95 8616 12.3 - (GT3000)
95 8616 12.3 - (GT3000)
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
GTS Sensor Module . . . . . . . . . . . . . . . . . . . . . . 1 GT3000 Calibration . . . . . . . . . . . . . . . . . . . . . . 12
GTX Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . 2 Calibration Procedure . . . . . . . . . . . . . . . . . . . . 13
Real Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . 2
History/Event Logs . . . . . . . . . . . . . . . . . . . . . . . 2 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
HART Communication . . . . . . . . . . . . . . . . . . . . 3 Routine Inspection . . . . . . . . . . . . . . . . . . . . . . 14
Magnetic Switch . . . . . . . . . . . . . . . . . . . . . . . . . 3 Sensor Module Replacement . . . . . . . . . . . . . . 14
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . . 15
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 15
IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . 5
GTS Gas Sensors . . . . . . . . . . . . . . . . . . . . . . . 15
Calibration Kits for Gas Sensors . . . . . . . . . . . . 15
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Parts & Accessories . . . . . . . . . . . . . . . . . . . . . 15
Identification of Vapor(s) to be Detected . . . . . . . 6
Identification of Detector Mounting Locations . . . 6
Device Mounting Orientation . . . . . . . . . . . . . . . . 6 APPENDIX A — FM APPROVAL DESCRIPTION . . . . 18
Detector Installation . . . . . . . . . . . . . . . . . . . . . . 7
APPENDIX B — CSA CERTIFICATION DESCRIPTION . 20
Sensor Termination Box . . . . . . . . . . . . . . . . . . . 7
APPENDIX C — IECEx APPROVAL DESCRIPTION . 21
WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Power Supply Requirements . . . . . . . . . . . . . . . . 7 APPENDIX D — OTHER APPROVALS . . . . . . . . . . . . . 22
Wiring Cable Requirements . . . . . . . . . . . . . . . . 7
APPENDIX E — SENSOR COMPARISON /
Intrinsic Safety Barriers . . . . . . . . . . . . . . . . . . . . 8 CROSS SENSITIVITY . . . . . . . . . . . . 23
Guidelines for Intrinsic Safety Wiring . . . . . . . . . 8
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 8 APPENDIX F — HART COMMUNICATION . . . . . . . . . 25
Transmitter
(GTX) Detector (GT3000)
Number Definition
0 EMPTY LOG
Transmitter Wiring 1 NOT USED
The GTX transmitter is a two-wire loop powered device 2 NOT USED
that uses a three-wire cable (power, signal, and earth 3 ZERO CAL
ground) for connecting to a controller or monitoring 4 SPAN CAL
device. The use of shielded cable is required. 5 ABORT CAL
6 FAILED CAL
7 NOT USED
REAL TIME CLOCK (RTC)
8 NOT USED
The GTX transmitter has a real time clock with battery 9 INIT CAL LOG
back‑up, that is used for time stamping the event logs. 10 NOT USED
The time and date are set and read using a UD10/UD20 11 CLR CAL FAULTS
Universal Display Unit, a HART communication device,
or AMS software. The time stamp on the logs will not be
correct if the RTC in the transmitter is not set correctly.
12.3 2 95-8616
GT3000
Gas Detector
Transmitter
RTC HART Interface
Event Logs
Sensor Module
Calibration Logs GREEN LED (ON)
Analog
Function Green LED Yellow LED 4-20 Signal
Output
MAGNETIC
SWITCH Warm-up* Single Flash On 3.5***
Normal
Steady On Off 4-20
Operation
Fault
Off On 3.5***
Condition
Calibration Off See Table 5 3.8**
No Power Off Off 0
B2443
*Warm-up time can last up to 150 seconds.
**O2 sensor generates 17.3 mA during calibration.
Figure 2—Location of Magnetic Switch on GT3000 Detector ***2.45 for TYPE OUTPUT "29," reference GTX Model Matrix .
12.3 3 95-8616
SPECIFICATIONS
6.2
(15.8)
5.6
SENSOR AND TRANSMITTER (14.3)
AVAILABLE SENSORS—
Refer to Appendix E.
2.5
(6.4)
CROSS SENSITIVITY—
See Appendix E for Cross Sensitivity information.
