LECTURE NOTES ON ELECTRICAL ACHINES I –REGULATION 2018

LECTURE NOTES
ON
ELECTRICAL MACHINES I
BE. EEE
II YEAR 3rd SEMESTER
(BIT-R2018)

A.NANDHAKUMAR
ASSISTANT PROFESSOR

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING


BANNARI AMMAN INSTITUTE OF TECHNOLOGY
SAHYAMANGALAM, ERODE(DT) TAMIL NADU - 638401

DEPARTMENT OF EEE BIT Page 1


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

18EE303 ELECTRICAL MACHINES I 3 1 04

Course Objectives

 To understand the production of torque and EMF.


 To understand the construction, operation and characteristics of various types of DC machines.
 To understand the operation and performance of special machines
 To understand the construction, operation and characteristics of transformers
 To estimate the performance of Transformers

Programme Outcomes (POs)

a. Apply the knowledge of mathematics, science, engineering fundamentals, and an engineering


specialization to the solution of complex engineering problems.
b. Identify, formulate, review research literature, and analyse complex engineering problems reaching
substantiated conclusions using first principles of mathematics, natural sciences, and engineering
sciences.
d. Use research-based knowledge and research methods including design of experiments, analysis and
interpretation of data, and synthesis of the information to provide valid conclusions.
m. PSO1: Modeling , design and Analysis of Electrical and Electronic Systems using design principles
and software tools
n. PSO2: Develop electrical machineries/Appliances for various Domestic and industrial needs

Course Outcomes (COs)


1. Analyze the electro-mechanical energy conversion process in rotating electrical machines
2. Analyze the various types and characteristics of DC Generator and DC motor
3. Examine the performance of special electrical machines
4. Construct the equivalent circuit and analyze the performance of the transformers
5. Evaluate the losses and regulation of transformers using different testing methods

Articulation Matrix

CO No PO1 PO2 PO3 PO4 PO5 PO6 PO7 PO8 PO9 PO10 PO11 PO12 PSO1 PSO2
1 3 1 3
2 2 3 2
3 2 1 3
4 2 2 3
5 3 3 3 3

DEPARTMENT OF EEE BIT Page 2


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

UNIT I 8 Hours
PRINCIPLES OF ENERGY CONVERSION
Faraday's law of electromagnetic induction -singly and doubly excited magnetic field systems -EMF and
torque production in rotating machines.

UNIT II 12 Hours
DC MACHINES
Generator and Motor- Construction - Principle of operation - Types - Characteristics - Armature reaction
and commutation - Starting and Speed control -Various testing-Braking -Applications

UNIT III 8 Hours


SPECIAL MACHINES
Stepper motor, permanent magnet brushless D.C. motor and switched reluctance motors -construction-
principle of operation-types- applications

UNIT IV 9 Hours
TRANSFORMERS
Construction - Principle of operation - Types - Equivalent circuit -Voltage regulation and efficiency -
Auto transformer

UNIT V 8 Hours
TRANSFORMER TESTING
Testing of transformers -Polarity, open circuit, short circuit and Sumpner's test - Three phase transformers
connections- Parallel operation
Total: 60 Hours
Reference(s)
1. 1.D. P. Kothari and I. J. Nagrath, Electric Machines, Tata McGraw Hill Publishing Company Ltd,
2017
2. 2.P. S. Bimbhra, Electrical Machinery, Khanna Publishers, Delhi, 2018
3. 3.E. Fitzgerald, Charles Kingsley, Stephen.D.Umans, Electric Machinery, Tata McGraw Hill
publishing Company Ltd, New Delhi ,2015
4. 4.Stephen J.Chapman, Electric Machinery Fundamentals, Tata McGraw Hill, New Delhi, 2018.
5. 5.T.Kenjo and S.Nagamori,Permanent magnet and Brushless DC motors, Clarendon press,
London, 2015
6. 6.T.Kenjo, Stepping motors and their microprocessor controls, Oxford University press, New
Delhi, 2011

DEPARTMENT OF EEE BIT Page 3


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

UNIT-II
DC GENERATORS

DEPARTMENT OF EEE BIT Page 4


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Generators
There are two types of generators, one is ac generator and other is dc generator. Whatever may
be the types of generators, it always converts mechanical power to electrical power. An ac
generator produces alternating power.
A DC generator produces direct power. Both of these generators produce electrical power, based
on same fundamental principle of Faraday's law of electromagnetic induction. According to these
law, when an conductor moves in a magnetic field it cuts magnetic lines force, due to which an
emf is induced in the conductor. The magnitude of this induced emf depends upon the rate of
change of flux (magnetic line force) linkage with the conductor. This emf will cause an current
to flow if the conductor circuit is closed. Hence the most basic two essential parts of a generator
are
1. a magnetic field
2. conductors which move inside that magnetic field.

Constructional Features
A DC generator has the following parts
1. Yoke
2. Pole of generator
3. Field winding
4. Armature of DC generator
5. Brushes of generator
6. Bearing

DEPARTMENT OF EEE BIT Page 5


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Fig. A Cut Away View Of Practical DC Generator

Yoke of DC Generator
Yoke of DC generator serves two purposes,
1. It holds the magnetic pole cores of the generator and acts as cover of the generator.
2. It carries the magnetic field flux.
In small generator, yoke are made of cast iron. Cast iron is cheaper in cost but heavier than steel.
But for large construction of DC generator, where weight of the machine is concerned, lighter
cast steel or rolled steel is preferable for constructing yoke of DC generator. Normally larger
yokes are formed by rounding a rectangular steel slab and the edges are welded together at the
bottom. Then feet, terminal box and hangers are welded to the outer periphery of the yoke frame.
Armature Core of DC Generator
The purpose of armature core is to hold the armature winding and provide low reluctance path
for the flux through the armature from N pole to S pole. Although a DC generator provides direct
current but induced current in the armature is alternating in nature. That is why, cylindrical or
drum shaped armature core is build up of circular laminated sheet. In every circular lamination,
slots are either die - cut or punched on the outer periphery and the key way is located on the
inner periphery as shown. Air ducts are also punched of cut on each lamination for circulation of
air through the core for providing better cooling.

DEPARTMENT OF EEE BIT Page 6


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Armature Winding of DC Generator


Armature winding are generally formed wound. These are first wound in the form of flat
rectangular coils and are then pulled into their proper shape in a coil puller. Various conductors
of the coils are insulated from each other. The conductors are placed in the armature slots, which
are lined with tough insulating material. This slot insulation is folded over above the armature
conductors placed in it and secured in place by special hard wooden or fiber wedges.

Commutator of DC Generator
The commutator plays a vital role in dc generator. It collects current from armature and sends it
to the load as direct current. It actually takes alternating current from armature and converts it to
direct current and then send it to external load. It is cylindrical structured and is build up of
wedge - shaped segments of high conductivity, hard drawn or drop forged copper. Each segment
is insulated from the shaft by means of insulated commutator segment shown below. Each
commutator segment is connected with corresponding armature conductor through segment riser
or lug.

Brushes of DC Generator
The brushes are made of carbon. These are rectangular block shaped. The only function of these
carbon brushes of DC generator is to collect current from commutator segments. The brushes are
housed in the rectangular box shaped brush holder. As shown in figure, the brush face is placed
on the commutator segment with attached to the brush holder.

Bearing of DC Generator
For small machine, ball bearing is used and for heavy duty dc generator, roller bearing is used.
The bearing must always be lubricated properly for smooth operation and long life of generator.

Emf equation for dc generator

The derivation of EMF equation for DC generator has two parts:


1. Induced EMF of one conductor
2. Induced EMF of the generator
Derivation for Induced EMF of One Armature Conductor
For one revolution of the conductor,
Let,

DEPARTMENT OF EEE BIT Page 7


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Φ = Flux produced by each pole in weber (Wb) and P


= number of poles in the DC generator. therefore,
Total flux produced by all the poles = ø*p
And,
Time taken to complete one revolution = 60/N
Where,
N = speed of the armature conductor in rpm.

Now,according to Faraday’s law of induction, the induced emf of the armature conductor is
denoted by “e” which is equal to rate of cutting the flux.

Therefore,

Induced emf of one conductor is

Derivation for Induced EMF for DC Generator


Let us suppose there are Z total numbers of conductor in a generator, and arranged in such a
manner that all parallel paths are always in series. Here,

Z = total numbers of conductor


A = number of parallel paths
Then,
Z/A = number of conductors connected in series
We know that induced emf in each path is same across the
line Therefore,
Induced emf of DC generator
E = emf of one conductor × number of conductor connected in series.

DEPARTMENT OF EEE BIT Page 8


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Induced emf of DC generator is

Simple wave wound generator


Numbers of parallel paths are only 2 = A
Therefore,
Induced emf for wave type of winding generator is

Simple lap-wound generator


Here, number of parallel paths is equal to number of conductors in one path i.e. P = A
Therefore,

Induced emf for lap-wound generator is

Methods Of Excitation

An electric generator or electric motor consists of a rotor spinning in a magnetic field. The
magnetic field may be produced by permanent magnets or by field coils. In the case of a machine
with field coils, a current must flow in the coils to generate the field, otherwise no power is
transferred to or from the rotor. The process of generating a magnetic field by means of an
electric current is called excitation.

For a machine using field coils, which is most large generators, the field current must be
supplied, otherwise the generator will be useless. Thus it is important to have a reliable supply.
Although the output of a generator can be used once it starts up, it is also critical to be able to
start the generators reliably. In any case, it is important to be able to control the field since this
will maintain the system voltage.

Types of excitation
(1)seperately excited generator.

DEPARTMENT OF EEE BIT Page 9


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

(2)self excited generator.


self generator is classified into 3 types.
1.shunt generator.
2.series generator.
3.compound generator.
compoud generator is again classified into 2 types.
1.short shunt generator.
2.long shunt generator.

Separately excited generators.


These kind of generators has provided field exciter terminals which are external DC
voltage source is supplies to produce separately magnetic field winding (shunt field) for
magnetize of the generator as illustrated in figure as below.

Self excited field generators.


This type of generator has produced a magnetic field by itself without DC sources from an
external. The electromotive force that produced by generator at armature winding is supply to a
field winding (shunt field) instead of DC source from outside of the generator. Therefore, field
winding is necessary connected to the armature winding. They may be further classified as

a) Shunt generator.

This generator, shunt field winding and armature winding are connected in parallel
through commutator and carbon brush as illustrated in the figure below.

DEPARTMENT OF EEE BIT Page 10


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

b) Series generator

The field winding and armature winding is connected in series. There is different from shunt
motor due to field winding is directly connected to the electric applications (load).
Therefore, field winding conductor must be sized enough to carry the load current
consumption and the basic circuit as illustrated below.

Series generator

c) Compound generator

The compound generator has provided with magnetic field in combine with excitation of shunt
and series field winding, the shunt field has many turns of fine wire and caries of a small current,
while the series field winding provided with a few turns of heavy wire since it is in series with an

DEPARTMENT OF EEE BIT Page 11


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

armature winding and caries the load current. There are two kinds of compound generator as
illustrated in figure 5 and 6.

