Technical Site Survey Report for ZTE Network Expansion 2 Project

LTE Upgrade Sector Implementation

Site Name: Kadathiha

Site ID: ANTWN1

Site Engineer: Mr. Jennis Fernando

Sub Contractor: ZTE

New Band: LTE

Survey Date: 29-Mar-21

Approval Mobitel ZTE

Name Mr.Asanka Herath

Signature

Date

Mobitel Remark :-
............................................................................................................................. ..................................
............................................................................................................................. ..................................
............................................................................................................................. ..................................
............................................................................................................................. ..................................
............................................................................................................................. .................................
1. Site Information

Site location Adderss : M.V.D.S.Gunasekara_No:519/12,Stage_2,Anuradhapura


information Coordinates- Latitude : 8.3286 Longitude: 80.4

Site Operator : Mobitel Access Key: Building owner


Information Mobitel regional leader : Mr.Amila Telephone No: 712760911
Equipment room location Equipment installation cabinet:

Roof top Floor No: 2 Shelter


Greenfield Outdoor Cabinet
Site
environment Other
checking Distance of Manual Transport required, Yes No

Any Special Delivery System Required? Yes . Crane required for material Deviver to 4th floor.

The Distance to the Site from Colombo 200Km


Site access
Access Restriction Yes No Contact person: :Mr: Kokila 714756781
information
Tower Type: Self Support tower (SST) Guyed Mast tower (GMT) Monopole Tower Pole
Tower Tower Leg Qty: 3 Tower Leg type: Angular Tubular

Tower Height: 18m

2.Existing Installation Details

Sector 1 Sector 2 Sector 3 Sector 4


Sector

Exsiting Band 1800 & LTE 1800 & LTE 1800 & LTE

Existing RRU Type R9214E S1800 R9214E S1800 R9214E S1800

Antenna Height 18m 18m 18m

Antenna Type 8 Port Antenna 8 Port Antenna 8 Port Antenna

Antenna Location H/F H/F H/F

Existing Antenna Direction 75 185 310


Antenna and
Tilt 2 2 2
RRU Details
Available Free Ports N/A N/A N/A

Exsisting Jumper Length 3m 3m 3m

Existing fiber Length 30m 30m 30m


Existing RRU Power Cable
Length 30m 30m 30m
Existing Fiber cable
condition Good Good Good
Existing RRU Power Cable
Condition Good Good Good
Remarks Sector 1, Sector 2 & Sector 3 Same 8 port Antenna used for 3G & 1800&900
Sector Sector 1 Sector 2 Sector 3 Sector 4
Exsiting Band 3G 3G 3G

Existing RRU Type R8882 S1800 R8882 S1800


Antenna Height 18m 18m 18m
Antenna Type 8 Port Antenna 8 Port Antenna 8 Port Antenna
Antenna Location H/F H/F H/F
Antenna Direction 75 185 310
Existing
Antenna and Tilt 2 2 2
RRU Details Available Free Ports N/A N/A N/A
Exsisting Jumper Length 3m 3m 3m
Existing fiber Length 30m 30m 30m
Existing RRU Power Cable
Length 30m 30m 30m
Existing Fiber cable
condition Good Good Good
Existing RRU Power Cable
Condition Good Good Good
Sector 1, Sector 2 & Sector 3 Same 8 port Antenna used for 3G & 1800&900 and u Sector 2 and Sector 3 share one 3G RRU
Remarks

Sector 1 Sector 2 Sector 3 Sector 4


Sector

Exsiting Band 900 900 900

Existing RRU Type RSU RSU RSU

Antenna Height 18m 18m 18m

Antenna Type 8 Port Antenna 8 Port Antenna 8 Port Antenna

Antenna Location H/F H/F H/F

Existing Antenna Direction 75 185 310


Antenna and
RRU Details Tilt 2 2 2

Available Free Ports N/A N/A N/A

Existing Jumper Length 3m 3m 3m

Existing fiber Length N/A N/A N/A


Existing RRU Power Cable
Length N/A N/A N/A
Existing Fiber cable
condition N/A N/A N/A
Existing RRU Power Cable
Condition N/A N/A N/A

