ST-101-2 COLUMNS LAYOUT PLAN FROM BASEMENT COVER SLAB TO GROUND COVER SLAB
ST-101-3 COLUMNS LAYOUT PLAN FROM GROUND COVER SLAB TO FIRST COVER SLAB
ST-101-4 COLUMNS LAYOUT PLAN FROM FIRST COVER SLAB TO SECOND COVER SLAB
J.4 Construction joints at floor slabs and beams shall be located at middle third of the span of columns. If interrupted
by intersecting beam, construction joint shall be offset by a distance not less than two times the width of the
F.1 The allowable bearing capacity is ( 170 KN/m2) based on soil test and must be review the soil test report intersecting beam. ABBREVIATIONS
before starting the execution.
F.2 Foundation level should not be less than 3.0m below existing ground level.
F.3 The contractor is responsible to verify that the above bearing pressure is achieved at foundation level and to consult REINFORCEMENT NOTES Add. = Additional STRUCT. = Structural
the engineer if otherwise. The contractor shall perform cavity probing below all columns. If any cavity is encountered, BOT. = Bottom T = Top
it should be filled with blinding concrete for shallow cavities and by injection for deep cavities. Cont. = Continuous T&B = Top & Bottom
R.1 All reinforcement bars should be deformed bars and should comply with ASTM A615-Grade 60 C/C = Center to center THK. = Thickness
F.4 At footing locations, all fill must be removed locally to expose the competent natural materials and excavation should be
and should have a minimum yield strength (fy) of 420 N/mm². CONC. = Concrete TYP. = Typical
back filled with blinding concrete of minimum compressive cylindrical strength at 28 days of 20 mPa.
CLR. = Clear T.O.B. = Top of beam
R.2 Mesh reinforcement and wire fabric shall conform to ASTM-A185. DIA. = Diameter T.O.F. = Top of footing
F.5 All structural fill should be placed where required, in lifts not exceeding 200mm thickness.
The structural fill should be compacted to at least 95% of the maximum dry density, as determined by R.3 Provide minimum 0.0018 times the cross sectional area in slabs as distribution steel where required. E.W. = Each way T.O.P = Top of pedestal
ASTM D1557 Method of Compaction. The moisture content of the structural fill at the time of placement must be EA = Each T.O.G.S. = Top of grade slab
R.4 Overlap splice and development length shall be as specified in drawing S-003.
within 2 percent of the optimum moisture content. E.F. = Each face T.O.Grd Beam = Top of grade beam
R.5 Provide at least Ø12 @ 250 on centers horizontal reinforcement on each face of the beam more than or equal E.J. = Expansion joint T.O.S.S. = Top of structural slab
F.6 The structural fill should have the following properties : to 700 mm in depth. EL. = Elevation U.O.N. = Unless otherwise noted
not more than 50% passing No. 10 sieve EQ. = Equal VERT. = Vertical
R.6 Beam reinforcement in multiple layers shall have Ø25 mm or the dia of the main bar (whichever is greater) as F.F.L = Finish floor level W = Width
not more than 30% passing No. 40 sieve spacer bars at between layers 1200mm spacing.
not more than 15% passing No. 200 sieve FL. = Floor W/ = With
plasticity index less than 6% H = Height W.W.F. = Welded wire fabric
maximum particle size of 150mm. HORZ. = Horizontal @ = At the rate of
L = Length C = Center line
chloride concentration less than 500 mg/l
MAX. = Maximum Ø = Diameter of deformed bars
sulphate concentration less than 1200 mg/l
MIN. = Minimum = Bottom reinforcement
F.7 In-place density testing of the structural fill in accordance with ASTM D1556 (or equivalent) should be carried out NO. = Number = Top reinforcement
regularly at the start of the filling operations to establish the number of passes of the available compaction N.T.S. = Not to scale
= Continuous column or wall
equipment needed to achieve the required degree of compaction. Once this has established, only occasional
insitu density testing is required provided that the filling operation is closely monitored by an experienced
LOADS P = Pedestal
= Terminated column or wall
REQD. = Required
geotechnical engineer or technician. REINF. = Reinforcement
F.8 The foundation excavation should be kept open for shortest time practical, should be kept dry, and any SCHED. = Schedule
rain water should be pumped out from the excavation prior to any concrete or steel placement. OWN WEIGHT AND FLOOR FINISHES :
F.9 If excavation is to be done below foundation level of any adjacent building, shoring of excavation side shall be made
Own Weight of Reinforced Concrete = 24.0 KN/m³
using micro piles of diameter 350 mm and extended at least 2.0 m below excavation level.
Weights of plaster mortar = 20.5 KN/m³
F.10 The contractor must provide equipment for temporary dewatering activities, such as pumps, hoses, etc. Weights of cement blocks = 14.0 KN/m³
Groundwater encountered during the excavation is expected to be controlled with surface pumping. Floor Finishes (Sand + mortar + marble) = 2.50 KN/m²
F.11 The site grading and foundation construction activities shall be performed under the direct supervision Weight of hordi blocks = 1.50 KN/m²
of a competent geotechnical or civil engineer familiar with the design aspects of the project. Failure to
comply with this requirement may cause significant settlement in the future due to improper removal of
fill, improper removal and replacement of soft spots, sub compaction, or combination of these factors.