A short-shunt compound generator

Characteristic of separately excited generator


The generated electromotive force (EMF) is proportional to both of a magnetic density of flux
per pole and the speed of the armature rotated as expression by the relation as following.

Eg = κ φ n
Where
K = Constant for a specific machine
φ = The density of flux per pole
n = Speed of the armature rotation
Eg = Generator voltage

DEPARTMENT OF EEE BIT Page 12


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

By holding the armature speed (n) at a constant value it can show that generator voltage (Eg) is
directly proportional to the magnetic flux density. Which, flux density is proportionately to the
amount of field current (If). The relation of field current and generate voltage as impressed by
figure .

From the figure when the field current (If) is become zero a small generate voltage is produce
due to a residual magnetism.

As the field current increases cause to increase generated voltage linearly up to the knee of the
magnetization curve. Beyond this point by increasing the field current still further causes
saturation of the magnetic structure.

Generator voltage (Eg) is also directly to the armature speed. The formula and a magnetization
curve can be both impressed about this relation.

Where
Eg = Generator voltage or the value of EMF at speed n
Eg' = Generator voltage or the value of EMF at speed n’
n = Speed of the generator armature ( n’ ≠ n )

DEPARTMENT OF EEE BIT Page 13


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Example 1:
The open circuit terminal voltage versus the field current for a separately excited
DC generator with provided the following test data at revolving speed 1400 rpm as show
by the table1 below.

Magnetic curve for example 3.1


Solution
Curve (a) in figure 8 shows the characteristic at revolving speed 1400 rpm
obtained by the data as show in table 1. To obtain the characteristic at 1000 rpm, is made
of the relation as Eg = Kφn

For instance, at a field current of 0.4 Amp the terminal voltage is 114 volts, when the speed is
reached to 1400 rpm and kept its field current constant at this value, the open circuit voltage at
1000 rpm becomes.

DEPARTMENT OF EEE BIT Page 14


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Voltage Regulation

When we add load on the generator, the terminal voltage will decrease due to

(a) The armature winding resistance is mainly of armature resistance. It is cause directly
decrease in terminal voltage as following relation.
Vt = Eg - Ia Ra

Where,

Vt = Terminal or output voltage

Ia = Armature current or load current


Ra = Armature resistance

(a) Load characteristic of (b) Circuit diagram


a separately excited DC generator

The decrease in magnetic flux due to armature reaction. The armature current establishes a
magneto motive force (MMF), which it distorts to main flux, and makes result in weakened flux.
We can put inter-pole between main field poles to reduce the armature reaction.

To have some measure by how much the terminal voltage change from no-load condition and on
load condition, which is called “voltage regulation”.

DEPARTMENT OF EEE BIT Page 15


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Where Vnl = No-load terminal voltage Vfl = Full-load terminal voltage

Remark:

A separately excited generator has disadvantage of requiring an external DC source. It is


therefore used only where a wide range of terminal voltage required.

Example 2

The separately excited generator of example 1 is driven at revolving speed 1000 rpm and the
field current is adjusted to 0.6 Amp. If the armature circuit resistance is 0.28 ohm, plot the output
voltage as the load current is varied from 0 to 60 Amp. Neglect armature reaction effects. If the
full-load current is 60 Amp, what is the voltage regulation?

Solution

From example 1, Eg = 153 volts when the field current is 0.6 Amp, which is the open circuit
terminal voltage. When the generator is loaded, the terminal voltage is decreased by internal
voltage drop,

namely.
Vt = Eg - Ia Ra
For a load current of, say 40 Amp.
Vt = 153 - (40 × 0.28) = 141.80 Volts.
This calculation is for a number of load currents and the external characteristic can
be plotted as show in fig. 10 at full load the terminal voltage.
Vt = 153 - (60 × 0.28) = 136.20 Volts.

DEPARTMENT OF EEE BIT Page 16


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Calculated load characteristic of an example 3.2

Critical Field Resistance And Critical Speed

The critical field resistance is the maximum field circuit resistance for a given speed with
which the shunt generator would excite. The shunt generator will build up voltage only if field
circuit resistance is less than critical field resistance. It is a tangent to the open circuit
characteristics of the generator at a given speed.

Critical resistance

DEPARTMENT OF EEE BIT Page 17


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Suppose a shunt generator has built up voltage at a certain speed. Now if the speed of the
prime mover is reduced without changing Rf, the developed voltage will be less as because the
O.C.C at lower speed will come down (refer to figure). If speed is further reduced to a certain
critical speed (ncr), the present field resistance line will become tangential to the O.C.C at ncr.
For any speed below ncr, no voltage built up is possible in a shunt generator.

Critical Speed

Load characteristics

Self excited DC shunt generator

A shunt generator has its shunt field winding connected in parallel with the armature so that the
machine provides it own excitation. For voltage to build up, there must be some residual
magnetism in the field poles. There will be a small voltage (Er) generated.

(a) Shunt generator circuit (b) load characteristic of shunt generator

DEPARTMENT OF EEE BIT Page 18


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

If the connection of the field and armature winding are such that the weak main pole flux aids to
the residual flux, the induced voltage will become larger. Thus more voltage applied to the main
field pole and cause to the terminal voltage increase rapidly to a large value.

When we add load on the generator, the terminal voltage will decrease due to.

a) The armature winding resistance

b) The armature reaction

c) The weakened flux due to the connection of the generator to aids or oppose to the residual

flux.

DEPARTMENT OF EEE BIT Page 19


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Circuit diagram for the solution of example 3

b) For a load of 20 kw when the terminal voltage is 135 volts, therefore the load current

Series Generator
The field winding of a series generator is connect in series with the armature winding. Since it
carries the load current, the series field winding consists of only a few turns of thick wire. At no-
load, the generator voltage is small due to residual field flux only. When a load is added, the flux
increase, and so does the generated voltage.

(a) Circuit diagram of series generator (b) load characteristics

DEPARTMENT OF EEE BIT Page 20


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Figure shows the load characteristic of a series generator driven at a certain speed. The dash line
indicated the generated EMF of the same machine with the armature opencircuited and the field
separated excited. The different between the two curves is simply the voltage drop (IR) in the
series field and armature winding.

V t = Eg - Ia Ra + Rf

Where
Rf = The series field winding resistance
Ra = The armature winding resistance

The series generators are obviously not suited for applications requiring good voltage regulation.
Therefore, they have been used very little and only in special applications for example, as
voltage booster. The generator is placed in series with a supply line. When the current
consumption is increase, the generated voltage of the series machine goes up because the
magnetic field current is increases.

Compound generator

The compound generator has both a shunt and a series winding. The series field winding usually
wound on the top of a shunt field. The two winding are usually connected such that their ampere-
turns act in the same direction. As such the generator is said to be cumulatively compound.

Simple circuit for compound generator

DEPARTMENT OF EEE BIT Page 21


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

(a) Curve s is represent the terminal voltage characteristic of shunt field winding alone. Under-
compound, this condition the addition of series field winding too short it is cause the terminal
voltage no rise to certain value and reduce while increasing in load current.

(b) Flat compound by increasing the number of a series field turns. It is cause to rise up in
terminal voltage and when no-load and full load condition a terminal voltage is made nearly
same value or equal.

(c) Over-compound, if the number of series field turns is more than necessary to compensated of
the reduce voltage. In this case while a full load condition a terminal voltage is higher than a
no-load voltage. Therefore over-compound generator may use where load is at some distance
from generator. Voltage drop in the line has compensated by used of an over-compound
generator.

(d) If a reversing the polarity of the series field occur this cause to the relation between series
field and shunt field, the field will oppose to each other more and more as the load current
increase. Therefore terminal voltage will drop, such generator is said to be a differentially
compound.

The compound generator are used more extensively than the other type of dc generator because
its design to have a wide variety of terminal voltage characteristics.

Machine Efficiency
The efficiency of any machine is the ratio of the ratio of the output power to the input power.
The input power is provided by the prime mover to drive the generator. Because part of the
energy delivered to the generator is converted into heat, it represents wasted energy. These losses
are generally minimized in the design stage; however, some of these losses are unavoidable.

DEPARTMENT OF EEE BIT Page 22


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

Losses of generator

The losses of generators may be classified as

1) Copper losses
The copper losses are present because of the resistance of the windings. Currents flowing
through these windings create ohmic losses. The windings that may be present in addition to
the (I2 R ) armature winding are the field windings, inter-pole and compensate windings.
2) Iron losses
As the armature rotates in the magnetic field, the iron parts of the armature as well as the
conductors cut the magnetic flux. Since iron is a good conductor of electricity, the EMF s
induced in the iron parts courses to flow through these parts. These are the eddy currents.
Another loss occurring in the iron is due to the Hysteresis loss is present in the armature core.

3) Other rotational losses consist


of 3.1 bearing friction loss
3.2 friction of the rushes riding on the commutator
3.3 windage losses

Windage losses are those associated with overcoming air friction in setting up circulation
currents of air inside the machine for cooling purposes. These losses are usually very small.

DEPARTMENT OF EEE BIT Page 23


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Applications Of Dc Generators

Applications of Separately Excited DC Generators


These types of DC generators are generally more expensive than self-excited DC generators
because of their requirement of separate excitation source. Because of that their applications are
restricted. They are generally used where the use of self-excited generators are unsatisfactory.

1. Because of their ability of giving wide range of voltage output, they are generally used for
testing purpose in the laboratories.
2. Separately excited generators operate in a stable condition with any variation in field
excitation. Because of this property they are used as supply source of DC motors, whose
speeds are to be controlled for various applications. Example- Ward Leonard Systems of
speed control.
Applications of Shunt Wound DC Generators
The application of shunt generators are very much restricted for its dropping voltage
characteristic. They are used to supply power to the apparatus situated very close to its position.
These type of DC generators generally give constant terminal voltage for small distance
operation with the help of field regulators from no load to full load.

1. They are used for general lighting.


2. They are used to charge battery because they can be made to give constant output voltage.
3. They are used for giving the excitation to the alternators.
4. They are also used for small power supply.

Applications of Series Wound DC Generators


These types of generators are restricted for the use of power supply because of their
increasing terminal voltage characteristic with the increase in load current from no load to full
load. We can clearly see this characteristic from the characteristic curve of series wound
generator. They give constant current in the dropping portion of the characteristic curve. For this
property they can be used as constant current source and employed for various applications.

1.They are used for supplying field excitation current in DC locomotives for regenerative
breaking.

DEPARTMENT OF EEE BIT Page 24


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

2.This types of generators are used as boosters to compensate the voltage drop in the feeder in
various types of distribution systems such as railway service.
3.In series arc lightening this type of generators are mainly used.

Applications of Compound Wound DC Generators


Among various types of DC generators, the compound wound DC generators are most
widely used because of its compensating property. We can get desired terminal voltage by
compensating the drop due to armature reaction and ohmic drop in the in the line. Such
generators have various applications.
1. Cumulative compound wound generators are generally used lighting, power supply purpose
and for heavy power services because of their constant voltage property. They are mainly
made over compounded.
2. Cumulative compound wound generators are also used for driving a motor.
3. For small distance operation, such as power supply for hotels, offices, homes and lodges, the
flat compounded generators are generally used.
4. The differential compound wound generators, because of their large demagnetization
armature reaction, are used for arc welding where huge voltage drop and constant current is
required.

