STRUCTURAL DRAWINGS

STRUCTURAL LIST OF DRAWINGS


SHEET NO. DESCRIPTION

ST-00A GENERAL NOTES & STRUCTURAL LIST OF DRAWINGS

ST-00B TYPICAL DETAILS (1)

ST-00C TYPICAL DETAILS (2)

ST-101-1 COLUMNS LAYOUT PLAN FROM FOUNDATIONS TO BASEMENT COVER SLAB

ST-101-2 COLUMNS LAYOUT PLAN FROM BASEMENT COVER SLAB TO GROUND COVER SLAB

ST-101-3 COLUMNS LAYOUT PLAN FROM GROUND COVER SLAB TO FIRST COVER SLAB

ST-101-4 COLUMNS LAYOUT PLAN FROM FIRST COVER SLAB TO SECOND COVER SLAB

ST-102-1 COLUMNS & WALLS DETAILS 1

ST-102-2 COLUMNS & WALLS DETAILS 2

ST-102-3 COLUMNS & WALLS DETAILS 3

ST-103 FOUNDATIONS LAYOUT PLAN

ST-104-1 FOUNDATIONS DETAILS

ST-104-2 FOUNDATIONS DETAILS

ST-201 BASEMENT COVER SLAB LAYOUT PLAN

ST-202 BASEMENT COVER SLAB BEAMS ARRANGEMENT LAYOUT PLAN

ST-203 GROUND COVER SLAB LAYOUT PLAN

ST-204 GROUND COVER SLAB BEAMS ARRANGEMENT LAYOUT PLAN

ST-205 FIRST COVER SLAB LAYOUT PLAN

ST-206 FIRST COVER SLAB BEAMS ARRANGEMENT LAYOUT PLAN

ST-207 SECOND COVER SLAB LAYOUT PLAN

ST-208 SECOND COVER SLAB BEAMS ARRANGEMENT LAYOUT PLAN

ST-301 BEAMS DETAILS-1

ST-302 BEAMS DETAILS-2

ST-401 BASEMENT STAIR CASE DETAILS

ST-402 GROUND STAIR CASE DETAILS

ST-403 FIRST STAIR CASE DETAILS

ST-404 OUTER ANNEX STAIR CASE DETAILS

ST-501 GROUND WATER TANK AND BAYARA DETAILS


GENERAL NOTES CONTINUE CONCRETE NOTES LATERAL LOAD
( UNLESS OTHERWISE NOTED ON DRAWINGS OR IN SPECIFICATIONS ) C.8 Aggregates :
1. WIND LOAD
a. Coarse and fine aggregates shall comply with ASTM C33 or equivalent.
G.1 Structural Drawings shall be read in conjunction with Architectural, Mechanical, Electrical, Shop drawings and specifications. b. Concrete temperature at time of placement shall be below 32 °C. WIND LOAD IS CALCULATED IN ACCORDANCE WITH SAUDI BUILDING CODE 301-2018
G.2 All levels are in meter U.O.N. c. Field quality control of aggregates and concrete is essential. Potential reactivity of aggregates are to be
periodically evaluated. BASIC WIND SPEED = 106 mph
G.3 All dimensions and conditions must be verified in the field and any discrepancies shall be brought to the attention of the
ENGINEER before proceeding with the portion of work involved. C.9 When it is necessary for a pipe to pass through a wall or floor, it is preferable to cast the pipe into the panel when WIND IMPORTANCE FACTOR,Iw = 1.00
it is concreted, if not possible it will be necessary to box out. The sides of the opening to be treated as construction
G.4 All dimensions are in metric system, the basic unit of length is in millimeter.
joints, and for pipes coming out from basement walls, the joints should be flexible to allow for settlement. EXPOSURE CATEGORY = C
G.5 Unless otherwise noted, details shown on Drawings are to be considered typical for all similar conditions.
C.10 All opening shall be formed or sleeved before placing concrete. In case of increasing size of any openings than
G.6 Shop drawings for reinforcing steel & structural steel shall be submitted and approved by the ENGINEER before shown on structural drawings, contractor should submit design calculations and shop drawing to the owner
2. SEISMIC LOAD 1. FOR MORE DETAILS & DIMENSIONS REFER
fabrication may proceed. or representative for review and approval. ARCHITECTURAL DWGS.
SEISMIC LOAD IS CALCULATED IN ACCORDANCE WITH SAUDI BUILDING CODE 301- 2018 AND ASCE 7-16 WHERE:
G.7 The contractor shall provide all measures and precautions necessary to prevent settlement or damage to 2. FOR FURTHER DETAILS REFER TO DWGS.
any existing facilities. SEISMIC PARAMETERS S1=0.043, SS=0.224 S-001 , S-002
G.8 Details required for shop drawings and not shown in Drawings shall be in accordance with standard details as in SOIL PROFILE = SC (SHALL BE VERIFIED BY GEOTECH. CONSULTANT) 3. CONTRACTOR SHOULD SUBMIT THE SHOP
ACI detailing manual or British Standard manual and AISC detailing manual as listed in specifications. CONSTRUCTION JOINTS DRAWINGS FOR APPROVAL IN WHICH A FULL
IMPORTANCE FACTOR = 1.00
G.9 No electrical boxes or conduits shall be installed in bottom of joists. COORDINATION WITH ARCH. & MEP DWGS.
G.10 The construction load on the floors should not exceed the specified live loads during any stage of construction. J.1 Vertical construction joints shall be provided in water tank retaining walls at spacing not greater than 15.0m if any. IS MADE.
The contractor should prepare all the shop Drawings for shoring and staging which shall come on any floor Key shall be provide in concrete at construction joints as shown in dwg. no. S-003, sections (6) and (7) in this drawing. 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
before construction proceeds. If the wall is constructed below ground, water-stop shall be used in all construction joints. Vertical construction ** THE SEISMIC DESIGN FOR THIS BUILDING IS BASED ON JEDDAL CITY SEISMIC PARAMETERS , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
G.11 In case of any structural changes or modifications, the contractor must submit the design calculations, drawings joints shall be located in the middle third of the span of columns.
and all necessary details as specified in the structural general notes and /or specifications. STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
J.2 Construction joints in reinforced concrete slabs casted monolithically with footings shall be provided every 30.0m max. ** FOR JAZAN, FIFA, ABOARISH, NAJRAN, TABUK, MAGNASH, AL-BADAM ALSHARAF AND HAQL A SPECIAL SEISMIC DESIGN 5. SOIL BEARING CAPACITY = 170 KN/m2
G.12 The tie beam at foundation level must be provided when the soil report require it. using in-fill strip of width 1.0m which shall be casted after complete hardening on concrete on both sides of the strip. SHALL BE DONE BASED ON THE MAXIMUM OF BOTH ASCE 7-16 AND SBC301-2018 6. BACKFILLING WORKS AROUND RETAINING WALLS
The in-fill strip shall be located inbetween the footings, preferably at the middle third of the span.
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
J.3 At construction joints, surface of hardened concrete shall be roughened, cleaned wetted and standing water removed
FOUNDATION NOTES immediately before pouring new concrete.

