MLM dn32s Honeywell PLC
MLM dn32s Honeywell PLC
AUTOMATION
MADE EASY & COMPACT
1|Page
M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE
Compact
ML50 series is extremely compact providing both powerful functions and performance. The dual combination of Compactness &
Performance is what makes ML50 such an ideal product.
unit=mm(in)
Item W H D
W Main Unit MLM-D_ _S 30(1.18) 90(3.54) 60(2.36)
MLC(I)-D_32H 114(4.49) 90(3.54) 64(2.52)
D MLC(I)-D_64H 180(7.09) 90(3.54) 64(2.52)
MLI-D_SU 135(5.3) 90(3.54) 64(2.52)
MLI-D20E/30E
MLI-D_10E/14E 100(3.94) 90(3.54) 64(2.52)
H MLI-D_ _U 135(5.31) 90(3.54) 64(2.52)
Expansion Modules 20(0.79) 90(3.54) 60(2.36)
H H
W D W D
D
W
1|Page
M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE
2|Page
M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE
Web Server
Monitoring of PLC information and data through web browser (PLC basic info., module info., diagnosis, variables
monitoring, special flag monitoring, data log file download from server, firmware/ project file update, etc.)
Time synchronization by setting basic parameters (SNTP: Simple Network Time Protocol)
Email service through commercial email (SMTP: Simple Mail Transfer Protocol)
3|Page
M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE
*1 Each number in ( ) is the number of modules that can be mounted for each function (network, special function, expansion I/O).
And the total number of mountable expansion modules is limited to 7.
*1 Each number in ( ) is the number of modules that can be mounted for each function (network, special function, expansion I/O).
And the total number of mountable expansion modules is limited to 10.
4|Page
M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE
Main Unit
MLI-D_ _SU
*1 Each number in ( ) is the number of modules that can be mounted for each function (network, special function, expansion I/O).
And the total number of mountable expansion modules is limited to 7.
Main Unit
MLI-D_ _E
5|Page
M a s t e r L o g i c 5 0 S e r i e s SPECIAL FEATURE
Network scan
Multifunctional
The ML50 series provides the optimum solution for your automation tasks with a range of powerful functions such as:
Model
MLI-U MLC-H, MLI-H MLI-SU MLI-E MLM-S
Phase
100kHz(4ch) 100kHz(2ch)
100kHz(ch) 4kHz 20kHz
1 Phase 20kHz(4Ch) 20kHz(6Ch)
8Ch 8Ch 8Ch 4Ch 4Ch
2 Phase 50kHz(4Ch) 50kHz(1Ch) 2 multiplication: 10kHz
50kHz(4Ch) 2kHz
10kHz(4Ch) 8kHz(3Ch) 4 multiplication: 8kHz
4Ch 4Ch 4Ch 2Ch 2Ch
6|Page
M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT
Square wave
impulse noise AC±1,500V / DC±900V Internal Standard
Electrostatic IEC61131-2
discharge 4kV(Contacted) IEC61000-4-2
7 Noise resistance
Radiated IEC61131-2
electromagnetic 80 ~ 1,000MHz, 10V/m IEC61000-4-3
Fast transient/ Main unit Expansion module IEC61131-2
Burst noise 2kV 1kV IEC61000-4-4
8 Operating Ambience Free from corrosive gasses and excessive dust
9 Altitude Up to 2,000m
10 Pollution level *1 Less than equal to 2
11 Cooling Air-cooling
*1 Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution
level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.
