden testauksen, ovat usein niitä, joita sertifioidaan,
ja valmistajilla on vahva kannustin rakentaa nämä laitteet
turvallisuusstandardien mukaisesti saadakseen sertifikaattimerkin. Kuitenkaan
laitteita, joita turvallisuusviranomainen testauttaa, eivät niiden valmistajat
välttämättä ole rakentaneet eurooppalaisten turvallisuusstandardien mukaisesti.
Niitä laitteita myydään maailmanlaajuisesti, eikä niitä ole suunnattu
nimenomaan Euroopan unionin sisämarkkinoille.
List of Abbreviations
1 Introduction 1
7 Conclusions 48
References 49
List of Terms and Abbreviations
1 Introduction
In order to ensure that electrical appliances are safe for consumers to use, they
undergo a series of tests that evaluate various aspects of their design,
construction, and performance. These tests are typically conducted according to
industry standards, such as the IEC 60335 standard, which provides a
framework for evaluating the safety of household and similar electrical
appliances.
The full testing of a device according to the IEC 60335 standard is expensive
and time consuming to conduct, so another custom for ensuring devices’ safety
has been developed: basic testing of an appliance. It involves selecting a
subset of tests from the standard that are relevant to the specific appliance
being tested.
The tests chosen are different for each type of appliance. Different tests may be
required for a hot plate than for a hair dryer, depending on their respective
electrical characteristics and intended uses. These tests are designed to assess
critical safety factors such as electrical insulation, resistance to fire, and
protection against electric shock.
The findings from this analysis can provide valuable insights into the
effectiveness of basic testing in ensuring product safety. It can also help to
improve the safety of electrical appliances and increase consumer confidence in
the products they use.
2
IEC standards are recognized by most countries around the world and are often
adopted as national or regional standards. Compliance with IEC standards can
help manufacturers access global markets and improve the safety and
performance of their products. [1.]
IEC publishes around 10 000 IEC international standards which touch on most
of the appliances found on the market. The focus of this thesis is IEC 60335,
which deals with the safety of electrical appliances for household and similar
purposes. This standard covers appliances with their voltage not more than 250
V for single-phase appliances and 480 V for other appliances including direct
current supplied appliances and battery-operated appliances. [3;4.]
2.4 EN Standards
2.5 Certification
It represents the range of values within which the true value of the quantity
being measured is expected to lie with a certain level of confidence. It is usually
expressed as a range of values in percentage or the measurement device’s
own units. For example: ±2 % or ±2 °C.
The reason this is important, is because when measuring for example voltage
or temperature, the standards have given a maximum value for a permissible
result. When a measured value falls within the uncertainty of the limit, a decisive
result cannot be given. This means that the verdict given can be pass/fail with
condition, depending on the probability of distribution.
As illustrated in Figure 1, when the limit value is given, and there are four
measurements (Illustrated with black circles) with the given uncertainty
(Illustrated with red lines), it is possible to be certain that measurements 1. and
4. are either pass or fail. For measurements 2. and 3. it is no longer possible to
say with certainty, that is the measured value over or under the limit value. For
these measurements a verdict of pass/fail with condition is given.
[6, 131.]
7
4.1 Thermocouple
- Type E is chromel-constantan
- Type J is iron-constantan
- Type K is chromel-alumel
- Type M is 82%Ni/18%Mo-99.2%Ni/0.8%Co
- Type N is Nicrosil-Nisil
- Type T is copper constantan
[7.]
The most used one is the K type, due to its general performance and low cost. It
is the default type of thermocouple used if properties from other types are not
required. [8.]
Another type that is commonly used for applications, where strong magnetic
fields are present is the T type. Both copper and constantan are non-magnetic
metals, which means that magnetic fields do not abruptly change the
characteristics of the thermocouple. [8.]
8
The tip of the thermocouple is glued onto the surface to measure its
temperature. It is important that too much glue is not used, because it can affect
the thermal reading of the thermocouple. A small blob, so that the thermocouple
tip stays in place is enough.
Tape may be used for strain relief on the wire, but never on top of the welding
point.