At present time the applications of DC generators become very limited because of technical
and economic reasons. Now a days the electric power is mainly generated in the form of
alternating current with the help of various power electronics devices.

DEPARTMENT OF EEE BIT Page 25


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

UNIT-II
DC MOTORS

DEPARTMENT OF EEE BIT Page 26


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Direct Current Motor (DC motor)

DC motor is similar to dc generator; in fact the same machine can act as motor or generator. The
only difference is that in a generator the EMF is greater than terminal voltage, whereas in motor
the generated voltage EMF is less than terminal voltage. Thus the power flow is reversed, that is
the motor converts electrical energy into mechanical energy. That is the reverse process of
generator.

DC motors are highly versatile machines. For example, dc motors are better suited fore many
processes that demand a high degree of flexibility in the control of speed and torque. The dc
motor can provided high starting torque as well as high decelerating torque for application
requiring quick stop or reversals.

DC motors are suited in speed control with over wide range is easily to achieve compare with
others electromechanical.

DC Motor Basic Principles

(a) Energy Conversion


If electrical energy is supplied to a conductor lying perpendicular to a magnetic field,
the interaction of current flowing in the conductor and the magnetic field will produce
mechanical force (and therefore, mechanical energy).

(b) Value of Mechanical Force


There are two conditions which are necessary to produce a force on the conductor. The
conductor must be carrying current, and must be within a magnetic field. When these two
conditions exist, a force will be applied to the conductor, which will attempt to move the
conductor in a direction perpendicular to the magnetic field. This is the basic theory by which
all DC motors operate.

DEPARTMENT OF EEE BIT Page 27


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

The force exerted upon the conductor can be expressed as follows.


F = B i l Newton (1)
where B is the density of the magnetic field, l is the length of conductor, and i the value of
current flowing in the conductor. The direction of motion can be found using Fleming’s Left
Hand Rule.

Fleming’s Left Hand Rule


The first finger points in the direction of the magnetic field (first - field), which goes
from the North pole to the South pole. The second finger points in the direction of the current in
the wire (second - current). The thumb then points in the direction the wire is thrust or pushed
while in the magnetic field (thumb - torque or thrust).

Principle of operation
Consider a coil in a magnetic field of flux density B (figure ). When the two ends of the
coil are connected across a DC voltage source, current I flows through it. A force is exerted on
the coil as a result of the interaction of magnetic field and electric current. The force on the two
sides of the coil is such that the coil starts to move in the direction of force.

DEPARTMENT OF EEE BIT Page 28


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Fig.1. Torque production in a DC motor


In an actual DC motor, several such coils are wound on the rotor, all of which experience
force, resulting in rotation. The greater the current in the wire, or the greater the magnetic field,
the faster the wire moves because of the greater force created.
At the same time this torque is being produced, the conductors are moving in a magnetic
field. At /dt) as shown indifferent positions, the flux linked with it changes, which causes an
emf to be induced (e = d figure 5. This voltage is in opposition to the voltage that causes current
flow through the conductor and is referred to as a counter-voltage or back emf.

Fig.2. Induced voltage in the armature winding of DC motor


The value of current flowing through the armature is dependent upon the difference between the
applied voltage and this counter-voltage. The current due to this counter-voltage tends to oppose
the very cause for its production according to Lenz’s law. It results in the rotor slowing down.
Eventually, the rotor slows just enough so that the force created by the magnetic field (F = Bil)
equals the load force applied on the shaft. Then the system moves at constant velocity.

Construction

DC motors consist of one set of coils, called armature winding, inside another set of coils or a set
of permanent magnets, called the stator. Applying a voltage to the coils produces a torque in the
armature, resulting in motion.

DEPARTMENT OF EEE BIT Page 29


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Stator

The stator is the stationary outside part of a motor.

 The stator of a permanent magnet dc motor is composed of two or more permanent magnet
pole pieces.

 The magnetic field can alternatively be created by an electromagnet. In this case, a DC coil
(field winding) is wound around a magnetic material that forms part of the stator.

Rotor

The rotor is the inner part which rotates.

 The rotor is composed of windings (called armature windings) which are connected to the
external circuit through a mechanical commutator. Both stator and rotor are made of
ferromagnetic materials. The two are separated by air-gap.

Winding

A winding is made up of series or parallel connection of coils.

 Armature winding - The winding through which the voltage is applied or induced.

 Field winding - The winding through which a current is passed to produce flux

(for the electromagnet)

 Windings are usually made of copper.

DEPARTMENT OF EEE BIT Page 30


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Torque Developed

The turning or twisting moment of a force about an axis is called torque. It is measured by the
product of the force and the radius at which this force acts.
Consider a pulley of radius meter acted upon by a circumferential force of newton which causes
it to rotate at rpm.

Armature torque of a motor

DEPARTMENT OF EEE BIT Page 31


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Shaft torque

Induced Counter-voltage (Back emf):


Due to the rotation of this coil in the magnetic field, the flux linked with it changes at different
positions, which causes an emf to be induced (refer to figure 2).

The induced emf in a single coil, e = døc/dt

Since the flux linking the coil, c = Sin

Induced voltage , e = cost (4)

DEPARTMENT OF EEE BIT Page 32


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Note that equation (4) gives the emf induced in one coil. As there are several coils wound all
around the rotor, each with a different emf depending on the amount of flux change through it,
the total emf can be obtained by summing up the individual emfs.

The total emf induced in the motor by several such coils wound on the rotor can be obtained by
integrating equation (4), and expressed as:

Eb = K m (5)

where K is an armature constant, and is related to the geometry and magnetic properties of
the motor, and m is the speed of rotation.

The electrical power generated by the machine is given by:

Pdev = Eb Ia = Km Ia (6)

DC Motor Equivalent circuit

The schematic diagram for a DC motor is shown below. A DC motor has two distinct
circuits: Field circuit and armature circuit. The input is electrical power and the output is
mechanical power. In this equivalent circuit, the field winding is supplied from a separate DC
voltage source of voltage Vf. Rf and Lf represent the resistance and inductance of the field
winding. The current If produced in the winding establishes the magnetic field necessary for
motor operation. In the armature (rotor) circuit, VT is the voltage applied across the motor
terminals, Ia is the current flowing in the armature circuit, Ra is the resistance of the armature
winding, and Eb is the total voltage induced in the armature.

Fig.4. DC motor representation

DEPARTMENT OF EEE BIT Page 33


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Counter EMF in DC motor


When voltage is applied to dc motor, current will flow into the positive brush through the
commutator into the armature winding. The motor armature winding is identical to the generator
armature winding. Thus the conductors on the north field poles are carry current in one direction,
while all conductors on the south field poles carry the current in opposite direction. When the
armature carry current it will produce a magnetic field around the conductor of it own which
interact with the main field. It is cause to the force developed on all conductors and tending to
turn the armature.

The armature conductors continually cut through this resultant field. So that voltages are
generated in the same conductors that experience force action. When operating the motor is
simultaneously acting as generator. Naturally motor action is stronger than generator action.

Although the counter EMF is opposite with the supplied voltage, but it cannot exceed to applied
voltage. The counter EMF is serves to limit the current in an armature winding. The armature
current will be limited to the value just sufficient to take care of the developed power needed to
drive the load.

In the case of no load is connected to the shaft. The counter EMF will almost equal to the applied
voltage. The power develops by the armature in this case is just the power needed to overcome
the rotational losses. It’s mean that the armature current IA is controlled and limited by counter
EMF therefore

Where:

VL = Line voltage across the armature winding

Ra = Resistance of the armature winding

Ea = Induced EMF or generated voltage

Ia = Armature current

DEPARTMENT OF EEE BIT Page 34


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Since, EA is induced or generated voltage it is depend on the flux per pole and the speed of the
armature rotate (n) in rpm.

Therefore

Ea=Kφn

Where:

K = the constant value depending on armature winding and number of pole of


machine.

φ = Rotation of the armature

Where:

Z = Total number of conductor in the armature winding

a = Number of parallel circuit in the armature winding between positive and negative brushes.
For wave wound armature “a” = 2

Lap wound armature “a” = P

Example

A dc motor operated at 1500 rpm when drawing 20 amps from 220 volts supply, if the armature
resistance is 0.2 ohms. Calculate the no load speed assumed Ia = 0 amp (This amount to
assuming the brushes and rotation loss are negligible)

Solution

When load condition Ia = 20 amps.

Ea = VL – Ia Ra = 220 – 20 (0.2) = 216 Volts.

And

Ea = k φ n

DEPARTMENT OF EEE BIT Page 35


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

216 = Kφ ×1500

Kφ = 216/1500

= 0.144

At no load condition Ia = 0 Amp.

Ea = VL = 220 Volts.

Hence

Ea = kφn

n =220/ kφ

=220/ 0.144

= 1528 rpm.

Mechanical power develop in dc motor (Pd)


Let,

Pd = Mechanical power develop

T = Torque exerted on the armature

Pd = ωT

DEPARTMENT OF EEE BIT Page 36


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

DC Machine Classification
DC Machines can be classified according to the electrical connections of the armature
winding and the field windings. The different ways in which these windings are connected lead
to machines operating with different characteristics. The field winding can be either self-excited
or separately-excited, that is, the terminals of the winding can be connected across the input
voltage terminals or fed from a separate voltage source (as in the previous section). Further, in
self-excited motors, the field winding can be connected either in series or in parallel with the
armature winding. These different types of connections give rise to very different types of
machines, as we will study in this section.

(a) Separately excited machines

 The armature and field winding are electrically separate from each other.

 The field winding is excited by a separate DC source.

Fig.5. Separately excited dc motor

The voltage and power equations for this machine are same as those derived in the previous
section. Note that the total input power = Vf If + VT Ia

DEPARTMENT OF EEE BIT Page 37


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

(b)Self excited machines

In these machines, instead of a separate voltage source, the field winding is connected
across the main voltage terminals.

1.Shunt machine

 The armature and field winding are connected in parallel.

 The armature voltage and field voltage are the same.

Fig.6. shunt motor

Total current drawn from the supply, IL = If + Ia

Total input power = VT IL

Voltage, current and power equations are given in equations (7), (8) and (9).

2.Series DC machine

 The field winding and armature winding are connected in series.

 The field winding carries the same current as the armature winding.

A series wound motor is also called a universal motor. It is universal in the sense that it will run
equally well using either an ac or a dc voltage source.

Reversing the polarity of both the stator and the rotor cancel out. Thus the motor will always
rotate the same direction regardless of the voltage polarity.

DEPARTMENT OF EEE BIT Page 38


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Fig.7.Series Motor

Compound DC machine

If both series and shunt field windings are used, the motor is said to be compounded. In a
compound machine, the series field winding is connected in series with the armature, and the
shunt field winding is connected in parallel. Two types of arrangements are possible in
compound motors:

Cumulative compounding - If the magnetic fluxes produced by both series and shunt field
windings are in the same direction (i.e., additive), the machine is called cumulative compound.

Differential compounding - If the two fluxes are in opposition, the machine is differential
compound.

In both these types, the connection can be either short shunt or long shunt.

