Report of Inspection / Test

Annual NFPA 25

2023-08-07 Conducted by: Tom Frink


Property
COLONIAL PARK ELEMENTARY SCHOOL Impact Fire Services - Hudson
6350988
Building #: 21352565
30 AVALON RD
STONEHAM MA 02180
Inspection Ref #: 27076045

Report of Inspection / Test General Questions


OWNER SECTION
Is the building occupied? Yes Has the occupancy classification, hazard of contents, Yes
and/or storage method remained the same since the
last inspection?

Are all fire protection systems in service? Yes Has the system remained in service without Yes
modification since the last inspection?

Was the system free of actuations of devices or alarms Yes


since the last inspection?

Copyright 2023 Inspect Point


Page 1 of 7
Report of Inspection / Test
Annual NFPA 25

2023-08-07 Conducted by: Tom Frink


Property
COLONIAL PARK ELEMENTARY SCHOOL Impact Fire Services - Hudson
6350988
Building #: 21352565
30 AVALON RD
STONEHAM MA 02180
Inspection Ref #: 27076045

Report of Inspection / Test for System - 4” CSC


Fire Department Connection
Is the FDC plainly visible? Yes Is the FDC easily accessible? Yes

Is the FDC identification sign(s) in place? Yes Are the FDC swivels and couplings not damaged? Yes

Are the FDC caps and plugs in place and undamaged? Yes Has the interior of the FDC been inspected for Yes
obstructions?

Are the FDC gaskets in place? Yes Is the FDC check valve free of leaks? Yes

Is the visible piping supplying the FDC undamaged? Yes Is the clapper and automatic drain valve in place and Yes
properly operating?

Sprinkler Heads
Are there proper number and type of spare sprinklers Yes Are there spare sprinkler head(s) and applicable Yes
with a list in place? wrench(es) for all types, makes and model sprinklers
installed in the system?

Are all the sprinklers dated 1920 or later? Yes Standard response sprinklers 50 or more years replaced N/A
or successfully sample tested within last 10 years?

Date that standard response sprinklers 50 or more years N/A Standard response sprinklers 75 or more years old N/A
were last tested: replaced or successfully sample tested within last 5
years?

Date that standard response sprinklers 75 or more years N/A Fast response sprinklers 20 or more years old replaced Yes
were last tested: or successfully sample tested within last 10 years?

Date that fast response sprinklers were tested or 2023 Dry-type sprinklers replaced or successfully sample N/A
replaced: tested within last 10 years?

Date that dry-type sprinklers were last tested: N/A Have sprinklers subject to harsh environments OR 325 N/A
degrees or higher been replaced or successfully sample
tested in the last 5 years?

Date that sprinklers subject to harsh environments were N/A If a sprinkler failed a sample test were all the sprinklers Yes
last tested: represented by that sample replaced

Are visible sprinklers free of foreign materials including Yes Are visible sprinklers in the proper position: upright, Yes
foreign paint? pendent, sidewall?

Is there proper clearance below the sprinklers? Yes Is there liquid in all visible glass bulb sprinklers? Yes

Sprinklers and spray nozzles protecting commercial N/A


cooking equipment and ventilating systems replaced
except for bulb-type which show no signs of grease
buildup?

Pipes
Does visible pipe have no external loads? Yes Are the visible pipe and fittings in good condition with Yes
no external corrosion?

Do visible pipe and fittings have no mechanical damage Yes Are visible pipe hangers, supports, and seismic braces Yes
or leaks? not damaged or loose?

Copyright 2023 Inspect Point


Page 2 of 7
Report of Inspection / Test
Annual NFPA 25

2023-08-07 Conducted by: Tom Frink


Property
COLONIAL PARK ELEMENTARY SCHOOL Impact Fire Services - Hudson
6350988
Building #: 21352565
30 AVALON RD
STONEHAM MA 02180
Inspection Ref #: 27076045

Is the pipe through freezers free if any ice blockage? N/A

Control Valve(s)
Are the control valves with electrical supervision/locks Yes Are the control valves with electrical supervision/locks Yes
accessible? properly identified?

Are the control valves with electrical supervision/locks, is Yes Are the control valves with electrical supervision/locks in Yes
the supervision in place? correct (open or closed) position?

All control valves operated through full range and Yes Have post indicating valves been opened until spring or N/A
returned to normal position? torsion felt in the rod and then closed back 1/4 turn?

Do the control valves (PIV) with electrical N/A


supervision/locks have the appropriate wrenches?

Riser Area
Is the information sign in place and legible indicating any No Is the sprinkler room maintained at a minimum of 40 Yes
antifreeze, dry systems, pre-action systems, auxiliary degrees F?
system controls valves, floor control and sectional
valves, heat tape, and low point drains?

Is the hydraulic name plate (calculated systems) or pipe Yes Are the gauges on system showing normal water supply Yes
schedule sign attached securely to the riser and legible? pressure?