ROOF LOADS :
F.12 Sulphate resisting portland cement (ASTM C 150 type-V latest revision) shall be used in all reinforced
concrete works in contact with earth. The water/cement ratio shall not exceed 0.45 Screed for roof drainage = 2.20 KN/m²
F.13 Underground water tank base slab shall be protected against ground water and / or surface water by water proofing membrane Water proofing + Rigid insulation = 0.30 KN/m²
below base slab and around vertical walls. Pea gravel = 1.00 KN/m²
HVAC machine and RC pads * = 1.50 KN/m²
PARTITION LOADS :
CONCRETE NOTES Weight of Plaster for Each face of the Partitions /m² of wall (if any) = 0.24 KN/m²
C.1 All concrete work shall conform to SBC201&301&302&303&304&305&801)-2018 AND ACI 318-14 Building Code Requirements Weight of Cement Block Wall 200mm thick /m² of wall = 1.70 KN/m²
for Reinforced Concrete . Weight of Cement Block Wall 250mm thick /m² of wall
C.2 Use Ordinary Portland Cement (Type 'I') for all super structure reinforced concrete ,for sub structure (wall 100mm + Isolation + wall 100mm) = 4.20 KN/m²
sulfate resistance cement should be used (type v) ,with with minimum cement content 360 Kg/m3 Weight of Cement Block Wall 300mm thick /m² of wall
and water cement ratio not more than 0.45. (wall 100mm + Isolation + wall 150mm) = 4.80 KN/m²
C.3 Minimum compressive strength of standard concrete cylinders at different ages shall be as mentioned below.
3 days > 0.4 times 28 days value
7 days > 0.7 times 28 days value LIVE LOADS :
C.4 Concrete cylinder shall be taken for each day's pour and each 50 cubic meters or fraction thereof, Residential building = 2.00 KN/m²
cast in accordance with ASTM C31 and tested in accordance with ASTM C39.
C.5 Required minimum CHARACTERISTIC COMPRESSIVE STRENGTH of concrete based on standard cylindrical specimen
shall be as follows: * Actual weight of mechanical equipment shall be calculated including dynamic magnification factor and shall be
applied if found to be higher than the given value. Weight of pads, if required, shall be added to dead loads.
35 Mpa (350 Kg/m2) for all reinforced concrete elements.
20 Mpa (200 Kg/cm2) for blinding concrete.
C.6 Clear cover for reinforcement should be not less than follows : GENERAL NOTES & STRUCTURAL
75mm Unformed concrete deposited agaist ground LIST OF DRAWINGS
25mm Formed concrete agaist ground or exposed to weather
25mm Ties, stirrups and spirals of beams not exposed to ground or weather
25mm Ties, stirrups and spirals of columns not exposed to ground or weather
25mm walls not exposed to ground or to weather
25mm Slabs not exposed to ground or to weather
C.7 All reinforcing steel dowels, anchor bolts, and other inserts shall be secured in position prior to pouring concrete.
N.T.S
ST-00A
L1 L2 L3
0.30 L2 OR L1
GREATER 0.3 (L1 or L2) 0.3 (L2 or L1) (0.3 L2) OR (1.5 L3)
0.25 L1 THE GREATER
0.30 (L3 OR L2) THE GRATER THE GRATER
0.30 (L2 OR L3) 0.25 L3
GREATER GREATER
50 50 50 50 50
L1
CANTILEVER
L2
INTERIOR CLEAR SPAN
L3
EXTERIOR CLEAR SPAN 0.10 L1 0.10 L1 0.10 L2 0.10 L2 1. FOR MORE DETAILS & DIMENSIONS REFER
CLEAR SPAN
LEFT STIRRUPS MIDDLE STIRRUPS RIGHT STIRRUPS LEFT STIRRUPS MIDDLE STIRRUPS RIGHT STIRRUPS
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
TYPICAL SOLID SLAB ON BEAM TYPICAL DETAIL ON CONTINUOUS BEAMS& GIRDERS DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
NOTE :- FOR TOP NEGATIVE REINFORCEMENT OF CONTINUOUS BEAMS THE GREATER
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
REINFORCEMENT FROM (E) BARS AND (C) BARS MUST BE PLACED. , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
W
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
CL
40mm
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
W W
SHOULD BE DONE AFTER CASTING THE BASEMENT
FOR REINF.
SLAB COVER.
GRID SEE COL. DETAIL
COLUMN
CAST-IN-PLACE
TIES
H
H
ON COMPRESSIBLE FILLER
A/2
VAR.
GROUND BEAM (GB) VAPOUR BARRIER
CENTERLINE OF SEE PLAN & SCHED. AS PER SPECIFICATIONS
FOOTING & COL.
VARIES
25mm OR Ø BAR MIN.
COMPACTED BACKFILL
B
4
TYPICAL SECTION FOR TYPICAL STIRRUPS TYPICAL STIRRUPS GRID S-003 S-003 S 1/2
GRID
B/2
TIE BEAM IF REQUIRED Ø10@300 BOTHWAYS TIE BEAM IF REQUIRED
75 CLEAR COVER(TYP)
PLAN
SEE
RECTANGULAR
COLUMN
GROVE SLAB ON GRADE
T.O.G.S.
(SEE PLAN)
229528 229528
40
155
6 REINF. BARS FOUNDATION
57382
B LEVEL
S-003 S-003 (SEE SCHED.)
100mm THICK
BLINDING CONCRETE
CONTRACTION JOINT
SECTION
IN SLAB ON GRADE TYPICAL SECTION FOOTING
SCALE N.T.S.
SEE AR. DWG
- SCALE N.T.S.
T.O.G.S.
600
153018
BLOCK WALL
SECTION ENTRANCE STEP
SLAB ON GRADE
T.O.G.S. SEE PLAN
SLAB ON GRADE
SEE PLAN
MIN.
VAPOUR BARRIER
229528
229528
5Ø10
229154
AS PER SPECIFICATIONS
COMPACTED COMPACTED
FILL FILL
Ø10@200 Ø10@200
3Ø12 3Ø12
WATER PROOFING PAINT
BLINDING CONC. 100mm THICK
N.T.S
ST-00B
CLASS "B" LAP SPLICES
50 BAR DIA 50 BAR DIA
60 BAR DIA.
t
EXTERNAL
FACE OF WALL
ARCHITECTURAL DWGS.