7|Page
M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT
i
Built-in function
Specification
Item Remark
MLI-DN32U MLI-DR28U MLI-DN32UA MLI-DR28UA
Control by instruction, auto-tuning, PWM output, Forced output, Operation scan time setting,
PID control
Anti-windup, Delta MV, PV tracking, Hybrid operation, Cascade operation
Serial Protocol Dedicated protocol, Modbus protocol, User defined protocol , Embedded00
communication Channel RS-232C 1 port and RS-485 1 port P2P : 01
Transfer Spec Cable: 100Base-TX, Speed: 100Mbps, Auto-MDIX *1, IEEE 802.3
Topology Line, Star
Ethernet Diagnosis Module information, service condition
Protocol Dedicated protocol, Modbus protocol, User defined protocol Embedded01P2P:02
Service P2P, High Speed link, Remote connection High-speedlink:01
Group Max 10 groups
Data set 32 per group
Format csv format(Comma Separated Values)
Data Log
File size Max 16Mbytes for each
SD memory type SD,SDHC type(Recommendation : SanDisk, Transcend), File system : FAT32
Memory size Max 16GB
Performance 1-phase : 100KHz 8 channels / 2-phase : 50KHz 4 channels
4 counter modes are supported based on input pulse and INC/DEC method
1 pulse operation Mode : INC/DEC count by program
High
Counter mode 1 pulse operation Mode : INC/DEC count by phase B pulse input
Speed
2 pulse operation Mode : INC/DEC count by input pulse
Counter
2 pulse operation Mode : INC/DEC count by difference of phase
Internal/external preset • Latch counter
Function
Compare output • No. of rotation per unit time
8|Page
M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT
Built-in function
Specification
Item Remark
MLI-DN32U MLI-DR28U MLI-DN32UA MLI-DR28UA
Protocol : HTTP(Ver 1.1)
Webserver
Other functions : Checking the PLC history, Device monitoring, user page, manage the Data log file
9|Page
M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT
Modular “S” type(MLM)
General specification
Item Descriptions Standard
1 Ambient 0~55℃
2 temperature
Storage -25~+75℃
3 temperature
Ambient humidity 5~95%RH (Non-condensing)
4 Storage humidity 5~95%RH (Non-condensing)
Occasional vibration
Frequency Acceleration Pulse width
10 ≤ f < 57Hz - 0.075mm
57 ≤ f < 150Hz 9.8m/s2(1G) - 10 times each direction IEC61131-2
5 Vibration resistance
Continuous vibration (X, Y and Z)
Frequency Acceleration Pulse width
10 ≤ f < 57Hz - 0.035mm
57 ≤ f < 150Hz 4.9m/s2(0.5G) -
∙Peak Acceleration : 147m/s2(15G) ∙Duration : 11ms
6 Shock resistance ∙Pulse waveform : Half-sine, 3times each direction per each axis IEC61131-2
Square wave
impulse noise AC±1,500V / DC±900V Internal Standard
Electrostatic IEC61131-2
discharge 4kV(Contacted) IEC61000-4-2
7 Noise resistance
Radiated IEC61131-2
electromagnetic 80 ~ 1,000MHz, 10V/m IEC61000-4-3
Fast transient/ Main unit Expansion module IEC61131-2
Burst noise 2kV 1kV IEC61000-4-4
8 Operating Ambience Free from corrosive gasses and excessive dust
9 Altitude Up to 2,000m
10 Pollution level *1 Less than equal to 2
11 Cooling Air-cooling
*1 Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution
level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.
Performance
Model
Item
MLM-DR16S MLM-DN16S MLM-DN32S
Control method Repetitive, cyclic, interrupt, constant scan
Refresh mode (Batch processing by scan synchronization)
I/O control mode
Direct mode by instruction
Programming language Ladder Diagram, Instruction List
No. of instructions Basic : 28, Applied : 677
Processing speed 160ns /Step (for basic instruction)
Program capacity 10k steps
Max. I/O points 256 points (Main + 7 expansions)
P P0000 ~ P127F (2,048 points)
M M0000 ~ M255F (4,096 points)
K K00000 ~ K2559F (Special area : K2600~2559F) (40,960 points)
L L00000 ~ L1279F (20,480 points)
F F000 ~ F255F (4,096 points)
T 100ms, 10ms, 1ms : T000 ~ T255 (Changeable by Parameter setting)
Data memory C C000 ~ C255
S S00.00 ~ S127.99
D D0000 ~ D5119 (5,120 word)
U U00.00 ~ U07.31 (Analog data refresh area : 256 word)
Z Z000~Z127 (128 word)
N N0000~N3935 (3,936 word)
Number of program 128
Operation mode RUN, STOP, DEBUG
Self diagnosis Operation delay monitoring, memory error, I/O error, battery error, power error, etc.
Program port RS-232C (Loader) Remote connection using RS-232C, RS-485
Data retention at power failure Latch range setting at Basic parameter
RS-232C/485, High-speed counter, PID control, Pulse catch, Input filter, Position control
Built-in function
External interrupt, Positioning *1
Internal current consumption 400mA 280mA 300mA
Weight 100g
10 | P a g e
M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT
Square wave
impulse noise ±1,500V Internal Standard
Electrostatic IEC61131-2
discharge 4kV IEC61000-4-2
7 Noise resistance
Radiated IEC61131-2
electromagnetic 27 ~ 500MHz, 10V/m IEC61000-4-3
Fast transient/ Main unit Expansion module IEC61131-2
Burst noise 2kV 1kV IEC61000-4-4
8 Operating Ambience Free from corrosive gasses and excessive dust
9 Altitude Up to 2,000m
10 Pollution level *1 Less than equal to 2
11 Cooling Air-cooling
*1 Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution
level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.
