Certificate of Compliance

FIRE PROTECTION EQUIPMENT


This certificate is issued for the following equipment:

System Description – Model Designations

See Following pages for complete ANSI and Local Protective Signaling text

Approval Guide Listing: Category:

Electrical Signaling, Signaling Systems (Fire), Central Station Signaling Systems


Electrical Signaling, Signaling Systems (Fire), Local Protective Signaling, Local Protective Signaling
Electrical Signaling, Signaling Systems (Fire), Remote Station Signaling Systems
Electrical Signaling, Fire Alarm Equipment – Controls & Systems Tested to ANSI Standards

Kidde-Fenwal Inc
400 Main St
Ashland, MA 01721
United States

This certifies that the equipment described has been found to comply with the applicable requirements, as stated in the Approval Report(s),
of the following FM Approval Standards and other documents:
Approval Standards Other Standards
Class Number Date Organization, Designation Date
3010 December 2010 ANSI/ NFPA 72 2002
ANSI/UL 864 September 2003

Original Approval Job Identification:0003044675 Approval Granted: 4/24/12

Related Report:

Subsequent Revisions:

_________________________
David Waite
Technical Team Manager
FM Approvals
1151 Boston-Providence Turnpike,
Norwood MA, 02062 USA

Page 1 of 4 Cert. No. «PeopleSoft_Project_ID»)


Certificate of Compliance
FenwalNET 8000-ML,ARIES NETLink

Model Designation Devices Signaling Applications

FenwalNET 8000-ML ARIES NETLink A,M,WF,SS NC,DAC,OT A,L,LS, RS,CS ARES,ARP&D

FenwalNET 8000-ML
FenwalNET 8000-ML programmable analog addressable fire alarm control system. The main control board with operating
software Rev. 2.0.X has two (Class A) Style 6, 7 or (Class B), Style 4 Signaling Line Circuits (SLC’s) that communicate with
up to 255 analog addressable devices each. The main control board also has two (Class A), Style Z or (Class B), Style Y
Notification Appliance Circuits (NACs) rated 2.0 A (max.) @ 24 V dc. Two more configurable output circuits are located on
the main control board. When configured as a notification appliance circuit, the wiring performance of the configurable output
circuits qualifies as (Class A) Style Z, or (Class B) Style Y, rated 2.0 A (max) @ 24 V dc; otherwise, the output circuits are
used for connection to initiator or solenoid based releasing devices, rated 2.4 A (max) @ 24 V dc. One un-powered Form C
relay contact is provided for trouble conditions. Three programmable, un-powered, Form C contacts are also provided. One
RS-485 communication circuit for connection to Approved remote user interface modules and annunciator-driver modules is
also provided. A switching power supply w/PMU Module operating from either 120 V ac or 240 V ac, 50/60 Hz primary
power, supplies 5.4 A @ 24 V dc to support the control and charge 24 V dc batteries. An optional second switching power
supply may be used to provide an additional 5.4 A @ 24 V dc. Up to four PMUs and eight associated power supplies may be
connected when the application requires up to 20A.

