friction Coefficient) of Steel On Concrete: Byb. G.Jrabbat, Mr-Asee and H.G. Russpuj
friction Coefficient) of Steel On Concrete: Byb. G.Jrabbat, Mr-Asee and H.G. Russpuj
---~ OR GROUT
By B. G.JRabbat, r ~Mr-ASeE a n d H. G. R U S S P U J * ^
or grout. Fifteen tests were performed under conditions that represented the
interior and exterior bearing surfaces of a containment vessel. Test parameters • "\
included concrete blocks or grout blocks, wet or dry interface, and level of nor-
mal compressive stress. For conditions tested, the average effective coefficient
of static friction varied between 0.57 and 0.70. It is recommended that the coef-
ficient of static friction for concrete cast on steel plate and grout cast below steel
plate should be taken as 0.65 for a wet interface with normal compressive stress
levels between 20 and 100 psi (0;14»=atrd 0:6?MFd). For dry interface, the coef-
ficient of static friction should be taken as 0.57.
INTRODUCTION
4. For grout specimens with wet interface and normal stress of 60 psi
(0.41 MPa), both average effective and average peak coefficients of static
friction were 0.68.
1. The coefficient of static friction for concrete cast on steel plate and
grout cast below steel plate should be taken as 0.65 for a wet interface
with normal compressive stress levels between 20 and 100 psi (0.14 and
0.69 MPa).
2. The coefficient of static friction for concrete cast on steel plate and
grout cast below steel plate should be taken as 0.57 for a dry interface
with normal compressive stress levels between 20 and 100 psi (0.14 and
0.69 MPa).
EXPERIMENTAL PROGRAM
V 1 in. = 25.4 mm
506
work was then stripped and specimens kept in the laboratory at a tem-
perature of 73° F (23° C) and a relative humidity of 50%. Specimens were
tested at an age of 28-30 days.
Grout-to-Steel Specimens.—These specimens were prepared in the
setup shown in Fig. 2. The setup was designed to simulate field con-
ditions of placing grout at the exterior bearing surface of a containment
vessel. Formwork was clamped to the underside of the steel plate. The
specimen was inclined during grouting. The difference in height be-
tween the bottom horizontal edges of the grout block was 4 in. (102
mm).
The grout mix specifications called for cement that was Type II, ASTM
designation C 150 (5), with no admixtures; a fine aggregate of Natural
Elgin Sand, ASTM designation C 33 (3); a cement to sand ratio of 1:2
by volume; and a water to cement ratio of 0.5 by weight. Flow of this
mix was measured on a flow table after five drops in 3 sec.
Grout was placed through a funnel secured to the top of the right-
hand side pipe shown in Fig. 2. This pipe had a 2 in. (51 mm) diameter.
Because of its consistency, the grout filled the form and flowed upward
in the left-hand pipe. The height of the left-hand side pipe corresponded
Grout compressive strength was measured using six 2 in. (51 mm) cubes.
Test Setup.—The test setup is shown in Figs.. 3 and 4. This setup is
capable of applying vertical loads normal to the shear plane and hori-
zontal loads parallel to the shear plane. Horizontal rams were used to
apply in-plane shear loads. Vertical rams were used to apply normal
stresses.
Instrumentation.—All loads were measured using calibrated load cells
(1) acting in series with the hydraulic rams. Slip of the concrete test block
relative to the steel plate was measured with two potentiometers.
Test Procedure.—Bond between concrete and steel was broken by ap-
plication of an in-plane shear force applied at the shear-friction interface.
No normal compressive stress other than the weight of the upper block
and loading equipment was applied at this stage. This weight was equiv-
-Load Cell
^Structural Tube
Sfeel
Ram for -Test Role
Push-Off Specimen il | H
Load
HALF-SECTION k-A
~t
HALF-SECTION B-B
Shear
40
u^www^#^
Downloaded from ascelibrary.org by NDSU LIBRARY on 05/26/14. Copyright ASCE. For personal use only; all rights reserved.
Stress,
psi
zo
I in. = 25.4 mm
I psi' 6.895 k Pa
0
0 0.1 0.2
Slip, Inch
alent to a nominal stress of 8.18 psi (56 kPa). The shear stress required
to cause first slip was noted. The concrete block was then moved back
to its original position on the steel plate.
For tests requiring a wet friction surface, the interfaces were separated
after bond was broken. The interfaces were then ponded in water to
ensure a wet surface during testing. Interfaces remained saturated dur-
ing subsequent testing. During each test, normal stress was held con-
stant.
After application of normal compressive force, the shear load was ap-
plied slowly. A continuous record of the horizontal load versus slip at
the shear-friction interface was obtained. A representative shear stress
versus slip curve is shown in Fig. 5. It can be seen that slip occurred in
increments. Each slip increment occurred within a fraction of a second
and was accompanied by a drop in shear stress. The drop was a result
of the stiffness of the loading system. The shear stress versus slip curves
reported in the results section were idealized by a curve joining the peaks
of the saw teeth of Fig. 5. Note that the testing rate was adjusted to
obtain 0.1 in. (2.5 mm) slip within 3-5 min. The test was stopped when
a slip of 0.5 in. (12.7 mm) was reached. At a slip of 0.5 in. (12.7 mm),
the horizontal component of the vertical loading system was negligible.