Remarks Sector 1, Sec 2 & Sector 3 Same 8 port Antenna used for 3G & 1800&900
BTS Type BTS Qty

BS8900
BS8900A 1
W201 1

Existing ZTE WR12 1


ZTE
Cabinet W301
Details
RC8910
RC8910A 1
Cabinet 2.5
Rack Qty 4

Existing Configuration 5 Mimo 15 Mimo

Existing BBU Module Type & Qty Status


CC LTE BBU-CC16B-1 OK
FS LTE BBU-FS5-1 OK

Existing LTE BPK1


BBU Details BP LTE BBU-BPN2-1 OK
CR0 & SA
UPBG LTE BBU-UPBG-2 OK
Space Available for new module? Yes No If Yes Qty: 3
Esisting 1800 RRU Power Existing LTE RRU Power

Existing LTE BTS Cabinet DCDB Existing LTE BTS Cabinet DCDB

Exsisting Rectifire Cabinet DCDB Exsisting Rectifire Cabinet DCDB

Location of Existing RSU Cabinet DCDB Existing RSU Cabinet DCDB


RRU Power
Existing 3G Cabinet DCDB Existing 3G Cabinet DCDB

Exiting DCPD 6 Existing Rectifire DCDB Exiting DCPD 6 Existing Rectifire DCDB

Remarks
3. New Expansion Solution
4T4R Dual Beam Sectors (L18+L21) 4T4R Sectors (L18+L21)

2T2R_Redep RRU L2100/RRU Redep


New LTE Type
Dual Band

Name Type Qty

CC

FS

PM3
BBU BBU Card Requirement
UBPG

BPK

BP BPQ7 1

CR0 CR0 1
Antenna Antenna
New Antenna Antenna Type Tilt
Height Azimuth
Cell 1
Antenna Antenna Band Cell 2 Existing Antenna 18m Existing Existing

Cell 3

Cell 4

Sec 01 Sec 02 Sec 03 Sec 04

New RRU Type R9224E

New RRU Height 18m

RRU New Jumper Length 3m

New Fibe Length 30m

New Power Cable Length 30m

New RRU Power Location Can use exi.DCPD.


Existing Bracket can use for New Antenna
Yes No
And RRU?
Required New Antenna Bracket? Yes No

GSM Bracket GSM Antenna Dual Arm Bracket


New Antenna Bracket Type
New Antenna Face Bracket Head Frame Bracket
Mount
New Bracket Qty?
IF Required Face Bracket Tower Leg
Proposed Tower Leg : …….. Distance in Between Leg : ………
Distance of Proposed Location?

Provided Bracket Bracket Design? Yes No

1.Propose to swap Existing 3G and 1800 RRUs to R9224E RRU for sec 2
2.Can use existing 8 port Antenna