60 BAR DIA.
2. FOR FURTHER DETAILS REFER TO DWGS.
t/3 t/3
( IF NEEDED )
t/3
S-001 , S-002
JOINT HOOPS
OR CONTINUOUS.
CLASS (A) SPLICE
8
t/4
S-004 S-004
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
COLUMN HOOPS
CONSTRUCTION JOINT
40
COLUMN HOOPS
SECTION
t/3
LAP SPLICE
LAP SPLICE
100 (MAX.)
t/3
t
LAP SPLICE
t/3
BEAM
LAP SPLICE
150 OR LESS
SLAB/
150 S
300
STIRRUPS STIRRUPS
2Ø16 (ADD.) 2Ø16 (ADD.) STRAIGHT
50 DIA. 50 DIA.
EMBEDMENT
SLAB, SEE SLAB, SEE COMPRESSION
CLASS B CLASS A CLASS B
CLASS A
Ldh
TYPICAL SECTION IN
ROOF SLAB OPENING & BASEMENT SLAB OPENING
S
S
ST-00B
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
200
C8* 1. FOR MORE DETAILS & DIMENSIONS REFER
200
500
600
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
500
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
500
100 100 C C8* , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 C8* STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
100
300
C8
300
200 5. SOIL BEARING CAPACITY = 170 KN/m2
500
2200
6. BACKFILLING WORKS AROUND RETAINING WALLS
100
100
C3 SHOULD BE DONE AFTER CASTING THE BASEMENT
C3 SLAB COVER.
3
500
1100
500
C1
100
4700
100
C4
2200
100
C3
4
500
2200
600
W
100 C2 200
5 C4 100 100
100
300
300
C4
2500
2500
C8 C8
5000
100 100
200
700
200
38750
100
6 C4 C5 C3*
200
1700
400
200
7
C8*
500 500
2500
1800
500
C8* C8*
8
200 100
2200
C5
4200
300
9000
100
1000
100
9
C9
200
1800
400
100
1200
300
10 C10
400
C10
1400
100
600
11 C9
C6
400
300
COLUMNS LAYOUT PLAN FORM
2750
150
150
150
C9 C7 C7 C7
12
100 300 300
3100
1:175
ST-001-1
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
100
C8* C8* C8* C2*
100
1. FOR MORE DETAILS & DIMENSIONS REFER
500
600
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
500
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
500
100 100 C C8* , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
C8* 200
300
C8 200 5. SOIL BEARING CAPACITY = 170 KN/m2
500
2200
6. BACKFILLING WORKS AROUND RETAINING WALLS
100
100
C3 C3 SHOULD BE DONE AFTER CASTING THE BASEMENT
3 SLAB COVER.
500
1100
500
C1
100
4700
100
C4
2200
100
C3
4
500
2200
600
W
100 C2 200
5 C4 100 100
100
300
300
C4
2500
2500
C8 C8
5000
100 100
200
38750
100
6 C3*
C4
200
200
1700
200 200
7
PC1 C8*
500
500
2500
500
500
PC1 PC1 C8* C8*
8
100 200 200 200
500
500
9000
100
9
C9
1800
400
100
10 PC2
400
1400
100
600
11 C9
C6
400
300
COLUMNS LAYOUT PLAN FORM BASEMENT
2750
150
150
150
C9 C7 C7 C7
12
100 300 300
3100
1:175
ST-001-2
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
100
C8* C8* C8* C2*
100
1. FOR MORE DETAILS & DIMENSIONS REFER
500
600
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
500
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
500
100 100 C C8* , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
C8* 200
300
C8 200 5. SOIL BEARING CAPACITY = 170 KN/m2
500
2200
6. BACKFILLING WORKS AROUND RETAINING WALLS
100
100
C3 C3 SHOULD BE DONE AFTER CASTING THE BASEMENT
3 SLAB COVER.
500
1100
500
C1
100
4700
100
C4
2200
100
C3
4
500
2200
600
W
100 C2 200
5
C4 100 100 C4
100
300
300
2500
2500
C8 C8
5000
100 100
200
200
38750
100
6
C4 C3*
200
1700
200 200
7
PC1 C8*
500
500
2500
500
500
PC1 PC1 C8* C8*
8
100 200 200 200
500
500
9000
9
1800
10
1400
11
12
1:175
ST-001-3
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
2200
6. BACKFILLING WORKS AROUND RETAINING WALLS
100
100
C3 C3 SHOULD BE DONE AFTER CASTING THE BASEMENT
3 SLAB COVER.
500
1100
500
C1
100
4700
100 300
C4 PC3
2200
2200
100
C3
4
500
2200
W
100 C2 1500 100
5
C4 100
100
100
300
300
PC3 C4
5000
200
400
400
200
38750
200
1100 1100
1700
7
2500
8
9000
9
1800
10
1400
11
12
1:175
ST-101-4
FLOOR From First cover Slab up FLOOR From First cover Slab up
COLUMN MKD.
From foundations up to From Basement cover slab up to From Ground cover slab up to COLUMN MKD.
From foundations up to From Basement cover slab up to From Ground cover slab up to
MKD. Basement cover slab. Ground cover slab. First cover slab. to Second cover slab. MKD. Basement cover slab. Ground cover slab. First cover slab. to Second cover slab. 1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
16T16 16T16 16T16 16T16 16T16 16T16 16T16 2. FOR FURTHER DETAILS REFER TO DWGS.
R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
200
200
200
200
C1 DRAWINGS FOR APPROVAL IN WHICH A FULL
300
300
300
C2*
COORDINATION WITH ARCH. & MEP DWGS.
700 700 700 700 IS MADE.