CALIBRATION— B2397
Sensors are calibrated at the factory. Gas type and Figure 4—Dimensions of GT3000 Gas Detector in Inches (CM)
range are read by the transmitter. Field calibration is
initiated at the detector, at the UD10/UD20 Universal HUMIDITY RANGE—
Display Unit, or by some other HART interface device. 15 to 90% RH.
WARM-UP—
Warm-up time can last up to 150 seconds.
Appendix:
OPERATING TEMPERATURE— Appendix A - FM
See Appendix E. Appendix B - CSA
Appendix C - IECEx
STORAGE TEMPERATURE— Appendix D - Other Approvals
Transmitter: –55°C to +75°C / –67°F to +167°F.
Sensor: 0°C to +20°C / +32°F to +68°F.
Ideal: +4°C to +10°C / +39°F to +50°F.
12.3 4 95-8616
IMPORTANT SAFETY NOTES LIABILITIES
The manufacturer’s warranty for this product is
CAUTION
void, and all liability for proper function of the
The wiring procedures in this manual are intended
detector is irrevocably transferred to the owner or
to ensure proper functioning of the device under
operator in the event that the device is serviced or
normal conditions. However, because of the
repaired by personnel not employed or authorized
many variations in wiring codes and regulations,
by Detector Electronics Corporation, or if the
total compliance to these ordinances cannot be
device is used in a manner not conforming to its
guaranteed. Be certain that all wiring complies
intended use.
with all local codes. If in doubt, consult the
authority having jurisdiction before wiring the
system. Installation must be done by a properly CAUTION
trained person. Observe precautions for handling electrostatic
sensitive devices.
CAUTION
NOTE
This product has been tested and approved
The sensor housing is made of Polyphthalamide
for use in hazardous areas. However, it must
(PPA), 30% carbon filled (Material Manufacturer
be properly installed and used only under the
RTP). Questions regarding chemical resistance
conditions specified within this manual and
should be addressed to:
the specific approval certificates. Any device
www.det-tronics.com
modification, improper installation, or use in a
US toll free 800-468-3244 or 952-941-5665
faulty or incomplete configuration will render
warranty and product certifications invalid.
CAUTION
To avoid nuisance outputs and/or resets, walkie-
CAUTION
talkie radios and other wireless devices must be
The GT3000 contains no field repairable
operated at a distance greater than 1 meter / 3.3
components. User performed service is limited to
feet from the detector.
replacement of the gas sensor module.
CAUTION
Hazardous location temperature limits exceed
the product operational temperature limits. If the
sensor is exposed to temperatures beyond the
operational temperature limits listed in Appendix
E, then the sensor module (GTS) should be
replaced or a response test, as described in
the GT3000 Safety Manual (95-8685), shall be
performed.
12.3 5 95-8616
INSTALLATION The most effective number and placement of detectors
varies depending on the conditions on site. The individual
The gas detector can be installed either in a stand‑alone designing the installation must often rely on experience
configuration as a loop powered device, or it can be and common sense to determine the detector quantity
connected to a UD10/UD20 Universal Display Unit. and best locations to adequately protect the area. Note
that it is typically advantageous to locate detectors
NOTE where they are accessible for maintenance. Locations
The gas detector housing must be electrically near excessive heat or vibration sources should be
connected to earth ground. A dedicated earth avoided if possible.
ground wire is provided on the transmitter for
connection to earth ground or to a grounded Final suitability of possible gas detector locations
housing. should be verified by a site survey. If any questions
arise regarding installation, please contact the factory.
The detector must always be installed per local
installation code.
DEVICE MOUNTING ORIENTATION
Before installing the gas detector, define the following The gas detector must be mounted in a vertical position
application details: only, with the sensor pointing down (See Figure 5).
CALIBRATION NOTCH
B2436
12.3 6 95-8616
DETECTOR INSTALLATION SENSOR TERMINATION BOX
A Det-Tronics sensor termination box (Model STB)
3/4" NPT Models
is required for installing the sensor in a stand alone
3/4" NPT models have Tapered Threads and no Lock configuration, or for installing the GT3000 remotely
Nut. Install the sensor as follows: from the UD10/UD20 Universal Display Unit.
1. Screw the detector into the appropriate entry on When installing the GT3000 remotely from a UD10/
the termination box. Ensure a minimum of 5 fully UD20, two‑conductor shielded cable is required to
engaged threads. Use of teflon tape on NPT threads prevent possible nuisance EMI/RFI. The maximum
is recommended to prevent thread damage. cable length between the GT3000 and the UD10/UD20
is 2000 ft.
