Switchboard Manufacturer - Surge Protection Device Selection Guide

Recommended Back- Max. Recommended Recommended Cable


Typical Installation Location Part Number Brief Specification Benefits
Up Fuse Back-Up Fuse Size (Stranded)

Main Switchboard with or without MEN

Primary protection device. 63A


3-Phase, Imax=200kA, In=80kA, Up=1.2kV@ 3kA, Modular, UL1449-Ed 4, IEC Class I, Class II, Panel or 5.26mm² Flying Leads
Large facilities or small facilities where TDX200M277/480TT (63A Fuse Included 315A
1.8kV@20kA, Uc=320V outside mount, flying leads, TD technology Inlcuded
risk is very high. Internally)

Example MSB Spec: 3200A 65kA MSB

Main Switchboard with or without MEN

Primary protection device. 63A


3-Phase, Imax=100kA, Iimp=12.5kA, Up=1.2kV@ 3kA, Modular, UL1449-Ed 4, IEC Class I, Class II, Panel or 5.26mm² Flying Leads
Large facilities or small facilities where TDX100M277/480TT (63A Fuse Included 315A
1.8kV@20kA, Uc=320V, IEC Class I outside mount, flying leads, TD technology Inlcuded
risk is high. Internally)

Example MSB Spec: 3200A 50kA MSB

Main Switchboard with MEN


IEC Class I, Class II, modular, very small, alarm contacts,
Primary protection device.
3-Phase, Imax=65kA, In=25kA, Up=1550V@ 3kA locking modules, universally coordinates with any
Small facilities where risk is high and DT1M27530R 63A 315A 25mm²
Uc=275V, Ut=442V, IEC Class I secondary surge protection device in small switchboard
there is limited space in SWB.

Example MSB Spec: 1600A 50kA MSB

Main Switchboard without MEN


IEC Class I, Class II, modular, very small, alarm contacts,
Primary protection device.
3-Phase, Imax=65kA, In=25kA, Up=1550V@ 3kA locking modules, universally coordinates with any
Small facilities where risk is high and DT1M27531R 63A 315A 25mm²

Colterlec - nVent Erico Surge Selection - 11.11.22


Uc=275V, Ut=442V, IEC Class I secondary surge protection device in small switchboard
there is limited space in SWB.

Example MSB Spec: 1600A 50kA MSB

Main Switchboard with MEN


Designed specifically for economical use within the
Primary protection device. 3-Phase, Imax=100kA, In=40kA, Up=800V@ 3kA Australian and New Zealand markets. Indication flag
DSD3100TNC275 63A 160A 25mm²
Small facilities where the risk is low. Uc=275V provides clear visual indication of life status.
Remote contacts provide remote status monitoring.
Example MSB Spec: 630A 36kA MSB

TM For more information


Call 1300 36 26 26 | sales@colterlec.com.au | www.colterlec.com.au
nVent.com/ERIFLEX | 1
Switchboard Manufacturer - Surge Protection Device Selection Guide
Recommended Back- Max. Recommended Recommended Cable
Typical Installation Location Part Number Brief Specification Benefits
Up Fuse Back-Up Fuse Size (Stranded)

Main Distribution Board without MEN


Designed specifically for economical use within the
Primary protection device. 3-Phase, Imax=100kA, In=40kA, Up=800V@ 3kA Australian and New Zealand markets. Indication flag
DSD3100TNS275 63A 160A 25mm²
Small facilities where the risk is low. Uc=275V provides clear visual indication of life status.
Remote contacts provide remote status monitoring.
Example MDB Spec: 1000A 36kA MDB

Distribution Board with MEN

Secondary protection device. 3-Phase, Imax=50kA, In=20kA, Up=1650V, TD Technology, Tested to IEC61643 Class II,
EDT230030R 32A 250A 25mm²
Small facilities where the risk is high. Uc=300V, Ut=442V, IEC Class II UL1449-Ed 4, Modular, Locking Modules

Example DB Spec: 250A 10kA DB

Distribution Board without MEN

Secondary protection device. 3-Phase, Imax=50kA, In=20kA, Up=1650V, TD Technology, Tested to IEC61643 Class II,
EDT230031R 32A 250A 25mm²
Small facilities where the risk is high. Uc=300V, Ut=442V, IEC Class II UL1449-Ed 4, Modular, Locking Modules

Example DB Spec: 250A 10kA DB

Distribution Board with MEN

Secondary protection device. 3-Phase, Imax=50kA, In=20kA, Up=1500V, Tested to IEC61643 Class II, UL1449-Ed 4,
DT230030R 32A 250A 25mm²
Small facilities where the risk is low. Uc=300V, Ut=442V Modular, Locking Modules

Colterlec - nVent Erico Surge Selection - 11.11.22


Example DB Spec: 250A 10kA DB

Distribution Board without MEN

Secondary protection device. 3-Phase, Imax=50kA, In=20kA, Up=1500V, Tested to IEC61643 Class II, UL1449-Ed 4,
DT230031R 32A 250A 25mm²
Small facilities where the risk is low. Uc=300V, Ut=442V Modular, Locking Modules

Example DB Spec: 250A 10kA DB

TM For more information


Call 1300 36 26 26 | sales@colterlec.com.au | www.colterlec.com.au
nVent.com/ERIFLEX | 1