700 700 700
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
16T16 16T16 16T16 12T14 12T14 12T14 12T14
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C R8@150C/C
5. SOIL BEARING CAPACITY = 170 KN/m2
200
200
200
C2 6. BACKFILLING WORKS AROUND RETAINING WALLS
300
300
300
300
C3* SHOULD BE DONE AFTER CASTING THE BASEMENT
700 700 700 SLAB COVER.
600 600 600 600
200
200
200
C3
C8*
300
300
300
600 600 600 600
300
300
300
R8@150C/C
C4
300
300
200
C
600 600 600 600
600 600 600
12T14
R8@150C/C
12T14 12T14
R8@150C/C R8@150C/C
300
C5
PC1
300
300
600
600 600
8T14 8T14 8T14 8T14
R8@150C/C R8@150C/C R8@150C/C R8@150C/C
8T14
200
200
200
200
C6 R8@150C/C
200
500 500 500 500 PC2
500
8T14 8T14
R8@150C/C R8@150C/C
12T14
R8@150C/C
300
300
C7
PC3
300
400 400
200
200
C8
600 600 600
10T14 8T14
R8@150C/C R8@150C/C
200
C9
300
500
500
8T14
R8@150C/C
200
C10
500
COLUMNS DETAILS-1
1:35
ST-102-1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
0
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
N.T.S
ST-102-2
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
2400 SLAB COVER.
200
V:T14@150mm-C/C
2000
2400
H:T14@150mm-C/C
200
200
-- LIFT WALL SECTION
S-102-3 Scale 1:25
N.T.S
ST-102-3
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
8800
1000
9700
1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
500mmTHICK.FOUNDATION 2. FOR FURTHER DETAILS REFER TO DWGS.
8300
Provide Full Top & Bottom Mesh : S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
5500
T14@150MM-C/C
DRAWINGS FOR APPROVAL IN WHICH A FULL
04 COORDINATION WITH ARCH. & MEP DWGS.
450
3200 T2 T1 3200 104 IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
2200
1500
150
6. BACKFILLING WORKS AROUND RETAINING WALLS
5701.770832
T1 SHOULD BE DONE AFTER CASTING THE BASEMENT
75
6756.555808
14 SLAB COVER.
3 14
3200.004224
3200.004224
7000
14
5700
14
14
14
20500
14
14
14
14
4700
14
14
14
1600.302107
1600.302107
1600
4 T2
5200
5200
3200
14100
150
01
2200
2000
1400 1400
1999.906144
1400.0938561400.093856
1999.853154
1999.853154
T2
1999.906144
1400.093856
1400.093856
75
104
2000 14
16
5 14
16
14
6245.215024
16
1600.302107
1600.302107
4800 14
16
14
4000
16
14
3200.004224
6000
16
5000
14
22800
2399.697894
3200
3200.004224
T1
1500
38750
3200 T1
6
3200 T1
1700
05
3100
3100
104
7
4800
EL. -2.65
2500
4800.208246
BASEMENT F.F.L.
3200.004224
8
02
3200.003391
104
2000
2200
2500
9000
5300
7300
20000
03
104
2000
2100
1500
9
400
1800
10
1400
8100
11
2750
12
11100
N.T.S
ST-103
5
500
LIFT PIT IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
LEGEND: , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
1500
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
WELL SELECTIVE V:T14@150mm-C/C WELL SELECTIVE
1. WELL SELECTIVE MATERIALS. MATERIALS MATERIALS
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
2. 100MM PLAIN CONCRETE. H:T12@200mm-C/C SLAB COVER.
500
4. 500MM REINFORCED CONCRETE.
5. WATER STOP TAPE.
2000
200 200 200 200
01 SECTION 1-1
S-104 Scale 1:45
300
T12@150mm-C/C T12@150mm-C/C 5
2000
T14@200mm-C/C T14@200mm-C/C
4
3
BALANCE TANK T14@150mm-C/C B.W
T14@150mm-C/C B.W
2
2000
500
SUM PIT
WELL SELECTIVE
1800
MATERIALS V:T14@150mm-C/C
1500
FOUNDATIONS DETAILS
200 200 200 200
02 SECTION 2-2
S-102 Scale 1:45
1:45
ST-104-1
300 300
+1.10 +1.10
400
400
300
25 75
25 75 25 75
500 500
N.G.L N.G.L N.G.L
3750
3750
ARCHITECTURAL DWGS.
3350
3350
3300 2. FOR FURTHER DETAILS REFER TO DWGS.
T14@125mm-C/C T14@200mm-C/C T14@200mm-C/C
5 5 5 S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
4 4 4 COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
3 3 3 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 2 2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
1 1 1 6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
500
500
500
PERFORATED PIPE 4in PERFORATED PIPE 4in
100
100
SOIL SOIL SOIL
1200
1200
ST.T8@150 C/C
300
LEGEND:
X 6T12 T8-150mm
1. WELL SELECTIVE MATERIALS.
200
S-501
decided on site
X SECTION-X-X
S-105 Scale 1:25
2T14
fence grade beam
100
1200 100
FOUNDATIONS DETAILS
BH4
CONCRETE WALL WITH T12@200mm V.H
SHOULD BE CAST AFTER COMPLETING
THE HOLE STRUCTURE
200 200 R2
1 BH4-40x60
1. FOR MORE DETAILS & DIMENSIONS REFER
T12@150mm T12@150mm ARCHITECTURAL DWGS.
150
T12@150mm T12@150mm 2. FOR FURTHER DETAILS REFER TO DWGS.
BH4-40x60
250
1100
S-001 , S-002
R2
300
5500
DB4
DB4
DRAWINGS FOR APPROVAL IN WHICH A FULL
R1 COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
01 SECTION 1-1 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
S-201 Scale 1:40 , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 DB3 DB2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
BH4
BH6
5. SOIL BEARING CAPACITY = 170 KN/m2
2200
DB2
R2 6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
BH4-40x60 SLAB COVER.
