POWER PROTECTION
UPStation GXT™ 6kVA Maintenance Bypass
USER MANUAL
Transformerless
with Configurable
Output Distribution
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Standard Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
BYPASS SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CONFIGURABLE OUTPUT DISTRIBUTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
15 Amp Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
20 Amp Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
30 Amp Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Other Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CABLE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
WIRING PREPARATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
POWER CABLE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
WALL-MOUNT DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DIAGRAM FOR ATTACHING UNIT TO WALL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
HARDWIRE OUTPUT OPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
OPERATING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Start-Up and Initialization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ON MAINTENANCE BYPASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ON UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Shutting Down the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ON UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ON MAINTENANCE BYPASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Transferring System From UPS to Maintenance Bypass Operation . . . . . . . . . . . . . . . 12
Transferring System From Maintenance Bypass to UPS Operation . . . . . . . . . . . . . . . 12
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE ! CAUTION
To reduce the risks of fire, connect
INSTRUCTIONS only to a circuit provided with
This manual contains important instructions that maximum branch circuit
should be closely followed during installation and overcurrent protection of 40A in
maintenance of this UPStation GXT 6kVA accordance with applicable
Maintenance Bypass. national and local electrical codes.
This product is designed for commercial / industrial Install the bypass equipment in a clean
use only. This product is not intended for use with environment, free of conductive contaminants,
life support and other designated “critical” devices. moisture, flammable liquids, gases, and corrosive
Maximum load must not exceed that shown on the substances.
Maintenance Bypass Cabinet rating label.
! WARNING
LETHAL VOLTAGES MAY BE
PRESENT WITHIN THIS UNIT
EVEN WHEN IT IS APPARENTLY
NOT OPERATING. OBSERVE ALL
CAUTIONS AND WARNINGS IN
THIS MANUAL. FAILURE TO DO
SO MAY RESULT IN SERIOUS
INJURY OR DEATH. NEVER
WORK ALONE.
The UPStation GXT 6 kVA Maintenance Bypass is
designed for use on properly grounded (earthed)
208/240VAC 60Hz supply, for installation by
qualified personnel. This UPS equipment is
intended to be installed by a qualified / certified
electrician who must review and approve customer
supplied wiring, circuit breakers, intended loads
and verify correct input, output and grounded
(earth) connections to ensure compliance with
technical standards and national and local
electrical codes. Installation instructions and
warning notices are in the Cable Installation
section of this manual beginning on page 6.
Downloaded from www.Manualslib.com manuals search engine
GLOSSARY OF SYMBOLS
Risk of electrical shock
Indicates Warning or Caution followed by important instructions
i Requests the user to consult the manual
Equipment grounding conductor
On
Off
Downloaded from www.Manualslib.com manuals search engine
GENERAL DESCRIPTION
Congratulations on your purchase of Liebert's Features
UPStation GXT 6 kVA Maintenance Bypass. As • Supports up to 30A loads
with every Liebert product, we stand behind our • Compact design
quality. If you have any questions concerning this
• Highly configurable
Maintenance Bypass, please feel free to contact
• Multiple power path indicators
your local sales representative, or call the
appropriate Technical Support number listed on • High-speed, break-before-make transfer
the back of this manual. switch
To ensure proper installation and operation of this Standard Components
unit, please read this manual thoroughly. • Provisions for hardwire output
While installation must be completed by a • Power indicator lamps
qualified / certified electrician, general operation • Branch rated circuit breakers
may be performed without special training. • Easily accessible terminal blocks
Options
SYSTEM DESCRIPTION
• Field-installable output distribution kits
The Liebert UPStation GXT 6 kVA Maintenance
Bypass is intended for use with the UPStation GXT
6 kVA UPS. Typical applications include
supporting workstations, servers, network, telecom
or other sensitive electronic equipment.
The UPStation GXT 6 kVA Maintenance Bypass
was designed to provide maximum system
availability to business-critical equipment. The
bypass allows for transfer of connected loads to an
alternate power path, allowing full isolation of the
UPS. After connected loads are switched to
alternate power and the UPS is isolated, the UPS
can be turned off and removed from service with
no interruption of power to connected loads.
The Configurable Output Distribution was
designed to provide maximum flexibility to
business-critical equipment.