It is possible to see voltage’s RMS value or peak value. If the voltage is DC,
peak value equals RMS value. However, if the voltage is AC, getting the RMS
value might not be as simple as just dividing by square root of two. This works if
the waveform is sinusoidal. However, if the voltage is not sinusoidal, the RMS
value may be incorrectly displayed on the digital multimeter. These kinds of
non-sinusoidal voltages may appear for example with switch mode power
supplies, or in devices which have positive or negative reactance. That is why to
get a true reading of the voltage, an oscilloscope or a true RMS multimeter is
used.
4.3 Oscilloscope
An oscilloscope is not a versatile tool, but it does one thing extremely well,
which is measuring voltage at higher frequencies. Most oscilloscopes can
measure voltage up to 5MHz. This covers most of the common appliances that
9
can be found for consumers. Instead of only getting a reading, it is also possible
to see what the waveform looks like.
It is extremely important that when delivering the blow, the spring hammer
should not be placed vertically delivering a blow from above or below the device
under test. This can greatly affect the precision of the blow delivered on the
surface due to gravity. Blows delivered from above the device can have a
greater impact on the device under test than intended. Blows delivered from
below the device can have a reduced impact on the device under test than
intended.
4.7 Datalogger
As the name implies, datalogger is used to log data. It typically includes sensors
or inputs to measure various things such as temperature, pressure, humidity or
voltage. Dataloggers can also include memory to store the collected data, but
often they are connected to a computer or a network for real-time monitoring or
data transmission.
Dataloggers are widely used for testing purpose. Mainly to log temperatures
with thermocouples and voltage at set intervals for devices under testing, but
also for logging data to monitor the testing environment to be certain that
environmental conditions have not affected test results.
The interval used for heating tests is 10 seconds, due to the length of the tests,
and to preserve the measurement device of undue stress. Sometimes
dataloggers are kept on for hours, if not days or weeks for some tests.
4.8 Calliper
To make sure that all the correct part 2 standards are chosen, CENELEC site is
checked for the most up-to-date published EN standards. Sometimes they may
be withdrawn. Any withdrawn standards are not considered when testing
appliances.
The standard IEC 60335 has many tests intended for full testing of a device
[6, 2]. They are the following:
“6. Classification
7. Marking and instructions
8. Protection against access to live parts
9. Starting of motor-operated appliances
10. Power input and current
11. Heating
12. Void
13. Leakage current and electric strength at operating temperature
14. Transient overvoltages
15. Moisture resistance
16. Leakage current and electric strength
17. Overload protection of transformers and associated circuits.
18. Endurance
19. Abnormal operation
20. Stability and mechanical hazards
21. Mechanical strength
22. Construction
23. Internal wiring
24. Components
25. Supply connection and external flexible cords
26. Terminals for external conductors
27. Provision for earthing
28. Screws and connections
29. Clearances, creepage distances and solid insulation
30. Resistance to heat and fire.
31. Resistance to rusting
32. Radiation, toxicity, and similar hazards.”
[6, 2.]
14
These are the chapters which include the tests in the standard. Each chapter
include many tests, and rarely all the tests are applicable to one appliance
because the part 1 is created for many appliances and is extremely broad.
However, in basic testing, only the more relevant tests are chosen that can be
done within a limited time, for instance in 6-8 hours. They must be chosen
logically. This knowledge comes with experience, but also with common sense.
For example, heating tests are quite common to be chosen for a device. But if
the device’s normal operation does not produce much heat, and there are no
heating resistors found in the initial inspection, this common test may be
skipped for time savings.
Most common tests that are chosen for the devices in basic testing are included
the following Clauses:
“6. Classification
7. Marking and instructions
8. Protection against access to live parts
10. Power input and current.
11. Heating
13. Leakage current and electric strength at operating temperature
19. Abnormal operation
20. Stability and mechanical hazards
21. Mechanical strength
25. Supply connection and external flexible cords
27. Provisions for earthing
29. Clearances, creepage distances and solid insulation.”
[6, 2.]
Each of the Clauses include many tests within, but only the ones which are the
most relevant for safety or quick are chosen for basic testing.