3 01
DB3
201 SLAB REINFORCEMENT SLAB REINFORCEMENT
100
AS PER TABLE ABOVE Ø8@250mmBW. R8@250mmBW.
BH4-40x60
BH4-40x60
2Ø12 2Ø12 2Ø12 2Ø12
4700
400
300
Light Weight Materials Light Weight Materials
DB2
DEPTH
5Ø14 5Ø14
4 DB3
200 400 200 400
200 200 Ø8@200mm Ø8@200mm
DB3
2200
R2
R2 TYPICAL SECTION FOR RIB (R1)
R1
5 BH6-40x40
BH4
BH6
SOLID BEAM FROM TWO SIDES
BH1
R2 A secondary transverse rib should be provided at
mid-span ( its direction is perpendicular to the
BH4-40x60 direction of main ribs ) and reinforced with the
5000
BH1
reinforcement shall be 3T14.
BH4-40x60
38750
6
R1
DEPTH
DB2 BH4-40x60
1700
BH4-40x60
100
Ø8@250mmBW. R8@250mmBW.
200 7
2Ø12 2Ø12
BH4
BH1
2500
R1 R1 R1
400
300
Light Weight Materials Light Weight Materials
BH4
PLANTED COLUMN R2
200 400 200 400
Ø8@200mm Ø8@200mm
BH4-40x60
SOLID PART DETAILS PLANTED COLUMN TYPICAL SECTION FOR RIB (R2)
9000
Swimming Pool
Provide Full T & B Mesh :
T12@200MM-C/C
200
100
9 T1
DB3
3000 T1 12
1800
12
1400
11 12
Solid Slab (Thickness 400 mm) 16
2350
T12@150mm c/c (Top & Bottom) 12 BASEMENT COVER SLAB
2750
16
DB3
LAYOUT PLAN
12
12
1:175
ST-201
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
8300
1800
BH4
200
6000 3700
R2
1 BH4-40x60
600 3400 1. FOR MORE DETAILS & DIMENSIONS REFER
500
1700 ARCHITECTURAL DWGS.
600
2. FOR FURTHER DETAILS REFER TO DWGS.
7800
BH4-40x60
S-001 , S-002
R2
5400
R1 3. CONTRACTOR SHOULD SUBMIT THE SHOP
5500
DB4
DB4
DRAWINGS FOR APPROVAL IN WHICH A FULL
R1 COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
300
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 DB3 DB2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
BH4
BH6
5. SOIL BEARING CAPACITY = 170 KN/m2
1700
2000
2200
DB2
R2 6. BACKFILLING WORKS AROUND RETAINING WALLS
100 SHOULD BE DONE AFTER CASTING THE BASEMENT
BH4-40x60 SLAB COVER.
3
1100 DB3
300 4450
BH4-40x60
3100
BH4-40x60
20000
1000
4700
4500
200
3000
DB2
1400
4250
4 DB3
DB3
2200
2000
R2
300
R2 2000
R1
5 BH6-40x40
BH4
BH6
BH1
EL. +1.10
R2
GROUND F.F.L. 300
22300
BH4-40x60
5000
BH1
BH4-40x60
2600
38750
300
6 2000
DB2 BH4-40x60 R1
1700
BH4-40x60
300
900
300
7
BH4
BH1
2500
R1 R1 R1
8 DB3
BH4
1650
300
R2
BH4-40x60
3700
1650
2000
5600
1800
1000
9000
6400
5500
6300
6300
19000
Swimming Pool
3500
4300 2600
9 1675
250
200
DB3
1800
10 DB3 DB3
1400
6600
11
EL. +0.65
YARD BASEMENT COVER SLAB BEAMS
2500
2750
DB3
1:175
ST-202
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
1 DB4 DB4
1. FOR MORE DETAILS & DIMENSIONS REFER
T12@150mm
T12@150mm
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
DB2
DB2
DB4
DB4
S-001 , S-002
300
R1 R1
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
BH6-40x40
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
01 SECTION 1-1 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
S-203 Scale 1:40 , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 BH4-40x60 DB2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
BH4
BH6
BH6-40x40 5. SOIL BEARING CAPACITY = 170 KN/m2
2200
DB4
R2 6. BACKFILLING WORKS AROUND RETAINING WALLS
BH2
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
DB4
3 01
DB3
203 SLAB REINFORCEMENT SLAB REINFORCEMENT
100
AS PER TABLE ABOVE Ø8@250mmBW. R8@250mmBW.
BH4-40x60
BH4-40x60
2Ø12 2Ø12 2Ø12 2Ø12
DB4
4700
BH2-40x60
400
300
Light Weight Materials Light Weight Materials
R2
DEPTH
5Ø14 5Ø14
DB4
4 DB3
200 400 200 400
200 200 Ø8@200mm Ø8@200mm
DB4
DB1
2200
DB1
SOLID BEAM FROM TWO SIDES
DB1
A secondary transverse rib should be provided at
DB4 R1 BH6-40x40
mid-span ( its direction is perpendicular to the
direction of main ribs ) and reinforced with the
5000
DB4
AS PER TABLE ABOVE
same amount of steel as the main ribs. its top
2Ø12 2Ø12 reinforcement shall be 3T14.
DB1
DB1
38750
6 R1
DEPTH
1700
100
DB4
Ø8@250mmBW. R8@250mmBW.
7
DB4
200 2Ø12 2Ø12
DB4
DB4
2500
400
300
Light Weight Materials Light Weight Materials
RIBS DIRECTION
DBC1
9 DB3
1800
11 DB2
Solid Slab (Thickness 400 mm)
DB3
DB3
DB3
LAYOUT PLAN
12 DB3 DB3
1:175
ST-203
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
6300 6300
1 DB4 DB4
1250
1250
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
100 100 2. FOR FURTHER DETAILS REFER TO DWGS.