Various output receptacle options are available
from 15 A to 30 A. Hardwire options are also
available with a branch rated circuit breaker.
NOTE
The 120V loads need to be balanced on
the UPS output. To do this, when
connecting 120V equipment to the
Maintenance Bypass (MB), start at one
end of the MB and fill in toward the
other end.
Downloaded from www.Manualslib.com manuals search engine
Maintenance Bypass component layout
Bypass availability
UPS input power indicator (amber)
present (amber)
UPS input
switch Bypass
(SW2) switch
(SW1)
Output
breaker UPS output
(CB1) availability
indicator
(green)
1 2 3 4 Hardwire
output
terminal
Configurable block
Output (TB4)
Distribution
GND3
GND1
1 2 3 1 2 3 1 2 3 4
GND2
TOP VIEW
Utility UPS UPS
input input output
TB1 TB2 TB3
INSIDE VIEW— RECEPTACLE
PLATES AND END PLATE REMOVED
Downloaded from www.Manualslib.com manuals search engine
MAJOR COMPONENTS
The following is a general description of each 20 Amp Options
component and its functions. Please review this 5-20R2 (T-Slot)
section carefully, as it will give you a better
understanding as to how the UPStation GXT 6 kVA L5-20R
Maintenance Bypass operates. L6-20R-208
L6-20R-240
BYPASS SWITCH
L14-20R-240
The Bypass Switch allows easy and rapid transfer
20A, 120V, 1 Pole Breaker for 1/2" & 3/4" conduit
of connected loads between the UPS and bypass
source. 20A, 208V, 2 Pole Breaker for 1/2" & 3/4" conduit
20A, 240V, 2 Pole Breaker for 1/2" & 3/4" conduit
CONFIGURABLE OUTPUT DISTRIBUTION
30 Amp Options
Several receptacle and hardwire options are
L5-30R
available as user-selectable output distribution.
These are factory-configured when ordered and L6-30R-208
also allow for field upgrades. Common receptacle L6-30R-240
and hardwire options include:
L14-30R-240
15 Amp Options 30A, 120V, 1 Pole Breaker for 1/2" & 3/4" conduit
5-15R2 30A, 208V, 2 Pole Breaker for 1/2" & 3/4" conduit
L5-15R2 30A, 240V, 2 Pole Breaker for 1/2" & 3/4" conduit
6-15R2-208
Other Options
6-15R2-240
Single Position Blanking Plate
L6-15R2-208
Hardwire Options
L6-15R2-240
Single Position Plate with 1/2", 3/4" and 1"
15A, 120V, 1 Pole Breaker for 1/2" & 3/4" conduit conduit knockouts
15A, 208V, 2 Pole Breaker for 1/2" & 3/4" conduit Double Position Plate with 1-3/4" and 2"
15A, 240V, 2 Pole Breaker for 1/2" & 3/4" conduit conduit knockouts
Downloaded from www.Manualslib.com manuals search engine
CABLE INSTALLATION
WIRING PREPARATION POWER CABLE INSTALLATION
Refer to the chart below when selecting cables:
! CAUTION Power Cable and Protection Ratings
Please read this section
thoroughly before attempting to
208V 240V
install wiring to this unit. Max Input Current 30 A 30 A
Be sure that the unit is not Input Protection 40 A 40 A
connected to any AC mains power Max Output Current 30 A 30 A
source or UPS before installing Max: 16 mm2 (6 AWG)
any wiring to this unit. This should Terminal Block Details Min: 2.5 mm2 (14 AWG)
be installed by a qualified/certified
electrician. Torque: 2 Nm (16 in/lb)
For access to terminal blocks, see diagrams on
page 4.
NOTE
NOTE Customer must supply power cables
The 120V loads need to be balanced on between Maintenance Bypass and UPS,
the UPS output. To do this, when utility and load. (GMB12 models are
connecting 120V equipment to the supplied with an attached input power
Maintenance Bypass, start at one end of cord complete with L14-30 plug.)
the output modules and fill in toward the
other end. Load balancing must be
performed with the UPStation
GXT6000T - 208X and 240X. It is not
required on the GXT6000T-208 because
the unit has no 120V output.
