Error Code VRV
Error Code VRV
k: ON h: OFF l: Blink
Error code Operation Error contents Reference
lamp page
System U0 k Refrigerant shortage 263
U1 l Open phase 264
U2 l Power supply insufficient or instantaneous abnormality 265
U3 l Check operation not executed 267
U4 l Transmission error between indoor units and outdoor units 268
U5 l Transmission error between remote controller and indoor unit 271
U7 l Transmission error between outdoor units 272
U8 l Transmission error between main and sub remote controllers 277
U9 l Transmission error between indoor unit and outdoor unit in the same system 278
UA l Improper combination of indoor unit and outdoor unit, indoor unit and remote 279
controller
UC k Address duplication of centralized controller 282
UE l Transmission error between centralized controller and indoor unit 283
UF l System not set yet 285
UH l System abnormality, refrigerant system address undefined 286
The system operates for error codes indicated in black squares, however, be sure to check and repair.
Troubleshooting
Error code
Description of error Description of diagnosis
E9 - 01 Electronic expansion valve coil Y1E error (Master)
E9 - 03 Electronic expansion valve coil Y2E error (Master)
E9 - 05 Electronic expansion valve coil Y1E error (Slave 1)
E9 - 06 Electronic expansion valve coil Y2E error (Slave 1)
E9 - 08 Electronic expansion valve coil Y1E error (Slave 2)
E9 - 09 Electronic expansion valve coil Y2E error (Slave 2)
E9 - 26 Electronic expansion valve coil Y4E error (Master)
E9 - 27 Electronic expansion valve coil Y4E error (Slave 1)
E9 - 28 Electronic expansion valve coil Y4E error (Slave 2) Refer to the E9 flowchart of each manual and make a diagnosis
of the relevant electronic expansion valve of the relevant unit
E9 - 48 Electronic expansion valve overcurrent (Master) based on the Error code shown to the left.
E9 - 49 Electronic expansion valve overcurrent (Slave 1)
E9 - 50 Electronic expansion valve overcurrent (Slave 2)
E9 - 51 Electronic expansion valve fuse thermal cutting (Master)
E9 - 52 Electronic expansion valve fuse thermal cutting (Slave 1)
E9 - 53 Electronic expansion valve fuse thermal cutting (Slave 2)
E9 - 54 Defective circuit (Master)
E9 - 55 Defective circuit (Slave 1)
E9 - 56 Defective circuit (Slave 2)
F3 - 01 Discharge pipe high temperature error (Master)
F3 - 03 Discharge pipe high temperature error (Slave 1)
F3 - 05 Discharge pipe high temperature error (Slave 2) Refer to the F3 flowchart of each manual and make a diagnosis
F3 - 20 Compressor overheat error (Master) of the relevant unit based on the Error code shown to the left.
F3 - 21 Compressor overheat error (Slave 1)
F3 - 22 Compressor overheat error (Slave 2)
F4 - 02 Wet alarm for inverter compressor M1C (Master)
F4 - 03 Wet alarm for inverter compressor M2C (Master)
F4 - 04 Wet alarm for inverter compressor M1C (Slave 1)
F4 - 05 Wet alarm for inverter compressor M2C (Slave 1)
F4 - 06 Wet alarm for inverter compressor M1C (Slave 2)
F4 - 07 Wet alarm for inverter compressor M2C (Slave 2)
F4 - 08 Wet error for inverter compressor M1C (Master) Refer to the F4 flowchart of each manual and make a diagnosis
of the relevant unit based on the Error code shown to the left.
F4 - 09 Wet error for inverter compressor M2C (Master)
F4 - 10 Wet error for inverter compressor M1C (Slave 1)
F4 - 11 Wet error for inverter compressor M2C (Slave 1)
F4 - 12 Wet error for inverter compressor M1C (Slave 2)
F4 - 13 Wet error for inverter compressor M2C (Slave 2)
F4 - 14 Indoor unit failure alarm
Troubleshooting
Error code
Description of error Description of diagnosis
F6 - 02 Excess refrigerant charge error Excess refrigerant charge was detected during test run.