DB2
DB2
1500
1500
DB4
DB4
S-001 , S-002
450
450
R1 R1
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
3400
DRAWINGS FOR APPROVAL IN WHICH A FULL
BH6-40x40
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
300
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 BH4-40x60 DB2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
BH4
BH6
BH6-40x40 5. SOIL BEARING CAPACITY = 170 KN/m2
2200
DB4
R2 6. BACKFILLING WORKS AROUND RETAINING WALLS
BH2
1400
100 SHOULD BE DONE AFTER CASTING THE BASEMENT
1000
SLAB COVER.
DB4
3
900 DB3
300 4450
BH4-40x60
3100
BH4-40x60
DB4
4700
4500
BH2-40x60
200
3000
R2
1400
24000
24000
4250
DB4
4 DB3
DB4
DB1
2200
2000
300
2000
5 BH6-40x40
DB1
DB1
1700
300
DB4 R1 BH6-40x40
5000
3600
DB4
EL. +5.90
FIRST F.F.L.
4500
4500
DB1
DB1
38750
6 R1
1700
100 100
DB4
DB4
DB4
DB4
2500
2700
2700
8 DB4 DB4
6300 6300
9000
2200
DBC1
9 DB3
1800
3200
DB3
10
1400
6200
6200
11 DB2
1800
DB3
DB3
3000
DB3
2800
1:175
ST-204
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
1 DB4 DB4
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
DB4
DB2
DB2
DB4
S-001 , S-002
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
BH6-40x40
COORDINATION WITH ARCH. & MEP DWGS.
R1
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
BH4
5. SOIL BEARING CAPACITY = 170 KN/m2
2200
DB4
6. BACKFILLING WORKS AROUND RETAINING WALLS
BH2
SHOULD BE DONE AFTER CASTING THE BASEMENT
R1 SLAB COVER.
DB4
3 DB3
SLAB REINFORCEMENT SLAB REINFORCEMENT
100
AS PER TABLE ABOVE Ø8@250mmBW. R8@250mmBW.
R2
BH4-40x60
2Ø12 2Ø12 PLANTED COLUMN 2Ø12 2Ø12
DB4
4700
400
300
BH2-40x60
Light Weight Materials Light Weight Materials
DEPTH
5Ø14 5Ø14
DB4
4 DB3
200 400 200 400
200 200 Ø8@200mm Ø8@200mm
DB4
DB1
2200
R2
TYPICAL SECTION FOR RIB (R1)
5 PLANTED COLUMN BH2-40x60 BH2 BH6-40x40
DB1
SOLID BEAM FROM TWO SIDES
R2 R2
DB1
A secondary transverse rib should be provided at
BH4-40x60 BH4-40x60
DB4
mid-span ( its direction is perpendicular to the
direction of main ribs ) and reinforced with the
DB4
5000
BH6-40x40
AS PER TABLE ABOVE R1
same amount of steel as the main ribs. its top
DB1
DB1
2Ø12 2Ø12 R2 reinforcement shall be 3T14.
38750
1700
100
DB4
Ø8@250mmBW.
7 R8@250mmBW.
200
DB4
R1 2Ø12 2Ø12
R1 R2
DB4
DB4
2500
400
300
Light Weight Materials Light Weight Materials
RIBS DIRECTION
9
1800
11
Solid Slab (Thickness 400 mm)
T12@150mm c/c (Top & Bottom) FIRST COVER SLAB
2750
LAYOUT PLAN
12
1:175
ST-205
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
6300 6300
1 DB4 DB4
1250
1250
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
100 100 2. FOR FURTHER DETAILS REFER TO DWGS.
1500
1500
DB4
DB2
DB2
DB4
S-001 , S-002
450
450
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
3400
DRAWINGS FOR APPROVAL IN WHICH A FULL
BH6-40x40
COORDINATION WITH ARCH. & MEP DWGS.
R1
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 EL. +10.10 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
BH4
SECOND F.F.L. 5. SOIL BEARING CAPACITY = 170 KN/m2
2200
DB4
6. BACKFILLING WORKS AROUND RETAINING WALLS
BH2
300
SHOULD BE DONE AFTER CASTING THE BASEMENT
R1 SLAB COVER.
DB4
3 DB3
4150
1300
R2
BH4-40x60
300 300
DB4
1800
4700
4500
500
BH2-40x60
1400
24000
24000
3950
DB4
4 DB3
DB4
DB1
2200
2000
300
R2
300
100
2000
5 BH2-40x60 BH2 BH6-40x40
1100
1100
DB1
R2 R2
DB1
BH4-40x60 BH4-40x60
DB4
DB4
5000
BH6-40x40
R1
300
DB1
DB1
R2
38750
1200
1200
1200
DB4
DB4
R1 R2 R1
DB4
DB4
2500
9
1800
10
1400
11
12
1:175
ST-206
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
2200
6. BACKFILLING WORKS AROUND RETAINING WALLS
DBC1
SHOULD BE DONE AFTER CASTING THE BASEMENT
DB3 SLAB COVER.
3 DB3
R2 SLAB REINFORCEMENT SLAB REINFORCEMENT
100
AS PER TABLE ABOVE
BH4-40x60
Ø8@250mmBW.
BH5-40x50 R8@250mmBW.
DB2
2Ø12 2Ø12 R2
2Ø12 2Ø12
DB4
4700
DB3
400
BH
300
Light Weight Materials Light Weight Materials
4- BH5-40x50
40
DEPTH
x6 R2 5Ø14 5Ø14
0
DB4
4 R2 DB3
DB3 200 400 200 400
200 200 Ø8@200mm Ø8@200mm
DB4
DB3
DB3
2200
R2
TYPICAL SECTION FOR RIB (R1)
DB3
5 BH4-40x60 DB3 BH4-40x60
SOLID BEAM FROM TWO SIDES
R2
A secondary transverse rib should be provided at
mid-span ( its direction is perpendicular to the
BH4-40x60
BH4-40x60
DB4 BH6
direction of main ribs ) and reinforced with the
DB4
5000
6
DB4 DB4 DB4
DEPTH
1700
100
Ø8@250mmBW.