Performance
Model
Item
MLC-DR32H MLC-DN32H MLC-DR64H MLC-DN64H MLI- DR32H MLI-DN32H MLI-DR64H MLI-DN64H
Control method Repetitive, cyclic, interrupt, constant scan
I/O Control mode Refresh mode (Batch processing by scan synchronization), Direct mode by instruction
Programming language Ladder Diagram(LD), Instruction List(IL) LD, IL, Structured Text(ST), Sequential Function Chart(SFC)
No. of instructions Basic : 28, Applied : 677 Function Blocks
Processing speed 83ns /Step (for basic instruction) 83ns /Step (for basic instruction)
Program capacity 15k steps 200kB(15k steps)
Max. I/O points 384 points (Main + 10 expansions) 384 points (Main + 10 expansions)
P P0000 ~ P1023F (16,384 points) A 32KB (Max. 16KB retain setting available)
M M0000 ~ M1023F (16,384 points) I 2KB(%IX 15.15.63)
K K00000 ~ K4095F (65,536 points) Q 2KB (%QX 15.15.63)
L L00000 ~ L2047F (32,768 points) M 16KB (Max. retain setting available)
F F000 ~ F1023F (16,384 points) R 20KB (1 block)
T 100ms, 10ms, 1ms : T000 ~ T1023 (Changeable by Parameter W 20KB, Same area as ‘R’
Data memory C C000 ~setting)
C1023(1,024) F 2KB, System flag
S S00.00 ~ S127.99 K 8KB, Built-in special flag
D D0000 ~ D10239 (10,240 word) L 4KB, High speed link flag
U U00.00 ~ U0A.31 (Analog data refresh area : 352 word) N 10KB, P2P flag
Z Z000~Z127 (128 word) U 1KB, Analog Flag
N N0000~N5119 (5,120 word) Flash 20KB (2 block), R device used
Number of program 128 128
Operation mode RUN, STOP, DEBUG RUN, STOP, DEBUG
Self diagnosis Detects error of scan time, memory error, I/O error, battery error, power error, etc.
Program port USB (Rev 1.1), RS-232C 1 channel (Loader)
Data retention at power failure Latch range setting at Basic parameter
RS-232C/485, High-speed counter, PID control, Pulse catch, Input filter
Built-in function
RTC, External interrupt,
Internal current consumption 660mA 260mA 1040mA Positioning *1 660mA
330mA 260mA 1040mA 330mA
Weight 600g 500g 900g 800g 600g 500g 900g 800g
11 | P a g e
M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT
Modular “SU” type(MLI-D_ _ SU) and Economic “E”(MLI-D_ _ E)
General specification
Item Descriptions Standard
1 Ambient 0~55℃
2 temperature
Storage -25~+75℃
3 temperature
Ambient humidity 5~95%RH (Non-condensing)
4 Storage humidity 5~95%RH (Non-condensing)
Occasional vibration
Frequency Acceleration Pulse width
10 ≤ f < 57Hz - 0.075mm
57 ≤ f < 150Hz 9.8m/s2(1G) - 10 times each direction IEC61131-2
5 Vibration resistance
Continuous vibration (X, Y and Z)
Frequency Acceleration Pulse width
10 ≤ f < 57Hz - 0.035mm
57 ≤ f < 150Hz 4.9m/s2(0.5G) -
∙Peak Acceleration : 147m/s2(15G) ∙Duration : 11ms
6 Shock resistance ∙Pulse waveform : Half-sine, 3times each direction per each axis IEC61131-2
Square wave
impulse noise ±1,500V Internal Standard
Electrostatic IEC61131-2
discharge 4kV IEC61000-4-2
7 Noise resistance
Radiated IEC61131-2
electromagnetic 27 ~ 500MHz, 10V/m IEC61000-4-3
Fast transient/ Main unit Expansion module IEC61131-2
Burst noise 2kV 1kV IEC61000-4-4
8 Operating Ambience Free from corrosive gasses and excessive dust
9 Altitude Up to 2,000m
10 Pollution level *1 Less than equal to 2
11 Cooling Air-cooling
*1 Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used. Pollution
level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due to condensing.
