Upgrading A GC's BOS Firmware
Upgrading A GC's BOS Firmware
c. Click Save. A progress bar displays, you re-connect to the GC: “Application
allowing you to monitor the status of not Downloaded”. See Downloading the
the upload. When the process is new application to the GC below.
complete, the Save Parameter File
If you do not receive this message then the
dialog displays.
UniBOS upgrade was completed
d. Assign a name to the parameter file successfully.
and click Save.
e. Disconnect from the Offline Edit Downloading the new application
mode. to the GC
Select Disconnect from the File To download a new application file to the
menu. GC, do the following:
17. Re-connect to the GC. 1. Select Download... from the File menu.
The Select GC Application file to
18. Select Upgrade Flash... from the File Download dialog displays.
menu. The Select BOS File to Download
dialog displays. 2. Locate the new application file on the
MON2000 CD and select it.
19. Navigate to the new BOS file and select
it. Note: The file should have the same root
name as the old application file;
20. Click Open. A progress bar displays, however, the version number (vNNN)
allowing you to monitor the status of the should be higher.
BOS upgrade.
3. Click Open. A progress bar appears,
Note: If the “Unexpected internal allowing your to monitor to status of the
GC controller error” message download. When the download
appears, do the following: disconnect completes, the Set GC Time dialog
from the GC; warm start the GC; re- appears.
connect to the GC; repeat step 18.
4. Set the correct time and click OK.
When the upgrade is complete, the GC
wil restart. 5. Set up the application parameters—i.e.,
component data tables and timed events
21. Connect to the GC. tables—using the values from the
If your current application file is not uploaded app.
compatible with the new UniBOS upgrade, it The upgrade is complete.
will be deleted during the upgrade process
and the following message will display when