2. When the detector gets tight, note the position of the
LEDs, GND lug and calibration notch and adjust the
detector as required so that the LEDs will be easily WIRING
visible.
POWER SUPPLY REQUIREMENTS
M25 Models
Calculate the total gas detection system power
M25 models have Straight Threads and a Lock Nut. consumption rate in watts from cold start-up. Select a
Install the detector as follows: power supply with adequate capability for the calculated
load. Ensure that the selected power supply provides
1. Screw the detector lock nut as far back as it will go, sufficient regulated and filtered output power for the
then screw the detector into the appropriate entry entire system. If a back-up power system is required, a
on the termination box. Ensure a minimum of 7 fully float‑type battery charging system is recommended. If
engaged threads. an existing source of power is being utilized, verify that
system requirements are met.
2. With the detector in the desired position (LEDs
visible as shown in Figure 5), tighten the lock nut NOTE
against the termination box to hold the detector The power supply must also meet the noise
securely in place. requirements for HART systems.
NOTE
The use of shielded cable in conduit or shielded
armored cable is highly recommended. In
applications where the wiring is installed in
conduit, dedicated conduit is recommended.
Avoid low frequency, high voltage, and
non‑signaling conductors to prevent nuisance
EMI problems.
Set Screws
CAUTION
The use of proper conduit installation techniques,
Figure 6—Location of Lock Nut and Set Screws breathers, glands, and seals is required to prevent
(Metric Models Only)
water ingress and/or maintain the explosion-proof
rating.
12.3 7 95-8616
INTRINSIC SAFETY BARRIERS WIRING PROCEDURE
When the GT3000 is used in an intrinsically safe Wire the transmitter as shown in Figures 7 through 12.
installation, care must be taken when selecting an I.S.
barrier to ensure proper function of the device. The CAUTION
GT3000 has been tested with the types of barriers listed If ripple on the main power source causes
in Tables 3 and 4. interference with the HART function, the use
of an isolated power source (Figure 12) is
Table 3 lists zener barriers. recommended for best HART performance.
Manufacturer P/N
Turck MZB87PX
MTL MTL7787P+
Pepperl & Fuchs Z787.h
Manufacturer P/N
Turck IM33-11Ex-Hi
MTL 5541
Pepperl & Fuchs KCD2-STC-Ex1
Stahl 9160/13-10-11
12.3 8 95-8616
SENSOR TERMINATION BOX
GREEN
+
RED
24 VDC
BLACK
D
–
RE
K
SEE NOTES 2 & 3
AC
BL
SEE NOTE 1
RED
BLACK
A2502
+
INTRINSIC
BARRIER
GREEN
SAFETY
RED
24 VDC
BLACK
D
–
RE
SEE NOTE 1
RED
BLACK
A2530
Figure 8— GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Intrinsically Safe)
12.3 9 95-8616
UD20 DISPLAY UNIT
+ J2-6 +
SEE NOTES 2 & 3 24 VDC
POWER – J2-5 –
LOOP
SHIELD J2-4
SEE NOTE 5
RED +
J2-3
BLACK SENSOR
J2-2 – LOOP
GREEN SEE NOTE 1
J2-1 SHIELD
J2
+ J2-6 +
24 VDC
POWER – J2-5 –
LOOP SEE NOTES 2 & 3
SENSOR TERMINATION BOX
SHIELD J2-4
SEE NOTE 1 SEE NOTE 1
GREEN J2-3 +
RED
BLACK
SENSOR
D
–
RE
J2-2
LOOP
K
AC
BL
J2-1 SHIELD
RED
BLACK
J2
Figure 10—GT3000 with Sensor Termination Box Wired to UD20 Display Unit (Explosion-Proof)
12.3 10 95-8616
NON-HAZARDOUS LOCATION HAZARDOUS LOCATION
BLACK
RED
UD10
DISPLAY UNIT GREEN
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
Output Loop SEE NOTE 1
Connector
HIGH ALARM COM J4-1
P1-3 4-20 mA +
HIGH ALARM NC J4-2
Relay Connector
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
24 VDC –
24 VDC –
24 VDC +
24 VDC +
250 24 VDC MODBUS
SHIELD
SHIELD
J4
OHMS + Connector
MINIMUM
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
P12
Power Supply Connector
Notes: Resistor may be external if voltage input card is used. NOTE 1 CONNECT THE GREEN DETECTOR LEAD
Sinking resistance at PLC must be 250 ohms minimum TO THE CHASSIS GROUND LUG ON THE
INSIDE BOTTOM OF THE DISPLAY UNIT
for HART communication.