Performance
Model
Model
MLI-DN20SU MLI-DN30SU MLI-DN40SU MLI-DN60SU MLI-DN10E MLI-DN14E MLI-DN20E MLI-DN30E
Specification
MLI-DR20SU MLI-DR30SU MLI-DR40SU MLI-DR60SU MLI-DR10E MLI-DR14E MLI-DR20E MLI-DR30E
Control method Repetitive, cyclic, interrupt, constant scan Repetitive, cyclic
Refresh mode (Batch processing by scan synchronization)
I/O control mode
Direct mode by instruction
Programming language Ladder Diagram(LD), Sequential Function Chart(SFC), Instruction List(IL), Structured Text(ST)
Processing speed 94ns /Step (for basic instruction) 240ns /Step
Program capacity 200kB(15k steps) 50kB(4k steps)
Main module I/O points 20 points 30 points 40 points 60 points 10 points 14 points 20 points 30 points
Max. I/O points 244 points 254 points 264 points 284 points 14 points 18 points 28 points 38 points
A 16KB (Max. 16KB retain setting available) 8KB (Max. 8KB retain setting available)
I 2KB(%IX 15.15.63) 256 Byte (%IX15.15.63)
Q 2KB (%QX 15.15.63) 256 Byte (%QX15.15.63)
M 8KB (Max. retain setting available) 4KB
R 20KB (1 block) 10KB (1 block)
W 20KB, Same area as ‘R’ 10KB
Data memory F 2KB, System flag 768 bytes
K 8KB, Built-in special flag 5,120 bytes
L 4KB, High speed link flag 2,560 bytes
U 1KB, Analog Flag 704 bytes
Flash 20KB (2 block), R device used -
Number of program 128 128
Operation mode RUN, STOP, DEBUG RUN, STOP, DEBUG
Self-diagnosis Operation delay monitoring, memory error, I/O error, battery error, Operation delay monitoring, memory error, I/O error, etc
power error, etc.
Program port RS-232C (Loader) Remote connection using RS-232C, RS-485 1ch RS-232C (Loader)
Data retention at power failure Latch range setting at Basic parameter Latch range setting at Basic parameter
RS-232C, RS485, High-speed counter, PID control, Pulse catch, Input RS-232C or RS485, High-speed counter, Pulse catch,
Built-in function filter, Position control Input filter *2
External interrupt, Positioning *1 -
Internal current consumption 252mA / 478mA 270mA / 626mA 288mA / 684mA 340mA / 942mA 180 / 250 mA 190 / 315mA 200 / 355 mA 210 / 485 mA
Weight(g) 475g (1.05lb) 474g (1.045lb) 578g (1.27lb) 636g (1.40lb) 313(0.69lb) 315(0.694lb) 418(0.92lb) 423(0.93lb)
514g (1.13lb) 528g (1.16lb) 594g (1.31lb) 804g (1.77lb) 330((0.72lb) 340(0.75lb) 450(0.992lb) 465(1.03lb)
*1. MLC-DR_H or MLI-DR_H are not supported.
*2. Not allowable to use RS232C and RS485 at the same time.
12 | P a g e
M a s t e r L o g i c 5 0 S e r i e s MAIN UNIT
3 Input connector
Input wiring connection -
/Terminal block
4 Output connector
Output wiring connection -
/Terminal block
5 Mode switch *2 Mode setting Setting Run/Stop mode of PLC
In case of STOP, the remote operation is available
Red On: Input signal On
PWR: Power indication
Red Off: Input signal Off
Green On: PLC Run
RUN: RUN indication
Green Off: PLC Stop
Red On-and-Off: PLC Error
6 Condition LED ERR: Error indication
Red Off: PLC Normal condition
Red On : SD card is inserted
STATE: Error indication
Red off : SD card has error(flickering)
8 Built-in FEnet connector Built-in FEnet connection FEnet, 2ports(one is for switch)
9 Built-in Serial communication Built-in RS-232C/RS485
*3
10 Battery Holder Battery holder
13 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Main Unit
Digital Input l DC24V
Model DC24V
Specification MLI-DN32U/MLI-DN32UA MLI-DR28U/MLI-DR28UA
Input points 16points 16points
Insulation method Photo-coupler insulation
Rated input voltage/current DC24V / 4mA (Contact 00~03 : 7mA)
Operation voltage range DC20.4~28.8V (Ripple rate < 5%)
On voltage/On current DC19V or more / 3mA or more
Off voltage/Off current DC6V or less / 1mA or less
Input resistance 5.6k Ω (Contact 00~07 : 4.7k Ω)
Off→On
Response time 1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value : 3ms
On→Off