The methods, in which the tests are conducted are explained below in the
following subchapters.
15
5.3.1 Classification
“Appliances shall be one of the following classes with respect to protection against
electric shock:
“Appliances shall have the appropriate degree of protection against harmful ingress of
water.
Often the IP rating is not checked by tests, but only by visual inspection. The
part 2 of IEC 60335 standard defines the required IP rating for an appliance if
such requirement exists.
[6, 24.]
Symbol IEC 60417-5172 (2003-02) for class II appliances is illustrated in
figure 7.
A visual test is done to the appliance to find possible openings in the casing
where a test probe could fit inside and make contact with a live part. The
appliance is used in all positions when it is operated in as in normal use with
removal of any detachable parts that can be opened without using a tool [6, 31].
The probes used for this type of testing are called “test probe B” and “test probe
13” [6, 31].
Test probe B, which is illustrated in figure 8 is also called a jointed test finger. It
has exact measurements specified in standard IEC 61032 [15].
17
Test probe B is inserted into any opening in the appliance with a force not
exceeding 1 N. The appliance may be in any possible position, with the
exception for appliances normally used on the floor with a mass exceeding 40
kg are not tilted. Test probe B may be rotated and angled before, during and
after insertion into any position. 20 N of force may be used if the test probe B is
in a straight position. [6, 31.]
18
Test probe 13, as illustrated in figure 9 is used for class II appliances only. It
can be applied to any openings with a force not exceeding 1 N. [6, 31.]
When an appliance is marked with a rated power input, the power input in
normal conditions shall not deviate more than the deviation shown in Table 1
[6, 33].
19
The permissible deviation depends on the type of appliance and the rated
power input. Often, the appliances do not have a lower limit, but only an upper
limit for deviation.
Having a power intake lower than stated is generally not dangerous, but it may
result in reduced performance or functionality of an electrical appliance.
However, having a power intake higher than stated can be dangerous, as it can
cause the appliance to overheat and potentially start a fire. It is important to
ensure that electrical appliances are operated within their rated power intake
range to ensure safe and reliable operation.
Part 2 of the IEC 60335 standard defines in which group each kind of appliance
belongs to. For example, battery chargers are tested as motor-operated
appliances.
When conducting the test for power input, the specific instructions for the
operation of the appliance are as follows:
- “All circuits which can operate simultaneously are actuated.
- The appliance is supplied rated voltage.
- The appliance is operated under normal operation.”
[6, 33.]
20
Clause 10 also includes tests for the current deviation measurements, but it is
not chosen for basic testing because the power deviation test matters more and
gives a good indication on whether the appliance is dangerous or not in terms of
current intake.
5.3.5 Heating
The heating tests are designed to ensure that household and similar electrical
appliances operate safely and do not pose a risk of fire or other hazards due to
excessive heat generation. There are specific guidelines on how an appliance is
to be constructed, so that no excessive heating is generated.
All appliances are operated under normal operation for the duration of the
heating tests. The type of appliance defines the power or voltage input.
Heating appliances are operated at 1.15 times rated power input, while motor-
operated appliances and Combined appliances are supplied with the most
unfavourable voltage between 0.94 times and 1.06 times the rated voltage
[6, 34-36].
“Hand-held appliances are held in their normal position of use” [6, 34]. Normal
position is defined by the instructions of the appliance.
“Built-in appliances are installed in accordance with the instructions” [6, 34].
21
“Other heating appliances and other combined appliances are placed in a test corner
as follows:
- Appliances normally placed on a floor or table in use, are placed on the floor as
near to the walls as possible.
- Appliances normally fixed to a wall are fixed to one of the walls, as near to the
other wall and floor or ceiling as is likely to occur, taking account the
instructions.
- Appliances normally fixed to a ceiling are fixed to the ceiling as near to the walls
as is likely to occur, taking into account in the instructions.
Dull, black-painted plywood approximately 20 mm thick is used for the test corner, the
supports and for the installation of built-in appliances.” [6, 34-35.]
Even if the appliance being tested does not strictly fall under one of the
categories of hand-held appliances, built-in appliances, heating appliances or
motor-operated appliances, its category is defined in the appropriate part 2 of
the standard.