Speed control of DC motor

Many applications require the speed of a motor to be varied over a wide range. One of
the most attractive features of DC motors in comparison with AC motors is the ease with which
their speed can be varied.

We know that the back emf for a separately excited DC motor:.

DEPARTMENT OF EEE BIT Page 39


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

(7)

From the above equation, it is evident that the speed can be varied by using any of the
following methods:

 Armature voltage control (By varying VT)

 Field Control (By Varying )

 Armature resistance control (By varying Ra)

Armature voltage control

This method is usually applicable to separately excited DC motors. In this method of


speed control, Ra and  are kept constant.

In normal operation, the drop across the armature resistance is small compared to Eb and
therefore: Eb VT

Since, Eb = Kø ωm

Angular speed can be expressed as:

ωm= VT/ Kø (8)

From this equation, If flux is kept constant, the speed changes linearly with VT.

 As the terminal voltage is increased, the speed increases and vice versa.

 The relationship between speed and applied voltage is shown in figure 8. This method
provides smooth variation of speed control.

DEPARTMENT OF EEE BIT Page 40


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Fig.8.Variation of speed with applied voltage

Field Control , ( )

In this method of speed control, Ra and VT remain fixed.

Therefore, from equation (7):

mI/

Assuming magnetic linearity,  If

(OR) m  I/IF (9)

i.e., Speed can be controlled by varying field current If.

 The field current can be changed by varying an adjustable rheostat in the field circuit (as shown
in figure 9).

 By increasing the value of total field resistance, field current can be reduced, and therefore
speed can be increased.

Fig.9.

DEPARTMENT OF EEE BIT Page 41


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

The relationship between the field winding current and angular speed is shown in figure 10

Fig.10: Variation of speed with field current

Armature Resistance Control

The voltage across the armature can be varied by inserting a variable resistance in series with
the armature circuit.

Fig.11. Armature resistance method for speed control

From speed-torque characteristics , we know that:

For a load of constant torque V T and  are kept constant, as the armature resistance Ra is
increased, speed decreases. As the actual resistance of the armature winding is fixed for a given
motor, the overall resistance in the armature circuit can be increased by inserting an additional
variable resistance in series with the armature. The variation if speed with respect to change in
this external resistance is shown in figure 12. This method provides smooth control of speed..

DEPARTMENT OF EEE BIT Page 42


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Fig. 12: Variation of speed with external armature resistance

DC Shunt Motor speed control

All three methods described above can be used for controlling the speed of DC Shunt Motors.

Series Motor speed control

The speed is usually controlled by changing an external resistance in series with the armature.
The other two methods described above are not applicable to DC series motor speed control.

Applications of dc motors

Types of Losses in a DC Machines

DEPARTMENT OF EEE BIT Page 43


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

The losses can be divided into three types in a dc machine (Generator or Motor). They are

1. Copper losses

2. Iron or core losses and

3. Mechanical losses.

All these losses seem as heat and therefore increase the temperature of the machine. Further the
efficiency of the machine will reduce.

1. Copper Losses:

This loss generally occurs due to current in the various windings on of the machine. The
different winding losses are;

2
Armature copper loss = I a Ra

2
Shunt field copper loss = I shRsh

2
Series field copper loss = I se Rse

Note: There’s additionally brush contact loss attributable to brush contact resistance (i.e.,
resistance in the middle of the surface of brush and commutator). This loss is mostly enclosed in
armature copper loss.

2. Iron Losses

This loss occurs within the armature of a d.c. machine and are attributable to the rotation of
armature within the magnetic field of the poles. They’re of 2 sorts viz.,

(i) Hysteresis loss

(ii) eddy current loss.

DEPARTMENT OF EEE BIT Page 44


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Hysteresis loss:

Hysteresis loss happens in the armature winding of the d.c. machine since any given part of the
armature is exposed to magnetic field of reverses as it passes underneath sequence poles. The
above fig shows the 2 pole DC machine of rotating armature. Consider a tiny low piece ab of the
armature winding. Once the piece ab is underneath N-pole, the magnetic lines pass from a to b.
Half a revolution well along, identical piece of iron is underneath S-pole and magnetic lines pass
from b to a in order that magnetism within the iron is overturned. So as to reverse constantly the
molecular magnets within the armature core, particular quantity of power must be spent that is
named hysteresis loss. It’s given by Steinmetz formula.

The steinmetz formula is

16
Hysteresis loss Ph= ηB max fV watts

Where,

η = Steinmetz hysteresis co-efficient

Bmax = Maximum flux Density in armature winding

F = Frequency of magnetic reversals

= NP/120 (N is in RPM)

3
V = Volume of armature in m

If you want to cut back this loss in a d.c. machine, armature core is created of such materials that
have an lesser value of Steinmetz hysteresis co-efficient e.g., silicon steel.

DEPARTMENT OF EEE BIT Page 45


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Eddy current loss:

In addition to the voltages evoked within the armature conductors, some of other voltages
evoked within the armature core. These voltages turn out current currents within the coil core as
shown in Fig. These are referred to as eddy currents and power loss attributable to their flow is
named eddy current loss. This loss seems as heat that increases the temperature of the machine
and efficiency will decrease.

If never-ending cast-iron core is employed, the resistance to eddy current path is tiny attributable
to massive cross-sectional space of the core. Consequently, the magnitude of eddy current and
therefore eddy current loss are massive. The magnitudes of eddy current are often decreased by
creating core resistance as high as sensible. The core resistances are often greatly exaggerated by
making the core of skinny, spherical iron sheets referred to as lamination's shown in the fig. The
lamination's are insulated from one another with a layer of varnish. The insulating layer features
a high resistance, thus only small amount of current flows from one lamination to the opposite.
Also, as a result of every lamination is extremely skinny, the resistance to current passing over
the breadth of a lamination is additionally quite massive. Therefore laminating a core will
increase the core resistance that drops the eddy current and therefore the eddy current loss.

2 2 2
Eddy Current loss Pe=KeB maxf t V Watts

Where, ke = constant

2
Bmax = Maximum flux density in wb/m

T = Thickness of lamination in m

DEPARTMENT OF EEE BIT Page 46


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

3
V = Volume of core in m
Note: Constant (Ke) depend upon the resistance of core and system of unit used.

It may well be noted that eddy current loss be subject to upon the sq. of lamination thickness. For
this reason, lamination thickness ought to be unbroken as tiny as potential.

3.Mechanical Loss

These losses are attributable to friction and windage.

 Friction loss occurs due to the friction in bearing, brushes etc.

 windage loss occurs due to the air friction of rotating coil.

These losses rely on the speed of the machine. Except for a given speed, they're much constant.

Constant and Variable Losses

The losses in a d.c. machine is also further classified into (i) constant losses (ii) variable losses.

Constant losses

Those losses in a d.c. generator that stay constant at all loads are referred to as constant losses.
The constant losses in a very d.c. generator are:
(a)iron losses

(b)mechanical losses

(c)shunt field losses

Variable losses

Those losses in a d.c. generator that differ with load are referred to as variable losses. The
variable losses in a very d.c. generator are:

2
Copper loss in armature winding (I Ra)

DEPARTMENT OF EEE BIT Page 47


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

2
Copper loss in series field winding (I seRse)

Total losses = Constant losses + Variable losses.

Generally this copper loss is constant for shunt and compound generators.

Three point starter

The figure above shows that typical representation diagram of a 3 point starter for DC shunt
motors with its protective devices. It contains 3 terminals namely L, Z, & A; hence named 3
point starter. The starter is made up of of starting resistances divided into many section and
which are connected in series within the armature. The each tapping point on the starting
resistances is carried out to a no. of studs. The starter 3 terminals L,Z & A are connected to the
positive terminal of line, shunt field and armature terminal of motor respectively. The remaining
terminal of the shunt and armature are connected to the negative line terminal. The No volt coil
release is connected in series with field winding. The handle one end is connected to the L
terminal by means of over load release coil. Then another end of handle travels against the
twisting spring & make touching base with every single stud in the course of starting operation,
tripping out the starting resistance as it moves above every stud in clockwise.

DEPARTMENT OF EEE BIT Page 48


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Armature Reaction in DC Motor

Working:

 Initially the DC supply is turned on with the handle is in OFF position.


st
 Now the handle is moved towards clockwise direction to the 1 stud. Once it contacts with
st
the 1 stud, immediately the shunt field coil is connected to the supply, however the entire
starting resistances is injected with armature circuit in series.

 As the handle moved gradually towards the final stud, so that the starting resistance is cut out
step by step in armature circuit. And finally the handle is detained magnetically by the No
volt coil release since it is energized by the filed winding.

 In case if the shunt field winding excitation is cut out by accident or else the supply is
interrupted then the no volt coil release gets demagnetized and handle returned back to the
original position under the influence of spring.

Note: If we were not used No volt coil release; then if the supply is cut off the handle would
remain in the same position, causing an extreme current in armature.

 If any fault occurs on motor or overload, it will draw extreme current from the source. This
current raise the ampere turns of OLR coil (over load relay) and pull the armature Coil, in
consequence short circuiting the NVR coil (No volt relay coil). The NVR coil gets
demagnetized and handle comes to the rest position under the influence of spring. Therefore
the motor disconnected from the supply automatically.

Characteristic of DC Shunt Motor

Disadvantage:

In point starter, no volt relay coil is connected in series with field circuit; hence it carries shunt
current in the field. When the speed control of DC motor through field regulator, it may be
weakened the shunt field current to such extent the no volt coil release might not in a position to

DEPARTMENT OF EEE BIT Page 49


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

hold the starter handle in ON position. This might the motor disconnected from the source when
it is not anticipated. This can be overcome by using the point starter.

Swinburne’s Test for DC Machines

In this technique, the DC Generator or DC Motor is run as a motor at no load; with that losses of
the DC machines are determined. When the losses of DC machine well-known, then we can find
the efficiency of a DC machine in advance at any desired load. In DC machines this test is
applicable only throughout the flux is constant at all load (DC Shunt machine and DC
Compound Machine). This test maintains of two steps;

Determination of Hot Resistance of Windings:

The resistance of armature windings and shunt field windings are measured with the help of a
battery, ammeter and voltmeter. Since these armature and shunt filed resistances are measured
while the DC machine is cold, it should be transformed to values equivalent to the temperature at
which the DC machine would work at full load. These values are measured generally when the
o
room temperature increases above 40 C. Take on the hot resistance of armature winding and
shunt field winding be Ra and Rsh correspondingly.

DEPARTMENT OF EEE BIT Page 50


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

 Condition for maximum Efficiency in DC Machine

Determination of Constant Losses:

On no load the DC machine run as a motor with the supply voltage is varied to the normal rated
voltage. With the use of the field regulator R the motor speed is varied to run the rated speed
which is shown in the figure.

Let

V = Supply Voltage

I0 = No load current read by A1

Ish = Shunt Field current ready by A2

No load armature current Iao = I0 – Ish

No load Input power to motor = VI0

No load Input power to motor = VIa0

= V (I0 – Ish)

As the output power is nil, the no loads input power to the armature provides Iron loss, armature
copper loss, friction loss and windage loss.