Downloaded from www.Manualslib.com manuals search engine
Connecting Maintenance Bypass to UPStation GXT6000T - 208
208
VAC
Output
1 2 TB4 3 4
GND3
MAINTENANCE BYPASS
NOTE
When using the Maintenance
Bypass with an UPStation
GXT6000T-208, a jumper
GND1 (included with the accessory
kit) must be connected to the
TB3 (UPS output) terminal
block on the Maintenance
Bypass between TB3-1 and
TB3-2, as shown.
GND2 Utility UPS input UPS output
TB1 TB2 TB3
1 2 3 1 2 3 1 2 3 4
Utility
L1
input
L2
NOTE
GMB12 models are supplied
with an attached input power
cord complete with L14-30 L1 L2 L1 L2 + -
plug. Input Output Ext. battery
GXT6000T - 208
Downloaded from www.Manualslib.com manuals search engine
Connecting Maintenance Bypass to UPStation GXT6000T - 208X
120V
208V
120V
Output TB4
1 2 3 4
GND3
MAINTENANCE BYPASS
GND1
Utility UPS input UPSoutput
GND2
TB1 TB2 TB3
1 2 3 1 2 3 1 2 3 4
Utility L2
input
L1
N
GEC
NOTE
GMB12 models are supplied L1 L2 N L1 L2 L2A + -
with an attached input power Input Output Ext. battery
cord complete with L14-30 plug.
GXT6000T - 208X
Downloaded from www.Manualslib.com manuals search engine
Connecting Maintenance Bypass to UPStation GXT6000T - 240X
120V
240V
120V
Output TB4
1 2 3 4
GND3
MAINTENANCE BYPASS
GND1
Utility UPS input UPSoutput
GND2
TB1 TB2 TB3
1 2 3 1 2 3 1 2 3 4
Utility L2
input
L1
N
GEC
NOTE
GMB12 models are supplied L1 L2 N L1 L2 + -
with an attached input power Input Output Ext. battery
cord complete with L14-30 plug.
GXT6000T - 240X
Downloaded from www.Manualslib.com manuals search engine
WALL-MOUNT DIAGRAM
DIAGRAM FOR ATTACHING UNIT TO WALL
Use the following diagram, which shows the location and measurements of factory-cut mounting slots,
when preparing to attach the GXT Maintenance Bypass to a wall. Liebert recommends using 1/4-20
mounting screws. Rubber pads are supplied for placing the Maintenance Bypass on the floor.
178mm
7.00"
514mm
20.25"
C
L
10
Downloaded from www.Manualslib.com manuals search engine
HARDWIRE OUTPUT OPTION
This product is intended to be installed by a 6. Connect the remaining wires in accordance
qualified electrician only. with the wiring diagram (located inside the
1. COMPLETELY REMOVE ALL POWER FROM base enclosure).
THE FRAME. If the Maintenance Bypass is NOTE
connected to the UPS, disconnect external When wiring 120 V loads, LINE must be
battery supply. alternated between TB4-1 and TB4-3 to
2. Remove the end cover plate to access the balance the 120V load. Connect all
terminal block (see Accessing terminal neutral wires to TB4-4.
block below). 7. Replace the receptacle plates and the end
3. Without disconnecting from the terminal block, cover plate, using care to not damage the
unscrew and pull out the hardwire plate(s). wires.
4. Route all wires from the hardwire plate(s) to
the terminal block.
5. Connect the GROUND wire to the grounding
bar strip (GND1).
Accessing terminal block
11
Downloaded from www.Manualslib.com manuals search engine
OPERATING PROCEDURES
START-UP AND INITIALIZATION TRANSFERRING SYSTEM FROM
Follow these steps in order to start up the UPS TO MAINTENANCE BYPASS
GXT 6kVA UPS while connected to the OPERATION
Maintenance Bypass.
1. On UPS verify that Bypass LED is lit, if not,
press UPS OFF/Bypass button for at least
ON MAINTENANCE BYPASS one second.
1. Set the Maintenance Bypass switch (SW1) to 2. On Maintenance Bypass verify that the
UPS position. Bypass lamp is illuminated.
2. Close (position I) UPS Input switch (SW2). 3. Rotate Bypass switch SW1 to the Bypass
3. Close (position I) Output Circuit breaker position.
(CB1). 4. Set UPS Input switch SW2 to the Off position
(position O). This will remove power from UPS
ON UPS input.