The duration is defined in the part 2 of the standard and is usually until stable
conditions are reached or for 60 minutes. However, for appliances like toasters
that are not powered on continuously for longer periods of time, the duration is
defined a lot more precisely. In the case of toasters, it is operated for 15
minutes. If the toaster is constructed to toast more than a single slice of bread
at one time, the appliance is operated for a further 5 minutes with only one slice
of bread inserted in the toaster in the most unfavourable position [16, 18].
22
Temperature limits for heating tests are found in tables 2 and 3 for each part of
the appliance. This table also defines where temperatures shall be measured
from.
Table 3 Maximum normal temperature rises continued. Copied from [6, 38].
Rarely all of the measuring points in table 3 are used for a single appliance.
Some appliances might not even have all the components that are listed in the
table. Only the measuring points which apply are measured.
24
“At operating temperature, the leakage current of the appliance shall not be
excessive and its electric strength shall be adequate” [6, 39].
Leakage current is what its name implies, current that leaks from an appliance.
Devices can leak current through insulation and other means. Low leakage
current is not dangerous and is allowed in the appliances. There are limits set
for the requirements the appliances need to meet to be deemed safe.
“The appliance is operated under normal operation for the duration specified in
11.7” [6, 39].
This applies only for the measurement of leakage current. Clause 11 is the
heating tests, so this test can sometimes be conducted at the same time as the
heating tests for time savings, because the test conditions are most of the time
the same.
The test conditions for testing leakage current are determined as follows:
Heating appliances are operated at 1.15 times the rated power input, while
motor-operated appliances and combined appliances are supplied at 1.06 times
rated voltage [6, 39-40].
For class I, class II and class III appliances, the leakage current is measured by
means of the circuit is illustrated in figure 10. For class I appliances, a low
impedance ammeter capable of measuring the true r.m.s. value of the leakage
current may also be used instead of the circuit illustrated in figure 10. [6, 40.]
25
Figure 10 Measuring network for touch current. Copied from [17, 27].
The leakage current is measured between any pole of the supply and
accessible metal parts connected to metal foil having an area not exceeding 20
cm × 10 cm which is in contact with accessible surfaces of insulating materials.
[6, 40.]
The measured leakage current shall not exceed the following values:
Stationary class I heating appliances: 0.75 mA or 0.75 mA per kW rated power input of
the appliance with a maximum of 5 mA, whichever is higher.” [6, 40.]
For class II and class III appliances the peak value is measured, while for class
I appliances r.m.s. value is measured.
For class I appliances, when measuring the leakage current between N and PE
the incoming PE wire must be disconnected while conducting the measurement.
26
The appliance is disconnected from the supply and the insulation is subjected to
a voltage having a frequency of 50 Hz or 60Hz for 1 minute [6, 41].
The voltage is applied between live, functional parts and the appliance’s
accessible parts. When an appliance has a class II construction, metal foil is
used to cover the appliance without the metal foil touching metallic parts.
[6, 41.]
The appliance shall withstand a voltage specified in table 4 for each of the
appliance’s type of insulation.
28
Table 4 Voltage for electric strength test. Copied from [6, 41].
The appliances meant for use by households in Europe always cover a rated
voltage of 220 V to 240 V, or 230V. So that is the rated voltage by the appliance
that is considered when testing for electric strength.
For class I appliances, the appliance must meet the requirements of basic
insulation. Meaning 1 000 V according to table 4 [6, 41].
When testing class II appliances, it is always assumed first that the appliance
complies with the reinforced insulation requirements. All class II appliances are
tested with 3 000 V electric strength test first. If it fails, then a subsequent test
with 1 750 V is conducted.
For failure to occur, the appliance must conduct over 100 mA of current within
60 seconds of reaching the target voltage for testing the electric strength test.
29
The Clause of Abnormal operation covers fault tests for electric appliances. All
appliances that come in for basic testing will be tested for abnormal operation.
The appropriate part 2 of the standard has the most applicable tests for each
appliance group and most often, one or two of them are chosen. For some
appliances, a universal test in the part 1 of the standard may give the worst
result in terms of safety.