F6 - 03 Excess refrigerant charge warning Excess refrigerant charge was detected during operation other
than test run.
H3 - 02 Connection error between main PCB and
inverter PCB 1 (Master)
H3 - 03 Connection error between main PCB and
inverter PCB 2 (Master)
H3 - 04 Connection error between main PCB and
inverter PCB 1 (Slave 1) Refer to the H3 flowchart of each manual and make a diagnosis
H3 - 05 Connection error between main PCB and of the relevant unit based on the Error code shown to the left.
inverter PCB 2 (Slave 1)
H3 - 06 Connection error between main PCB and
inverter PCB 1 (Slave 2)
H3 - 07 Connection error between main PCB and
inverter PCB 2 (Slave 2)
H7 - 21 Defective fan PCB for M1F (A7P) (Master)
H7 - 22 Defective fan PCB for M2F (A4P) (Master)
H7 - 23 Defective fan PCB for M1F (A7P) (Slave 1) Refer to the H7 flowchart of each manual and make a diagnosis
H7 - 24 Defective fan PCB for M2F (A4P) (Slave 1) of the relevant unit based on the Error code shown to the left.
H7 - 25 Defective fan PCB for M1F (A7P) (Slave 2)
H7 - 26 Defective fan PCB for M2F (A4P) (Slave 2)
H9 - 01 Defective outdoor air thermistor (Master)
Refer to the H9 flowchart of each manual and make a diagnosis
H9 - 02 Defective outdoor air thermistor (Slave 1) of the relevant unit based on the Error code shown to the left.
H9 - 03 Defective outdoor air thermistor (Slave 2)
J3 - 16 Defective discharge pipe 1 thermistor: Open
(Master)
J3 - 17 Defective discharge pipe 1 thermistor: Short
(Master)
J3 - 18 Defective discharge pipe 2 thermistor: Open
(Master)
J3 - 19 Defective discharge pipe 2 thermistor: Short
(Master)
J3 - 22 Defective discharge pipe 1 thermistor: Open
(Slave 1)
J3 - 23 Defective discharge pipe 1 thermistor: Short
(Slave 1)
J3 - 24 Defective discharge pipe 2 thermistor: Open
(Slave 1)
J3 - 25 Defective discharge pipe 2 thermistor: Short
(Slave 1)
J3 - 28 Defective discharge pipe 1 thermistor: Open
(Slave 2) Refer to the J3 flowchart of each manual and make a diagnosis
of the relevant compressor of the relevant unit based on the Error
J3 - 29 Defective discharge pipe 1 thermistor: Short code shown to the left.
(Slave 2)
J3 - 30 Defective discharge pipe 2 thermistor: Open
(Slave 2)
J3 - 31 Defective discharge pipe 2 thermistor: Short
(Slave 2)
J3 - 38 Defective compressor body thermistor for
M1C: Open (Master)
J3 - 39 Defective compressor body thermistor for
M1C: Short (Master)
J3 - 42 Defective compressor body thermistor for
M1C: Open (Slave 1)
J3 - 43 Defective compressor body thermistor for
M1C: Short (Slave 1)
J3 - 44 Defective compressor body thermistor for
M1C: Open (Slave 2)
J3 - 45 Defective compressor body thermistor for
M1C: Short (Slave 2)
Troubleshooting
Error code
Description of error Description of diagnosis
J3 - 47 Defective compressor body thermistor for
M2C: Open (Master)
J3 - 48 Defective compressor body thermistor for
M2C: Short (Master)
J3 - 49 Defective compressor body thermistor for
M2C: Open (Slave 1)
J3 - 50 Defective compressor body thermistor for Refer to the J3 flowchart of each manual and make a diagnosis
M2C: Short (Slave 1) of the relevant compressor of the relevant unit based on the Error
J3 - 51 Defective compressor body thermistor for code shown to the left.
