Data sheet 3UG4651-1AW30
Digital monitoring relay Speed monitoring from 0.1 to 2200 rpm Overshoot
and undershoot 24 to 240 V AC/DC 50 to 60 Hz DC and AC ON delay 1 to
900 s Tripping delay 0.1 to 99.9 s Hysteresis 0.1 to 99 rpm 1 change-over
contact with or without fault buffer screw terminal Successor product for
3UG3051
product brand name SIRIUS
product designation Speed monitoring relay with digital setting
product type designation 3UG4
General technical data
product function RPM monitoring relay
design of the display LCD
● apparent power consumption at AC
— at 24 V maximum 4 VA
— at 240 V maximum 9 VA
insulation voltage
● for overvoltage category III according to IEC
60664
— with degree of pollution 3 rated value 300 V
degree of pollution 3
type of voltage of the control supply voltage AC/DC
surge voltage resistance rated value 4 kV
protection class IP IP20
shock resistance according to IEC 60068-2-27 sinusoidal half-wave 15g / 11 ms
mechanical service life (operating cycles) typical 10 000 000
electrical endurance (operating cycles) at AC-15 at 100 000
230 V typical
reference code according to IEC 81346-2 K
relative repeat accuracy 1%
Substance Prohibitance (Date) 05/01/2012
Product Function
product function
● standstill monitoring No
● rotation speed monitoring Yes
● error memory Yes
● adjustable open/closed-circuit current principle Yes
● external reset Yes
● auto-RESET Yes
● manual RESET Yes
suitability for use safety-related circuits No
Control circuit/ Control
control supply voltage at AC
● at 50 Hz rated value 24 ... 240 V
● at 60 Hz rated value 24 ... 240 V
control supply voltage at DC
● rated value 24 ... 240 V
operating range factor control supply voltage rated
value at DC
3UG46511AW30 Subject to change without notice
2/10/2023
Page 1/4 © Copyright Siemens
● initial value 0.8
● full-scale value 1.1
operating range factor control supply voltage rated
value at AC at 50 Hz
● initial value 1.1
● full-scale value 0.8
operating range factor control supply voltage rated
value at AC at 60 Hz
● initial value 1.1
● full-scale value 0.8
Measuring circuit
measurable line frequency 50 ... 60 Hz
adjustable response delay time
● when starting 1 ... 900 s
● with lower or upper limit violation 0.1 ... 99.9 s
buffering time in the event of power failure minimum 10 ms
accuracy of digital display +/- 1 Digit
Precision
relative metering precision 10 %
Auxiliary circuit
number of NC contacts delayed switching 0
number of NO contacts delayed switching 0
number of CO contacts delayed switching 1
operating frequency with 3RT2 contactor maximum 5 000 1/h
Inputs/ Outputs
design of input feedback input No
number of outputs as contact-affected switching
element
● for signaling function
— instantaneous contact 0
— delayed switching 1
● safety-related
— delayed switching 0
— instantaneous contact 0
number of outputs as contact-less semiconductor
switching element
● for signaling function
— delayed switching 0
— instantaneous contact 0
● safety-related
— delayed switching 0
— instantaneous contact 0
ampacity of the output relay at AC-15
● at 250 V at 50/60 Hz 3A
ampacity of the output relay at DC-13
● at 24 V 1A
● at 125 V 0.2 A
● at 250 V 0.1 A
operational current at 17 V minimum 5 mA
continuous current of the DIAZED fuse link of the 4A
output relay
Electromagnetic compatibility
conducted interference
● due to burst according to IEC 61000-4-4 2 kV
● due to conductor-earth surge according to IEC 2 kV
61000-4-5
● due to conductor-conductor surge according to IEC 1 kV
61000-4-5
field-based interference according to IEC 61000-4-3 10 V/m
electrostatic discharge according to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge
Galvanic isolation
galvanic isolation
● between input and output Yes
● between the outputs No
3UG46511AW30 Subject to change without notice
2/10/2023
Page 2/4 © Copyright Siemens
Safety related data
Safety Integrity Level (SIL) according to IEC 61508 without
Connections/ Terminals
product component removable terminal for auxiliary Yes
and control circuit
type of electrical connection screw-type terminals
type of connectable conductor cross-sections
● solid 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2)
● finely stranded with core end processing 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at AWG cables solid 2x (20 ... 14)
● at AWG cables stranded 2x (20 ... 14)
connectable conductor cross-section
● solid 0.5 ... 4 mm²
● finely stranded with core end processing 0.5 ... 2.5 mm²
AWG number as coded connectable conductor cross
section
● solid 20 ... 14
● stranded 20 ... 14
tightening torque with screw-type terminals 0.8 ... 1.2 N·m
Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting
height 86 mm
width 22.5 mm
depth 102 mm
required spacing
● with side-by-side mounting
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— at the side 0 mm
— downwards 0 mm
● for live parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -25 ... +60 °C
● during storage -40 ... +80 °C
● during transport -40 ... +80 °C
Certificates/ approvals
Declaration of
General Product Approval EMC
Conformity
Confirmation
Declaration of
Test Certificates Marine / Shipping other
Conformity
3UG46511AW30 Subject to change without notice
2/10/2023
Page 3/4 © Copyright Siemens
Type Test Certific- Special Test Certific- Confirmation
ates/Test Report ate
Railway
Vibration and Shock
Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3UG4651-1AW30
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3UG4651-1AW30
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3UG4651-1AW30
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3UG4651-1AW30&lang=en
Characteristic: Derating
https://support.industry.siemens.com/cs/ww/en/ps/3UG4651-1AW30/manual
last modified: 1/25/2022
3UG46511AW30 Subject to change without notice
2/10/2023
Page 4/4 © Copyright Siemens