J.4 Construction joints at floor slabs and beams shall be located at middle third of the span of columns. If interrupted
by intersecting beam, construction joint shall be offset by a distance not less than two times the width of the
F.1 The allowable bearing capacity is ( 170 KN/m2) based on soil test and must be review the soil test report intersecting beam. ABBREVIATIONS
before starting the execution.
F.2 Foundation level should not be less than 3.0m below existing ground level.
F.3 The contractor is responsible to verify that the above bearing pressure is achieved at foundation level and to consult REINFORCEMENT NOTES Add. = Additional STRUCT. = Structural
the engineer if otherwise. The contractor shall perform cavity probing below all columns. If any cavity is encountered, BOT. = Bottom T = Top
it should be filled with blinding concrete for shallow cavities and by injection for deep cavities. Cont. = Continuous T&B = Top & Bottom
R.1 All reinforcement bars should be deformed bars and should comply with ASTM A615-Grade 60 C/C = Center to center THK. = Thickness
F.4 At footing locations, all fill must be removed locally to expose the competent natural materials and excavation should be
and should have a minimum yield strength (fy) of 420 N/mm². CONC. = Concrete TYP. = Typical
back filled with blinding concrete of minimum compressive cylindrical strength at 28 days of 20 mPa.
CLR. = Clear T.O.B. = Top of beam
R.2 Mesh reinforcement and wire fabric shall conform to ASTM-A185. DIA. = Diameter T.O.F. = Top of footing
F.5 All structural fill should be placed where required, in lifts not exceeding 200mm thickness.
The structural fill should be compacted to at least 95% of the maximum dry density, as determined by R.3 Provide minimum 0.0018 times the cross sectional area in slabs as distribution steel where required. E.W. = Each way T.O.P = Top of pedestal
ASTM D1557 Method of Compaction. The moisture content of the structural fill at the time of placement must be EA = Each T.O.G.S. = Top of grade slab
R.4 Overlap splice and development length shall be as specified in drawing S-003.
within 2 percent of the optimum moisture content. E.F. = Each face T.O.Grd Beam = Top of grade beam
R.5 Provide at least Ø12 @ 250 on centers horizontal reinforcement on each face of the beam more than or equal E.J. = Expansion joint T.O.S.S. = Top of structural slab
F.6 The structural fill should have the following properties : to 700 mm in depth. EL. = Elevation U.O.N. = Unless otherwise noted
not more than 50% passing No. 10 sieve EQ. = Equal VERT. = Vertical
R.6 Beam reinforcement in multiple layers shall have Ø25 mm or the dia of the main bar (whichever is greater) as F.F.L = Finish floor level W = Width
not more than 30% passing No. 40 sieve spacer bars at between layers 1200mm spacing.
not more than 15% passing No. 200 sieve FL. = Floor W/ = With
plasticity index less than 6% H = Height W.W.F. = Welded wire fabric
maximum particle size of 150mm. HORZ. = Horizontal @ = At the rate of
L = Length C = Center line
chloride concentration less than 500 mg/l
MAX. = Maximum Ø = Diameter of deformed bars
sulphate concentration less than 1200 mg/l
MIN. = Minimum = Bottom reinforcement
F.7 In-place density testing of the structural fill in accordance with ASTM D1556 (or equivalent) should be carried out NO. = Number = Top reinforcement
regularly at the start of the filling operations to establish the number of passes of the available compaction N.T.S. = Not to scale
= Continuous column or wall
equipment needed to achieve the required degree of compaction. Once this has established, only occasional
insitu density testing is required provided that the filling operation is closely monitored by an experienced
LOADS P = Pedestal
= Terminated column or wall
REQD. = Required
geotechnical engineer or technician. REINF. = Reinforcement
F.8 The foundation excavation should be kept open for shortest time practical, should be kept dry, and any SCHED. = Schedule
rain water should be pumped out from the excavation prior to any concrete or steel placement. OWN WEIGHT AND FLOOR FINISHES :
F.9 If excavation is to be done below foundation level of any adjacent building, shoring of excavation side shall be made
Own Weight of Reinforced Concrete = 24.0 KN/m³
using micro piles of diameter 350 mm and extended at least 2.0 m below excavation level.
Weights of plaster mortar = 20.5 KN/m³
F.10 The contractor must provide equipment for temporary dewatering activities, such as pumps, hoses, etc. Weights of cement blocks = 14.0 KN/m³
Groundwater encountered during the excavation is expected to be controlled with surface pumping. Floor Finishes (Sand + mortar + marble) = 2.50 KN/m²
F.11 The site grading and foundation construction activities shall be performed under the direct supervision Weight of hordi blocks = 1.50 KN/m²
of a competent geotechnical or civil engineer familiar with the design aspects of the project. Failure to
comply with this requirement may cause significant settlement in the future due to improper removal of
fill, improper removal and replacement of soft spots, sub compaction, or combination of these factors.
ROOF LOADS :
F.12 Sulphate resisting portland cement (ASTM C 150 type-V latest revision) shall be used in all reinforced
concrete works in contact with earth. The water/cement ratio shall not exceed 0.45 Screed for roof drainage = 2.20 KN/m²
F.13 Underground water tank base slab shall be protected against ground water and / or surface water by water proofing membrane Water proofing + Rigid insulation = 0.30 KN/m²
below base slab and around vertical walls. Pea gravel = 1.00 KN/m²
HVAC machine and RC pads * = 1.50 KN/m²

PARTITION LOADS :
CONCRETE NOTES Weight of Plaster for Each face of the Partitions /m² of wall (if any) = 0.24 KN/m²

C.1 All concrete work shall conform to SBC201&301&302&303&304&305&801)-2018 AND ACI 318-14 Building Code Requirements Weight of Cement Block Wall 200mm thick /m² of wall = 1.70 KN/m²
for Reinforced Concrete . Weight of Cement Block Wall 250mm thick /m² of wall
C.2 Use Ordinary Portland Cement (Type 'I') for all super structure reinforced concrete ,for sub structure (wall 100mm + Isolation + wall 100mm) = 4.20 KN/m²
sulfate resistance cement should be used (type v) ,with with minimum cement content 360 Kg/m3 Weight of Cement Block Wall 300mm thick /m² of wall
and water cement ratio not more than 0.45. (wall 100mm + Isolation + wall 150mm) = 4.80 KN/m²
C.3 Minimum compressive strength of standard concrete cylinders at different ages shall be as mentioned below.
3 days > 0.4 times 28 days value
7 days > 0.7 times 28 days value LIVE LOADS :
C.4 Concrete cylinder shall be taken for each day's pour and each 50 cubic meters or fraction thereof, Residential building = 2.00 KN/m²
cast in accordance with ASTM C31 and tested in accordance with ASTM C39.
C.5 Required minimum CHARACTERISTIC COMPRESSIVE STRENGTH of concrete based on standard cylindrical specimen
shall be as follows: * Actual weight of mechanical equipment shall be calculated including dynamic magnification factor and shall be
applied if found to be higher than the given value. Weight of pads, if required, shall be added to dead loads.
35 Mpa (350 Kg/m2) for all reinforced concrete elements.
20 Mpa (200 Kg/cm2) for blinding concrete.

C.6 Clear cover for reinforcement should be not less than follows : GENERAL NOTES & STRUCTURAL
75mm Unformed concrete deposited agaist ground LIST OF DRAWINGS
25mm Formed concrete agaist ground or exposed to weather
25mm Ties, stirrups and spirals of beams not exposed to ground or weather
25mm Ties, stirrups and spirals of columns not exposed to ground or weather
25mm walls not exposed to ground or to weather
25mm Slabs not exposed to ground or to weather
C.7 All reinforcing steel dowels, anchor bolts, and other inserts shall be secured in position prior to pouring concrete.
N.T.S

ST-00A
L1 L2 L3
0.30 L2 OR L1
GREATER 0.3 (L1 or L2) 0.3 (L2 or L1) (0.3 L2) OR (1.5 L3)
0.25 L1 THE GREATER
0.30 (L3 OR L2) THE GRATER THE GRATER
0.30 (L2 OR L3) 0.25 L3
GREATER GREATER

50 50 50 50 50

L1
CANTILEVER
L2
INTERIOR CLEAR SPAN
L3
EXTERIOR CLEAR SPAN 0.10 L1 0.10 L1 0.10 L2 0.10 L2 1. FOR MORE DETAILS & DIMENSIONS REFER
CLEAR SPAN
LEFT STIRRUPS MIDDLE STIRRUPS RIGHT STIRRUPS LEFT STIRRUPS MIDDLE STIRRUPS RIGHT STIRRUPS
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
TYPICAL SOLID SLAB ON BEAM TYPICAL DETAIL ON CONTINUOUS BEAMS& GIRDERS DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
NOTE :- FOR TOP NEGATIVE REINFORCEMENT OF CONTINUOUS BEAMS THE GREATER
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
REINFORCEMENT FROM (E) BARS AND (C) BARS MUST BE PLACED. , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
W
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
CL
40mm
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
W W
SHOULD BE DONE AFTER CASTING THE BASEMENT
FOR REINF.
SLAB COVER.
GRID SEE COL. DETAIL
COLUMN
CAST-IN-PLACE
TIES
H

A ISOLATION JOINT WITH 10 TO T.O.G.S.