7 R8@250mmBW.
200 2Ø12 2Ø12
2500
400
300
Light Weight Materials Light Weight Materials
RIBS DIRECTION 9
1800
10
Solid Slab (Thickness 200 mm)
1400
LAYOUT PLAN
12
1:175
ST-207
A B C D E F G
19800
2000 6000 3800 2200 3800 2000
1
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
5500
3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
2 STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
2200
6. BACKFILLING WORKS AROUND RETAINING WALLS
DBC1
10000 SHOULD BE DONE AFTER CASTING THE BASEMENT
DB3 SLAB COVER.
3 DB3
800
R2
2600
750
BH4-40x60
BH5-40x50
DB2
R2
6000
DB4
1800
4700
DB3
BH 3250
4- BH5-40x50
40
x6
1000
0 R2
DB4
4 R2 DB3
DB3
EL. +14.30
DB4
DB3
DB3
2200
2000
R2
12302
ROOF TOP F.F.L.
300
2000
DB3
5 BH4-40x60 DB3 BH4-40x60
9702
1600
300
R2
500
BH4-40x60
BH4-40x60
DB4 BH6
DB4
5000
2000
R1 R1
2300
38750
6
DB4 DB4 DB4
1700
16000
7
2500
8
9000
9
1800
10
1400
11
12
1:175
ST-208
SIZES AND REINFORCEMENT OF DROP BEAMS
DB2 20 60 3Ø14 2Ø14 3Ø14 2Ø14 ....... Ø8@15cm-c/c Ø8@15cm-c/c 2 1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
DB3 20 60 3Ø14 ....... 3Ø14 ....... ....... Ø8@20cm-c/c Ø8@20cm-c/c 2 2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
....... ....... ....... 3. CONTRACTOR SHOULD SUBMIT THE SHOP
DB4 30 60 3Ø16 3Ø16 Ø8@20cm-c/c Ø8@20cm-c/c 2
DRAWINGS FOR APPROVAL IN WHICH A FULL
IN CANTILEVERS TOP REINFORCEMENT COORDINATION WITH ARCH. & MEP DWGS.
DBC1 20 60 3Ø14 ....... 3Ø14 2Ø14 ....... Ø8@20cm-c/c Ø8@20cm-c/c 2 SHOULD BE EXTENT1.5 TIMES IT'S LENGTH IS MADE.
BEYOND THE SUPPORT
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5 4 5 4 5 5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
6T16 3T16 6T16 3T16 6T16 SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
2L-T8@100 2L-T8@100
6T16 6T16
VARIES VARIES
5 4 5 4 5
-- DB1-60X20
--
3T14 2L-T8@200 3T14 2L-T8@200 5T14 2L-T8@200
3 2 3 2 3
5T14 3T14 5T14 3T14 5T14
600
600
600
2L-T8@200 2L-T8@200
1 1
600
600
600
3T14 3T14
2L-T8@200 2L-T8@200
1 1 3
3T16 3T16 5T14
2L-T8@200 2L-T8@200 2L-T8@200 2L-T8@200
BEAMS DETAILS-1
3T16 3T16
VARIES VARIES VARIES VARIES
1 1 3
-- DB4-60X30 -- DBC1-60X20 N.T.S
-- --
ST-301
SIZES AND REINFORCEMENT OF WIDE BEAMS
BH2 60 40 6Ø14 6Ø14 6Ø14 6Ø14 Ø8@10cm-c/c Ø8@10cm-c/c 4 1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
BH3 60 40 6Ø14 2Ø14 6Ø14 2Ø14 Ø8@15cm-c/c Ø8@15cm-c/c 4 2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
3. CONTRACTOR SHOULD SUBMIT THE SHOP
BH4 60 40 6Ø14 ....... 6Ø14 ....... Ø8@15cm-c/c Ø8@15cm-c/c 4 DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
BH5 50 40 5Ø14 ....... 5Ø14 ....... Ø8@15cm-c/c Ø8@15cm-c/c 3 IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
BH6 40 40 4Ø14 ....... 4Ø14 ....... Ø8@15cm-c/c Ø8@15cm-c/c 2 , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
100
100
400
400
400
300
300
300
4LEGT8 4LEGT8 4LEGT8
12T16 12T14 8T14
100
100
400
400
400
300
300
300
4LEGT8 3LEGT8 2LEGT8
6T14 5T14 4T14
BEAMS DETAILS-2
N.T.S
ST-302
6 x 300=1800 1450
200
T14@150
3T16
T12@200 T14@200
220
7x150=1050
600
1. FOR MORE DETAILS & DIMENSIONS REFER
T14@150 2L-T8@150
T12@200 ARCHITECTURAL DWGS.
2. FOR FURTHER DETAILS REFER TO DWGS.
T14@200 5T16
220
S-001 , S-002
RAFT REINF. 3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
D E F 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
01 SECTION-1 5. SOIL BEARING CAPACITY = 170 KN/m2
2200 3800 6. BACKFILLING WORKS AROUND RETAINING WALLS
S-401 Scale 1:45 SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
3
01 02 03 04 05 06 07 08
01
UP
401
09
7x150=1050
4700
T14@150
T12@200 11
T14@150
220
CR 12
ANK T14@200
BEA
M 13
14
T14@250
02 SECTION-2 03
S-401 Scale 1:45
401
25 24 23 22 21 20 19 18 17 16 15
4
02
401
10 x 300=3000 1350
SLAB REINF.
