Technical Information ASSET DOC 19962464
Technical Information ASSET DOC 19962464
COATED BOARD
CFS-CT HDB
Technical Manual
October 2023
Firestop coated board
Technical data
Approx. density 160 kg /m³
Dimensions (L x W x H) 1200 x 600 x 60 mm
1000 x 600 x 60 mm
Color White
Storage & application temp. -5 ̵ 40°
Base material Drywall, concrete, aerated
concrete, masonry
Applications
• Single, multiple and mixed penetrations in flexible and rigid
walls from 100 mm and rigid floors from 150 mm.
• Openings up to 1200 x 1000 mm in wall and 1000 x 800 mm
in floors
• Cables, cable bundles, cable trays and cable conduits
• Non-combustible (metal) pipes with non-combustible
insulation
• Non-combustible (metal) and composite pipes with
combustible insulation in combination with firestop
bandage CFS-B
• Combustible pipes in combination with firestop collars
CFS-C P or firestop endless collar CFS-C EL
Advantages
• 1-board installation for EI 60 applications
• Can be placed in any position within floors and walls
• Extensive EN testing ensures wide range of application
• Board pre-coated for immediate use
• Easy cutting, no fraying of edges and no mineral fiber exposure,
thanks to extremely low delamination of elastic firestop surface
10/2023 2
Firestop coated board
INSTALLATION INSTRUCTIONS
10/2023 3
Firestop coated board
Geberit Silent PP, Silent Pro L’Isolante K-Flex ECO, K-Flex ST Frigo,
KeKelit PhonEx AS Aeroflex HF
Manufacturer & type
10/2023 4
Firestop coated board
GENERAL INFORMATIONS
10/2023 5
Firestop coated board
non-combustible insulation
non-combustible insulation
combustible insulation
Al-com-posite pipe w/
Mininal distance (mm)
Conduit Ø<16mm
Conduit Ø>16mm
Plastic exhaust
Cable sup-port
Al-comp. pipe,
non-insulated
Metal pipe w/
Metal pipe w/
Plastic pipe
channels
Cables
Edge
Cable 0 0 0 0 0 50 50 50 50 50 50 50 100 100 50 0
Metal pipe w/
combustible insultation 50 50 50 50 50 50 100 100 50 50
Al-comp. pipe,
non-insulated 50 50 50 100 100 50 50
Al-combustible pipe w/
combustible insulation 50 50 100 100 50 50
Al-composite pipe
wit non-combustible 50 100 100 50 50
insulation
Plastic exhaust
channels 100 100 100 100
10/2023 6
Firestop coated board
CFS-IS 60 mm deep CFS-ACR 10/60 mm deep CFS-ACR 10/60 mm deep CFS-ACR 10/60 mm deep
Annular gap seal
Annular gap ≤ 15 mm Annular gap ≤ 5 mm Annular gap ≤ 5 mm Annular gap ≤ 5 mm
+
+ + + +
Service seal
None None CFS-B 1 or 2 layers CFS-C EL or CFS-C P
Non insulated
Combustible & non-combustible pipes
Insulated LS
Insulated CS
Insulated CS
+ Additional
protection
(Rockwool
DuctWrap LI)
Cable trays
Insulated LI
Conduits
Insulated LI
HVAC Bundles
Insulated CS
10/2023 7