Insulation pressure AC560Vrms / 3 Cycle (altitude 2000m)
Insulation resistance 10㏁ or more by megger
COMMON method 16 points/COM
Proper cable size Twisted wire 0.3~0.75mm2 (external diameter ≤2.8mm)
Operation indication Input On LED On
8-pin terminal block + 10 point terminal connector
External connection method
14 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Features and Functions (MLC/MLI “H”, MLI “SU”/”E”, MLM)
10 72 1
9 1 3
Name Descriptions Descriptions
44 Red On: Input signal On
1 Input LED Input indication
5 Red Off: Input signal Off
5 6
Red On: Input signal On
PWR: Power indication
6 Red Off: Input signal Off
MasterLogic 50 configuration
15 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Main Unit
Digital Input l DC24V
DC24V
Model Modular type(MLM) Block type(MLC, MLI)
Specification MLM-DR16S MLM-DN16S MLM-DN32S ML_-DR32H ML_-DN32H ML_-DR64H ML_-DN64H
ML_-DR32H/DC ML_-DN32H/DC ML_-DR64H/DC ML_-DN64H/DC
Input points 8points 8points 16points 16points 16points 32points 32points
Insulation method Photo-coupler insulation
Rated input voltage/current DC24V / 4mA (Contact 00~03 : 7mA) DC24V / 4mA (Contact 0~7 : 9mA)
Operation voltage range DC20.4~28.8V (Ripple rate < 5%)
On voltage/On current DC19V or more / 3mA or more
Off voltage/Off current DC6V or less / 1mA or less
Input resistance 5.6k Ω (Contact 00~03 : 3.3k Ω) 5.6k Ω (P00~P07 : 2.k Ω)
Off→On
Response time 1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value : 3ms
On→Off
Insulation pressure AC560Vrms / 3 Cycle (altitude 2000m)
Insulation resistance 10㏁ or more by megger
COMMON method 8 points/COM 16 points/COM 16 points/COM 16 points/COM
Proper cable size Twisted wire 0.3~0.75mm2 (external diameter ≤2.8mm)
Operation indication Input On LED On
9-pin terminal 20-pin 20-pin 24 points connecting connector 42 points connecting connector
External connection method block connector connector (M3 x 6 screws) (M3 x 6 screws)
16 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
17 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
18 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Expansion
Digital Input l DC24V
Model DC24V
Expansion module
Specification
MLE-DC08A MLE-DC16A MLE-DC32A MLE-DR16A
Input points 8points 16points 32points 8points
Insulation method Photo-coupler insulation
Rated input voltage/current DC24V / 4mA
Operation voltage range DC20.4~28.8V (Ripple rate < 5%)
On voltage/On current DC19V or more / 3mA or more
Off voltage/Off current DC6V or less / 1mA or less
Input resistance 5.6k Ω
Off→On
Response time 1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value : 3ms
On→Off
Insulation pressure AC560Vrms / 3 Cycle (altitude 2000m)
Insulation resistance 10㏁ or more by megger
COMMON method 8 points/COM 16 points/COM 32 points/COM
Proper cable size Twisted wire 0.3~0.75mm2 (external diameter ≤ 2.8mm)
Operation indication Input On LED On
9-pin terminal block 8-pin + 10-pin terminal block 40-pin connector 9-pin terminal block
External connection method
19 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Expansion
Analog Input l
Model MLF-AD04A MLF-AD08A Remark
Specification Voltage Current Voltage Current
Number of Channels 4 channels 8 channels
Analog Item DC voltage DC current DC Voltage DC Current
Range Range DC 0~10V DC 4~20mA, DC 0~20 mA DC 1~5V, DC 0~5V DC 4~20mA,
(Input resistance : 1MΩ min.) (Input resistance : 250Ω) DC 0~10V, DC-10~10V DC 0~20 mA
(Input resistance : 1MΩ min.) (Input resistance : 250Ω)
For analog module(8channel), it’s needed to connect the following version info.
1 No Name Descriptions
►Indicates condition of modules
1 RUN LED LED ON : Normal Condition
LED ON and OFF : Flickering
2 LED Off : Power Off or Module malfunction
►in wiring between input module and external device, please use 22AWG and 2-core, twisted-
shielded wire.