20mm THICK x 20mm DEEP SEALANT

H
ON COMPRESSIBLE FILLER
A/2

VAR.
GROUND BEAM (GB) VAPOUR BARRIER
CENTERLINE OF SEE PLAN & SCHED. AS PER SPECIFICATIONS
FOOTING & COL.

VARIES
25mm OR Ø BAR MIN.

COMPACTED BACKFILL

B
4
TYPICAL SECTION FOR TYPICAL STIRRUPS TYPICAL STIRRUPS GRID S-003 S-003 S 1/2

GRID

B/2
TIE BEAM IF REQUIRED Ø10@300 BOTHWAYS TIE BEAM IF REQUIRED
75 CLEAR COVER(TYP)

PLAN
SEE
RECTANGULAR
COLUMN
GROVE SLAB ON GRADE
T.O.G.S.
(SEE PLAN)
229528 229528

40

155
6 REINF. BARS FOUNDATION

57382
B LEVEL
S-003 S-003 (SEE SCHED.)

TYPICAL FOOTING PLAN


Ø8 STIRRUP: 1 @ 50 100 LENGTH OR WIDTH 100
D

600 400 FROM END, REST @ 200


W VAPOUR BARRIER TWO COATS OF SEE SCHEDULE
(MIN) (MIN)
AS PER SPECIFICATIONS WATER PROOFING PAINT.

100mm THICK
BLINDING CONCRETE
CONTRACTION JOINT
SECTION
IN SLAB ON GRADE TYPICAL SECTION FOOTING
SCALE N.T.S.
SEE AR. DWG

- SCALE N.T.S.

PEJ WITH T.O.G.S. SLAB ON GRADE SLAB ON GRADE


MASTIC SEALANT SEE PLAN SEE PLAN
SLAB ON GRADE PEJ WITH SLAB ON GRADE
(MIN)

T.O.G.S.
600

SIDE WALK SEE PLAN MASTIC SEALANT SEE PLAN


Ø10@250
Ø10/STEP

NOTE: VAPOUR BARRIER


GROUND BEAM (GB) 2Ø12
4Ø10 AS PER SPECIFICATIONS VAPOUR BARRIER VAPOUR BARRIER
SEE PLAN & SCHED.
Ø10@200
Ø12@200 VAPOR BARRIER
AS PER SPECIFICATIONS GROUND BEAM (GB) 4Ø10 AS PER SPECIFICATIONS
SEE PLAN & SCHED. AS PER SPECIFICATIONS SIDE WALK
Ø12@200 COMPACTED FILL
CONC. MASONRY UNIT WALL
WATER PROOFING PAINT
BLINDING CONC. 100mm THICK
WATER PROOFING PAINT 229528

BLINDING CONC. 100mm THICK

153018

TYPICAL GROUND BEAM DETAILS TYPICAL GROUND BEAM DETAILS 2Ø12

BLOCK WALL
SECTION ENTRANCE STEP
SLAB ON GRADE
T.O.G.S. SEE PLAN
SLAB ON GRADE
SEE PLAN

F.G.L SLOPE T.O.G.S. SLAB ON GRADE


229528

SEE PLAN SEE PLAN SEE PLAN


F.G.L
Ø12@200 SEE PLAN
MIN.

MIN.

VAPOUR BARRIER
229528

229528

5Ø10

TIE BEAM (TB), IF AVAILABLE


AS PER SPECIFICATIONS VAPOUR BARRIER SCHEDULE OF LINTEL BEAMS
AS PER SPECIFICATIONS VAPOUR BARRIER
SEE PLAN & SCHED.
229154

229154
AS PER SPECIFICATIONS
COMPACTED COMPACTED
FILL FILL
Ø10@200 Ø10@200

3Ø12 3Ø12
WATER PROOFING PAINT
BLINDING CONC. 100mm THICK

TYPICAL DETAIL OF SLAB ON GRADE TYPICAL EDGE SECTION


TYPICAL RAMP SECTION GENERAL DETAILS (1)

N.T.S

ST-00B
CLASS "B" LAP SPLICES
50 BAR DIA 50 BAR DIA
60 BAR DIA.

1. FOR MORE DETAILS & DIMENSIONS REFER

t
EXTERNAL
FACE OF WALL
ARCHITECTURAL DWGS.

60 BAR DIA.
2. FOR FURTHER DETAILS REFER TO DWGS.
t/3 t/3
( IF NEEDED )
t/3
S-001 , S-002
JOINT HOOPS

3. CONTRACTOR SHOULD SUBMIT THE SHOP


DRAWINGS FOR APPROVAL IN WHICH A FULL

OR CONTINUOUS.
CLASS (A) SPLICE
8

t/4
S-004 S-004
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
COLUMN HOOPS

MAX. SPACING 15.0 M


4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
300 mm WATER STOPPER , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
REFER TO NOTE J-1
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
TYP. WALL INTERSECTION 5. SOIL BEARING CAPACITY = 170 KN/m2
TYP. WALL CORNER
6. BACKFILLING WORKS AROUND RETAINING WALLS
t SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
CLEAR HEIGHT OF COLUMN

TYPICAL SECTIONAL PLAN


COLUMN STIRRUPS

CONSTRUCTION JOINT

40
COLUMN HOOPS

SECTION

t/3

LAP SPLICE

LAP SPLICE
100 (MAX.)

t/3
t

LAP SPLICE

t/3
BEAM

TYPICAL CONSTRUCTION JOINT

LAP SPLICE

RECTANGULAR OPENING CIRCULAR OPENING


COL. W OR L

SUSPENDED CONCRETE SLAB OPENING


NOT MORE
- SCALE N.T.S.
S

CLASS (B) SPLICE


S
L/5

150 OR LESS
SLAB/
150 S

MINIMUM DEVELOPMENT AND SPLICE LENGTHS (mm)


L/5

TYP. AHU CONCRETE PAD


S
S
S
S

TYPICAL INTERIOR COLUMN BLOCK WALL


IF ANY
BLOCK WALL
IF ANY

200 SEE PLAN 200

2Ø16 (ADD.) 2Ø16 (ADD.)


300

300

Ø10@200 (ADD.) Ø10@200 (ADD.)


80 CLEAR

STIRRUPS STIRRUPS
2Ø16 (ADD.) 2Ø16 (ADD.) STRAIGHT

50 DIA. 50 DIA.
EMBEDMENT
SLAB, SEE SLAB, SEE COMPRESSION
CLASS B CLASS A CLASS B

CLASS A
Ldh

PLAN & SCHED. PLAN & SCHED. SIDE


SLAB/
S
150

TYPICAL SECTION IN
ROOF SLAB OPENING & BASEMENT SLAB OPENING
S
S

GENERAL DETAILS (2)


S
S

TYPICAL TOP OF COLUMN N.T.S

ST-00B
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

500 400 200 200


1
C8* C2*
C8*

200
C8* 1. FOR MORE DETAILS & DIMENSIONS REFER

200

500

600
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002

5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.

500
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN

500
100 100 C C8* , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 C8* STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
100

300
C8

300
200 5. SOIL BEARING CAPACITY = 170 KN/m2

500
2200
6. BACKFILLING WORKS AROUND RETAINING WALLS

100
100
C3 SHOULD BE DONE AFTER CASTING THE BASEMENT
C3 SLAB COVER.
3
500

1100
500
C1
100

4700
100

C4

2200

100
C3
4
500
2200

600
W
100 C2 200
5 C4 100 100

100
300

300
C4

2500

2500
C8 C8
5000

100 100
200

700
200
38750

100
6 C4 C5 C3*

200
1700

400
200
7
C8*

500 500
2500

1800

500
C8* C8*
8
200 100
2200

C5

4200
300
9000

100

1000

100
9
C9
200
1800

400

100

1200
300
10 C10
400

C10
1400

100
600

11 C9
C6
400

300
COLUMNS LAYOUT PLAN FORM
2750

FOUNDATIONS TO BASEMENT COVER SLAB


350

150
150

150

C9 C7 C7 C7
12
100 300 300
3100

1:175

ST-001-1
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

500 400 200 200


1

100
C8* C8* C8* C2*

100
1. FOR MORE DETAILS & DIMENSIONS REFER

500

600
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002

5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.