M2C: Open (Slave 2)
J3 - 52 Defective compressor body thermistor for
M2C: Short (Slave 2)
J3 - 56 Discharge pipe warning (Master)
J3 - 57 Discharge pipe warning (Slave 1)
J3 - 58 Discharge pipe warning (Slave 2)
J5 - 01 Defective suction pipe thermistor (Master) Refer to the J5 flowchart of each manual and make a diagnosis
J5 - 03 Defective suction pipe thermistor (Slave 1) of the relevant thermistor of the relevant unit based on the Error
code shown to the left.
J5 - 05 Defective suction pipe thermistor (Slave 2)
J7 - 06 Defective subcooling heat exchanger liquid
pipe thermistor (Master)
Refer to the J7 flowchart of each manual and make a diagnosis
J7 - 07 Defective subcooling heat exchanger liquid of the relevant thermistor based on the Error code shown to the
pipe thermistor (Slave 1) left.
J7 - 08 Defective subcooling heat exchanger liquid
pipe thermistor (Slave 2)
J8 - 01 Defective heat exchanger liquid pipe
thermistor (Master)
J8 - 02 Defective heat exchanger liquid pipe Refer to the J8 flowchart of each manual and make a diagnosis
thermistor (Slave 1) of the relevant thermistor of the relevant unit based on the Error
code shown to the left.
J8 - 03 Defective heat exchanger liquid pipe
thermistor (Slave 2)
J9 - 01 Defective subcooling heat exchanger outlet
thermistor (Master)
J9 - 02 Defective subcooling heat exchanger outlet
thermistor (Slave 1)
J9 - 03 Defective subcooling heat exchanger outlet
thermistor (Slave 2) Refer to the J9 flowchart of each manual and make a diagnosis
of the relevant thermistor based on the Error code shown to the
J9 - 08 Error detection of subcooling heat left.
exchanger outlet pipe thermistor (Master)
J9 - 09 Error detection of subcooling heat
exchanger outlet pipe thermistor (Slave 1)
J9 - 10 Error detection of subcooling heat
exchanger outlet pipe thermistor (Slave 2)
JA - 06 Defective high pressure sensor: Open
(Master)
JA - 07 Defective high pressure sensor: Short
(Master)
JA - 08 Defective high pressure sensor: Open
(Slave 1) Refer to the JA flowchart of each manual and make a diagnosis
JA - 09 Defective high pressure sensor: Short of the relevant sensor based on the Error code shown to the left.
(Slave 1)
JA - 10 Defective high pressure sensor: Open
(Slave 2)
JA - 11 Defective high pressure sensor: Short
(Slave 2)
JC - 06 Defective low pressure sensor: Open (Master)
JC - 07 Defective low pressure sensor: Short (Master)
JC - 08 Defective low pressure sensor: Open (Slave 1) Refer to the JC flowchart of each manual and make a diagnosis
JC - 09 Defective low pressure sensor: Short (Slave 1) of the relevant sensor based on the Error code shown to the left.
JC - 10 Defective low pressure sensor: Open (Slave 2)
JC - 11 Defective low pressure sensor: Short (Slave 2)
Troubleshooting
Error code
Description of error Description of diagnosis
L1 - 01 IPM error: Inverter compressor M1C
(Master)
L1 - 02 Defective current sensor: Inverter
compressor M1C (Master)
L1 - 03 Current offset: Inverter compressor M1C
(Master)
L1 - 04 IGBT error: Inverter compressor M1C
(Master)
L1 - 05 Jumper settings error: Inverter compressor
M1C (Master)
L1 - 07 IPM error: Inverter compressor M1C (Slave 1) The inverter PCB may be defective or a PCB other than the
L1 - 08 Defective current sensor: Inverter specified is mounted.
compressor M1C (Slave 1) Refer to the L1 flowchart of each manual and make a diagnosis
of the relevant unit based on the Error code shown to the left.