Firestop coated board
Uponor Unipipe Plus ≤ 32 (2.0 ̵ 3.0) CS, AF1 ̵ AF4 (8 ̵ 19 mm) EI 60 U/C CFS-IS 60 mm deep
+ FEF insulation 16 ≤ x ≤ 50 (2.0 ̵ 4.50) CS, AF1 ̵ AF5 (8.5 ̵ 28.5 mm) See ETA
Uponor Unipipe Plus 40 ≤ x ≤ 50 (4.0 - 4.50) CS (13 mm) EI 60 U/C CFS-IS 60 mm deep
+ PE insulation
Geberit Mepla 16 ≤ x ≤ 40 (2.25 - 3.50) CS, AF1 ̵ AF4 (8.0 ̵ 20.5 mm) EI 60 U/C CFS-IS 60 mm deep
+ FEF insulation 16 ≤ x ≤ 50 (2.25 - 4.50) CS, AF1 ̵ AF6 (9.0 ̵ 28.5 mm) See ETA
Metal pipe ≤ 42 (≥ 1.0) LS ≥ 470 mm (30 mm) EI 60 C/U CFS-IS 60 mm deep
+ Isover Climacover insulation
Metal pipe LS ≥ 970 mm (20 mm) EI 45 C/U
≤ 54 (≥ 1.0) CFS-S ACR 10 mm deep
+ Rockwool Klimarock insulation LS ≥ 470 mm (30 mm) EI 60 C/U
≤ 42 (≥ 1.0) CS, AF1 ̵ AF4 (8.0 ̵ 20.5 mm) EI 45 C/U CFS-IS 60 mm deep
Metal pipe
+ FEF insulation ≤ 28 (≥ 1.0) CS, AF1 ̵ AF6 (7.5 ̵ 35.5 mm) CFS-S ACR 60 mm deep
EI 60 C/U
≤ 54 (≥ 2.0) CS, AF1 ̵ AF6 (17 ̵ 38 mm) + CFS-B 2 layers
Metal pipes bundle
(zero distance)
Cu / Steel / Iron pipes
+ FEF insulation ≤ 28 (≥ 0.6) CS, AF1 ̵ AF6 (8.0 ̵ 8.5 mm) EI 60 U/C CFS-IS 60 mm deep
+ Additional protection (25 mm
thick Rockwool DuctWrap of LI
≥ 250 mm)
Metal pipe 0 ≤ x ≤ 15 (≥ 0.7)
+ FEF insulation 15 ≤ x ≤ 28 (≥ 0.9) CS, AF1 ̵ AF5 (8.0 ̵ 31.5 mm) EI 60 C/U CFS-IS 60 mm deep
+ Additional protection (25 mm 28 ≤ x ≤ 54 (≥ 1.2)
thick Rockwool DuctWrap of LI CFS-S ACR 60 mm deep
≥ 250 mm) ≤ 28 (≥ 0.6) CS, AF1 ̵ AF6 (7.5 ̵ 8.5 mm) EI 60 C/U + CFS-B 2 layers
Metal pipe
+ FEF insulation ≤ 28 (≥ 1.0) CS, AF1 ̵ AF6 (7.5 ̵ 35.0 mm) CFS-S ACR 60 mm deep
+ Additional protection (30 mm EI 60 C/U
thick Isover ML-3 Glasswool of ≤ 54 (≥ 1.5) CS, AF1 ̵ AF6 (17 ̵ 38 mm) + CFS-B 1 layer
LI ≥ 30 mm)
Metal pipe
+ Kingspan Kooltherm 0 ≤ x ≤ 15 (≥ 0.7)
insulation 15 ≤ x ≤ 28 (≥ 0.9) CS, (15 ̵ 25 mm) EI 60 C/U CFS-IS 60 mm deep
+ Additional protection (25 mm 28 ≤ x ≤ 54 (≥ 1.2)
thick Rockwool DuctWrap of LI
≥ 250 mm)
Metal pipe ≤ 114.3 (≥ 3.2) LS ≥ 700 mm (30 mm) EI 60 C/U CFS-S ACR 10 mm deep
+ Isover ORStech insulation
Metal pipe ≤ 114.3 (≥ 1.8) CS (20mm) EI 60 C/U CFS-S ACR 10 mm deep
+ Rockwool Klimarock insulation
Metal pipe
Steel / Iron pipes
+ FEF insulation
+ Additional protection (25 mm ≤ 114.3 (≥ 2.0) CS, AF3 ̵ AF5 (18.5 ̵ 31.5 mm) EI 60 C/U CFS-IS 60 mm deep
thick Rockwool DuctWrap of LI
≥ 250 mm)
Metal pipe
+ FEF insulation
+ Additional protection (30mm ≤ 114.3 (≥ 2.0) CFS-S ACR 60 mm deep
CS, AF1 ̵ AF6 (18.5 ̵ 43.0 mm) EI 60 C/U
thick Isover ML-3 Glasswool of + CFS-B 2 layers
LI ≥ 30mm)
Omegaflex Tracpipe See ETA See ETA See ETA See ETA
corrugated, sleeved
Excerpt of ETA document. Check the exact field of application in the ETA 23/0267 document.