Constant loss Wc = Input power to Motor – Armature copper loss

2
Wc = VI0 – (I0 – Ish Ra)

As the constant losses are identified, the efficiency of the DC machine at any loads can be
determined. Suppose it is desired to determine the DC machine efficiency at no load current.
Then,

DEPARTMENT OF EEE BIT Page 51


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Armature current Ia = I-Ish (For Motoring)

Ia = I+Ish (For Generating)

To find the Efficiency when running as a motor:

Input power to motor = VI

2 2
Armature copper loss =Ia Ra = (I-Ish Ra)

Constant Loss = Wc

Total Loss = (I-Ish2Ra)+Wc

Motor Efficiency η = (Input power – Losses)/ Input

2
η = {VI – (I-Ish Ra)} / VI

 Condition for maximum Efficiency in DC Machine

To find the Efficiency when running as a Generator:

Output Power of Generator = VI

2 2
Armature copper loss =Ia Ra = (I+Ish Ra)

Constant Loss = Wc

2
Total Loss = (I+Ish Ra)+Wc

Motor Efficiency η= Output power/ (Output power + Losses)

2
η = VI / {VI + (I+Ish Ra) + Wc}

DEPARTMENT OF EEE BIT Page 52


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Merits:

 Since this test is no load test, power required is less. Hence the cost is economic.

 The efficiency of the machine can be found very easily, because the constant losses are
well known.

 This test is appropriate.

Demerits:

 When the DC machine is loaded, this test does not deliberate the stray load loss that
occurs.

 Using this method we cannot check the DC machine performances at full load.

Example: It does not indicate the commutation performance is satisfactory on full load and
cannot indicate the specified limit of temperature rise.

 Using this test we cannot determine the accurate efficiency of DC machine, because iron
loss at actual loads is greater than at no load. This is primarily owed to armature reaction
interfere with field.

DEPARTMENT OF EEE BIT Page 53


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

UNIT-IV
TRANSFORMERS

DEPARTMENT OF EEE BIT Page 54


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

TRANSFORMERS
The transformer is a device that transfers electrical energy from one electrical circuit to
another electrical circuit. The two circuits may be operating at different voltage levels but always
work at the same frequency. Basically transformer is an electro-magnetic energy conversion
device. It is commonly used in electrical power system and distribution systems.

SINGLE PHASE TRANSFORMERS


INTRODUCTION

In its simplest form a single-phase transformer consists of two windings, wound on an iron
core one of the windings is connected to an ac source of supply f. The source supplies a current
to this winding (called primary winding) which in turn produces a flux in the iron core. This flux
is alternating in nature (Refer Figure 4.1). If the supplied voltage has a frequency f, the flux in
the core also alternates at a frequency f. the alternating flux linking with the second winding,
induces a voltage E2 in the second winding (called secondary winding). [Note that this
alternating flux linking with primary winding will also induce a voltage in the primary winding,
denoted as E1. Applied voltage V1 is very nearly equal to E1]. If the number of turns in the
primary and secondary windings is N1 and N2 respectively, we shall see later in this unit that

The load is connected across the secondary winding, between the terminals a1, a2. Thus, the load
can be supplied at a voltage higher or lower than the supply voltage, depending upon the ratio
N1/N2

DEPARTMENT OF EEE BIT Page 55


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

When a load is connected across the secondary winding it carries a current I2, called load
current. The primary current correspondingly increases to provide for the load current, in
addition to the small no load current. The transfer of power from the primary side (or source) to
the secondary side (or load) is through the mutual flux and core. There is no direct electrical
connection between the primary and secondary sides.

In an actual transformer, when the iron core carries alternating flux, there is a power loss in the
core called core loss, iron loss or no load loss. Further, the primary and secondary windings have
a resistance, and the currents in primary and secondary windings give rise to I 2 R losses in
transformer windings, also called copper losses. The losses lead to production of heat in the
transformers, and a consequent temperature rise. Therefore, in transformer, cooling methods are
adopted to ensure that the temperature remains within limit so that no damage is done to
windings’ insulation and material.

In the Figure 4.1 of a single-phase transformer, the primary winding has been shown connected
to a source of constant sinusoidal voltage of frequency f Hz and the secondary terminals are kept
open. The primary winding of N1 turns draws a small amount of alternating current of
instantaneous value i0, called the exciting current. This current establishes flux φ in the core (+ve
direction marked on diagram). The strong coupling enables all of the flux φ to be confined to the
core (i.e. there is no leakage of flux).

CONSTRUCTION OF A TRANSFORMER
There are two basic parts of a transformer:
1. Magnetic core

2. Winding or coils
MAGNETIC CORE:
The core of a transformer is either square or rectangular in size. It is further divided in two
parts. The vertical portion on which the coils are bound is called limb, while the top and bottom
horizontal portion is called yoke of the core as shown in fig. 2.
Core is made up of laminations. Because of laminated type of construction, eddy current
losses get minimized. Generally high grade silicon steel laminations (0.3 to 0.5 mm thick) are used.
These laminations are insulated from each other by using insulation like varnish. All laminations are

DEPARTMENT OF EEE BIT Page 56


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

varnished. Laminations are overlapped so that to avoid the airgap at the joints. For this generally ‗L‘
shaped or ‗I‘ shaped laminations are used which are shown in the fig. 3 below.

WINDING:

There are two windings, which are wound on the two limbs of the core, which are
insulated from each other and from the limbs as shown in fig. 4. The windings are made up of
copper, so that, they possess a very small resistance. The winding which is connected to the load
is called secondary winding and the winding which is connected to the supply is called primary
winding. The primary winding has N1 number of turns and the secondary windings have N 2
number of turns.

DEPARTMENT OF EEE BIT Page 57


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Fig. 4 Single Phase Transformer


PRINCIPLE OF OPERATION OF A SINGLE PHASE TRANSFORMER

A single phase transformer works on the principle of mutual induction between two magnetically
coupled coils. When the primary winding is connected to an alternating voltage of r.m.s value,
V1 volts, an alternating current flows through the primary winding and setup an alternating flux
ϕ in the material of the core. This alternating flux ϕ, links not only the primary windings but also

DEPARTMENT OF EEE BIT Page 58


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

the secondary windings. Therefore, an e.m.f e1 is induced in the primary winding and an e.m.f e2
is induced in the secondary winding, e1 and e2 are given:

If the induced e.m.f is e1 and e2 are represented by their rms values E1 and E2 respectively, then

K is known as the transformation ratio of the transformer. When a load is connected to the
secondary winding, a current I2 flows through the load, V2 is the terminal voltage across the
load. As the power transfered from the primary winding to the secondary winding is same,
Power input to the primary winding = Power output from the secondary winding.

The directions of emf‘s E1 and E2 induced in the primary and secondary windings are such that,
they always oppose the primary applied voltage V1.
EMF Equation of a transformer:
Consider a transformer having,
N1 =Primary turns
N2 = Secondary turns
Φm = Maximum flux in the core
Φm = Bm × A webers

DEPARTMENT OF EEE BIT Page 59


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

f= frequency of ac input in hertz (Hz)

The flux in the core will vary sinusoidal as shown in figure, so that it increases from zero to
maximum “ϕm” in one quarter of the cycle i.e, 1/4f second.

i.e, E1 =4.44fφm×N1 = 4.44fBm×A×N1


Similarly;
E2= 4.44 f φm × N2 = 4.44 f Bm × A × N2

Transformation Ratio:
(1) Voltage Transformation Ratio

(2) Current Transformation Ratio

DEPARTMENT OF EEE BIT Page 60


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Voltage Transformation Ratio:


Voltage transformation ratio can be defined as the ratio of the secondary voltage to the primary
voltage denoted by K.

Current Transformation Ratio:


Consider an ideal transformer and we have the input voltampere is equal to output
voltampere. Mathematically, Input Voltampere = Output Voltampere

TRANSFORMER ON NO-LOAD
Theory of Transformer On No-load, and Having No Winding Resistance and No Leakage
Reactance of Transformer
Let us consider one electrical transformer with only core losses, which means, it has only
core losses but no copper loss and no leakage reactance of transformer. When an alternating
source is applied in the primary, the source will supply the current for magnetizing the core of
transformer.

But this current is not the actual magnetizing current, it is little bit greater than actual
magnetizing current. Actually, total current supplied from the source has two components, one is
magnetizing current which is merely utilized for magnetizing the core and other component of
the source current is consumed for compensating the core losses in transformer. Because of this
core loss component, the source current in transformer on no-load condition supplied from the

DEPARTMENT OF EEE BIT Page 61


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

source as source current is not exactly at 90° lags of supply voltage, but it lags behind an angle θ
is less than 90°. If total current supplied from source is I o, it will have one component in phase
with supply voltage V1 and this component of the current I w is core loss component. This
component is taken in phase with source voltage, because it is associated with active or working
losses in transformer. Other component of the source current is denoted as I μ. This component
produces the alternating magnetic flux in the core, so it is watt-less; means it is reactive part of
the transformer source current. Hence Iμ will be in quadrature with V1 and in phase with
alternating flux Φ.

Hence, total primary current in transformer on no-load condition can be represented as

Now you have seen how simple is to explain the theory of transformer in no-load.

DEPARTMENT OF EEE BIT Page 62


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

TRANSFORMER ON LOAD

Theory of Transformer On Load But Having No Winding Resistance and Leakage


Reactance
Now we will examine the behavior of above said transformer on load, that means load is
connected to the secondary terminals. Consider, transformer having core loss but no copper loss
and leakage reactance. Whenever load is connected to the secondary winding, load current will
start to flow through the load as well as secondary winding. This load current solely depends
upon the characteristics of the load and also upon secondary voltage of the transformer. This
current is called secondary current or load current, here it is denoted as I2. As I2 is flowing
through the secondary, a self mmf in secondary winding will be produced. Here it is N2I2, where,
N2 is the number of turns of the secondary winding of transformer.

This mmf or magneto motive force in the secondary winding produces flux φ 2. This φ2 will
oppose the main magnetizing flux and momentarily weakens the main flux and tries to reduce
primary self induced emf E1. If E1 falls down below the primary source voltage V 1, there will be
an extra current flowing from source to primary winding. This extra primary current I2′ produces

DEPARTMENT OF EEE BIT Page 63


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

extra flux φ′ in the core which will neutralize the secondary counter flux φ 2. Hence the main
magnetizing flux of core, Φ remains unchanged irrespective of load.

So total current, this transformer draws from source can be divided into two components, first
one is utilized for magnetizing the core and compensating the core loss i.e. I o. It is no-load
component of the primary current. Second one is utilized for compensating the counter flux of
the secondary winding. It is known as load component of the primary current. Hence total no
load primary current I1 of a electrical power transformer having no winding resistance and
leakage reactance can be represented as follows

Where θ2 is the angle between Secondary Voltage and Secondary Current of transformer. Now
we will proceed one further step toward more practical aspect of a transformer.

Transformer On Load, With Resistive Winding, But No Leakage Reactance


Now, consider the winding resistance of transformer but no leakage reactance. So far we have
discussed about the transformer which has ideal windings, means winding with no resistance and
leakage reactance, but now we will consider one transformer which has internal resistance in the
winding but no leakage reactance. As the windings are resistive, there would be a voltage drop in
the windings.

