MT8052iP series
4 Power Connections
Power Connector Specifications: Spécifications du connecteur d'alimentation:
Installation Instruction Wire AWG: 24~12 AWG de fil: 24 ~ 12
Wiring Conductor Minimum Temperature: 75°C Température minimale du conducteur de câblage: 75°C
Screw Torque: 4.5 lbf-in (max.) Couple de vis: 4.5 lbf-in (max.)
1 Installation and Startup Guide Copper conduct only. Conducteur en cuivre seulement
NOTE:
This document covers the installation of MT8052iP Series HMI, for the detailed specifications and 1. Connect positive DC line to the ‘+’ terminal and the DC
operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all ground to the ‘-’ terminal.
warnings, precautions, and instructions on the device carefully before use. 2. When downloading project using a USB cable, do not
connect HMI with PLC and PC simultaneously, for electric
Install Environment:
potential difference may result in damage to HMI or PC.
NEMA Rating The HMI product is NEMA 4 rated (indoor use only).
The HMI product has been tested to conform to European CE requirements. This
Electrical means that the circuitry is designed to resist the effects of electrical noise. This
Environment does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
(1) Make sure that the displays are installed correctly and that the operating 5 System Settings
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present. When HMI is powered up and displays image, click the system setting
(2) Do not operate the unit in areas subject to explosion hazards due to
Environmental flammable gases, vapors or dusts. button. (Default System Password: 111111)
Considerations (3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) For use in Pollution Degree 2 Environment and dry location.
(6) Relative Humidity: 10% ~ 90% (non-condensing) Go to Security tab, the default password is 111111, click Go to the Network tab, you may
Cleaning Clean the device using dry cloths. Do not use liquid or spray detergents for the buttons to set your own passwords. choose to auto get DHCP IP, or
Considerations cleaning. In MISC2 tab, if “Enable [Reset HMI to default] button in designate your own IP. It is necessary
IP Rating IP 65 calibration mode” is selected, the [RESET HMI TO to connect the HMI to your network
Protection impairment if used in a manner not specified by the manufacturer. DEFAULT] button can be found in calibration mode, as through a RJ-45 cable.
Warning Déficit de protection si utilisé d'une manière non spécifiée par le fabricant. shown in Part 8.
2 Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the supplier.
NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it
fall may cause damage.
The package includes:
(1) Installation Instruction, 2-sided A4 *1 (2) Human Machine Interface *1 (3) Power Connector *1
(4) Brackets & Screws *1 pack
3 Installation Instructions
Use a control box that provides enough stiffness. Cutout
Dimension: 119 mm x 93 mm. Secure the operator panel in
position, using all the fastening holes and the provided
brackets and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For
reaching waterproof effect and preventing the panel from
6 EasyBuilder Pro Software Settings
being deformed.)
Plan for adequate space around the unit and inside the Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download
enclosure, for ventilation and cables. Consider the heat from dialog box: Select Ethernet > IP tab > Enter your HMI IP > Click Download to download this project
other devices inside the enclosure. The ambient temperature file to HMI.
around the unit must be 0 ~ 55°C Using screensaver and backlight saver is recommended in order to avoid image persistence caused
Minimum required clearances (along the overlay): Top 15 mm / Bottom 50 mm / Sides 15 mm by displaying the same image on HMI for a long time.
Maximum panel thickness: 4.5 mm ( Please refer to EasyBuilder Pro User Manual for software operation details. )
NOTE: Make sure that all local and national electrical standards are met when
7 Communication Connections CAUTION installing the unit. Contact your local authorities to determine which codes apply.
Use power output that meets SELV (Safety Extra-Low Voltage) requirements. The unit can be
NOTE: COM1 / COM3 RS485 2W support MPI 187.5K, please use one at a time. powered by DC power only, voltage range: 24±20%, compatible with most controller DC
Power
systems. The power conditioning circuitry inside the unit is accomplished by a switching power
supply. The peak starting current can be as high as 2A.
9 Pin, Male, D-sub COM1 COM3
COM1 [RS485] If the display does not come on within 5 seconds of power up, remove power. A resettable fuse
COM1 [RS232] PIN# [RS232] [RS485] Fusing Require-
COM1 [RS485] 4W 2W will protect against overcurrent faults in DC circuit and the resetting will take place after a
2W 2W ments period of time. Check wiring for proper connections and try to power up again.
COM3 [RS485]
1 Rx- Data-
A resettable fuse will prevent damage for overcurrent condition however it isn’t guaranteed.
2 Rx+ Data+ High Voltage DC voltage sources should provide proper isolation from main AC power and similar hazards
3 Tx-
A Hard-wired EMERGENCY STOP should be fitted in any system using an HMI to comply with
4 TX+ Emergency Stop
ICS Safety Recommendations.
5 GND
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
6 TxD Supply Voltage
power supply. Note: The 24 VDC output from some controllers may not have enough current to
Condition power the unit.
7 Data-
8 Data+ a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
9 RxD b. Please use twisted pair cables for power wire and signal wire and conform to the
impedance matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression
Wire Routing devices.
8 Touchscreen Calibration Mode d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency
Press and hold anywhere on the screen when HMI starts until
dissipation. Typical values to use are 1M Ohm and 4700pF.
it enters touchscreen calibration mode. If “Enable [Reset HMI
to default] button in calibration mode” is selected as DANGER
described in Part 5 System Settings, then [RESET HMI TO The system designer should be aware that devices in Controller systems could fail and
DEFAULT] and [SYSTEM SETTINGS] buttons can be found thereby create an unsafe condition. Furthermore, electrical interference in an operator
in calibration mode. Follow the onscreen guide and press interface can lead to equipment start-up, which could result in property damage and/or
[yes] to restore factory default, and please note that the physical injury to the operator.
Hardware
If you use any programmable control systems that require an operator, be aware that this
projects and data stored in the unit will all be cleared after Considerations potential safety hazard exists and take appropriate precautions. Although the specific design
this. steps depend on your particular application, the following precautions generally apply to
installation of solid-state programmable control devices, and conform to the guidelines for
installation of Controllers recommended in NEMA ICS 3-304 Control Standards.
9 Battery Replacement
To conform to ICS Safety Recommendations, checks should be placed in the controller to
Battery Specification: Type CR1220, Rated 2V ensure that all writable registers that control critical parts of plant or machinery have limit
Programming
Battery replacement shall be performed by qualified personnel (engineer) only and care must be taken checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of
Considerations personnel.
when handling lithium batteries. For more information on battery replacement and disposal
GME852P00_MT8052iP_Installation_230310
considerations, please refer to the following link:
http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.