Electronic circuits shall be designed and applied so that a fault condition will not render
the appliance unsafe with regard to electric shock, fire hazard, mechanical hazard or
dangerous malfunction.” [6, 47.]
During the tests, only one abnormal condition may be simulated at any one time
unless stated otherwise [6, 48].
The different types of appliances also have test conditions for the duration of
the test. They may be the same conditions as in the heating tests, but most of
the time they differ. More voltage or power is usually what changes in addition
to position of the appliance. Some test may also have a single fault condition. It
means that a single component of the appliance is presumed to be broken or at
a faulty condition, and it cannot continue to carry out its functions.
The most common tests that are given by the part 1 of the standard are the
following:
Appliances that have heating elements are tested under the same conditions as
specified in the heating tests of Clause 11, but so that heat dissipation is
restricted. Supply voltage is determined such, that it is 0.85 times the rated input
30
power when device is operated normally, and the power input has stabilized.
[6,48.]
Appliance is tested under the same conditions as specified in the heating tests of
Clause 11. Any control that limits the temperature during the heating test is short-
circuited. If the appliance has more than one control, only one control is short-
circuited at any one time. [6,48.]
Appliance is operated normally, with a stalled condition. Any motor or moving part
of the appliance is locked. If the appliance has more than one motor or moving
part, they are locked separately. Appliances are supplied at their rated voltages
for a period, that depends on the type of the appliance. [6,49.]
This test has restrictions, like short circuits cannot be made between primary
and secondary sides of a transformer, and certified components cannot be
altered in any way.
“During the tests, the appliance shall not emit flames, molten metal, or poisonous or
ignitable gas in hazardous amounts and temperature rises shall not exceed the values
shown in table 5.
After the tests, and when the appliance has cooled to approximately room temperature,
compliance with Clause 8 shall not be impaired and the appliance shall comply with
Clause 20.2 if it can still be operated” [6, 54.]
31
Clause 20.2 is the tests for mechanical hazards in an appliance. Mainly for
moving parts and spinning motors. [6, 56.] The tests are explained more
thoroughly in the next chapter.
The test corner or wooden supports intended to hold fixed appliances shall not
have a temperature rise of over 150 K. The insulation of supply cord shall not
have a temperature rise of 150 K or if it has a T marking above 75 °C, T+75 K.
[6, 54.]
32
Clause 20 includes the tests for appliance’s stability and mechanical hazards
[6, 55-56].
Appliances intended to be filled with liquids by the user, are tested empty or
filled with the most unfavourable amount of water up to the capacity stated in
the instructions. [6, 56.]
Mechanical hazards
against access to live parts. All detachable parts and parts intended to be
serviced are removed before the testing. The test can also be conducted using
the tester’s own arms using extreme caution while having the appliance
disconnected from all power sources and preventing accidental start-up of the
appliance.
Compliance is checked by applying blows to the appliance in accordance with test Ehb
of IEC 60068-2-75, the spring hammer test.” [6, 56-57.]
Weak points can be identified by feel and visual inspection. Sections of the
enclosure that protect live parts and moving parts are tested thoroughly.
Normally grilles that protect heating elements, clips and screws that keep two
halves of the enclosure together and places where material is thin, are the most
likely to fail and may cause the appliance to become dangerous by exposing
live parts or reducing clearance and creepage distances, making the insulation
of the appliance weaker.
“After the test, the appliance shall show no damage that could impair
compliance with this standard and compliance with 8.1, 15.1 and Clause 29
shall not be impaired” [6, 57].
Test 8.1 is the protection against access to live parts, test 15.1 is moisture
resistance and Clause 29 is clearances, creepage distances and solid insulation
test. This means that after applying three blows to all points that are likely to be
34
The appliance shall not have any live parts accessible by test probes B and 13.
If the appliance has a degree of protection against moisture, the protection shall
not be impaired after the spring hammer test. And lastly, clearance and
creepage distances shall not be lowered after the tests.
Clause 25 includes the tests for supply cables and other external flexible cords.