L1 - 09 Current offset: Inverter compressor M1C
(Slave 1)
L1 - 10 IGBT error: Inverter compressor M1C
(Slave 1)
L1 - 11 IPM error: Inverter compressor M1C (Slave 2)
L1 - 12 Defective current sensor: Inverter
compressor M1C (Slave 2)
L1 - 13 Current offset: Inverter compressor M1C
(Slave 2)
L1 - 14 IGBT error: Inverter compressor M1C
(Slave 2)
L1 - 15 Jumper settings error: Inverter compressor
M1C (Slave 1)
L1 - 16 Jumper settings error: Inverter compressor
M1C (Slave 2)
L1 - 17 IPM error: Inverter compressor M2C
(Master)
L1 - 18 Defective current sensor: Inverter
compressor M2C (Master)
L1 - 19 Current offset: Inverter compressor M2C
(Master)
L1 - 20 IGBT error: Inverter compressor M2C
(Master)
L1 - 21 Jumper settings error: Inverter compressor
M2C (Master)
L1 - 22 IPM error: Inverter compressor M2C (Slave 1)
L1 - 23 Defective current sensor: Inverter
compressor M2C (Slave 1) The inverter PCB may be defective or a PCB other than the
specified is mounted.
L1 - 24 Current offset: Inverter compressor M2C Refer to the L1 flowchart of each manual and make a diagnosis
(Slave 1) of the relevant unit based on the Error code shown to the left.
L1 - 25 IGBT error: Inverter compressor M2C
(Slave 1)
L1 - 26 Jumper settings error: Inverter compressor
M2C (Slave 1)
L1 - 36 EEPROM abnormality: Inverter compressor
M1C (Master)
L1 - 37 EEPROM abnormality: Inverter compressor
M2C (Master)
L1 - 38 EEPROM abnormality: Inverter compressor
M1C (Slave 1)
L1 - 39 EEPROM abnormality: Inverter compressor
M2C (Slave 1)
L1 - 40 EEPROM abnormality: Inverter compressor
M1C (Slave 2)
L1 - 41 EEPROM abnormality: Inverter compressor
M2C (Slave 2)
Troubleshooting
Error code
Description of error Description of diagnosis
L1 - 42 IPM error: Inverter compressor M2C (Slave 2)
L1 - 43 Defective current sensor: Inverter
compressor M2C (Slave 2)
L1 - 44 Current offset: Inverter compressor M2C
(Slave 2)
L1 - 45 IGBT error: Inverter compressor M2C
(Slave 2)
L1 - 46 Jumper settings error: Inverter compressor
M2C (Slave 2)
The inverter PCB may be defective or a PCB other than the
L1 - 47 Power supply voltage abnormality: Inverter specified is mounted.
compressor M1C (Master) Refer to the L1 flowchart of each manual and make a diagnosis
L1 - 48 Power supply voltage abnormality: Inverter of the relevant unit based on the Error code shown to the left.
compressor M2C (Master)
L1 - 49 Power supply voltage abnormality: Inverter
compressor M1C (Slave 1)
L1 - 50 Power supply voltage abnormality: Inverter
compressor M2C (Slave 1)
L1 - 51 Power supply voltage abnormality: Inverter
compressor M1C (Slave 2)
L1 - 52 Power supply voltage abnormality: Inverter
compressor M2C (Slave 2)
L2 - 01 Momentary power failure (Master)
L2 - 02 Momentary power failure (Slave 1)
L2 - 03 Momentary power failure (Slave 2) Refer to the L2 flowchart of each manual and make a diagnosis
L2 - 04 Power ON (Master) of the relevant unit based on the Error code shown to the left.