ENCLOSURE.
Figure 11—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Non-Isolated Sourcing Output
BLACK
RED
UD10
DISPLAY UNIT GREEN
Sensor Connector
J3-1
J3-2
J3-3
J3-4
J3-5
J3
CALIBRATE
24 VDC –
SHIELD
24 VDC +
4-20 mA
P1-1 SHIELD
AUX ALARM NC J4-5
P1
AUX ALARM NO J4-6
24 VDC +
24 VDC +
SHIELD
J4
OHMS + Connector
MINIMUM
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
P2
P12
Power Supply Connector NOTE 1 CONNECT THE GREEN DETECTOR
LEAD TO THE CHASSIS GROUND
LUG ON THE INSIDE BOTTOM OF
Notes: Resistor may be external if voltage input card is used. THE DISPLAY UNIT ENCLOSURE.
Sinking resistance at PLC must be 250 ohms minimum
for HART communication. – NOTE 2 JUNCTION BOXES MUST BE
24 VDC ELECTRICALLY CONNECTED
C2479 +
TO EARTH GROUND.
Figure 12—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Isolated Sourcing Output
12.3 11 95-8616
CALIBRATION The calibration process proceeds automatically after
initiation. Onboard LEDs signal the operator when to
GT3000 CALIBRATION apply the calibration gas and inform of the progress.
The GT3000 supports one person calibration, which The calibration can be aborted by activating the
can be initiated locally using a calibration magnet, or magnetic switch or with a command from the HART
remotely with a command from the HART interface. communication device in lieu of applying the calibration
The calibration process is automatic, with the exception gas.
of gas delivery. LEDs on the transmitter guide the
operator when to apply and remove the calibration gas If the calibration process takes longer than 10 minutes,
See Table 5. the detector will time-out and signal a calibration fault.
All GT3000 gas detectors require a two-point The calibration process can fail for the following
calibration — zero and span. The calibration process causes:
can be initiated using the magnetic switch or through a • Zero is out of range
HART interface, such as the UD10/UD20. All sensors,
• Span is out of range
including oxygen, should be in clean air (20.9% oxygen)
when the calibration sequence is initiated. • Time-Out.
12.3 12 95-8616
CALIBRATION PROCEDURE NOTE
The calibration procedure must be completed
NOTE
within a ten minute period. If the calibration is not
When attaching or removing the calibration cup,
completed, a calibration fault will be generated
push or pull the cup with a slight clockwise twist.
and the transmitter will continue to use the
Turning counterclockwise can cause the filter
previous calibration data.
assembly on the GT3000 to loosen. If the filter
assembly is inadvertently loosened, tighten it by
NOTE
hand (no tools required).
To ensure reliable detection performance,
calibration should be performed at regularly
Toxic and Hydrogen Sensors scheduled intervals. Various factors affect the
time interval between periodic calibrations
1. Clean air must be present at the GT3000 sensor (typically 30, 60, or 90 day intervals, depending
module prior to initiating calibration. The use of on the ambient conditions).
bottled air is recommended.
NOTE
2. Initiate calibration by momentarily holding the Calibration of ammonia sensor is recommended
calibration magnet against the designated location any time the sensor has been exposed to 90 ppm
on the sensor module (see Figure 13) until the ammonia.
green LED turns off and the yellow LED turns on
steady (approximately one second). Remove
the magnet when the green LED turns off. The Oxygen Sensor
detector immediately begins taking zero readings. 1. Using the magnet, activate the magnetic calibration
Calibration can also be initiated via HART interface switch on the GT3000. The green LED turns off and
(see Appendix F) or the UD10 (see manual number the yellow LED turns on steady.
95-8618).
2. The device automatically performs the zero
3. When the zero calibration is complete, the yellow calibration.
LED changes from steady to blinking. Apply the
calibration gas to the sensor. 3. When the yellow LED on the GT3000 flashes, the
device automatically performs the span calculation.
4. When the yellow LED turns off, remove the calibration If using bottled 20.9% oxygen, apply immediately.
gas. The gas level at the sensor gradually returns to
zero. The green LED turns on steady to indicate that 4. After successful calibration, the yellow LED turns off
the device has returned to normal operation, using and the green LED turns on steady to indicate that
the new calibration data. the device has returned to normal operation, using
the new calibration data. Remove calibration gas (if
used).