The system may be expanded by using one to four Expansion Card Cage Assemblies (P/N 74-800010-001) which accept
the following optional modules: DACT Module (P/N 74-800015-001), ICM Module (P/N 74-800017-001), SLC Card (P/N 74-
800011-001), Relay Card (P/N 74-800012-001), R-NAC Card (P/N 74-800013-001), or the City-Tie Card (P/N 74-800016-
001). Optional dead front covers are available along with a FenwalNET – 2000 Control Unit Retrofit Kit (P/N 74-800400-
001) The following addressable devices are compatible with the FenwalNET 8000-ML control: 70-407008-001, and 70-
407018-001 addressable contact input device modules, 70-408004-001 and 70-408014-001 addressable relay output device
modules, addressable manual station (P/N 30-330002-001), Addressable Signal Sounder Module (P/N 70-200200-003),
PSD-7152 (P/N 71-402001-100) and CPD-7052 (P/N 70-402001-100) analog addressable photoelectric and ionization type
smoke detectors with the 6 in. 6SB (P/N 70-400001-100) and 4 in. 4SB (P/N 70-400001-101) detector bases, DH-2000 duct
detector with PSD-7152 (P/N 70-403001-152) and DH-2000 duct detector with CPD-7052 (P/N 70-403001-052). The panel is
also compatible with the THD-7252 thermistor heat detector (P/N 70-404001-100) rated 135°F (37°C) to 155°F (68.3°C),
Fixed RTI classification for both temperatures: Quick, spacing guide: 20 by 20 ft (6.1 x 6.1 m) max, loop isolator base mount
(P/N 74-200012-004), loop isolator single gang mount (P/N 74-200012-002). The panel is also compatible with the
Addressable AlarmLine Module (P/N 73-100001-003) installed in either a standard electrical outlet box or a suitably rated
NRTL listed NEMA 4 enclosure. For one or more HSSD AnaLASER II’s, the FenwalNET 8000-ML can be connected to an
AnaLASER Interface Module (AIM), (P/N 89-300010-001) mounted inside each detector enclosure and interfaced to the
signaling line circuit. For one or more Air-Intelligence HSSD’s the FenwalNET 8000-ML can be connected to a SmartOne
APIC, (P/N 74-333001-001) mounted inside a detector enclosure and interfaced to the signaling line circuit. Suitable for
indoor use only in ambient temperatures from 32° to 120°F (0° to 49°C). When connected with the Intelligent Interface
Module (P/N 74-800014-001 or 74-800015-001) the FenwalNET 8000-ML can monitor up to 127 AnaLASER II detectors via
RS-485 connection. (See separate AnaLASER II listing under Fire Detection, Smoke Actuated). The FenwalNET 8000-ML is
also compatible with the Remote Display Control Module (RDCM) (P/N 74-800300-001), Remote LED Annunciator Module
(R-LAM) (P/N 74-800300-002) and City of Chicago Stand-Alone Control Box (P/N 74-800500-001) as well as optional

Page 2 of 4 Cert. No. «PeopleSoft_Project_ID»)


Certificate of Compliance
Annunciator Driver Module ATM-L (P/N 74-300004-032) and optional Relay Driver Module ATM-R (P/N 74-300005-032).
Depending on its configuration, optional Network Interface Card (P/N 74-800014-001) provides an RS-485 (Class A) Style 7
or (Class B) Style 4 signaling line circuit enabling a network of 64 FenwalNET 8000-ML systems to be combined into an
integrated, peer-to-peer network. An optional Fiber-Optic Converter Module P/N 74-800300-005, with Add-On Channel
Module 74-800300-015, or 74-800300-006, with Add-On Channel 74-800300-016, allows networked FenwalNET 8000-ML 's
to be interconnected using fiber-optic medium. The RRM (P/N 70-600000-001 Standard Mounting, and P/N 70-600000-002
In-Cabinet Mounting) has the ability to remotely activate extinguishing-system control devices. It provides a releasing circuit
rated 2.4A (max) @ 24 V dc for initiator or solenoid based releasing devices and connects to the signaling line circuit of the
FenwalNET 8000-ML. 24 V dc batteries rated 7-165 AH are available to provide 24 hours of emergency operation.

ARIES NETLink

ARIES NETLink programmable analog addressable fire alarm control system. The main control board with operating software Rev. 2.0.X
has two (Class A) Style 6, 7 or (Class B), Style 4 Signaling Line Circuits (SLC’s) that communicate with up to 255 analog addressable
devices each. The main control board also has two (Class A), Style Z or (Class B), Style Y Notification Appliance Circuits (NACs) rated 2.0 A
(max.) @ 24 V dc. Two more configurable output circuits are located on the main control board. When configured as a notification appliance
circuit, the wiring performance of the configurable output circuits qualifies as (Class A) Style Z, or (Class B) Style Y, rated 2.0 A (max) @ 24
V dc; otherwise, the output circuits are used for connection to initiator or solenoid based releasing devices, rated 2.4 A (max) @ 24 V dc.
One un-powered Form C relay contact is provided for trouble conditions. Three programmable, un-powered, Form C contacts are also
provided. One RS-485 communication circuit for connection to Approved remote user interface modules and annunciator-driver modules is
also provided. A switching power supply w/PMU Module operating from either 120 V ac or 240 V ac, 50/60 Hz primary power, supplies 5.4 A
@ 24 V dc to support the control and charge 24 V dc batteries. An optional second switching power supply may be used to provide an
additional 5.4 A @ 24 V dc. Up to four PMUs and eight associated power supplies may be connected when the application requires up to
20A.