L2 - 05 Power ON (Slave 1)
L2 - 06 Power ON (Slave 2)
L4 - 01 Radiation fin temperature rise: Inverter PCB
for M1C (Master)
L4 - 02 Radiation fin temperature rise: Inverter PCB
for M1C (Slave 1)
L4 - 03 Radiation fin temperature rise: Inverter PCB
for M1C (Slave 2)
L4 - 06 Radiation fin temperature rise: Fan M1F
(Master)
L4 - 07 Radiation fin temperature rise: Fan M2F
(Master)
L4 - 09 Radiation fin temperature rise: Inverter PCB
for M2C (Master) Refer to the L4 flowchart of each manual and make a diagnosis
L4 - 10 Radiation fin temperature rise: Inverter PCB of the relevant unit based on the Error code shown to the left.
for M2C (Slave 1)
L4 - 11 Radiation fin temperature rise: Inverter PCB
for M2C (Slave 2)
L4 - 18 Radiation fin temperature rise: Fan M1F
(Slave 1)
L4 - 19 Radiation fin temperature rise: Fan M2F
(Slave 1)
L4 - 20 Radiation fin temperature rise: Fan M1F
(Slave 2)
L4 - 21 Radiation fin temperature rise: Fan M2F
(Slave 2)
Troubleshooting
Error code
Description of error Description of diagnosis
L5 - 03 Current offset error (Master)
L5 - 05 Current offset error (Slave 1)
L5 - 07 Current offset error (Slave 2)
L5 - 14 Inverter compressor M2C instantaneous Refer to the L5 flowchart of each manual and make a diagnosis
overcurrent (Master) of the relevant unit based on the Error code shown to the left.
L5 - 15 Inverter compressor M2C instantaneous
overcurrent (Slave 1)
L5 - 16 Inverter compressor M2C instantaneous
overcurrent (Slave 2)
L8 - 03 Inverter compressor M1C overcurrent error
(Master)
L8 - 06 Inverter compressor M1C overcurrent error
(Slave 1)
L8 - 07 Inverter compressor M1C overcurrent error
(Slave 2) Refer to the L8 flowchart of each manual and make a diagnosis
of the relevant compressor of the relevant unit based on the Error
L8 - 11 Inverter compressor M2C overcurrent error code shown to the left.
(Master)
L8 - 12 Inverter compressor M2C overcurrent error
(Slave 1)
L8 - 13 Inverter compressor M2C overcurrent error
(Slave 2)
L9 - 01 Inverter compressor M1C startup error
(Master)
L9 - 05 Inverter compressor M1C startup error
(Slave 1)
L9 - 06 Inverter compressor M1C startup error
(Slave 2)
L9 - 10 Inverter compressor M2C startup error
(Master)
L9 - 11 Inverter compressor M2C startup error
(Slave 1)
L9 - 12 Inverter compressor M2C startup error
(Slave 2) Refer to the L9 flowchart of each manual and make a diagnosis
of the relevant compressor of the relevant unit based on the Error
L9 - 13 Inverter compressor M1C output open code shown to the left.
phase (Master)
L9 - 14 Inverter compressor M1C output open
phase (Slave 1)
L9 - 15 Inverter compressor M1C output open
phase (Slave 2)
L9 - 16 Inverter compressor M2C output open
phase (Master)
L9 - 17 Inverter compressor M2C output open
phase (Slave 1)
L9 - 18 Inverter compressor M2C output open
phase (Slave 2)
Troubleshooting
Error code
Description of error Description of diagnosis
LC - 14 Transmission error (Between outdoor units,
inverter PCB 1) (Master)
LC - 15 Transmission error (Between outdoor units,
inverter PCB 1) (Slave 1)
LC - 16 Transmission error (Between outdoor units,
inverter PCB 1) (Slave 2)
LC - 19 Transmission error (Between outdoor units,
fan PCB 1) (Master)
LC - 20 Transmission error (Between outdoor units,
fan PCB 1) (Slave 1)
LC - 21 Transmission error (Between outdoor units,
fan PCB 1) (Slave 2) Refer to the LC flowchart of each manual and make a diagnosis
LC - 24 Transmission error (Between outdoor units, of the relevant unit based on the Error code shown to the left.