500
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN

500
100 100 C C8* , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
C8* 200

300
C8 200 5. SOIL BEARING CAPACITY = 170 KN/m2

500
2200
6. BACKFILLING WORKS AROUND RETAINING WALLS

100
100
C3 C3 SHOULD BE DONE AFTER CASTING THE BASEMENT
3 SLAB COVER.
500

1100
500
C1
100

4700
100

C4

2200

100
C3
4
500
2200

600
W
100 C2 200
5 C4 100 100

100
300

300
C4

2500

2500
C8 C8
5000

100 100

200
38750

100
6 C3*
C4
200

200
1700

200 200
7
PC1 C8*

500
500
2500

500

500
PC1 PC1 C8* C8*
8
100 200 200 200

500
500
9000

100
9
C9
1800

400

100
10 PC2
400
1400

100
600

11 C9
C6
400

300
COLUMNS LAYOUT PLAN FORM BASEMENT
2750

COVER SLAB TO GROUND COVER SLAB


350

150
150

150

C9 C7 C7 C7
12
100 300 300
3100

1:175

ST-001-2
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

500 400 200 200


1

100
C8* C8* C8* C2*

100
1. FOR MORE DETAILS & DIMENSIONS REFER

500

600
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002

5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.

500
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN

500
100 100 C C8* , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
C8* 200

300
C8 200 5. SOIL BEARING CAPACITY = 170 KN/m2

500
2200
6. BACKFILLING WORKS AROUND RETAINING WALLS

100
100
C3 C3 SHOULD BE DONE AFTER CASTING THE BASEMENT
3 SLAB COVER.
500

1100
500
C1
100

4700
100
C4

2200

100
C3
4
500
2200

600
W
100 C2 200
5
C4 100 100 C4

100
300

300
2500

2500
C8 C8
5000

100 100
200

200
38750

100
6
C4 C3*

200
1700

200 200
7
PC1 C8*

500
500
2500

500

500
PC1 PC1 C8* C8*
8
100 200 200 200

500
500
9000

9
1800

10
1400

11

COLUMNS LAYOUT PLAN FORM GROUND


2750

COVER SLAB TO FIRST COVER SLAB

12

1:175

ST-001-3
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002

5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2

2200
6. BACKFILLING WORKS AROUND RETAINING WALLS

100
100
C3 C3 SHOULD BE DONE AFTER CASTING THE BASEMENT
3 SLAB COVER.
500

1100
500
C1
100

4700
100 300

C4 PC3

2200

2200

100
C3
4
500
2200

W
100 C2 1500 100
5
C4 100

100

100
300

300
PC3 C4
5000

200

400

400
200
38750

100 PC3 PC3


6 C3*
C4

200
1100 1100
1700

7
2500

8
9000

9
1800

10
1400

11

COLUMNS LAYOUT PLAN FORM FIRST COVER


2750

SLAB TO SECOND COVER SLAB

12

1:175

ST-101-4
FLOOR From First cover Slab up FLOOR From First cover Slab up
COLUMN MKD.
From foundations up to From Basement cover slab up to From Ground cover slab up to COLUMN MKD.
From foundations up to From Basement cover slab up to From Ground cover slab up to
MKD. Basement cover slab. Ground cover slab. First cover slab. to Second cover slab. MKD. Basement cover slab. Ground cover slab. First cover slab. to Second cover slab. 1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
16T16 16T16 16T16 16T16 16T16 16T16 16T16 2. FOR FURTHER DETAILS REFER TO DWGS.
R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
200

200

200

200
C1 DRAWINGS FOR APPROVAL IN WHICH A FULL

300

300

300
C2*
COORDINATION WITH ARCH. & MEP DWGS.
700 700 700 700 IS MADE.
700 700 700
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
16T16 16T16 16T16 12T14 12T14 12T14 12T14
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C
5. SOIL BEARING CAPACITY = 170 KN/m2
200

200

200
C2 6. BACKFILLING WORKS AROUND RETAINING WALLS

300

300

300

300
C3* SHOULD BE DONE AFTER CASTING THE BASEMENT
700 700 700 SLAB COVER.
600 600 600 600

12T14 12T14 12T14 12T14


R8@150C/C R8@150C/C R8@150C/C R8@150C/C 12T14 12T14 12T14
R8@150C/C R8@150C/C R8@150C/C
200

200

200

200
C3
C8*

300

300

300
600 600 600 600

600 600 600


12T14 12T14 12T14 12T14
R8@150C/C R8@150C/C R8@150C/C R8@150C/C 12T14 12T14
R8@150C/C R8@150C/C 10T14
300

300

300

300
R8@150C/C
C4

300

300

200
C
600 600 600 600
600 600 600
12T14
R8@150C/C
12T14 12T14
R8@150C/C R8@150C/C
300

C5
PC1

300

300
600

600 600
8T14 8T14 8T14 8T14
R8@150C/C R8@150C/C R8@150C/C R8@150C/C
8T14
200

200

200

200

C6 R8@150C/C

200
500 500 500 500 PC2
500
8T14 8T14
R8@150C/C R8@150C/C
12T14
R8@150C/C
300

300

C7
PC3

300
400 400

10T14 10T14 10T14 600


R8@150C/C R8@150C/C R8@150C/C
200

200

200

C8
600 600 600

10T14 8T14
R8@150C/C R8@150C/C
200

C9
300

500
500

8T14
R8@150C/C
200

C10
500

COLUMNS DETAILS-1

1:35

ST-102-1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
0
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.

COLUMNS & WALLS DETAILS-2

N.T.S

ST-102-2
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
2400 SLAB COVER.

200
V:T14@150mm-C/C

2000

2400
H:T14@150mm-C/C

200

200
-- LIFT WALL SECTION
S-102-3 Scale 1:25

COLUMNS & WALLS DETAILS-3

N.T.S

ST-102-3
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
8800

1000
9700

1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
500mmTHICK.FOUNDATION 2. FOR FURTHER DETAILS REFER TO DWGS.

8300
Provide Full Top & Bottom Mesh : S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP

5500
T14@150MM-C/C
DRAWINGS FOR APPROVAL IN WHICH A FULL
04 COORDINATION WITH ARCH. & MEP DWGS.

450
3200 T2 T1 3200 104 IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2

2200
1500

150
6. BACKFILLING WORKS AROUND RETAINING WALLS

5701.770832
T1 SHOULD BE DONE AFTER CASTING THE BASEMENT

75
6756.555808
14 SLAB COVER.
3 14

3200.004224
3200.004224
7000
14

5700
14
14
14

20500
14
14
14
14

4700
14
14
14

Add. Bottom bars - T14-150 4800 T1

1600.302107
1600.302107
1600
4 T2

5200

5200
3200

14100
150
01
2200

2000
1400 1400

1999.906144
1400.0938561400.093856
1999.853154
1999.853154
T2

1999.906144
1400.093856
1400.093856
75
104
2000 14
16
5 14
16
14

6245.215024
16

1600.302107
1600.302107
4800 14
16
14

4000
16
14

3200.004224
6000
16
5000

14

22800
2399.697894
3200

3200.004224
T1
1500
38750

3200 T1
6
3200 T1
1700

05
3100
3100
104
7

4800
EL. -2.65
2500

4800.208246
BASEMENT F.F.L.

3200.004224
8
02

3200.003391
104
2000

2200
2500
9000

5300

7300
20000

03
104

2000
2100
1500

9
400
1800

10
1400

8100

11
2750

FOUNDATIONS LAYOUT PLAN

12

11100
N.T.S

ST-103
5

3 1. FOR MORE DETAILS & DIMENSIONS REFER


ARCHITECTURAL DWGS.
T14@150mm-C/C B.W 2. FOR FURTHER DETAILS REFER TO DWGS.
T14@150mm-C/C B.W
2 S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.