DEPARTMENT OF EEE BIT Page 64


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

We have proved earlier that, total primary current from the source on load is I 1. The voltage drop
in the primary winding with resistance, R 1 is R1I1. Obviously, induced emf across primary
winding E1, is not exactly equal to source voltage V1. E1 is less than V1 by voltage drop I1R1.

Again in the case of secondary, the voltage induced across the secondary winding, E 2 does not
totally appear across the load since it also drops by an amount I 2R2, where R2 is the secondary
winding resistance and I2 is secondary current or load current.

Similarly, voltage equation of the secondary side of the transformer will be

Theory of Transformer On Load, With Resistance As Well As Leakage Reactance in


Transformer Windings
Now we will consider the condition, when there is leakage reactance of transformer as well
as winding resistance of transformer.

Let leakage reactances of primary and secondary windings of the transformer are X1 and X2
respectively.

DEPARTMENT OF EEE BIT Page 65


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Hence total impedance of primary and secondary winding of transformer with resistance R 1 and
R2 respectively, can be represented as,

We have already established the voltage equation of a transformer on load, with only
resistances in the windings, where voltage drops in the windings occur only due to resistive
voltage drop. But when we consider leakage reactances of transformer windings, voltage drop
occurs in the winding not only because of resistance, it is because of impedance of transformer
windings. Hence, actual voltage equation of a transformer can easily be determined by just
replacing resistances R1 & R2 in the previously established voltage equations by Z1 and Z2.
Therefore, the voltage equations are,

Resistance drops are in the direction of current vector but, reactive drop will be perpendicular to
the current vector as shown in the above vector diagram of transformer.

Equivalent Circuit of Transformer


Equivalent impedance of transformer is essential to be calculated because the electrical power
transformer is an electrical power system equipment for estimating different parameters of
electrical power system which may be required to calculate total internal impedance of an
electrical power transformer, viewing from primary side or secondary side as per requirement.
This calculation requires equivalent circuit of transformer referred to primary or equivalent
circuit of transformer referred to secondary sides respectively. Percentage impedance is also very
essential parameter of transformer. Special attention is to be given to this parameter during

DEPARTMENT OF EEE BIT Page 66


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

installing a transformer in an existing electrical power system. Percentage impedance of different


power transformers should be properly matched during parallel operation of power transformers.
The percentage impedance can be derived from equivalent impedance of transformer so, it can
be said that equivalent circuit of transformer is also required during calculation of % impedance.

Equivalent Circuit of Transformer Referred to Primary


For drawing equivalent circuit of transformer referred to primary, first we have to establish
general equivalent circuit of transformer then, we will modify it for referring from primary side.
For doing this, first we need to recall the complete vector diagram of a transformer which is
shown in the figure below

Let us consider the transformation ratio be,

In the figure above, the applied voltage to the primary is V 1 and voltage across the primary
winding is E1. Total current supplied to primary is I1. So the voltage V1 applied to the primary is
partly dropped by I1Z1 or I1R1 + j.I1X1 before it appears across primary winding. The voltage

DEPARTMENT OF EEE BIT Page 67


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

appeared across winding is countered by primary induced emf E 1. So voltage equation of this
portion of the transformer can be written as,

The equivalent circuit for that equation can be drawn as below,

From the vector diagram above, it is found that the total primary current I 1 has two components,
one is no - load component Io and the other is load component I2′. As this primary current has
two components or branches, so there must be a parallel path with primary winding of
transformer. This parallel path of current is known as excitation branch of equivalent circuit of
transformer. The resistive and reactive branches of the excitation circuit can be represented as

DEPARTMENT OF EEE BIT Page 68


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

The load component I2′ flows through the primary winding of transformer and induced voltage
across the winding is E1 as shown in the figure right. This induced voltage E 1 transforms to
secondary and it is E2 and load component of primary current I 2′ is transformed to secondary as
secondary current I2. Current of secondary is I2. So the voltage E2 across secondary winding is
partly dropped by I2Z2 or I2R2 + j.I2X2 before it appears across load. The load voltage is V2.

The complete equivalent circuit of transformer is shown below.

Now if we see the voltage drop in secondary from primary side, then it would be ′K′ times
greater and would be written as K.Z2.I2. Again I2′.N1 = I2.N2

Therefore,

From above equation, secondary impedance of transformer referred to primary is,

So, the complete equivalent circuit of transformer referred to primary is shown in the
figure below,

DEPARTMENT OF EEE BIT Page 69


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Approximate Equivalent Circuit of Transformer


Since Io is very small compared to I1, it is less than 5% of full load primary current, I o changes
the voltage drop insignificantly. Hence, it is good approximation to ignore the excitation circuit
in approximate equivalent circuit of transformer. The winding resistance and reactance being in
series can now be combined into equivalent resistance and reactance of transformer, referred to
any particular side. In this case it is side 1 or primary side.

DEPARTMENT OF EEE BIT Page 70


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Equivalent Circuit of Transformer Referred to Secondary


In similar way, approximate equivalent circuit of transformer referred to secondary can be
drawn.

Where equivalent impedance of transformer referred to secondary, can be derived as

Losses in Transformer:

Losses of transformer are divided mainly into two types:


1. Iron Loss

2. Copper Losses
IRON LOSS:
This is the power loss that occurs in the iron part. This loss is due to the alternating frequency of
the emf. Iron loss in further classified into two other losses.
a) Eddy current loss
b) Hysterisis loss

DEPARTMENT OF EEE BIT Page 71


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

a) Eddy Current Loss:


This power loss is due to the alternating flux linking the core, which will induced an emf in the
core called the eddy emf, due to which a current called the eddy current is being circulated in the
core. As there is some resistance in the core with this eddy current circulation converts into heat
called the eddy current power loss. Eddy current loss is proportional to the square of the supply
frequency.
b) Hysterisis Loss:
This is the loss in the iron core, due to the magnetic reversal of the flux in the core, which results
in the form of heat in the core. This loss is directly proportional to the supply frequency.
Eddy current loss can be minimized by using the core made of thin sheets of silicon steel
material, and each lamination is coated with varnish insulation to suppress the path of the eddy
currents. Hysterisis loss can be minimized by using the core material having high permeability.

COPPER LOSS:
This is the power loss that occurs in the primary and secondary coils when the transformer is on
load. This power is wasted in the form of heat due to the resistance of the coils. This loss is
proportional to the sequence of the load hence it is called the Variable loss where as the Iron loss
is called as the Constant loss as the supply voltage and frequency are constants

EFFICIENCY:
It is the ratio of the output power to the input power of a transformer
Input = Output + Total losses
= Output + Iron loss + Copper loss

DEPARTMENT OF EEE BIT Page 72


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

where,
Wcopper is the copper loss at full load
2
Wcopper = I R watts

CONDITION FOR MAXIMUM EFFICIENCY:


In general for the efficiency to be maximum for any device the losses must be minimum.
Between the iron and copper losses the iron loss is the fixed loss and the copper loss is the
variable loss. When these two losses are equal and also minimum the efficiency will be
maximum.
Therefore the condition for maximum efficiency in a transformer
is Copper loss = Iron loss

DEPARTMENT OF EEE BIT Page 73


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

O.C. and S.C. Tests on Single Phase Transformer


The efficiency and regulation of a transformer on any load condition and at any power
factor condition can be predetermined by indirect loading method. In this method, the actual load
is not used on transformer. But the equivalent circuit parameters of a transformer are determined
by conducting two tests on a transformer which are,
1. Open circuit test (O.C Test)
2. Short circuit test (S.C.Test)
The parameters calculated from these test results are effective in determining the
regulation and efficiency of a transformer at any load and power factor condition, without
actually loading the transformer. The advantage of this method is that without much power loss
the tests can be performed and results can be obtained. Let us discuss in detail how to perform
these tests and how to use the results to calculate equivalent circuit parameters.
Open Circuit Test (O.C. Test)
The experimental circuit to conduct O.C test is shown in the Fig. 1.

Fig 1. Experimental circuit for O.C. test

The transformer primary is connected to a.c. supply through ammeter, wattmeter and
variac. The secondary of transformer is kept open. Usually low voltage side is used as primary
and high voltage side as secondary to conduct O.C test.

DEPARTMENT OF EEE BIT Page 74


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

The primary is excited by rated voltage, which is adjusted precisely with the help of a
variac. The wattmeter measures input power. The ammeter measures input current. The
voltemeter gives the value of rated primary voltage applied at rated frequency.
Sometimes a voltmeter may be connected across secondary to measure secondary voltage
which is V2 = E2 when primary is supplied with rated voltage. As voltmeter resistance is very
high, though voltmeter is connected, secondary is treated to be open circuit as voltmeter current
is always negligibly small.
When the primary voltage is adjusted to its rated value with the help of variac, readings of
ammeter and wattmeter are to be recorded.
Let,
Vo = Rated voltage
Wo = Input power
Io = Input current = no load current
As transformer secondary is open, it is on no load. So current drawn by the primary is no
load current Io. The two components of this no load current are,
Im = Io sin Φo
Ic = Io cos Φo
where cos Φo = No load power factor

And hence power input can be written as,

Wo = Vo Io cos Φo

The phasor diagram is shown in the Fig.

Fig.

DEPARTMENT OF EEE BIT Page 75


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

As secondary is open, I2 = 0. Thus its reflected current on primary is also zero. So we have
primary current I1 =Io. The transformer no load current is always very small, hardly 2 to 4 % of
its full load value. As I2 = 0, secondary copper losses are zero. And I 1 = Io is very low hence
copper losses on primary are also very very low. Thus the total copper losses in O.C. test are
negligibly small. As against this the input voltage is rated at rated frequency hence flux density
in the core is at its maximum value. Hence iron losses are at rated voltage. As output power is
zero and copper losses are very low, the total input power is used to supply iron losses. This
power is measured by the wattmeter i.e. Wo. Hence the wattmeter in O.C. test gives iron losses
which remain constant for all the loads.
... Wo = Pi = Iron losses

Calculations : We know that,


Wo = Vo Io cos Φ
cos Φo = Wo /(Vo Io ) = no load power factor
Once cos Φo is known we can obtain,
Ic = Io cos Φo
and Im = Io sin Φo
Once Ic and Im are known we can determine exciting circuit parameters as,
Ro = Vo /Ic Ω
and Xo = Vo /Im Ω
Key Point : The no load power factor cos Φ o is very low hence wattmeter used must be low
power factor type otherwise there might be error in the results. If the meters are connected on
secondary and primary is kept open then from O.C. test we get R o'and Xo' with which we can
obtain Ro and Xo knowing the transformation ratio K.

Short Circuit Test (S.C. Test)


In this test, primary is connected to a.c. supply through variac, ammeter and voltmeter as
shown in the Fig. 3.