Remarks 3 Can use existing 1800 RRU path

4.Power can be taken from existing DCPD6

4. Photos List
Existing Tower Photos

Existing Cabinet Out Look and Inlook Photos

Close View of Existing Antenna and Ports

Close View of Existing LTE Cabinet and BBU with Modules


Existing Rectifirer DCDB Photos with Label
Existing Vertical and Horizontal Cable ladder
New Antenna and RRU Solution
New Cabinet BBU and Module Solution
New RRU Power Solution
New Fieber and Power cable solution
Critical Access road or Manual Transport Evidence Photos
5.Drawing
If any Issue with Antenna Installation location of Tower Pls give the New location With Tower Drawing
5.Material List For L1800 Sector Site Unit Quantity
ZXRAN R9214E S1800 RRU Pcs
ZXRAN R8882 S1800 RRU Pcs
ZXRAN R8852E S1800 RRU Pcs
ZXRAN R8882 S21000 RRU Pcs
ZXRAN R8862A S2100 RRU Pcs
ZXRAN R9224E M1821(AAB)(DC 1805-75 2110-60)<10G,4.3-10> Pcs 1
ZXDU 68 W301 Cabinet Pcs
ZXDU68 W (V6.0)Accessories Battery And Battery Cabinet Pcs
12V150Ah Battery(Front-Access) Pcs
8ports ANT Pcs
4H 1710-2690MHz 19dB 2.7m Dual-Beam antenna with integrated RCU-4.3(Twin Beam Antenna Pcs
10 port antenna Pcs
TB Antenna (6port Antenna) Pcs
CCE1B Pcs
CR0 Pcs 1
BPQ7 Pcs 1
PM 5E Pcs
DCPD6 Pcs
GPS Set
10G/1310nm SM Optical Module (1.4km) Pcs 2
ANT Jumper Cable (RF-96514-016) S (3M) Pcs 4
ANT Jumper Cable (RF-96514-016) S (5M) Pcs
2 cores outdoor braid power cable m 30m
Installation Accessories (Bonding-13,Tapes-25,Lugs,Ties,Etc,) Kit 1
Optical Fiber Cable Pcs 30m x 1
Fiber clamp/Feeder clamp Pcs
Metal tube with PVC surface (32mm2) M
Metal tube with PVC surface (20mm2) M 10m
16mm yellow-green outdoor cable|yellow-green ;3AWG ;|UL1015 3AWG | UL1015 Pcs 3
PVC Pipe 20MM M
PVC Pipe 40MM M
PVC Socket 40MM Set
T Socket 20mm Set
T Socket 40mm Unit
UPVC Bend Socket 20mm Unit
UPVC Bend Socket 40mm Unit
Extention Bars (Type T) Pcs
Extention Bars (Type 2) Pcs
Dual Bracket Pcs
Face Bracket Pcs
RRU and combiner mounting bracket Pcs
Seling Muds Pcs 1
Existing BBU Card Details & New Card Requirement

Existing Required
BBU Module BBU Qty BBU Qty
Module Module
CC CCE1B 1 N/A
FS FS5 1 N/A
CR0 CR0 1
SE N/A
PM PM3 1 N/A
UBPG UBPG 2 N/A
BPC/BPK N/A
BPL/BPN0/ BPQ2 BPN2 1 BPQ7 1

Site Name Kadathiha


Site ID ANTWN1
Photo list Broadband Expansion

Tower Photos
Photo list Broadband Expansion

Photos of Existing Cabinet Out Look and Inlook


Photo list Broadband Expansion

Photos of Existing Cabinet Out Look and Inlook


Photo list Broadband Expansion

Close View of Existing Antenna and Ports

8 Port Antenna
Photo list Broadband Expansion

Close View of Existing Antenna and Ports

8 Port Antenna
Photo list Broadband Expansion

Close View of Existing Antenna and Ports

8 Port Antenna
Photo list Broadband Expansion

Close View of Existing LTE Cabinet and BBU with Modules


Photo list Broadband Expansion

New Antenna and RRU Solution


Sector 1

N/A

Sector 2

Propose to swap 1800 and 3G


RRU with R9224E RRU

Can Use Existing 8 port antenna


Photo list Broadband Expansion

New Antenna and RRU Solution

Sector 3

Sector 4

N/A
Photo list Broadband Expansion

New BBU and Module Solution

Need to Remove UBPG1 and


install BPQ7 and CR0 Carsd
Photo list Broadband Expansion

New RRU Power Solution

can use exi.DCPD6


Photo list Broadband Expansion

New Fiber and Power cable solution


Photo list Broadband Expansion

Evidance of Critical Access road or Manual Transportation.

N/A
Photo list Broadband Expansion

Mesurement of Bracket Photo

N/A