500
LIFT PIT IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
LEGEND: , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS

1500
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
WELL SELECTIVE V:T14@150mm-C/C WELL SELECTIVE
1. WELL SELECTIVE MATERIALS. MATERIALS MATERIALS
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
2. 100MM PLAIN CONCRETE. H:T12@200mm-C/C SLAB COVER.

T14@150mm-C/C B.W T14@150mm-C/C B.W


3. WATER PROOFING LAYERS.

500
4. 500MM REINFORCED CONCRETE.
5. WATER STOP TAPE.

2000
200 200 200 200
01 SECTION 1-1
S-104 Scale 1:45

300

T12@150mm-C/C T12@150mm-C/C 5
2000

T14@200mm-C/C T14@200mm-C/C
4

3
BALANCE TANK T14@150mm-C/C B.W
T14@150mm-C/C B.W
2
2000

500
SUM PIT

WELL SELECTIVE

1800
MATERIALS V:T14@150mm-C/C

T14@150mm-C/C B.W H:T12@200mm-C/C

T14@150mm-C/C B.W 1495


500

1500
FOUNDATIONS DETAILS
200 200 200 200
02 SECTION 2-2
S-102 Scale 1:45

1:45

ST-104-1
300 300
+1.10 +1.10

400

400
300

25 75
25 75 25 75
500 500
N.G.L N.G.L N.G.L

T12@150mm-C/C T12@150mm-C/C T12@150mm-C/C 1. FOR MORE DETAILS & DIMENSIONS REFER

3750

3750
ARCHITECTURAL DWGS.

3350

3350
3300 2. FOR FURTHER DETAILS REFER TO DWGS.
T14@125mm-C/C T14@200mm-C/C T14@200mm-C/C
5 5 5 S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
4 4 4 COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
3 3 3 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 2 2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
1 1 1 6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
500

500

500
PERFORATED PIPE 4in PERFORATED PIPE 4in

WELL SELECTIVE WELL SELECTIVE WELL SELECTIVE


100

100

100
SOIL SOIL SOIL

03 SECTION 3-3 04 SECTION 4-4 05 SECTION 5-5


S-104 Scale 1:50 S-104 Scale 1:50 S-104 Scale 1:50

1200
1200

ST.T8@150 C/C
300
LEGEND:
X 6T12 T8-150mm
1. WELL SELECTIVE MATERIALS.
200

S-501
decided on site

N.G.L 2. 100MM PLAIN CONCRETE.


Depth to be

X SECTION-X-X
S-105 Scale 1:25

3. WATER PROOFING LAYERS.


200
2T14
T12@200C/C,B.W 2L-T8-200mm 4. 500MM REINFORCED CONCRETE.
T12@200C/C,B.W
5. WATER STOP TAPE.
500

10cm BRICK WALL


400

2T14
fence grade beam
100

1200 100

FOUNDATIONS DETAILS

-- FENCE SECTION EACH 3.5M


1:50 1:50
S-105 Scale
ST-104-2
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

BH4
CONCRETE WALL WITH T12@200mm V.H
SHOULD BE CAST AFTER COMPLETING
THE HOLE STRUCTURE
200 200 R2
1 BH4-40x60
1. FOR MORE DETAILS & DIMENSIONS REFER
T12@150mm T12@150mm ARCHITECTURAL DWGS.
150
T12@150mm T12@150mm 2. FOR FURTHER DETAILS REFER TO DWGS.

BH4-40x60
250
1100
S-001 , S-002
R2
300

R1 3. CONTRACTOR SHOULD SUBMIT THE SHOP

5500

DB4

DB4
DRAWINGS FOR APPROVAL IN WHICH A FULL
R1 COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
01 SECTION 1-1 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
S-201 Scale 1:40 , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 DB3 DB2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2

BH4

BH6
5. SOIL BEARING CAPACITY = 170 KN/m2

2200

DB2
R2 6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
BH4-40x60 SLAB COVER.
3 01
DB3
201 SLAB REINFORCEMENT SLAB REINFORCEMENT

100
AS PER TABLE ABOVE Ø8@250mmBW. R8@250mmBW.

BH4-40x60

BH4-40x60
2Ø12 2Ø12 2Ø12 2Ø12

4700

400
300
Light Weight Materials Light Weight Materials

DB2
DEPTH

5Ø14 5Ø14

4 DB3
200 400 200 400
200 200 Ø8@200mm Ø8@200mm

DB3
2200

R2
R2 TYPICAL SECTION FOR RIB (R1)
R1
5 BH6-40x40

BH4

BH6
SOLID BEAM FROM TWO SIDES

BH1
R2 A secondary transverse rib should be provided at
mid-span ( its direction is perpendicular to the
BH4-40x60 direction of main ribs ) and reinforced with the
5000

AS PER TABLE ABOVE


same amount of steel as the main ribs. its top
2Ø12 2Ø12

BH1
reinforcement shall be 3T14.

BH4-40x60
38750

6
R1
DEPTH

DB2 BH4-40x60
1700

BH4-40x60

SLAB REINFORCEMENT SLAB REINFORCEMENT

100
Ø8@250mmBW. R8@250mmBW.
200 7
2Ø12 2Ø12

BH4
BH1
2500

R1 R1 R1

400
300
Light Weight Materials Light Weight Materials

SOLID BEAM FROM ONE SIDE 8 DB3


2Ø14 2Ø14

BH4
PLANTED COLUMN R2
200 400 200 400
Ø8@200mm Ø8@200mm
BH4-40x60
SOLID PART DETAILS PLANTED COLUMN TYPICAL SECTION FOR RIB (R2)
9000

Swimming Pool
Provide Full T & B Mesh :
T12@200MM-C/C

Water Tank Size


5.0L x 3.0W x 2H
RIBS DIRECTION
PLANTED COLUMN

200

100
9 T1
DB3

3000 T1 12
1800

Solid Sunk Slab (Thickness 300 mm) 16


6699.999128
T12@150mm c/c (Top & Bottom) 12
3200
10
3001.837637
DB3 DB3 16
3000

12
1400

Add. Bottom bars - T12-200


200mmTHICK.SLAB
16
Add. Bottom bars - T12-200

11 12
Solid Slab (Thickness 400 mm) 16
2350
T12@150mm c/c (Top & Bottom) 12 BASEMENT COVER SLAB
2750

16
DB3

LAYOUT PLAN
12
12

1:175

ST-201
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
8300

1800

BH4
200
6000 3700
R2
1 BH4-40x60
600 3400 1. FOR MORE DETAILS & DIMENSIONS REFER

500
1700 ARCHITECTURAL DWGS.

600
2. FOR FURTHER DETAILS REFER TO DWGS.

7800
BH4-40x60
S-001 , S-002
R2

5400
R1 3. CONTRACTOR SHOULD SUBMIT THE SHOP

5500

DB4

DB4
DRAWINGS FOR APPROVAL IN WHICH A FULL
R1 COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
300
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 DB3 DB2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2

BH4

BH6
5. SOIL BEARING CAPACITY = 170 KN/m2

1700
2000

2200

DB2
R2 6. BACKFILLING WORKS AROUND RETAINING WALLS
100 SHOULD BE DONE AFTER CASTING THE BASEMENT
BH4-40x60 SLAB COVER.
3
1100 DB3
300 4450

BH4-40x60

3100
BH4-40x60
20000

1000
4700

4500
200

3000

DB2

1400
4250
4 DB3

DB3
2200

2000
R2

300
R2 2000
R1
5 BH6-40x40

BH4

BH6
BH1
EL. +1.10
R2
GROUND F.F.L. 300

22300
BH4-40x60
5000

BH1

BH4-40x60

2600
38750

300
6 2000
DB2 BH4-40x60 R1
1700

BH4-40x60

300

900
300
7

BH4
BH1
2500

R1 R1 R1
8 DB3

BH4

1650
300
R2

BH4-40x60
3700

1650
2000

5600
1800
1000
9000

6400
5500
6300

6300
19000

Swimming Pool
3500

Water Tank Size


5.0L x 3.0W x 2H

4300 2600

9 1675
250
200
DB3
1800

10 DB3 DB3
1400

6600

11
EL. +0.65
YARD BASEMENT COVER SLAB BEAMS
2500
2750

DB3

ARRANGEMENT LAYOUT PLAN


3750
12
10600

1:175

ST-202
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

CONCRETE WALL WITH T12@200mm V.H


SHOULD BE CAST AFTER COMPLETING 200 200
THE HOLE STRUCTURE

1 DB4 DB4
1. FOR MORE DETAILS & DIMENSIONS REFER
T12@150mm
T12@150mm
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.