20 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Expansion
Analog Output l
Model MLF-DV04A MLF-DC04A Remark
Specification Voltage Current
Number of Channels 4 Channels 4 Channels
Analog Range DC 0~10V (Load resistance ≥ 2kΩ) DC 4~20mA / DC 0~20 mA (Load resistance ≤ 510Ω)
Analog range selection - Softmaster I/O parameter
Output Range 0 ~ 10V 4 ~ 20mA / 0 ~ 20mA
Unsigned Value 0 ~ 4000 0 ~ 4000
Singed Value -2000 ~ 2000 -2000 ~ 2000
Digital data
Precise value 0 ~ 1000 200 ~ 2000 / 0 ~ 2000
Percentile value 0 ~ 1000 0 ~ 1000
Data format of digital input is set by user program or I/O parameter
Data Format
(Setting for each channel is available)
1/4000 1/4000
Resolution
2.5mV 5µA
Accuracy ±0.5% less
Max. Conversion Speed 1.0msec / channel
Max. Absolute input DC ±15V DC ±25mA
Analog Input channels 4 channel / module
Photo-coupler insulation between I/O terminal and Photo-coupler insulation between I/O terminal and
Insulation
power supply power supply
Connection Terminal 11-point terminal block 11-point terminal block
Occupied I/O points Fixed type : 64 points
Consumption DC5V(Internal) 110mA 110mA
Current DC24V(External) 70mA 120mA
Max Connectable modules 7sets (MLM series, “S” type), 10sets(MLC series, “H” type)
Weight 64g 70g
No Name Descriptions
►Indicates condition of modules
LED ON : Normal Condition
1 RUN LED
LED ON and OFF : Flickering
LED Off : Power Off or Module malfunction
2 Terminal Block ►External device connection
2 External power
3 ►External DC24V input
supply terminal
MLF- MLF-
2kΩ or more 510Ω or more
DV04A DC04A
21 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Expansion
Analog Input and Output l
Model MLF-AH04A
Specification Remark
Voltage Current Voltage Current
Analog Item DC Voltage DC Current DC Voltage DC Current
Range Range DC 1~5V, DC 0~5V DC 4~20mA, DC 1~5V, DC 0~5V DC 4~20mA,
DC 0~10V, DC-10~10V DC 0~20 mA DC 0~10V, DC-10~10V DC 0~20 mA
(Input resistance : 1MΩ min.) (Input resistance : 250Ω) (Input resistance : 2kΩ min.) (Input resistance : 510Ω)
For analog IO(4channel), it’s needed to connect the following version info.
No Name Descriptions
1 ►Indicates working condition of inputs
1 INPUT LED LED ON : Normal Condition
2 LED ON and OFF : Flickering
LED Off : Power Off or Module malfunction
►in wiring between input module and external device, please use 22AWG and 2-core, twisted-
shielded wire.
22 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Expansion
RTD input l
No Name Descriptions
Name of parts ►Indicates condition of modules
LED ON : Normal Condition
1 RUN LED LED ON and OFF : Flickering
LED Off : Power Off or Module malfunction
23 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Expansion
TC input l
No Name Descriptions
Name of parts ►Indicates condition of modules
LED ON : Normal Condition
1 RUN LED LED ON and OFF : Flickering
LED Off : Power Off or Module malfunction
Compensation
Module cable Terminals Shield cable Sensor
24 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Expansion
Positioning Module l
25 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Expansion
High Speed Counter Module l
Model Specification
1 Specification MLF-HO02A MLF-HD02A
Count input Signal A-phase, B-phase
signal Input type Voltage input (Open Collector) Differential input (Line Drive)
Signal level DC 5/12/24V RS-422A Line Drive/HTL LEVEL Line Drive
Max. Coefficient speed 200 kpps 500 kpps(HTL input : 250 kpps)
Number of channels 2 channels
Coefficient Range Signed 32-bit (-2,147,483,648 ~ 2,147,483,647)
Linear Count (When 32-bit range exceeded, Carry /Borrow occurs, The count value stopped)
Count Mode
Ring Count (Repeated count within setting range)
1-phase input
Input Pulse Mode 2-phase input
2 CW/CCW input
Increasing / Decreasing operation setting by B-phase input
1 phase input
Increasing / Decreasing operation setting by program
Up/down
2 phase input Automatic setting by difference in phase
setting
A-phase input: Increasing operation
CW/CCW
B-phase input: Decreasing operation
1 phase input 1/2 multiplication
Multiplication 2 phase input 1/2/4 multiplication
CW/CCW 1 multiplication
Signal Preset instruction input, Auxiliary mode instruction input
Control input Signal level DC 5V/12V/24V (by terminal selection) input type
Signal type Voltage
Output points 2-point/channel (for each channel): Terminal output available
External Select single-compared (>, >=, =, =<, <) or
Type
output section compared output (Included or excluded)
Output type Open collector output (Sink)
Input Signal A-phase input, B-phase input, Preset instruction input, Auxiliary mode instruction input
Operation
Output Signal External output 0, External output 1
Status Display
Busy Status Module Ready
Count enable To be set through program (Count available only in enable status)
Preset function To be set through terminal or program
Count clear,
Count latch,
Section count(time setting value: 0~60000㎳),
Auxiliary mode function
Measurement of input frequency(for respective input phase),
Measurement of counts per hour(time setting value: 0~60000㎳)
Count prohibited function
Terminal 40 pin connector
I/O occupied points Fixed point: 64
Current consumption(mA) 200 260
Weight 90g
26 | P a g e
M a s t e r L o g i c 5 0 S e r i e s INPUT & OUTPUT
Option Board
MLI “SU” and “E” of ML50 PLC provides the optimal solution of cost-effective and attachable for MLI series.