1.
2.
Close (position I) battery circuit breaker.
Close (position I) input circuit breaker. ! CAUTION
The connected load is now
3. Close (position I) output circuit breaker.
powered by the bypass source and
4. After the start-up sequence the UPS will
is not protected.
automatically default to its internal bypass.
The bypass LED will be lit.
5. Press UPS On/Alarm/Battery Test button for at TRANSFERRING SYSTEM FROM
least one second to turn the UPS on. The MAINTENANCE BYPASS TO UPS
UPS ON LED will be lit. OPERATION
6. Connected equipment may now be switched
on. 1. On Maintenance Bypass close (position I)
UPS Input switch (SW2).
2. On UPS close (position I) input, output and
SHUTTING DOWN THE UPS battery circuit breakers.
Use the following procedure to power down the 3. After the start-up sequence the UPS will
system. automatically default to its internal bypass.
The bypass LED will be lit.
ON UPS 4. Press UPS ON/Alarm/Battery Test button for
1. Press Output OFF/Bypass button for at least at least one second to turn the UPS on. The
1 second, twice, within 4 seconds. UPS ON LED will be lit.
2. Open (position O) UPS output, input and 5. On Maintenance Bypass verify that UPS
battery circuit breakers. Output LED is illuminated.
6. Rotate Bypass switch SW1 to the UPS
position.
ON MAINTENANCE BYPASS
1. Open (position O) output breaker (CB1).
2. Open (position O) UPS input switch (SW2).
12
Downloaded from www.Manualslib.com manuals search engine
SPECIFICATIONS
Typical Transfer Time
< 6 milliseconds
(to or from maintenance bypass)
Input Voltage Nominal 208VAC or 240VAC
Total Current 30A max.
Operating Ambient Temperature 0° to +40° C
Storage Ambient Temperature -20° to +60° C
Dimensions, W x D x H, in (mm) 8.2 x 21.0 x 6.2 (209 x 534 x 158)
Chassis Weight (no receptacles) 10 lbs.
Distribution Module Weights (each) 2 lbs.
Connections to UPS Hardwire Terminal Blocks
Humidity 0 to 95%, non-condensing
Agency/Standards UL 1778, c-UL
13
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
POWER PROTECTION
UPStation GXT 6kVA Maintenance Bypass
USER MANUAL
The Company Behind the Products Technical Support/Service
Web Site
With over a million installations around the globe, www.liebert.com
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has Monitoring
800-222-5877
developed a complete range of support and
[email protected] protection systems for sensitive electronics:
Outside the US: 614-841-6755
• Environmental systems—close-control air Single-Phase UPS
conditioning from 1 to 60 tons 800-222-5877
• Power conditioning and UPS with power
[email protected] ranges from 300 VA to more than 1000 kVA Outside the US: 614-841-6755
• Integrated systems that provide both
Three-Phase UPS
environmental and power protection in a 800-543-2378
single, flexible package
[email protected] • Monitoring and control—from systems of any
size or location, on-site or remote Environmental Systems
• Service and support through more than 100 800-543-2778
service centers around the world and a 24/7 Outside the United States
Customer Response Center 614-888-0246
While every precaution has been taken to ensure Locations
the accuracy and completeness of this literature, United States
Liebert Corporation assumes no responsibility and 1050 Dearborn Drive
disclaims all liability for damages resulting from P.O. Box 29186
use of this information or for any errors or Columbus, OH 43229
omissions. Italy
© 2002 Liebert Corporation Via Leonardo Da Vinci 8
All rights reserved throughout the world. Zona Industriale Tognana
Specifications subject to change without notice. 35028 Piove Di Sacco (PD)
+39 049 9719 111
® Liebert and the Liebert logo are registered Fax: +39 049 5841 257
trademarks of Liebert Corporation. All names Asia
referred to are trademarks or registered 23F, Allied Kajima Bldg.
trademarks of their respective owners. 138 Gloucester Road
Wanchai
Hong Kong
SL-23447 (8/02) Rev. 2 +852 2 572 2201
Fax: +852 2 831 0114
Downloaded from www.Manualslib.com manuals search engine