10/2023 8
Firestop coated board
10/2023 9
Firestop coated board
insulation
Metal
10/2023 10
Firestop coated board
Cable ≤ 14
CFS-S ACR 60mm deep
Metal ≤ 10 (≥ 1) CS, AF1 ̵ AF6 (9 mm) EI60
+ CFS-B 1 layers
Clima Split Plastic ≤ 20 (≤ 1.5)
FEF insulation Cable ≤ 14
CFS-S ACR 60mm deep
Metal ≤ 18 (≥ 1) CS, AF1 ̵ AF6 (8 mm) EI 30 / E 60
HVAC bundles
+ CFS-B 1 layers
Plastic ≤ 20 (≤ 1.5)
Clima Split
FEF insulation
Cable ≤ 14
+ additional protection CFS-S ACR 60mm deep
Metal ≤ 28 (≥ 0.9) CS, AF1 ̵ AF6 (8.5 mm) EI 60
(25 mm thick Rockwool + CFS-B 1 layers
Plastic ≤ 20 (≤ 1.5)
DuctWrap of
LI ≥ 150 mm)
channels
Plastic
Excerpt of ETA document. Check the exact field of application in the ETA 23/0267 document.
10/2023 11
Firestop coated board
CFS-IS 60 mm deep CFS-ACR 10/60 mm deep CFS-ACR 10/60 mm deep CFS-ACR 10/60 mm deep
Annular gap seal
Annular gap ≤ 15 mm Annular gap ≤ 5 mm Annular gap ≤ 5 mm Annular gap ≤ 5 mm
+
+ + + +
Service seal
None None CFS-B 1 or 2 layers CFS-C EL or CFS-C P
Non insulated
Combustible & non-combustible pipes
Insulated LS
Insulated CS
Insulated CS
+ Additional
protection
(Rockwool
DuctWrap LI)
Cable trays
Insulated LI
Conduits
Insulated LI
HVAC Bundles
Insulated CS
10/2023 12
Firestop coated board
≤ 40 (2.25 ̵ 3.50) CS, AF1 ̵ AF4 (8.0 ̵ 20.5mm) EI 60 U/C CFS-IS 60 mm deep
+ FEF insulation
Uponor Unipipe Plus ≤ 32 (2.0 ̵ 3.0) CS, AF1 ̵ AF4 (8 ̵ 19 mm) EI 60 U/C CFS-IS 60 mm deep
+ FEF insulation
≤ 42 (≥ 1.0) CS, AF1 ̵ AF4 (8.0 ̵ 20.5 mm) EI 45 C/U CFS-IS 60 mm deep
≤ 42 (any) CS, AF4 (20.5 mm) EI 60 C/U
Metal pipe ≤ 10 (≥ 1.0) CS, AF1 ̵ AF4 (7.5 ̵ 15.5 mm) EI 60 C/U
+ FEF insulation ≤ 18 (≥ 1.0) CS, AF1 ̵ AF6 (8.5 ̵ 33.5 mm) EI 30 C/U CFS-S ACR 60 mm deep
Cu / Steel / Iron pipes
Metal pipe
+ Isover Climacover ≤ 42 (≥ 1.0) LS ≥ 470 mm (20 mm) EI 30 C/U CFS-IS 60 mm deep
insulation
Metal pipe
+ Rockwool Klimarock ≤ 54 (≥ 1.5) LS ≥ 470 mm (30 mm) EI 60 C/U CFS-S ACR 10 mm deep
insulation ≤ 54 (≥ 1.0) LS ≥ 970 mm (20 mm)
Metal pipe
+ Isover ORStech LSP40 ≤ 114.3 (≥ 3.2) LS ≥ 970mm (30 mm) EI 60 C/U CFS-S ACR 10 mm deep
insulation
Steel / Iron pipes
Excerpt of ETA document. Check the exact field of application in the ETA 23/0267 document.
10/2023 13
Firestop coated board
PVC-U
CFS-S ACR 10 mm deep
160 (3.2) EI 30 U/U
+ CFS-C P
Excerpt of ETA document. Check the exact field of application in the ETA 23/0267 document.
10/2023 14
Firestop coated board
Cable ≤ 14
HVAC
10/2023 15
Firestop coated board
Water permeability Watertight up to 1000mm head of water or 9806 Pa. for 0.7mm
Annex C of EAD 350454-00-1104
dry film thickness on mineral wool
Rw = 30 dB (Single board)
Acoustics EN ISO 140-3
Rw = 35 dB (Double board)