DEPARTMENT OF EEE BIT Page 76


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Experimental circuit for O.C. test

The secondary is short circuited with the help of thick copper wire or solid link. As high voltage
side is always low current side, it is convenient to connect high voltage side to supply and
shorting the low voltage side.
As secondary is shorted, its resistance is very very small and on rated voltage it may draw
very large current. Such large current can cause overheating and burning of the transformer. To
limit this short circuit current, primary is supplied with low voltage which is just enough to cause
rated current to flow through primary which can be observed on an ammeter. The low voltage
can be adjusted with the help of variac. Hence this test is also called low voltage test or reduced
voltage test. The wattmeter reading as well as voltmeter, ammeter readings are recorded.
Now the current flowing through the windings are rated current hence the total copper loss is full
load copper loss. Now the voltage supplied is low which is a small fraction of the rated voltage.
The iron losses are function of applied voltage. So the iron losses in reduced voltage test are very
small. Hence the wattmeter reading is the power loss which is equal to full load copper losses as
iron losses are very low.
.
.. Wsc = (Pcu) F.L. = Full load copper loss
Calculations : From S.C. test readings we can write,
Wsc = Vsc Isc cos Φsc
.
.. cos Φsc = Vsc Isc /Wsc = short circuit power factor
2
Wsc = Isc R1e = copper loss
. 2
.. R1e =Wsc /Isc
2 2
while Z1e =Vsc /Isc = √(R1e + X1e )
. 2 2
.. X1e = √(Z1e - R1e )

DEPARTMENT OF EEE BIT Page 77


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Thus we get the equivalent circuit parameters R 1e, X1e and Z1e. Knowing the transformation
ratio K, the equivalent circuit parameters referred to secondary also can be obtained.

Important Note : If the transformer is step up transformer, its primary is L.V. while secondary
is H.V. winding. In S.C. test, supply is given to H.V. winding and L.V is shorted. In such case
we connect meters on H.V. side which is transformer secondary through for S.C. test purpose
H.V side acts as primary. In such case the parameters calculated from S.C. test readings are
referred to secondary which are R2e, Z2e and X2e. So before doing calculations it is necessary to
find out where the readings are recorded on transformer primary or secondary and accordingly
the parameters are to be determined. In step down transformer, primary is high voltage itself to
which supply is given in S.C. test. So in such case test results give us parameters referred to
primary i.e. R1e, Z1e and X1e.
Key point : In short, if meters are connected to primary of transformer in S.C. test, calculations
give us R1e and Z1e if meters are connected to secondary of transformer in S.C. test calculations
give us R2e and Z2e.

Calculation of Efficiency from O.C. and S.C. Tests


We know that,
From O.C. test, Wo = Pi
From S.C. test, Wsc = (Pcu) F.L.

Thus for any p.f. cos Φ2 the efficiency can be predetermined. Similarly at any load which is
fraction of full load then also efficiency can be predetermined as,

where n = fraction of full load

DEPARTMENT OF EEE BIT Page 78


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

where I2= n (I2) F.L.


Calculation of Regulation
From S.C. test we get the equivalent circuit parameters referred to primary or secondary.
The rated voltages V1, V2 and rated currents (I1) F.L. and (I2) F.L. are known for the given
transformer. Hence the regulation can be determined as,

where I1, I2 are rated currents for full load regulation.


For any other load the currents I1, I2 must be changed by fraction n.
.
. . I1, I2 at any other load = n (I1) F.L., n (I2) F.L.
Key Point : Thus regulation at any load and any power factor can be predetermined, without
actually loading the transformer.

Example 1 : A 5 KVA, 500/250 V, 50 Hz, single phase transformer gave the following readings,
O.C. Test : 500 V, 1 A, 50 W (L.V. side open)
S.C. Test : 25 V, 10 A, 60 W (L.V. side shorted)
Determine : i) The efficiency on full load, 0.8 lagging p.f.
ii) The voltage regulation on full load, 0.8 leading p.f.
iii) The efficiency on 60% of full load, 0.8 leading p.f.
iv) Draw the equivalent circuit referred to primary and insert all the values in it.
Solution : In both the tests, meters are on H.V. side which is primary of the transformer. Hence
the parameters obtained from test results will be referred to primary.
From O.C. test,Vo = 500 V, Io = 1 A, Wo= 50 W
.
.. cos Φo = Wo/Vo Io = 50/(500x1) = 0.1
.
.. Ic = Io cos = 1 x 0.1 = 0.1 A

DEPARTMENT OF EEE BIT Page 79


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

and Im = Io sin Φo = 1 x 0.9949 = 0.9949 A


.
.. Ro =Vo /Ic = 500/0.1 = 5000 Ω
and Xo = Vo/Im = 500/0.9949 = 502.52 Ω
and Wo = Pi= iron losses = 50 W
From S.C. test, Vsc = 25 V, Isc = 10 A, Wsc = 60 W
. 2 2
.. R1e = Wsc /Isc = 60/(10) = 0.6 Ω
Z1e = Vsc /Isc = 25/10 = 2.5 Ω
. 2 2
.. X1e= √(2.5 - 0.6 ) = 2.4269 Ω
(I1) F.L. = VA rating/V1
3
= (5 x 10 )/500 = 10 A
and Isc = (I1) F.L.
.
.. Wsc = (Pcu) F.L. = 60 W
i) η on full load, cos = 0.8 lagging

ii) Regulation on full load, cos Φ2 = 0.8 leading

= - 1.95 %
iii) For 60% of full load, n = 0.6 and cos Φ2 = 0.8 leading]
. 2
.. Pcu = copper loss on new load = n x (Pcu) F.L.
2
= (0.6) x 60 = 21.6 W
= 97.103 %
iv) The equivalent circuit referred to primary is shown in the Fig. 4.

DEPARTMENT OF EEE BIT Page 80


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Fig. 4

Example 2 : The open circuit and short circuit tests on a 10 KVA, 125/250 V, 50 Hz, single
phase transformer gave the following results :
O.C. test : 125 V, 0.6 A, 50 W (on L.V. side)
S.C. test : 15 V, 30 A. 100 W (on H.V. side)
Calculate : i) copper loss on full load
ii) full load efficiency at 0.8 leading p.f.
iii) half load efficiency at 0.8 leading p.f.
iv) regulation at full load, 0.9 leading p.f.

Solution : From O.C. test we can weite,


Wo = Pi = 50 W = Iron loss
From S.C. test we can find the parameters of equivalent circuit. Now S.C. test is conducted
on H.V. side i.e. meters are on H.V. side which is transformer secondary. Hence parameters from
S.C. test results will be referred to secondary.
Vsc = 15 V, Isc = 30 A, Wsc = 100 W
. 2 2
.. R2e = Wsc/(Isc) =10/(30) = 0.111Ω
Z1e = Vsc /Isc = 15/30 = 0.5 Ω
. 2 2
.. X2e = √(Z2e - R2e ) = 0.4875 Ω
i) Copper loss on full load
3
(I2) F.L. = VA rating/V2 = (10 x 10 )/250 = 40 A
In short circuit test, Isc = 30 A and not equal to full load value 40 A.
Hence Wsc does not give copper loss on full load

DEPARTMENT OF EEE BIT Page 81


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018
.
..
Wsc = Pcu at 30 A = 100 W
2
Now Pcu α I
2
( Pcu at 30 A)/( Pcu at 40 A) = (30/40)
100/( Pcu at 40 A) = 900/1600
Pcu at 40 A = 177.78 W
.
.. (Pcu) F.L. = 177.78 W
ii) Full load η , cos Φ2 = 0.8

iii) Half load η , cos Φ2 = 0.8


n = 0.5 as half load, (I2) H.L. = 0.5 x 40 = 20

= 97.69%
iv) Regulation at full load, cos Φ = 0.9 leading

= -1.8015%

DEPARTMENT OF EEE BIT Page 82


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Sumpner's Test Or Back-To-Back Test On Transformer


Sumpner's test or back to back test on transformer is another method for
determining transformer efficiency, voltage regulation and heating under loaded conditions.
Short circuit and open circuit tests on transformer can give us parameters of equivalent circuit of
transformer, but they cannot help us in finding the heating information. Unlike O.C. and S.C.
tests, actual loading is simulated in Sumpner's test. Thus the Sumpner's test give more accurate
results of regulation and efficiency than O.C. and S.C. tests.

Sumpner's Test
Sumpner's test or back to back test can be employed only when two identical transformers are
available. Both transformers are connected to supply such that one transformer is loaded on
another. Primaries of the two identical transformers are connected in parallel across a supply.
Secondaries are connected in series such that emf's of them are opposite to each other. Another
low voltage supply is connected in series with secondaries to get the readings, as shown in the
circuit diagram shown below.

DEPARTMENT OF EEE BIT Page 83


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

In above diagram, T1 and T2 are identical transformers. Secondaries of them are connected in
voltage opposition, i.e. EEF and EGH. Both the emf's cancel each other, as transformers are
identical. In this case, as per superposition theorem, no current flows through secondary. And
thus the no load test is simulated. The current drawn from V1 is 2I0, where I0 is equal to no load
current of each transformer. Thus input power measured by wattmeter W1 is equal to iron
losses of both transformers.
i.e. iron loss per transformer Pi = W1/2.

Now, a small voltage V2 is injected into secondary with the help of a low voltage transformer.
The voltage V2 is adjusted so that, the rated current I2 flows through the secondary. In this
case, both primaries and secondaries carry rated current. Thus short circuit test is simulated and
wattmeter W2 shows total full load copper losses of both transformers.
i.e. copper loss per transformer PCu = W2/2.

From above test results, the full load efficiency of each transformer can be given as –

Predetermination of Voltage Regulation


Modern power systems operate at some standard voltages. The equipments working on these
systems are therefore given input voltages at these standard values, within certain agreed
tolerance limits. In many applications this voltage itself may not be good enough for obtaining
the best operating condition for the loads. A transformer is interposed in between the load and
the supply terminals in such cases. There are additional drops inside the transformer due to the
load currents. While input voltage is the responsibility of the supply provider, the voltage at the
load is the one which the user has to worry about.
If undue voltage drop is permitted to occur inside the transformer the load voltage becomes too
low and affects its performance. It is therefore necessary to quantify the drop that takes place
inside a transformer when certain load current, at any power factor, is drawn from its output

DEPARTMENT OF EEE BIT Page 84


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

leads. This drop is termed as the voltage regulation and is expressed as a ratio of the terminal
voltage (the absolute value per se is not too important).
The voltage regulation can be defined in two ways - Regulation Down and Regulation up. These
two definitions differ only in the reference voltage as can be seen below. Regulation down: This
is defined as ‖ the change in terminal voltage when a load current at any power factor is applied,
expressed as a fraction of the no-load terminal voltage.

Expressed in symbolic form we have,

Where,
Vnl is the no-load terminal voltage.
Vl is load voltage.
Normally full load regulation is of interest as the part load regulation is going to be lower.
This definition is more commonly used in the case of alternators and power systems as the user-
end voltage is guaranteed by the power supply provider. He has to generate proper no-load
voltage at the generating station to provide the user the voltage he has asked for. In the
expressions for the regulation, only the numerical differences of the voltages are taken and not
vector differences.

In the case of transformers both definitions result in more or less the same value for the
regulation as the transformer impedance is very low and the power factor of operation is quite
high. The power factor of the load is defined with respect to the terminal voltage on load. Hence
a convenient starting point is the load voltage. Also the full load output voltage is taken from the
name plate. Hence regulation up has some advantage when it comes to its application. Fig. 23
shows the phasor diagram of operation of the transformer under loaded condition. The no-load
current I0 is neglected in view of the large magnitude of I‘2.