Name of parts
No Name Descriptions
1,4 Hook for fixing Hook for fixing on front side of Main module
6 Connector for wiring Connects the option board with an main module
27 | P a g e
M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS
HMI HMI
Item MLL-EMTA
Communication spec. 10/100BASE-TX
Protocol TCP/IP, UDP/IP
Service With ML PLCs High-speed link, P2P service
With other devices P2P service
Application Dedicated protocol service, SoftMaster service
HS link sending/receiving data 200words/block(Max.128blocks)
No. of channel connectable to upper stage 8 channels
Service Communication with PC(HMI) and external devices, High-speed communication among ML PLCs
Media UTP/STP Category 5
Current consumption (mA) 410
RS-232C
SoftMaster
Main unit
Dedicated modem
RS-232C/485 Dedicated
modem
Other net Smart I/O
devices
HCi/HCiX ML50 Inverter
Specification
Item
Built-in RS-232C MLL-C21A Built-in RS-485 MLL-C41A
interface RS-232C 1Ch RS-232C 1Ch RS-485 1Ch RS-422/485 1Ch
Modem connection Remote communication with external devices via modem connection, Available for only RS-232C port.
communication Dedicated mode 1:1 or 1:N communication using MLDP
mode SoftMaster mode Program upload/download and remote control
P2P mode Communication by protocal using SoftMaster-NM (Interface with other PLCs),
MLDP, MODBUS RTU/ASCII master communication
Operation Server(Slave) Remote connection simultaneoualy using MLDP/Modbus Server, user-defined
mode Master MLDP, MODBUS RTU/ASCII master, user-defined
Start Bit 1
Data Bit 7 or 8
Data type Stop Bit 1 or 2
Parity Even/Odd/None
Setting Basic parameter setting with SoftMaster-NM
Synchronization Asynchronous
Transmission speed (bps) Selectable among 1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps
Station number setting Up tp 32 stations from 0 to 31 with SoftMaster-NM
Transmission distsnce RS-232C: Max. 15m (Extendfible by using modem), RS-422/485: Max. 500m
Modem communication Not available Available Not available Not available
Network configuration 1:1 1:N
Diagnosis function Available through LED and SoftMaster-NM dagnosis service
Max. number of installation Built-in 2 Built-in 2
28 | P a g e
M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS
Features-Ethernet IP
Communication : Extensive Client Messaging Support
- Encapsulated Messages, UCMM Explicit Messaging
- Class 3 Connected Explicit Messaging(Server only)
- Class 1 Connected Implicit(IO) Messaging(Cyclic I/O Service Oly)
Compatibility : Complied with Ethernet/IP conformance Test Suite Ver 2.10
Not required to add any Switch Hub by internal function, but provided wiring reduction and flexibility of
installation
Diagnostics and status of each module and Network
- Provided the status of Communication module, Communication service(EIP, non-cyclic server)
- Automatic scanning to detect all module information for Honeywell or other makers
- Forecasting network traffic from various packets and data rate to receive into communication module
- Diagnosis of communication module over network
Item MLL-EIPT
Transmission Speed 10Mbps
Transmission Method Base band
Max. Extension distance
Transmission Standard 100meters(328 feets)
between nodes
Access Method to service zone CSMA / CD
Frame Error Check CRC 32 = X32+ X26 + X23 + ,,,,, + X2 + X + 1
Topology Linear, Star
Periodic Client Implicit IO Client
Service Aperiodic Client UCMM Client
Periodic Server Implicit IO Server
The number of TCP 16 / 32
connections(Client/Server)CIP(IO communication) 32 / 64
No. of Max. services(P2P) 2
No. of Max. installations 2
Max setting data size Periodic client 500 bytes
per block Non-periodic client 512 bytes
Dimension (mm) H x W x D = 90 x 27 x 60 mm (3.54 x 1.06 x 2.36 inch)
Basic standard Current consumption (mA) 290
Weight(g) 102
29 | P a g e
M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS
CANopen Slaves
CANopen CANopen Master HMI Speed Driver Encoder
Configuration
120 120
Features-CANopen
Open network to use on industrial fields