The system may be expanded by using one to four Expansion Card Cage Assemblies (P/N 76-800010-001) which accept the following
optional modules: DACT Module P/N (76-800015-001), ICM Module (P/N 76-800017-001), SLC Card (P/N 76-800011-001), Relay Card
(P/N 76-800012-001), R-NAC Card (P/N 76-800013-001), or the City-Tie Card (P/N 76-800016-001). Optional dead front covers are
available along with a PEGAsys Control Unit Retrofit Kit (P/N 76-800400-001).

The following addressable devices are compatible with the ARIES NETLink control: 70-407008-001, and 70-407018-001 addressable
contact input device modules, 70-408004-001 and 70-408014-001 addressable relay output device modules, addressable manual station
(P/N 30-330002-001), Addressable Signal Sounder Module (P/N 70-200200-003), PSD-7152 (P/N 71-402001-100) and CPD-7052 (P/N 70-
402001-100) analog addressable photoelectric and ionization type smoke detectors with the 6 in. 6SB (P/N 70-400001-100) and 4 in. 4SB
(P/N 70-400001-101) detector bases, DH-2000 duct detector with PSD-7152 (P/N 70-403001-152) and DH-2000 duct detector with CPD-
7052 (P/N 70-403001-052). The panel is also compatible with the THD-7252 thermistor heat detector (P/N 70-404001-100) rated 135°F
(37°C) to 155°F (68.3°C), Fixed RTI classification for both temperatures: Quick, spacing guide: 20 by 20 ft (6.1 x 6.1 m) max, loop isolator
base mount (P/N 74-200012-004), loop isolator single gang mount (P/N 74-200012-002). The panel is also compatible with the Addressable
AlarmLine Module (P/N 73-100001-003) installed in either a standard electrical outlet box or a suitably rated NRTL listed NEMA 4 enclosure.
For one or more HSSD ORION XT’s, the ARIES NETLink can be connected to a PEGAsys Addressable Loop Module (PALM), (P/N 77-
297103-000) mounted inside each detector enclosure and interfaced to the signaling line circuit. For one or more Air-Intelligence HSSD’s
the ARIES NETLink can be connected to a SmartOne APIC, (P/N 76-333002-001) mounted inside a detector enclosure and interfaced to the
signaling line circuit. Suitable for indoor use only in ambient temperatures from 32° to 120°F (0° to 49°C). The ARIES NETLink is also
compatible with the Remote Display Control Module (RDCM) (P/N 76-800300-001), Remote LED Annunciator Module (R-LAM) (P/N 76-
800300-002) and City of Chicago Stand-Alone Control Box (P/N 76-800500-001) as well as optional Annunciator Driver Module ATM-L (P/N
76-200004-032) and optional Relay Driver Module ATM-R (P/N 76-200005-032). Depending on its configuration, optional Network Interface

Page 3 of 4 Cert. No. «PeopleSoft_Project_ID»)


Certificate of Compliance
Card (P/N 76-800014-001) provides an RS-485 (Class A) Style 7 or (Class B) Style 4 signaling line circuit enabling a network of 64 ARIES
NETLink systems to be combined into an integrated, peer-to-peer network. An optional Fiber-Optic Converter Module P/N 76-800300-005,
with Add-On Channel Module 76-800300-015, or 76-800300-006, with Add-On Channel 76-800300-016, allows networked ARIES NETLink
's to be interconnected using fiber-optic medium. The RRM (P/N 70-600000-001 Standard Mounting, and P/N 70-600000-002 In-Cabinet
Mounting) has the ability to remotely activate extinguishing-system control devices. It provides a releasing circuit rated 2.4A (max) @ 24 V
dc for initiator or solenoid based releasing devices and connects to the signaling line circuit of the ARIES NETLink. 24 V dc batteries rated
7-165 AH are available to provide 24 hours of emergency operation

Page 4 of 4 Cert. No. «PeopleSoft_Project_ID»)