fan PCB 2) (Master)
LC - 25 Transmission error (Between outdoor units,
fan PCB 2) (Slave 1)
LC - 26 Transmission error (Between outdoor units,
fan PCB 2) (Slave 2)
LC - 30 Transmission error (Between outdoor units,
inverter PCB 2) (Master)
LC - 31 Transmission error (Between outdoor units,
inverter PCB 2) (Slave 1)
LC - 32 Transmission error (Between outdoor units,
inverter PCB 2) (Slave 2)
P1 - 01 Unbalanced power supply voltage (Master)
P1 - 02 Unbalanced power supply voltage (Slave 1)
P1 - 03 Unbalanced power supply voltage (Slave 2)
P1 - 07 Inverter 2 power supply unbalanced voltage Refer to the P1 flowchart of each manual and make a diagnosis
(Master) of the relevant unit based on the Error code shown to the left.
P1 - 08 Inverter 2 power supply unbalanced voltage
(Slave 1)
P1 - 09 Inverter 2 power supply unbalanced voltage
(Slave 2)
P3 - 01 Defective reactor thermistor 1 (Master:
Inverter PCB 1)
P3 - 02 Defective reactor thermistor 1 (Slave 1:
Inverter PCB 1)
P3 - 03 Defective reactor thermistor 1 (Slave 2:
Inverter PCB 1)
P3 - 04 Defective reactor thermistor 2 (Master:
Inverter PCB 1)
P3 - 05 Defective reactor thermistor 2 (Slave 1:
Inverter PCB 1)
P3 - 06 Defective reactor thermistor 2 (Slave 2:
Inverter PCB 1) Refer to the P3 flowchart of each manual and make a diagnosis
P3 - 07 Defective reactor thermistor 1 (Master: of the relevant unit based on the Error code shown to the left.
Inverter PCB 2)
P3 - 08 Defective reactor thermistor 1 (Slave 1:
Inverter PCB 2)
P3 - 09 Defective reactor thermistor 1 (Slave 2:
Inverter PCB 2)
P3 - 10 Defective reactor thermistor 2 (Master:
Inverter PCB 2)
P3 - 11 Defective reactor thermistor 2 (Slave 1:
Inverter PCB 2)
P3 - 12 Defective reactor thermistor 2 (Slave 2:
Inverter PCB 2)
Troubleshooting
Error code
Description of error Description of diagnosis
P4 - 01 Defective radiation fin thermistor (Master:
Inverter PCB 1)
P4 - 02 Defective fan M1F fin sensor (Master)
P4 - 03 Defective fan M2F fin sensor (Master)
P4 - 04 Defective radiation fin thermistor (Slave 1:
Inverter PCB 1)
P4 - 05 Defective radiation fin thermistor (Slave 2:
Inverter PCB 1)
P4 - 06 Defective radiation fin thermistor (Master: Refer to the P4 flowchart of each manual and make a diagnosis
Inverter PCB 2) of the relevant unit based on the Error code shown to the left.
P4 - 07 Defective radiation fin thermistor (Slave 1:
Inverter PCB 2)
P4 - 08 Defective radiation fin thermistor (Slave 2:
Inverter PCB 2)
P4 - 15 Defective fan M1F fin sensor (Slave 1)
P4 - 16 Defective fan M2F fin sensor (Slave 1)
P4 - 17 Defective fan M1F fin sensor (Slave 2)
P4 - 18 Defective fan M2F fin sensor (Slave 2)
PJ - 04 Incorrect type of inverter PCB 1 (Master)
PJ - 05 Incorrect type of inverter PCB 1 (Slave 1)
PJ - 06 Incorrect type of inverter PCB 1 (Slave 2)
PJ - 09 Incorrect type of fan PCB 1 (Master)
PJ - 10 Incorrect type of fan PCB 2 (Master)
PJ - 12 Incorrect type of inverter PCB 2 (Master) Refer to the PJ flowchart of each manual and make a diagnosis
PJ - 13 Incorrect type of inverter PCB 2 (Slave 1) of the relevant unit based on the Error code shown to the left.