They shall have adequate protection against external ingress, mechanical
damage, and environmental conditions.
[6, 74.]
Supply cord is fixed to the appliance and must have a plug constructed to one
end that is meant to connect to the socket-outlet. This type of construction is
also known as type Y attachment. They are commonly found in household
appliances, such as toasters, coffeemakers, and heaters. One such example
can be found in an extension cord, as illustrated in figure 13.
An appliance inlet is a supply connection without a fixed supply cord. The cord
can be removed and replaced easily by the user if the type of cable taken into
consideration, so that the same wire gauge is replaced as was in the original
cable. This type of construction is also known as type X attachment. They can
be found for example in computer power supplies and some laptop chargers.
Figure 14 illustrates this well.
Pins for insertion is mainly for smaller appliances, where the whole appliance
excluding the cord of the output is attached to the pins of the supply. This kind
of appliance stays attached to the socket-outlet. This type of construction is also
known as type Z attachment. They can be found for example in power supplies
for phone chargers or for decoration lights. Pins for insertion is illustrated in
figure 15.
36
Appliances, other than stationary appliances for multiple supply, shall not be
provided with more than one means for connection to the supply mains [6, 74].
It is not allowed to have more than one connection to any kind of power supply
for portable appliances. Some manufacturers might want to add a second
supply cord to split the required load between two fuse groups for tools that
draw higher current than the fuses for sockets are intended, but such practice is
strictly prohibited [6, 74].
The nominal cross-sectional area of conductors in supply cords shall not be less
than the value specified in Table 6 [6, 76].
37
The rated current may not be marked on the appliance, but if the markings are
in order, the rated power and voltage are marked on the appliance. The rated
current can be calculated using this equation for power:
𝑅𝑎𝑡𝑒𝑑 𝑃𝑜𝑤𝑒𝑟
𝑅𝑎𝑡𝑒𝑑 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 = 𝑅𝑎𝑡𝑒𝑑 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 (1)
The rated current must not exceed the corresponding nominal cross-sectional
area of the supply cord’s conductors found in table 6.
38
“Supply cords shall not be in contact with sharp points or edges of the
appliance” [6, 77].
Sharp edges can easily damage the insulation of the supply cord, and possibly
expose the copper conductors inside the cable. Sharp edges may be allowed in
some circumstances, like if it is made of a soft material, like plastic. A softer
material may not cause damage to the supply cord. This is reviewed on a case-
by-case basis and even some sharp edges made of plastic may not pass this
test.
In this test the cord anchorage is tested. It is done by pulling and rotating the
supply cord. Depending on the mass of the appliance, pull force ranges from 30
N to 100 N and rotation force (Torque) ranges from 0.1 Nm to 0.35 Nm. The
forces applied are specified in Table 7 for each appliance weight class. [6, 79.]
Table 7 Pull force and torque applied to appliances. Copied from [6, 79].
The testing begins by marking the supply cord’s starting position with a marker.
The supply cord is then tied to a loop with a cable tie for the digital force gauge
to hook onto, as close as possible to the appliance.
39
“The cord is then pulled, without jerking, for 1 s in the most unfavourable
direction with the force specified. The test is carried out 25 times.” [6, 79.]
After the test, the cord shall not extrude more than 2 mm from the appliance.
[6, 79.]
Then for the rotation test, the torque meter is attached to the supply cord by first
cutting the cord about 30mm away from the appliance, or as close to the
appliance as the torque meter allows [6, 79]. The torque meter is then tightened
around the cord by the clamping mechanism in the torque meter.
The specified torque in Table 7 is applied for 1 minute. The cord shall not be
damaged, shall show no strain at the terminals and no wires may come loose.
[6, 79.]
“Accessible metal parts of class I appliances that may become live in the event of an
insulation fault, shall be permanently and reliably connected to an earthing terminal
within the appliance or to the earthing contact of the appliance inlet.
Class II appliances and class III appliances shall have no provision for earthing.”
[6, 84].
“Appliances shall be constructed so that the clearances, creepage distances and solid
insulation are adequate to withstand the electrical stresses to which the appliance is
liable to be subjected.