TEST RESULTS
3 CWC-1 28 3,275
4 CWB-2 28 3,510
5 CWA-2 28 3,780
6 CWC-2 28 3,525
7 CWB-3 28 3,030
8 CWA-3 28 3,800
9 CWC-3 28 3,270
10 CDB-1 28 3,620
11 CDB-2 28 3,720
12 CDB-3 28 3,710
Note: 1,000 psi = 6.895 MPa.
511
_ _ CWB-I . *>&
fS / " • —- . CWB-2
CWB-3
20
rcwc-2 CWC-3TE0PSI
r " C-cwcT'
lin.=25.4mm
1pst=6B95kPa
0
0 0.1 02 0.3 0.4 0.5
Slip, inch.
Shear
Stress,
psi
Normal Compressive
Stress, 60 psi
I in. = 25.4 mm
lpsi=6.895kPo
Shear
Stress,
psi
fGWB-3 GWB-I
Normal Compressive
Stress, 60psi
i in.= 25.4mm
lpsi=6.895kPa
Slip, inch.
513
than the value specified in the ACI Building Code for design of shear
friction reinforcement.
Effect of Normal Stresses.—The effect of normal stress on coefficient
of friction can be determined from the results of Series I, concrete-to-
concrete specimens with wet interface. At normal stresses of 20, 60, and
100 psi (0.14, 0.41, and 0.69 MPa), the average peak coefficients of static
friction were 0.70, 0.68, and 0.64, respectively. The corresponding av-
erage effective coefficients of static friction were 0.67, 0.65, and 0.64,
respectively. Average coefficients of static friction tended to decrease as
normal compressive stress increased.
Effect of Wetting Interface.—The effect of wet interface on coefficient
of static friction can be seen when comparing average results of CWB
and CDB tests in Table 4. Corresponding to peak shear stresses, the
average coefficients of static friction were 0.68 and 0.69 for wet and dry
interfaces, respectively. These coefficients were fairly close. However,
the average coefficients corresponding to effective shear stress were 0.65
and 0.57 for wet and dry interfaces, respectively. Therefore, it appears
that the average coefficient of friction corresponding to effective shear
stress was about 12% lower for the dry interface.
Grout versus Concrete Interface.—Comparison between coefficient of
static friction for grout and concrete against rolled steel is based on re-
sults of GWB and CWB tests. The average peak coefficient of static fric-
tion was the same in both cases although, in the grout series, not all of
the interface area was in contact with the steel plate. This interface con-
dition with air gaps and bubbles can be expected in the field. However,
variation of the grout surface condition did not appear to affect the mea-
sured coefficient of friction.
The average effective coefficient of static friction for concrete and grout
specimens was 0.65 and 0.68, respectively. The observed coefficient for
the grout specimens was about 5% higher than for the concrete speci-
mens.
Effect of Concrete Strength.—Concrete strengths are listed in Table 2,
and coefficients of static friction are listed in Table 4. Based on the test
results of Series I, the coefficient of static friction apparently increased
with increased concrete strength. However, the range of concrete strengths
was too small to state definitively the effect of concrete strength on the
coefficient of static friction.
ACKNOWLEDGMENTS
DISCLAIMER
This paper is based on the facts, tests, and authorities stated herein.
Downloaded from ascelibrary.org by NDSU LIBRARY on 05/26/14. Copyright ASCE. For personal use only; all rights reserved.
APPENDIX.—REFERENCES
1. Building Code Requirements for Reinforced Concrete, ACI Committee 318, Amer-
ican Concrete Institute, Detroit, Mich., 1983.
2. Hognestad, E., et al., "Facilities and Test Methods of PCA Structural Labo-
ratory," Journal of the PCA Research and Development Laboratories, Vol. 1, No. 1,
Jan., 1959, pp. 12-20, 40-45; Vol. 1, No. 2, May, 1959, pp. 30-37; and Vol.
1, No. 3, Sept., 1959, pp. 35-41. Reprinted as PCA Development Department
Bulletin D33, Portland Cement Association, Skokie, 111.
3. Standard Specification for Concrete Aggregate, ASTM C 33-82, American Society
for Testing and Materials, Section 4, Vol. 04.02, Philadelphia, Pa., 1983.
4. Standard Specification for Flow Table for Use in Tests of Hydraulic Cement, ASTM
C 230-80, American Society for Testing and Materials, Section 4, Vol. 04.02,
Philadelphia, Pa., 1983.
5. Standard Specification for Portland Cement, ASTM C 150-83, American Society
for Testing and Materials, Section 1, Vol. 04.02, Philadelphia, Pa., 1983.
6. Standard Specification for Pressure Vessel Plates, Carbon Steel, for Moderate- and
Lower-Temperature Service, ASTM A516-82, American Society for Testing and
Materials, Section 1, Vol. 01.04, Philadelphia, Pa., 1983.
7. Surface Preparation Specifications—No. 2 Hand Tool Cleaning, SSPC-SP2-63, Steel
Structures Painting Council, Oct., 1963.
515