DB2

DB2
DB4

DB4
S-001 , S-002
300

R1 R1

5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
BH6-40x40
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
01 SECTION 1-1 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
S-203 Scale 1:40 , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 BH4-40x60 DB2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2

BH4

BH6
BH6-40x40 5. SOIL BEARING CAPACITY = 170 KN/m2

2200

DB4
R2 6. BACKFILLING WORKS AROUND RETAINING WALLS

BH2
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.

DB4
3 01
DB3
203 SLAB REINFORCEMENT SLAB REINFORCEMENT

100
AS PER TABLE ABOVE Ø8@250mmBW. R8@250mmBW.
BH4-40x60

BH4-40x60
2Ø12 2Ø12 2Ø12 2Ø12

DB4
4700

BH2-40x60

400
300
Light Weight Materials Light Weight Materials
R2
DEPTH

5Ø14 5Ø14

DB4
4 DB3
200 400 200 400
200 200 Ø8@200mm Ø8@200mm

DB4
DB1
2200

TYPICAL SECTION FOR RIB (R1)


5 BH6-40x40

DB1
SOLID BEAM FROM TWO SIDES

DB1
A secondary transverse rib should be provided at
DB4 R1 BH6-40x40
mid-span ( its direction is perpendicular to the
direction of main ribs ) and reinforced with the
5000

DB4
AS PER TABLE ABOVE
same amount of steel as the main ribs. its top
2Ø12 2Ø12 reinforcement shall be 3T14.

DB1
DB1
38750

6 R1
DEPTH

1700

SLAB REINFORCEMENT SLAB REINFORCEMENT

100
DB4

Ø8@250mmBW. R8@250mmBW.
7

DB4
200 2Ø12 2Ø12

DB4

DB4
2500

400
300
Light Weight Materials Light Weight Materials

SOLID BEAM FROM ONE SIDE 8 DB4 DB4


2Ø14 2Ø14

200 400 200 400


Ø8@200mm Ø8@200mm

SOLID PART DETAILS TYPICAL SECTION FOR RIB (R2)


9000

RIBS DIRECTION
DBC1
9 DB3
1800

Solid Sunk Slab (Thickness 300 mm) 150mmTHICK.SLAB


DB3

Provide Full Top & Bottom Mesh :


T12@150mm c/c (Top & Bottom) 10 T10@200MM-C/C
1400

11 DB2
Solid Slab (Thickness 400 mm)
DB3
DB3

T12@150mm c/c (Top & Bottom) GROUND COVER SLAB


2750

DB3

LAYOUT PLAN

12 DB3 DB3

1:175

ST-203
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

6300 6300
1 DB4 DB4

1250

1250
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
100 100 2. FOR FURTHER DETAILS REFER TO DWGS.

DB2

DB2
1500

1500
DB4

DB4
S-001 , S-002

450

450
R1 R1

5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
3400
DRAWINGS FOR APPROVAL IN WHICH A FULL
BH6-40x40
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN

300
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 BH4-40x60 DB2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2

BH4

BH6
BH6-40x40 5. SOIL BEARING CAPACITY = 170 KN/m2

2200

DB4
R2 6. BACKFILLING WORKS AROUND RETAINING WALLS

BH2

1400
100 SHOULD BE DONE AFTER CASTING THE BASEMENT

1000
SLAB COVER.

DB4
3
900 DB3
300 4450

BH4-40x60

3100
BH4-40x60

DB4
4700

4500
BH2-40x60
200

3000
R2

1400
24000

24000
4250

DB4
4 DB3

DB4
DB1
2200

2000
300

2000
5 BH6-40x40

DB1

DB1
1700

300
DB4 R1 BH6-40x40
5000

3600

DB4
EL. +5.90
FIRST F.F.L.

4500

4500
DB1
DB1
38750

6 R1
1700

100 100
DB4

DB4
DB4

DB4
2500

2700

2700
8 DB4 DB4
6300 6300
9000

2200
DBC1
9 DB3
1800

3200
DB3

10
1400

6200
6200

11 DB2
1800
DB3
DB3

GROUND COVER SLAB BEAMS


2500
2750

3000
DB3
2800

ARRANGEMENT LAYOUT PLAN


6000
12 DB3 DB3

1:175

ST-204
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

1 DB4 DB4
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.

DB4

DB2

DB2

DB4
S-001 , S-002

5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
BH6-40x40
COORDINATION WITH ARCH. & MEP DWGS.
R1
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2

BH4
5. SOIL BEARING CAPACITY = 170 KN/m2

2200

DB4
6. BACKFILLING WORKS AROUND RETAINING WALLS

BH2
SHOULD BE DONE AFTER CASTING THE BASEMENT
R1 SLAB COVER.

DB4
3 DB3
SLAB REINFORCEMENT SLAB REINFORCEMENT

100
AS PER TABLE ABOVE Ø8@250mmBW. R8@250mmBW.
R2

BH4-40x60
2Ø12 2Ø12 PLANTED COLUMN 2Ø12 2Ø12

DB4
4700

400
300
BH2-40x60
Light Weight Materials Light Weight Materials
DEPTH

5Ø14 5Ø14

DB4
4 DB3
200 400 200 400
200 200 Ø8@200mm Ø8@200mm

DB4
DB1
2200

R2
TYPICAL SECTION FOR RIB (R1)
5 PLANTED COLUMN BH2-40x60 BH2 BH6-40x40

DB1
SOLID BEAM FROM TWO SIDES
R2 R2

DB1
A secondary transverse rib should be provided at
BH4-40x60 BH4-40x60
DB4
mid-span ( its direction is perpendicular to the
direction of main ribs ) and reinforced with the

DB4
5000

BH6-40x40
AS PER TABLE ABOVE R1
same amount of steel as the main ribs. its top

DB1

DB1
2Ø12 2Ø12 R2 reinforcement shall be 3T14.
38750

6 BH3-40x60 BH3-40x60 BH3-40x60


PLANTED COLUMN
DEPTH

1700

SLAB REINFORCEMENT SLAB REINFORCEMENT

100
DB4

Ø8@250mmBW.
7 R8@250mmBW.
200

DB4
R1 2Ø12 2Ø12
R1 R2
DB4

DB4
2500

400
300
Light Weight Materials Light Weight Materials

8 DB4 BH6-40x40 DB4


SOLID BEAM FROM ONE SIDE
2Ø14 2Ø14

200 400 200 400


Ø8@200mm Ø8@200mm

SOLID PART DETAILS TYPICAL SECTION FOR RIB (R2)


9000

RIBS DIRECTION

9
1800

Solid Sunk Slab (Thickness 300 mm)


T12@150mm c/c (Top & Bottom) 10
1400

11
Solid Slab (Thickness 400 mm)
T12@150mm c/c (Top & Bottom) FIRST COVER SLAB
2750

LAYOUT PLAN

12

1:175

ST-205
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

6300 6300
1 DB4 DB4

1250

1250
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
100 100 2. FOR FURTHER DETAILS REFER TO DWGS.

1500

1500
DB4

DB2

DB2

DB4
S-001 , S-002

450

450
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
3400
DRAWINGS FOR APPROVAL IN WHICH A FULL
BH6-40x40
COORDINATION WITH ARCH. & MEP DWGS.
R1
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 EL. +10.10 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2

BH4
SECOND F.F.L. 5. SOIL BEARING CAPACITY = 170 KN/m2

2200

DB4
6. BACKFILLING WORKS AROUND RETAINING WALLS

BH2
300
SHOULD BE DONE AFTER CASTING THE BASEMENT
R1 SLAB COVER.