T14@100
T12@200
11x150=1650
3T16
0
22
T12@200
T14@100
200
R8@150
600
T14@150
3T16
220
ST-401
11x300=3300 1450
200
T14@150
3T16
T14@100
240
T12@200
600
T14@100 2L-T8@150
12x160=1920
5T16
24
0
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
SLAB REINF. IS MADE.
D E F 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
01 SECTION-1 2200 3800
6. BACKFILLING WORKS AROUND RETAINING WALLS
SHOULD BE DONE AFTER CASTING THE BASEMENT
S-402 Scale 1:45 SLAB COVER.
3
01 02 03 04 05 06 07 08 09 10 11 12
UP
T14@100
402
7x160=1120
T14@150 13
14
CR
24
ANK
240
BEA T14@100 15
4700
M
3T16
T12@200 16
T14@150 17
18
02 SECTION-2 19
S-402 Scale 1:45
03
402
30 29 28 27 26 25 24 23 22 21 20
4
10 x 300 = 3000 1550
SLAB REINF.
02
402
T14@100
T12@200
11x160=1760
T12@200
0
24
T14@100 3T16
T14@150
T12@200
3T16
R8@150
600
240
600
T14@100 2L-T8@150
03 SECTION-3 GROUND STAIRCASE DETAILS
S-402 Scale 1:45 5T16
200
5T16
- CRANK BEAM
- Scale 1:25
N.T.S
ST-402
10 x 300=3000 1450
200
T14@150
3T16
T14@100
220
T12@200
600
T14@150 2L-T8@150
1. FOR MORE DETAILS & DIMENSIONS REFER
11x150=1650
ARCHITECTURAL DWGS.
5T16
2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
T12@200 3. CONTRACTOR SHOULD SUBMIT THE SHOP
DRAWINGS FOR APPROVAL IN WHICH A FULL
T14@100 COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
SLAB REINF. 4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
D E F , BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
5. SOIL BEARING CAPACITY = 170 KN/m2
01 6. BACKFILLING WORKS AROUND RETAINING WALLS
SECTION-1 SHOULD BE DONE AFTER CASTING THE BASEMENT
2200 3800
S-403 Scale 1:45 SLAB COVER.
3
01 02 03 04 05 06 07 08 09 10 11
01
UP
403
14
4700
7x150=1050
T14@150
T12@200 15
T14@150
220
CR 16
ANK T14@100
BEA
M 17
18
T14@150
02 SECTION-2 03
S-403 Scale 1:45 403
28 27 26 25 24 23 22 21 20 19
4
02
403
9 x 300=2700 1300
SLAB REINF.
T14@150
T12@200
10x150=1500
3T16
T12@200
220
T14@150 R8@150
600
200
T14@150
3T16
FIRST STAIRCASE DETAILS
220
600
T14@150 2L-T8@150
200
03 SECTION-3 5T16
S-403 Scale 1:45 5T16 - CRANK BEAM
- Scale 1:25
N.T.S
ST-403
B C
2750
SHOULD BE DONE AFTER CASTING THE BASEMENT
SLAB COVER.
2499.92
19 18 17 16 15 14 13 12 11
UP 02
404
12
9 x 300=2700 1200
9 x 300=2700 1250
200
T14@150 SLAB REINF.
3T16
T14@200
220
T14@150
T12@200 T12@200
600
T14@200 2L-T8@150
10x150=1500
10x150=1500
3T16
T12@200 T12@200
220
T14@200 T14@150
200
SLAB REINF. T14@150
3T16
220
600
T14@150 2L-T8@150
03 SECTION-3
01 SECTION-1 3T16
S-404 Scale 1:45 3T16
S-404 Scale 1:45
R8@150
600
ST-404
A
4000~7000 4000~7000
250 3Layer of Bitumen 250 250 250
200
250
1. FOR MORE DETAILS & DIMENSIONS REFER
ARCHITECTURAL DWGS.
200 200 2. FOR FURTHER DETAILS REFER TO DWGS.
S-001 , S-002
25CM 3. CONTRACTOR SHOULD SUBMIT THE SHOP
2000~3000
2000~3000
DRAWINGS FOR APPROVAL IN WHICH A FULL
COORDINATION WITH ARCH. & MEP DWGS.
IS MADE.
4. CONCRETE STRENGTH = 35 N/mm2 FOR COLUMN
, BEAMS, STAIRS ,SLABS, FOUNDATION & WALLS
STRENGTH FOR PLAIN CONCRETE = 20 N/mm2
200 200 5. SOIL BEARING CAPACITY = 170 KN/m2
6. BACKFILLING WORKS AROUND RETAINING WALLS
B B T12@150mmC/ C-TOP &BOTTOM SHOULD BE DONE AFTER CASTING THE BASEMENT
200
200
SLAB COVER.
300
BLOCK WALL
TYPICAL WATER TANK PLAN A TYPICAL WATER TANK COVER SLAB
2000~3000 4000~7000
250 250 250
250
500
WATER LEVEL WATER LEVEL
500
T12@150C/C T12@150C/C
MIN.2500
2500
T12@150C/C T12@150C/C
FOR PIPES AND PUMP ACCESSORIES FOR PIPES AND PUMP ACCESSORIES
T14@150C/C T14@150C/C T14@150C/C T14@150C/C T14@150C/C
T14@150C/C T12@150C/C
200
T14@150 C/C TYP WATER BAR T14@150 C/C TYP WATER BAR
T14@150 C/C T14@150 C/C T14@150 C/C T14@150 C/C
400
400
100
100
T14@150 C/C, B.W. T14@150 C/C, B.W. T14@150 C/C, B.W. T14@150 C/C, B.W.
250 250
250 250
SECTION A-A SECTION B-B
250
300
2D
300
400
ST-501