LED
B2452
12.3 13 95-8616
MAINTENANCE IMPORTANT
Always exercise caution when working in
NOTE combustible gas areas. Follow replacement
Refer to the GT3000 Safety Manual (number instructions explicitly.
9 5 - 8 6 8 5 ) fo r s p e c i fi c re q u i re m e n t s a n d
recommendations applicable to the proper NOTE
installation, operation, and maintenance of all Removing the sensor module with power applied
certified SIL 2 capable GT3000 gas detectors. will result in a fault condition until a new sensor
module of the same type is installed. When
replacing an oxygen sensor, this action will result
ROUTINE INSPECTION
in an alarm condition as the decreasing 4–20 mA
The gas inlet to the sensor should be inspected signal passes through the alarm range. Inhibit
periodically, or during scheduled maintenance, to response devices to prevent unwanted actuation.
ensure that external obstructions such as plastic bags,
litter, heavy oil and tar, paint, mud, snow, or other NOTE
materials do not block the flow of gas to the sensor, Oxygen (O2) electrochemical sensors contain
thereby impairing the performance of the device. lead (Pb). Observe all local waste management
requirements when disposing of exhausted O2
To replace a dirty or damaged filter, simply grasp the electrochemical sensors.
filter assembly and twist counterclockwise to remove.
Screw the new filter in place on the sensor module. Do NOTE
not overtighten. See Figure 14. Electrochemical sensors are highly sensitive
to antiseptic wipes and/or cleaning products
To ensure reliable protection, it is important to check and that contain alcohol and antibacterial/antiviral
calibrate the detection system on a regularly scheduled agents. Antiseptic products should be removed
basis. The frequency of these checks is determined by from areas where sensors are stored, handled,
the requirements of the particular installation – typically or used. If antiseptic products are being used on
30, 60, or 90 day intervals, depending on the ambient workers' hands, sufficient time should be allowed
conditions. for the alcohol to evaporate before handling
sensors.
SENSOR MODULE REPLACEMENT
(Live Maintenance)
The hot swappable, intrinsically safe sensor module
can be replaced in the field without removing power or
de‑classifying the hazardous area.
A2481 B2451
Figure 14—GT3000 with Replaceable Filter Removed Figure 15—Location of Screws for Sensor Module Replacement
12.3 14 95-8616
DEVICE REPAIR AND RETURN
*Oxygen detector for O2 depletion (< 21% V/V) only.
Prior to returning devices, a Return Materials Oxygen sensor will indicate a fault if <1% volume
Authorization (RMA) number must be obtained. The oxygen is detected.
process for obtaining this number can be found here
(www.det-tronics.com/Products/repair-and-warranty- CALIBRATION KITS FOR GAS SENSORS
services). You may also contact your authorized local Part Number Gas / Concentration
sales representative or Det-Tronics Technical Support 010274-001 H2S / 10 ppm
for assistance: 010274-002 H2S / 25 ppm
010274-003 H2S / 50 ppm
+1 800.765.3473, ext.3 010274-008 H2 / 500 ppm
+1 952.941.5665 010274-009 O2 / 20.9%
M-F, 8 AM - 5 PM, Central Prevailing Time, US 010274-010 CO / 50 ppm
RMA@Det-Tronics.com 010274-011 CO / 250 ppm
010274-005 NH3 / 50 ppm
Pack the unit properly. Always use sufficient packing 010274-006 NH3 / 250 ppm
material. Where applicable, use an antistatic bag as 010274-013 SO2 / 10 ppm
protection from electrostatic discharge. 010274-014 SO2 / 50 ppm
010274-004 Cl2 / 5 ppm
NOTE 010274-016 NO2 / 10 ppm
Inadequate packaging that ultimately causes Replacement gas cylinders for all calibration kits are
damage to the returned device during shipment available.
will result in a service charge to repair the damage
incurred during shipment.