DB4
3 DB3
4150

1300
R2

BH4-40x60
300 300

DB4
1800
4700

4500
500

BH2-40x60

1400
24000

24000
3950

DB4
4 DB3

DB4
DB1
2200

2000
300
R2

300

100
2000
5 BH2-40x60 BH2 BH6-40x40

1100

1100
DB1
R2 R2

DB1
BH4-40x60 BH4-40x60
DB4

DB4
5000

BH6-40x40
R1
300

DB1

DB1
R2
38750

6 BH3-40x60 BH3-40x60 BH3-40x60


1700

1200

1200

1200
DB4

DB4
R1 R2 R1
DB4

DB4
2500

8 DB4 BH6-40x40 DB4


16000
9000

9
1800

10
1400

11

FIRST COVER SLAB BEAMS


2750

ARRANGEMENT LAYOUT PLAN

12

1:175

ST-206
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002

5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2

2200
6. BACKFILLING WORKS AROUND RETAINING WALLS
DBC1
SHOULD BE DONE AFTER CASTING THE BASEMENT
DB3 SLAB COVER.
3 DB3
R2 SLAB REINFORCEMENT SLAB REINFORCEMENT

100
AS PER TABLE ABOVE

BH4-40x60
Ø8@250mmBW.
BH5-40x50 R8@250mmBW.

DB2
2Ø12 2Ø12 R2
2Ø12 2Ø12

DB4
4700
DB3

400
BH

300
Light Weight Materials Light Weight Materials
4- BH5-40x50
40
DEPTH

x6 R2 5Ø14 5Ø14
0

DB4
4 R2 DB3
DB3 200 400 200 400
200 200 Ø8@200mm Ø8@200mm

DB4
DB3

DB3
2200

R2
TYPICAL SECTION FOR RIB (R1)
DB3
5 BH4-40x60 DB3 BH4-40x60
SOLID BEAM FROM TWO SIDES
R2
A secondary transverse rib should be provided at
mid-span ( its direction is perpendicular to the

BH4-40x60
BH4-40x60
DB4 BH6
direction of main ribs ) and reinforced with the

DB4
5000

AS PER TABLE ABOVE R1 R1


same amount of steel as the main ribs. its top
2Ø12 2Ø12 reinforcement shall be 3T14.
38750

6
DB4 DB4 DB4
DEPTH

1700

SLAB REINFORCEMENT SLAB REINFORCEMENT

100
Ø8@250mmBW.
7 R8@250mmBW.
200 2Ø12 2Ø12
2500

400
300
Light Weight Materials Light Weight Materials

SOLID BEAM FROM ONE SIDE 8


2Ø14 2Ø14

200 400 200 400


Ø8@200mm Ø8@200mm

SOLID PART DETAILS TYPICAL SECTION FOR RIB (R2)


9000

RIBS DIRECTION 9
1800

10
Solid Slab (Thickness 200 mm)
1400

T12@150mm c/c (Top & Bottom)


11

SECOND COVER SLAB


2750

LAYOUT PLAN

12

1:175

ST-207
A B C D E F G
19800
2000 6000 3800 2200 3800 2000

1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002

5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2

2200
6. BACKFILLING WORKS AROUND RETAINING WALLS
DBC1
10000 SHOULD BE DONE AFTER CASTING THE BASEMENT
DB3 SLAB COVER.
3 DB3

800
R2

2600
750

BH4-40x60
BH5-40x50

DB2
R2
6000

DB4
1800
4700
DB3
BH 3250
4- BH5-40x50
40
x6

1000
0 R2

DB4
4 R2 DB3
DB3
EL. +14.30

DB4
DB3

DB3
2200

2000
R2

12302
ROOF TOP F.F.L.

300
2000
DB3
5 BH4-40x60 DB3 BH4-40x60

9702

1600

300
R2
500

BH4-40x60
BH4-40x60
DB4 BH6

DB4
5000

2000
R1 R1

2300
38750

6
DB4 DB4 DB4
1700

16000

7
2500

8
9000

9
1800

10
1400

11

SECOND COVER SLAB BEAMS


2750

ARRANGEMENT LAYOUT PLAN

12

1:175

ST-208
SIZES AND REINFORCEMENT OF DROP BEAMS

DIMENSIONS (cm) BOTTOM REINFORCEMENT TOP REINFORCEMENT STIRRUPS


MARK SIDE BARS REMARKS
(EACH SITE)
WIDTH DEPTH MAIN REIN. ADDITIONAL REIN. MAIN REIN. ADDITIONAL REIN. AT SUPPORT AT MID SPAN No.Legs

DB1 20 60 3Ø16 3Ø16 3Ø16 3Ø16 ....... Ø8@10cm-c/c Ø8@10cm-c/c 2

DB2 20 60 3Ø14 2Ø14 3Ø14 2Ø14 ....... Ø8@15cm-c/c Ø8@15cm-c/c 2 1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
DB3 20 60 3Ø14 ....... 3Ø14 ....... ....... Ø8@20cm-c/c Ø8@20cm-c/c 2 2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
....... ....... ....... 3. CONTRACTOR SHOULD SUBMIT THE SHOP
DB4 30 60 3Ø16 3Ø16 Ø8@20cm-c/c Ø8@20cm-c/c 2
DRAWINGS FOR APPROVAL IN WHICH A FULL
IN CANTILEVERS TOP REINFORCEMENT COORDINATION WITH ARCH. & MEP DWGS.
DBC1 20 60 3Ø14 ....... 3Ø14 2Ø14 ....... Ø8@20cm-c/c Ø8@20cm-c/c 2 SHOULD BE EXTENT1.5 TIMES IT'S LENGTH IS MADE.
BEYOND THE SUPPORT
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5 4 5 4 5 5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
6T16 3T16 6T16 3T16 6T16 SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.

2L-T8@100 2L-T8@100

6T16 6T16
VARIES VARIES
5 4 5 4 5
-- DB1-60X20
--
3T14 2L-T8@200 3T14 2L-T8@200 5T14 2L-T8@200

3 2 3 2 3
5T14 3T14 5T14 3T14 5T14

600

600

600
2L-T8@200 2L-T8@200

5T14 5T14 3T14 5T14 3T14


200 200 200
VARIES VARIES
3 2 3 2 3 SECTION 1-1 SECTION 2-2 SECTION 3-3
-- DB2-60X20
--

3T16 2L-T8@100 6T16 2L-T8@100 3T16 2L-T8@200

1 1

600

600

600
3T14 3T14

2L-T8@200 2L-T8@200

3T14 3T14 6T16 3T16 3T16


200 200 300
VARIES VARIES
1 1 SECTION 4-4 SECTION 5-5 SECTION 6-6
-- DB3-60X20
--

1 1 3
3T16 3T16 5T14
2L-T8@200 2L-T8@200 2L-T8@200 2L-T8@200
BEAMS DETAILS-1
3T16 3T16
VARIES VARIES VARIES VARIES
1 1 3
-- DB4-60X30 -- DBC1-60X20 N.T.S
-- --

ST-301
SIZES AND REINFORCEMENT OF WIDE BEAMS

DIMENSIONS (cm) BOTTOM REINFORCEMENT TOP REINFORCEMENT STIRRUPS


MARK REMARKS
WIDTH DEPTH MAIN REIN. ADDITIONAL REIN. MAIN REIN. ADDITIONAL REIN. AT SUPPORT AT MID SPAN No.Legs

BH1 60 40 6Ø16 6Ø16 6Ø16 6Ø16 Ø10@10cm-c/c Ø10@10cm-c/c 4

BH2 60 40 6Ø14 6Ø14 6Ø14 6Ø14 Ø8@10cm-c/c Ø8@10cm-c/c 4 1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
BH3 60 40 6Ø14 2Ø14 6Ø14 2Ø14 Ø8@15cm-c/c Ø8@15cm-c/c 4 2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
BH4 60 40 6Ø14 ....... 6Ø14 ....... Ø8@15cm-c/c Ø8@15cm-c/c 4 DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
BH5 50 40 5Ø14 ....... 5Ø14 ....... Ø8@15cm-c/c Ø8@15cm-c/c 3 IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
BH6 40 40 4Ø14 ....... 4Ø14 ....... Ø8@15cm-c/c Ø8@15cm-c/c 2 , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.