DEPARTMENT OF EEE BIT Page 85


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Fig. Regulation of Transformer

DEPARTMENT OF EEE BIT Page 86


LECTURE NOTES ON DC MACHINES AND TRANSFORMER –REGULATION 2015

Fig. Variation of full load regulation with power factor

DEPARTMENT OF EEE BIT Page 87


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Predetermination of Efficiency
Transformers which are connected to the power supplies and loads and are in operation
are required to handle load current and power as per the requirements of the load. An unloaded
transformer draws only the magnetization current on the primary side, the secondary current
being zero. As the load is increased the primary and secondary currents increase as per the load
requirements. The volt amperes and wattage handled by the transformer also increases. Due to
the presence of no load losses and I2R losses in the windings certain amount of electrical energy
gets dissipated as heat inside the transformer. This gives rise to the concept of efficiency.
Efficiency of power equipment is defined at any load as the ratio of the power output to
the power input. Putting in the form of an expression,

While the efficiency tells us the fraction of the input power delivered to the load, the
deficiency focuses our attention on losses taking place inside transformer. As a matter of fact the
losses heat up machine. The temperature rise decides the rating of the equipment.
The temperature rise of the machine is a function of heat generated the structural
configuration, method of cooling and type of loading (or duty cycle of load). The peak
temperature attained directly affects the life of the insulations of the machine for any class of
insulation.

DEPARTMENT OF EEE BIT Page 88


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

Fig. Efficiency

A typical curve for the variation of efficiency as a function of output is given in Fig. The losses
that take place inside the machine expressed as a fraction of the input is sometimes termed as
deficiency. Except in the case of an ideal machine, a certain fraction of the input power gets lost
inside the machine while handling the power. Thus the value for the efficiency is always less
than one. In the case of a.c. machines the rating is expressed in terms of apparent power. It is
nothing but the product of the applied voltage and the current drawn. The actual power delivered
is a function of the power factor at which this current is drawn. As the reactive power shuttles
between the source and the load and has a zero average value over a cycle of the supply wave it
does not have any direct effect on the efficiency. The reactive power however increases the
current handled by the machine and the losses resulting from it. Therefore the losses that take
place inside a transformer at any given load play a vital role in determining the efficiency. The
losses taking place inside a transformer can be enumerated as below:

1. Primary copper loss


2. Secondary copper loss
3. Iron loss
4. Dielectric loss
5. Stray load loss

DEPARTMENT OF EEE BIT Page 89


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

These are explained in sequence below.


Primary and secondary copper losses take place in the respective winding resistances due to the
flow of the current in them

The primary and secondary resistances differ from their d.c. values due to skin effect and
the temperature rise of the windings. While the average temperature rise can be approximately
used, the skin effect is harder to get analytically. The short circuit test gives the value of Re
taking into account the skin effect.
The iron losses contain two components - Hysteresis loss and Eddy current loss. The
Hysteresis loss is a function of the material used for the core.

For constant voltage and constant frequency operation this can be taken to be constant. The eddy
current loss in the core arises because of the induced emf in the steel lamination sheets and the
eddies of current formed due to it. This again produces a power loss Pe in the lamination.

where t is the thickness of the steel lamination used. As the lamination thickness is much
smaller than the depth of penetration of the field, the eddy current loss can be reduced by
reducing the thickness of the lamination. Present day laminations are of 0.25 mm thickness and
are capable of operation at 2 Tesla. These reduce the eddy current losses in the core. This loss
also remains constant due to constant voltage and frequency of operation. The sum of hysteresis
and eddy current losses can be obtained by the open circuit test.

DEPARTMENT OF EEE BIT Page 90


LECTURE NOTES ON ELECTRICAL MACHINES I–REGULATION 2018

The dielectric losses take place in the insulation of the transformer due to the large electric
stress. In the case of low voltage transformers this can be neglected. For constant voltage
operation this can be assumed to be a constant.
The stray load losses arise out of the leakage fluxes of the transformer. These leakage fluxes
link the metallic structural parts, tank etc. and produce eddy current losses in them. Thus they
take place ‘all round‘ the transformer instead of a definite place , hence the name ‘stray‘. Also
the leakage flux is directly proportional to the load current unlike the mutual flux which is
proportional to the applied voltage. Hence this loss is called ‘stray load‘ loss. This can also be
estimated experimentally. It can be modeled by another resistance in the series branch in the
equivalent circuit. The stray load losses are very low in air-cored transformers due to the absence
of the metallic tank

Thus, the different losses fall in to two categories Constant losses (mainly voltage dependant)
and Variable losses (current dependant). The expression for the efficiency of the transformer
operating at a fractional load x of its rating, at a load power factor of Ө2, can be written as

Here S in the volt ampere rating of the transformer (V‘2 I‘2 at full load), Pconst being constant
losses and Pvar the variable losses at full load.

DEPARTMENT OF EEE BIT Page 91


LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

UNIT-V
Transformer Testing and Power
Transformers

DEPARTMENT OF EEE BIT Page 92


5 Testing of Transformers
The structure of the circuit equivalent of a practical transformer is developed earlier. The
performance parameters of interest can be obtained by solving that circuit for any load
conditions. The equivalent circuit parameters are available to the designer of the transformers
from the various expressions that he uses for designing the transformers. But for a user these are
not available most of the times. Also when a transformer is rewound with different primary and
secondary windings the equivalent circuit also changes. In order to get the equivalent circuit
parameters test methods are heavily depended upon. From the analysis of the equivalent circuit
one can determine the electrical parameters. But if the temperature rise of the transformer is
required, then test method is the most dependable one. There are several tests that can be done on
the transformer; however a few common ones are discussed here.

5.1 Winding resistance test


This is nothing but the resistance measurement of the windings by applying a small d.c voltage
to the winding and measuring the current through the same. The ratio gives the winding
resistance, more commonly feasible with high voltage windings. For low voltage windings a
resistance-bridge method can be used. From the d.c resistance one can get the a.c. resistance by
applying skin effect corrections.

7.2 Polarity Test


This is needed for identifying the primary and secondary phasor polarities. It is a must for
poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the
induced emfs. The dot method discussed earlier is used to indicate the polarities. The transformer
is connected to a low voltage a.c. source with the connections made as shown in the fig. 18(a). A
supply voltage Vs is applied to the primary and the readings of the voltmeters V1, V2 and V3 are
noted. V1 : V2 gives the turns ratio. If V3 reads V1−V2 then assumed dot locations are correct
(for the connection shown). The beginning and end of the primary and secondary may then be
marked by A1 −A2 and a1 −a2 respectively. If the voltage rises from A1 to A2 in the primary, at
any instant it does so from a1 to a2 in the secondary. If more secondary terminals are present due
to taps taken from the windings they can be labeled as a3, a4, a5, a6. It is the voltage rising from
smaller number towards larger ones in each winding. The same thing holds good if more
secondaries are present.

Fig. 18(b) shows the d.c. method of testing the polarity. When the switch S is closed if
thesecondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is
correct. If the meter kicks back the assumed polarity is wrong.

5.3 Open Circuit Test

As the name suggests, the secondary is kept open circuited and nominal value of the input
voltage is applied to the primary winding and the input current and power are measured. In Fig.
19(a) V,A,W are the voltmeter, ammeter and wattmeter respectively. Let these meters read V1,
I0 and W0 respectively.Fig. 19(b) shows the equivalent circuit of the transformer under this test.
The no load current at rated voltage is less than 1 percent of nominal current and hence the loss
and drop that take place in primary impedance r1 +jxl1 due to the no load current I0 is
negligible. The active component Ic of the no load current I 0.represents the core losses and
reactive current Im is the current needed for the magnetization. Thus the watt meter reading

The parameters measured already are in terms of the primary. Sometimes the pri- mary voltage
required may be in kilo-Volts and it may not be feasible to apply nominal voltage to primary
from the point of safety to personnel and equipment. If the secondary voltage is low, one can
perform the test with LV side energized keeping the HV side open circuited. In this case the
parameters that are obtained are in terms of LV . These have to be referred to HV side if we need
the equivalent circuit referred to HV side.
LECTURE NOTES ON ELECTRICAL MACHINES I –REGULATION 2018

DEPARTMENT OF EEE BIT Page 96

Short Circuit Test


The purpose of this test is to determine the series branch parameters of the equiv-alent circuit of
Fig. 21(b). As the name suggests, in this test primary applied voltage, the current and power
input are measured keeping the secondary terminals short circuited. Let these values be Vsc, Isc
and Wsc respectively. The supply voltage required to circulate rated current through the
transformer is usually very small and is of the order of a few percent of the nominal voltage. The
excitation current which is only 1 percent or less even at rated voltage becomes negligibly small
during this test and hence is neglected. The shunt branch is thus assumed to be absent. Also

Therefore Wsc is the sum of the copper losses in primary and


secondary put together. The reactive power consumed is that absorbed by the leakage reactance
of the two windings.
5.5 Load Test
Load Test helps to determine the total loss that takes place, when the transformer is loaded.
Unlike the tests described previously, in the present case nominal voltage is applied across the
primary and rated current is drown from the secondary. Load test is used mainly 1. to determine
the rated load of the machine and the temperature rise 2. to determine the voltage regulation and
efficiency of the transformer. Rated load is determined by loading the transformer on a
continuous basis and observ- ing the steady state temperature rise. The losses that are generated
inside the transformer on load appear as heat. This heats the transformer and the temperature of
the transformer increases. The insulation of the transformer is the one to get affected by this rise
in the temperature. Both paper and oil which are used for insulation in the transformer start get-
ting degenerated and get decomposed. If the flash point of the oil is reached the transformer goes
up in flames. Hence to have a reasonable life expectancy the loading of the transformer must be
limited to that value which gives the maximum temperature rise tolerated by the insulation. This
aspect of temperature rise cannot be guessed from the electrical equivalent circuit. Further, the
losses like dielectric losses and stray load losses are not modeled in the equivalent circuit and the
actual loss under load condition will be in error to that extent.
Many external means of removal of heat from the transformer in the form of different cooling
methods give rise to different values for temperature rise of insulation. Hence these permit
different levels of loading for the same transformer. Hence the only sure way of ascertaining the
rating is by conducting a load test. It is rather easy to load a transformer of small ratings. As the
rating increases it becomes difficult to find a load that can absorb the requisite power and a
source to feed the necessary current. As the transformers come in varied transformation ratios, in
many cases it becomes extremely difficult to get suitable load impedance. Further, the
temperature rise of the transformer is due to the losses that take place ‘inside’ the transformer.
The efficiency of the transformer is above 99% even in modest sizes which means 1 percent of
power handled by the transformer actually goes to heat up the machine. The remaining 99% of
the power has to be dissipated in a load impedance external to the machine. This is very
wasteful in terms of energy also. ( If the load is of unity power factor) Thus the actual loading of
the transformer is seldom resorted to. Equivalent loss methods of loading and ‘Phantom’ loading
are commonly used in the case of transformers. The load is applied and held constant till the
temperature rise of transformer reaches a steady value. If the final steady temperature rise is
lower than the maximum permissible value, then load can be increased else it is decreased. That
load current which gives the maximum permissible temperature rise is declared as the nominal or
rated load current and the volt amperes are computed using the same.