Clearances shall not be less than the values specified in Table 9, taking into account
the rated impulse voltage for the overvoltage categories of Table 8.
For reinforced insulation, instead of using the rated impulse voltage of 2 500 V,
the next higher step is used as reference. According to Table 8, the next higher
step from 2 500 V is 4 000 V. Minimum clearance for a rated impulse voltage of
4 000 V is 3.0mm. [6, 89-91.]
“Creepage distances of basic insulation shall not be less than those specified in
Table 10” [6, 94].
Table 10 Minimum creepage distances for basic insulation. Copied from [6, 94].
42
For all home appliances, Material group IIIa/IIIb is used. The pollution degree is
either 2 or 3, depending on where the appliance is to be used according to
instructions. If it is inside a home with no excessive amounts of moisture or
particles such as dust, pollution degree 2 applies. If the appliance may be
subjected to excessive amounts of moisture, water or particles, or the appliance
is meant to be used outside, pollution degree 3 applies.
Table 11 Minimum creepage distances for functional insulation. Copied from [6,
95].
43
Each layer of material shall withstand the electric strength test of 16.3 for
supplementary insulation. Supplementary insulation shall consist of at least 2 layers of
material and reinforced insulation of at least 3 layers.” [6, 96.]
The electric strength test of Clause 16.3 for supplementary insulation is 1 750 V
for appliances with rated voltage between 150 V and 250 V [6, 46]. However,
this test is done when there is doubt about the quality of the material, or when
there are less than 3 layers found.
The results of three chargers full testing were analysed, and only the tests that
would be conducted in basic testing were taken into account for the charger’s
safety evaluation. These test results can be found in Table 12, Table 13 and
Table 14 for chargers A, B and C respectively.
By comparing the results of the two testing methods, this chapter aims to
provide insights into the effectiveness of basic testing and the value of
conducting full testing for appliances that do not seek certification.
45
In all three sample cases, the result with basic testing would seem to show that
the appliance would give the same perception of safety as full testing. The
appliance passed all of the tests chosen for basic testing.
48
7 Conclusions
The analysis conducted with this small sample size indicated that basic testing
provides a similar perception of device’s safety as full testing. Indeed, the small
sample size has a significant impact on the final result. It does not provide a
true overall perception of the safety of all devices that would undergo basic
testing.
The analysis was performed specifically on fully tested chargers seeking for the
certification mark. Manufacturers have a strong incentive to build these
appliances in compliance with safety standards to obtain the certification mark
to make the certification process quick and cost-effective. On the other hand, for
devices that are not intended for certification, the standard may not even be
considered. In Finland, devices are required to comply with CENELEC
standards, which are based on IEC standards. It is possible that in other parts
of the world, such requirements do not exist, and the manufacturer has
produced their product for that kind of market. Then a Finnish importer
discovers the product and decides to bring it to Finland for sale. Of course, the
seller wants to sell their device, so they just put the importer's label on it, slightly
modify the appearance of the device, and place it on the shelves for sale in
Finland. Devices sold in Europe must have the CE marking, which means that
the device complies with EU directives, but the manufacturer itself assigns the
marking. It does not actually mean anything because, in Finland, only the
importer is reliable for ensuring that the manufacturer has conformed to the
regulations of the EU directives for the electrical appliance [22, 8].
To obtain a more reliable result regarding the difference between basic testing
and full testing, more analysis and tests would need to be conducted.
49
References
10 Kern & Sohn. Digital force gauge FK [Internet]. Kern & Sohn website shop;
[cited 2023 Apr 17] Available from: https://www.kern-
sohn.com/shop/en/measuring-instruments/force-gauges/FK/
https://fi.rsdelivers.com/product/mitutoyo/50019630/mitutoyo-150mm-
digital-caliper-001-mm-resolution/3074571
21 Retro Game Supply. Power supply for NEC PC Engine, CoreGrafX 1 & 2
[Internet]. Retro Game Supply webstore; [cited 2023 Apr 23].
Available from:
https://en.retrogamesupply.com/collections/frtvaexecption/products/power-
supply-for-nec-pc-engine-coregrafx-1-2