- Transmitting Method : CSMA/BA(Carrier Sense Multiple Access/Bitwise Arbitration)
- Compliant with CANopen(CiA DS301) standard
Attachable up to 2 sets per basic unit
8kinds of Communication speed are available. (10, 20, 50, 100, 125, 250, 500, 800, 1000Kbps)
Connectable max 32sets for slaves, provided Diagnostics and status information for each module
With provision of switch function internally, not needed to add any switch-hub. Benefit to reduced wirings and
flexible for installation
Due to Auto Cross-over function, ease to wiring and cable work
Diagnostics and status of each module and Network
- Provided the status of Communication between Master and Slave over Device Diagnosis
- Automatic scanning to detect all module information for Honeywell or other makers
- Shows the recent 10 items of historical information (MLL-CSEA)
30 | P a g e
M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS
Common Specs
No Name Descriptions Remark
2 I/F Flickering Interface status with main unit - Normal In abnormal case,
(Yellow) Stopped ON or OFF
OFF or ON Not interface status with main unit
Green
3 TX Flickering Sending a packet frame Display sending
(Green) status of frame
OFF or ON Not sending
Green
4 RX Flickering Receiving a packet Display receiving
(Green) status of frame
OFF or ON Not receiving
Green
5 ERR ON/Flickering On Error
(Red) Display by CiA303-3
OFF Normal operation
Green
31 | P a g e
M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS
When I/O module is installed, check the current consumption, supplicable Max 1.5A
32 | P a g e
M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS
Product List l
Item Model Descriptions
33 | P a g e
M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS
Product List l
Item Model Descriptions
Communication
MLL-EMTA Fast Ethernet (100Mbps), 1ch
module MLL-EIPT Ethernet/IP, 2channel
MLL-CMEA CANopen(max 1000kbps, Num of PDO : 32)
MLL-CSEA CANopen(max 1000kbps, Num of PDO : 64)
MLL-PMEC Profibus-DP, Master
PMC-310S Configuring Cable serial, PC(9pin)-PLC(6pin)
USB-301A Configuring Cable, USB
MLO-AD02A 2-channel Analog input (Current/Voltage)
MLO-DA02A 2-channel Analog output
Option Boards MLO-AH02A 1-ch Analog input(I/V), 1ch Analog output(I/V)
for “SU”, “E”
MLO-TC02A 2-channel Thermo-couple input(non-isolation)
MLO-RD01A 1-channel RTD input
MLO-RTCA RTC, BAT for back-up
MLO-M2MB Option Memory, 2Mbytes
Smart IO MPL-BSSA Profibus-DP Adapter
Extendable
MDL-BSSA Device Net Adapter
MEL-BSSA Ethernet, Modbus TCP adapter
MEL-BSSB Ethernet IP adapter
34 | P a g e
M a s t e r L o g i c 5 0 S e r i e s COMMUNICATIONS
Smart Link
Terminal MLM-DN16S
Connection Cable MLE-DC32A MLE-TN32A Cable Length Remark
Board MLM-DN32S
R40H/20HH-05S 0.5m
R40H/20HH-10S 1.0m
TG7-1H40S
C40HH-15S-XBI 1.5m
C40HH-30S-XBI 3.0m
Configuration Cable
PC side
(9pin, Female)
35 | P a g e
Australia Japan Philippines
Honeywell Ltd. Honeywell Inc. Honeywell Systems (Philippines) Inc.
Phone: (61) 2-9353-7000 Phone: (81) 3-6730-7149 Phone: (63) 2-633-2830/31
Fax: (61) 7-3840-6488 Fax: (81) 3-6730-7228 Fax: (63) 2-638-4013
Honeywell offers a complete portfolio of products and solutions for process and machine control applications, including controllers, recorders,
transmitters, actuators, smart sensors, and analytical instruments. To learn more about these offerings and how they can help your organization
achieve breakthrough results, contact your local Honeywell representative, or contact us at the following phone numbers:
Warranty / Remedy
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales
office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or
replace without charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all other warranties,
expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without
notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility
for its use. While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the
customer to determine the suitability of the product in the application.
36 | P a g e