PJ - 14 Incorrect type of inverter PCB 2 (Slave 2)
PJ - 15 Incorrect type of fan PCB 1 (Slave 1)
PJ - 16 Incorrect type of fan PCB 1 (Slave 2)
PJ - 17 Incorrect type of fan PCB 2 (Slave 1)
PJ - 18 Incorrect type of fan PCB 2 (Slave 2)
U0 - 05 Refrigerant shortage warning (cooling)
U0 - 06 Refrigerant shortage warning (heating)
U0 - 08 Refrigerant shortage (Master) Refer to the U0 flowchart of each manual and make a diagnosis
of the relevant unit based on the Error code shown to the left.
U0 - 09 Refrigerant shortage (Slave 1)
U0 - 10 Refrigerant shortage (Slave 2)
U1 - 16 Open phase for power supply (Master)
U1 - 17 Open phase for power supply (Slave 1)
U1 - 18 Open phase for power supply (Slave 2) Refer to the U1 flowchart of each manual and make a diagnosis
U1 - 19 Hz error for power supply (Master) of the relevant unit based on the Error code shown to the left.
U1 - 20 Hz error for power supply (Slave 1)
U1 - 21 Hz error for power supply (Slave 2)
U2 - 01 Shortage of inverter power supply voltage (Master)
U2 - 08 Shortage of inverter power supply voltage (Slave 1)
U2 - 11 Shortage of inverter power supply voltage (Slave 2) Refer to the U2 flowchart of each manual and make a diagnosis
U2 - 22 Shortage of inverter 2 power supply voltage (Master) of the relevant unit based on the Error code shown to the left.
U2 - 25 Shortage of inverter 2 power supply voltage (Slave 1)
U2 - 28 Shortage of inverter 2 power supply voltage (Slave 2)
Troubleshooting
Error code
Description of error Description of diagnosis
U3 - 02 Initial installation alarm / Test operation
failed due to indoor unit error
U3 - 03 Test operation not conducted
U3 - 04 Abnormal end of test operation
U3 - 05 Premature end of test operation during
initial transmission error – check indoor unit
error U4 / U9
Refer to the U3 flowchart of each manual and make a diagnosis
U3 - 06 Premature end of test operation during of the relevant unit based on the Error code shown to the left.
normal transmission error
U3 - 07 Premature end of test operation due to
transmission error
U3 - 08 Premature end of test operation due to
transmission error of all units
U3 - 10 System refrigerant auto charge operation
not yet executed
U4 - 01 Transmission error between indoor and
outdoor units Refer to the U4 flowchart of each manual and make a diagnosis
U4 - 03 Transmission error between indoor unit and of the relevant unit based on the Error code shown to the left.
system: check indoor unit error
U7 - 01 Error when external control adaptor for
outdoor unit is installed
U7 - 02 Alarm when external control adaptor for
outdoor unit is installed
U7 - 03 Transmission error between master and
slave 1 units
U7 - 04 Transmission error between master and Refer to the U7 flowchart of each manual and make a diagnosis
slave 2 units of the relevant unit based on the Error code shown to the left.
U7 - 05 Multi system error
U7 - 06 Error in address settings of slave 1 and 2
U7 - 07 Connection of four or more outdoor units in
the same system
U7 - 11 Error in indoor unit connection capacity for
test operation
U9 - 01 Other indoor units and outdoor unit Refer to the U9 flowchart of each manual and make a diagnosis
abnormality of the relevant unit based on the Error code shown to the left.
UA - 00 TSS plus unit field settings error, CT
address duplication warning
UA - 03 Connection of excessive indoor units
UA - 17 Connection of excess indoor units
UA - 18 Connection of incorrect models of indoor Refer to the UA flowchart of each manual and make a diagnosis
units of the relevant unit based on the Error code shown to the left.