12T16 12T14 8T14


100

100

100
400

400

400
300

300

300
4LEGT8 4LEGT8 4LEGT8
12T16 12T14 8T14

600 600 600


HB1: SECTION HB2: SECTION HB3: SECTION

6T14 5T14 4T14


100

100
100
400

400

400
300

300

300
4LEGT8 3LEGT8 2LEGT8
6T14 5T14 4T14

600 500 400


HB4: SECTION HB5: SECTION HB6: SECTION

BEAMS DETAILS-2

N.T.S

ST-302
6 x 300=1800 1450

200
T14@150
3T16

T12@200 T14@200

220

7x150=1050
600
1. FOR MORE DETAILS & DIMENSIONS REFER
T14@150 2L-T8@150
T12@200 ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
T14@200 5T16

220
S-001 , S-002
RAFT REINF. 3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
D E F 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
01 SECTION-1 5. SOIL BEARING CAPACITY = 170 KN/m2
2200 3800 6. BACKFILLING WORKS AROUND RETAINING WALLS
S-401 Scale 1:45 SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.

3
01 02 03 04 05 06 07 08

01

UP
401

1350 6 x 300=1800 1350


07
T14@150
08

CRANK BEAM (60X20)


T14@150
T12@200
220

09
7x150=1050

4700
T14@150
T12@200 11
T14@150
220

CR 12
ANK T14@200
BEA
M 13

14
T14@250

02 SECTION-2 03
S-401 Scale 1:45
401

25 24 23 22 21 20 19 18 17 16 15
4

02
401
10 x 300=3000 1350
SLAB REINF.

T14@100
T12@200
11x150=1650

3T16
0
22

T12@200

T14@100
200
R8@150

600
T14@150
3T16
220

BASEMENT STAIRCASE DETAILS


600

T14@150 2L-T8@150 200


03 SECTION-3
5T16
S-401 Scale 1:45 5T16
- CRANK BEAM
- Scale 1:25
N.T.S

ST-401
11x300=3300 1450
200
T14@150
3T16
T14@100

240
T12@200

600
T14@100 2L-T8@150

12x160=1920
5T16

1. FOR MORE DETAILS & DIMENSIONS REFER


T12@200 ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
T14@100 3. CONTRACTOR SHOULD SUBMIT THE SHOP

24
0
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
SLAB REINF. IS MADE.
D E F 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
01 SECTION-1 2200 3800
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
S-402 Scale 1:45 SLAB COVER.

3
01 02 03 04 05 06 07 08 09 10 11 12

1350 6 x 300 = 1800 1550


01

UP
T14@100
402
7x160=1120

T14@150 13

14

CRANK BEAM (60X20)


T14@150
0

CR
24

ANK
240

BEA T14@100 15

4700
M
3T16
T12@200 16

T14@150 17

18
02 SECTION-2 19
S-402 Scale 1:45

03
402

30 29 28 27 26 25 24 23 22 21 20
4
10 x 300 = 3000 1550
SLAB REINF.

02
402
T14@100

T12@200
11x160=1760

T12@200
0
24

T14@100 3T16

T14@150

T12@200
3T16
R8@150

600
240
600

T14@100 2L-T8@150
03 SECTION-3 GROUND STAIRCASE DETAILS
S-402 Scale 1:45 5T16
200
5T16
- CRANK BEAM
- Scale 1:25
N.T.S

ST-402
10 x 300=3000 1450

200
T14@150
3T16
T14@100

220
T12@200

600
T14@150 2L-T8@150
1. FOR MORE DETAILS & DIMENSIONS REFER

11x150=1650
ARCHITECTURAL DWGS.
5T16
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
T12@200 3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
T14@100 COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
SLAB REINF. 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
D E F , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
01 6. BACKFILLING WORKS AROUND RETAINING WALLS
SECTION-1 SHOULD BE DONE AFTER CASTING THE BASEMENT
2200 3800
S-403 Scale 1:45 SLAB COVER.

3
01 02 03 04 05 06 07 08 09 10 11

01

UP
403

1350 6 x 300=1800 1350


12
T14@150
13

CRANK BEAM (60X20)


T14@150
T12@200
220

14

4700
7x150=1050

T14@150
T12@200 15
T14@150
220

CR 16
ANK T14@100
BEA
M 17

18
T14@150

02 SECTION-2 03
S-403 Scale 1:45 403

28 27 26 25 24 23 22 21 20 19
4

02
403
9 x 300=2700 1300
SLAB REINF.

T14@150
T12@200
10x150=1500

3T16
T12@200
220

T14@150 R8@150

600
200
T14@150
3T16
FIRST STAIRCASE DETAILS
220
600

T14@150 2L-T8@150
200
03 SECTION-3 5T16
S-403 Scale 1:45 5T16 - CRANK BEAM
- Scale 1:25
N.T.S

ST-403
B C

6000 1. FOR MORE DETAILS & DIMENSIONS REFER


ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
11 DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
01 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
404 , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2

LANDING BEAM (60X20)


5. SOIL BEARING CAPACITY = 170 KN/m2
01 02 03 04 05 06 07 08 09 10 6. BACKFILLING WORKS AROUND RETAINING WALLS

2750
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.

2499.92
19 18 17 16 15 14 13 12 11

UP 02
404

12

9 x 300=2700 1200
9 x 300=2700 1250
200
T14@150 SLAB REINF.
3T16
T14@200
220

T14@150
T12@200 T12@200
600

T14@200 2L-T8@150
10x150=1500

10x150=1500

3T16
T12@200 T12@200

220
T14@200 T14@150
200
SLAB REINF. T14@150
3T16

220
600
T14@150 2L-T8@150
03 SECTION-3
01 SECTION-1 3T16
S-404 Scale 1:45 3T16
S-404 Scale 1:45

R8@150
600

OUTER ANNEX STAIRCASE DETAILS


200
3T16
- LANDING BEAM
- Scale 1:25
N.T.S

ST-404
A
4000~7000 4000~7000
250 3Layer of Bitumen 250 250 250

T12@150mmC/ C-TOP &BOTTOM


200

200

250
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
200 200 2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
25CM 3. CONTRACTOR SHOULD SUBMIT THE SHOP

2000~3000

2000~3000
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
200 200 5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
B B T12@150mmC/ C-TOP &BOTTOM SHOULD BE DONE AFTER CASTING THE BASEMENT
200

200
SLAB COVER.
300

BLOCK WALL
TYPICAL WATER TANK PLAN A TYPICAL WATER TANK COVER SLAB

2000~3000 4000~7000
250 250 250
250
500
WATER LEVEL WATER LEVEL

500
T12@150C/C T12@150C/C
MIN.2500

BUFFER AREA T12@150C/C T12@150C/C BUFFER AREA T12@150C/C

2500
T12@150C/C T12@150C/C
FOR PIPES AND PUMP ACCESSORIES FOR PIPES AND PUMP ACCESSORIES
T14@150C/C T14@150C/C T14@150C/C T14@150C/C T14@150C/C
T14@150C/C T12@150C/C

T14@150 C/C T14@150 C/C


TYP WATER BAR TYP WATER BAR
200

200
T14@150 C/C TYP WATER BAR T14@150 C/C TYP WATER BAR
T14@150 C/C T14@150 C/C T14@150 C/C T14@150 C/C
400

400
100

100
T14@150 C/C, B.W. T14@150 C/C, B.W. T14@150 C/C, B.W. T14@150 C/C, B.W.
250 250
250 250
SECTION A-A SECTION B-B
250

EXTERNAL SIDE INTERNAL SIDE


300
400

300
2D
300

400

GROUND WATER TANK AND BAYARA


DETAILS

TYP. DETAIL OF PIPE TYPICAL DETAILS OF OPENING


TYPICAL DETAILS A THRU CONC. WALL
N.T.S

ST-501