PARTS & ACCESSORIES
Return all equipment transportation prepaid to the Part Number Description
factory in Minneapolis. 009700-001 Magnetic Tool
009737-001 Calibration Cup
NOTE 107427-059 Calibration Cup O-ring
It is highly recommended that a complete spare 101678-007 3 Foot Tubing
be kept on hand for field replacement to ensure 162552-001 Regulator, 1 LPM
continuous protection. 009640-001 Replacement Filter
012509-001 Q312 Sample Draw without Fittings
ORDERING INFORMATION 012509-002 Q312 Sample Draw with Fittings
010780-003 GT3000 Remote Calibration Adaptor
Sensor module (GTS) and transmitter (GTX) must be 010783-001 GT3000 Remote Calibration Filter
ordered separately. Refer to the Transmitter and Sensor 012513-XXX* Q912 Duct Mount Enclosure, M25
Model Matrix on next page for ordering details. 012514-XXX* Q912 Duct Mount Enclosure, 3/4"
*Refer to the Product Catalog for a list of options.
GTS GAS SENSORS
Gas Concentration
Hydrogen Sulfide (H2S) 0-20 ppm
Hydrogen Sulfide (H2S) 0-50 ppm
Hydrogen Sulfide (H2S) 0-100 ppm
Oxygen (O2)* 1-25% V/V
Carbon Monoxide (CO) 0-100 ppm
Carbon Monoxide (CO) 0-500 ppm
Ammonia (NH3) 0-100, or 0-500 ppm
Sulfur Dioxide (SO2) 0-20 ppm
Sulfur Dioxide (SO2) 0-100 ppm
Chlorine (Cl2) 0-10 ppm
Hydrogen (H2) 0-1000 ppm
Nitrogen Dioxide (NO2) 0-20 ppm
12.3 15 95-8616
GTS Sensor Model Matrix
MODEL DESCRIPTION
GTS Gas Sensor Module
TYPE GAS / RANGE
H2S+ Hydrogen Sulfide (certified SIL 2 capable)
20P 0 - 20 PPM
50P 0 - 50 PPM
100P 0 - 100 PPM
CL2 Chlorine
10P 0 - 10 PPM
NH3 Ammonia
100P 0 - 100 PPM
500P 0 - 500 PPM
H2 Hydrogen
1000P 0 - 1000 PPM
O2 Oxygen (certified SIL 2 capable)
25V 0 - 25 % by Vol
CO Carbon Monoxide
100P 0 - 100 PPM
500P 0 - 500 PPM
SO2+ Sulfur Dioxide
20P 0 - 20 PPM
100P 0 - 100 PPM
NO2 Nitrogen Dioxide
20P 0 - 20 PPM
TYPE SAFETY INTEGRITY LEVEL
S SIL 2
N NON-SIL
TYPE LABEL
C CHINESE
E ENGLISH
K KAZAKH
P PORTUGUESE (Brazil)
R RUSSIAN
TYPE HOUSING
S STANDARD
ENHANCED
E
SHIELDING
12.3 16 95-8616
GTX Transmitter Model Matrix
MODEL DESCRIPTION
GTX Gas Transmitter
TYPE MATERIAL
S Stainless Steel (316)
TYPE THREAD SIZE
N 3/4" NPT
M Metric M25
TYPE OUTPUTS
26 4-20 mA, HART (3.5 mA FAULT)
29 4-20 mA, HART (2.45 mA FAULT)
TYPE APPROVALS
B INMETRO (Brazil)
K KAZAKH
N FM/CSA/IEXEx
R RUSSIA
Y CHINA
TYPE CLASSIFICATION (Division/Zone)
4 Intrinsically Safe
5 Explosion-Proof
12.3 17 95-8616
APPENDIX A
FM APPROVAL DESCRIPTION
APPROVAL
Electrochemical Gas Detector, GT3000 Series.
12.3 18 95-8616
APPROVED ACCESSORIES
12.3 19 95-8616
APPENDIX B
CSA CERTIFICATION DESCRIPTION
The following items, functions, and options describe the CSA approval.
APPROVAL
Electrochemical Gas Detector, GT3000 Series.
12.3 20 95-8616
APPENDIX C
IECEx APPROVAL DESCRIPTION
The following items, functions, and options describe the IECEx approval.
APPROVAL
Electrochemical Gas Detector, GT3000 Series.
12.3 21 95-8616
APPENDIX D
OTHER APPROVALS
The following items, functions, and options describe various other approvals applicable to the GT3000.
SIL APPROVAL
IEC 61508
Certified SIL 2 Capable.
SIL Certification includes H2S and O2 GTS models only. For specific information regarding SIL models, refer to the
GT3000 Safety Reference Manual, form 95-8685.
INMETRO (BRAZIL)
DNV
Type Approval Certificate TAA000002D (O2);
TAA000002F (CO & H2S)
12.3 22 95-8616
APPENDIX E
1 Time to reach percentage of final reading when gas concentration equal to full scale is applied to sensor.
2 Background concentrations of ammonia may shorten lifetime of sensor.
3 Sensor approved for oxygen depletion (< 21% V/V) only.
4 Factory Mutual Performance Approved.
5 Oxygen sensor will indicate a fault if <1% volume oxygen is detected
12.3 23 95-8616
Typical Cross Sensitivity of H2S Sensor (0-20 ppm / 0-50 ppm / 0-100 ppm)
Reading
Gas Concentration
H2S H2S+
Carbon monoxide 300 ppm ≤ 2 ppm ≤ 2 ppm
Sulfur dioxide 5 ppm ~ 1 ppm ~ 0 ppm
Nitric oxide 35 ppm < 0.7 ppm ~ 0 ppm
Hydrogen 10000 ppm ≤ 10 ppm
Ammonia 50 ppm ~ 0 ppm
Nitrogen dioxide 5 ppm ~ –1 ppm ~ 0 ppm
Methanol 200 ppm ~ 0 ppm ~ 0 ppm
Typical Cross Sensitivity of NH3 Sensor (0-100 ppm) Typical Cross Sensitivity of NH3 Sensor (0-500 ppm)
Typical Cross Sensitivity of CO Sensor (0-100 ppm / 0-500 ppm) Typical Cross Sensitivity of SO2 Sensor (0-20 ppm / 0-100 ppm)
Typical Cross Sensitivity of Cl2 Sensor (0-10 ppm) Typical Cross Sensitivity of NO2 Sensor (0-20 ppm)
For details on other interfering gases, please contact Detector Electronics Corp.
12.3 24 95-8616
APPENDIX F
HART COMMUNICATION
12.3 25 95-8616
12.3
General Info
26
Enable 5) Min Temp Time
Change Password 1) Sensor Sensitivity xxxxx
2) Sensor Type xxxxx Cal Log
Hart Option Menu 3) Snsr Serial Num xxxxx
Calibration Menu
4) Snsr Revision xxxxx Cal Log:
Change Password 5) PV USL xxxxx Index xxxx
1) Cal Gas Concentraton xx 1) Tag xxxxx
6) PV LSL xxxxx DD-MM-YY xx-xx-xx
2) Sensor Calibration 2) Descriptor xxxxx
xxxxxxxx 7) Snsr Hardware Rev hh:mm:ss xx:xx:xx
3) Response Factor xxx 3) Message xxxxx
8) Snsr Firmware Rev Cal Code xx
4) Snsr Cal Point Zero xxx 4) Poll Adrs xxxxx
9) Snsr Run Hours xxxxx Zero Value xx
5) Snsr Cal Point Span xxx 5) Date xxxxx
Snsr PPM Hours xxxxx Span Value xx
6) Change Gas Sensor Type 6) Final asmbly num xxxx
Event Log
History Info
Event Log:
1) Snsr History
Index xxxx
2) Tx History
DD-MM-YY xx-xx-xx
3) Read Calibration Log
Test Menu RTC Menu hh:mm:ss xx:xx:xx
4) Read Event Log
Event Code xx
1) Self Test 1) Seconds
2) Response Test 2) Minutes
3) Reset 3) Hours Debug Menu DD Build Version
4) Reset min-max Temps 4) Day
5) Loop Test 5) Month 1) Debug Hart Err Cntr xxxx GT3000 DD
6) D/A Trim 6) Year 2) Debug Modbus Err Cntr Build Version: xx.xx
3) DD Build Version Build Date: xxxxxx
95-8616
APPENDIX G
12.3 27 95-8616
INTRINSIC SAFETY CONTROL DRAWING — CSA
009803-002 Rev. B
12.3 28 95-8616
EXPLOSION PROOF CONTROL DRAWING — FM
012555-001 Rev. A
12.3 29 95-8616
95-8616
FlexSonic ™ Acoustic X3301 Multispectrum PointWatch™ Eclipse ® IR FlexVu ® Universal Display Eagle Quantum Premier ®
Leak Detector IR Flame Detector Combustible Gas Detector with GT3000 Toxic Gas Detector Safety System