Are the gauges on system operable and in good working Yes Date of gauges: 2023
condition?

Is the trim/valves in correct (open or closed) position? Yes Is there no leakage in the retarding chamber or drains? Yes

Are alarms and supervisory devices not damaged? Yes Is the riser valve free from physical damage? Yes

Are Pressure reducing valves (sprinkler system) in open N/A Are Pressure reducing valves in good condition including N/A
position and not leaking? no handwheels broken?

Are Pressure reducing valves (sprinkler system) with N/A Have pressure reducing valves passed partial flow test? N/A
downstream pressure per the design?

Backflow Preventers
Backflow Preventer Make: 4" Backflow Preventer Size: Ames

Backflow Preventer Model: 2000ss Have backflow devices passed forward flow test? Yes

Is the relief port on RPZ device not discharging N/A The reduced pressure backflow preventer (indicate size, N/A
make, and model) is missing the air gap drain cup and
piping to a safe discharge. Is there an air gap in place
and proper drain?

Maintenance
Has an internal investigation of the pipe been Yes Date that the last internal pipe investigation was 2023
performed in the last 5 years? (If no, conduct performed:
investigation)

Are there conditions found that warrant flushing of the N/A Was flushing of the system conducted? N/A
system?

Copyright 2023 Inspect Point


Page 3 of 7
Report of Inspection / Test
Annual NFPA 25

2023-08-07 Conducted by: Tom Frink


Property
COLONIAL PARK ELEMENTARY SCHOOL Impact Fire Services - Hudson
6350988
Building #: 21352565
30 AVALON RD
STONEHAM MA 02180
Inspection Ref #: 27076045

What date was the flushing conducted? N/A Has the the piping from the fire department connection Yes
to the fire department check valve been hydrostatically
tested at 150 psi (10 bar) for 2 hours at least once in the
last 5 years?

Date the piping from the fire department connection to 2023 If sprinklers have been replaced, were they proper Yes
the fire department check valve has been hydrostatically replacements?
tested?

Have backflow preventers been internally inspected to Yes If so, what date was backflow internally inspected? 2023
verify all components are in good condition, operate
correctly and move freely at least once in the last 5
years?

Operating stem of all OS&Y valves lubricated, completely Yes Was a drain test conducted after opening any closed Yes
closed and reopened? valve?

Date the drain test was conducted: 9/7/23 Have adjusted, repaired, reconditioned, or replaced N/A
components had proper tests/inspections performed?

Was heat tape inspected per the manufacturer's N/A Are the pressure relief valves of wet systems that are N/A
instructions? looped or gridded, in good condition and properly piped
to drain safely?

Were marine systems normally having fresh water N/A


drained and refilled twice if raw water got into the
system?

Alarms and Supervisorys


Have the mechanical waterflow alarm devices passed Yes The electrical waterflow alarm devices/pressure switches Yes
tests by opening inspector's test connection/bypass passed test by opening inspector's test
connection with alarms actuating and flow observed for connection/bypass connection with alarms actuating
5 minutes? and flow observed?

Do valve supervisory switches indicate movement? Yes

MAIN DRAIN FLOW TESTS


System Initial Static Residual Static Seconds to Flow Did waterflow Are results
Return to Observed? alarm operate? comparable
Initial Static to previous
test?

4” CSC 75 65 75 2 Yes Yes Yes

INSPECTORS TEST CONNECTION


System Location Description Time Reported? Smooth Easily Signs? Pass?
to Orifice Accessible
Alarm
(seconds)

4” CSC Telle/catv off 1” gate valve Yes Yes Yes Yes Yes
storage 119A

Copyright 2023 Inspect Point


Page 4 of 7
Report of Inspection / Test
Annual NFPA 25

2023-08-07 Conducted by: Tom Frink


Property
COLONIAL PARK ELEMENTARY SCHOOL Impact Fire Services - Hudson
6350988
Building #: 21352565
30 AVALON RD
STONEHAM MA 02180
Inspection Ref #: 27076045

VALVES
Tam
Valve Ope Easily Stems Flow per
System Description Location Type Size Secured n Accessible Signs Exercised Lubricated Pass Pass

4” CSC City side Before OS&Y 4" Supervision Yes Yes Yes Yes Yes Pass Pass
shut off Backflow

4” CSC System side After Backflow OS&Y 4" Supervision Yes Yes Yes Yes Yes Pass Pass
shut off

4” CSC Grooved Fdc Sprinkler riser Fdc Check Yes Yes Yes Yes Yes Pass Pass
check Valve

DRAIN VALVES
System Description Location Drain Aux Drain Drained Water Flow Observed

4” CSC 2” main drain Riser Ball Valve Yes Yes

Copyright 2023 Inspect Point


Page 5 of 7
Report of Inspection / Test
Annual NFPA 25

2023-08-07 Conducted by: Tom Frink


Property
COLONIAL PARK ELEMENTARY SCHOOL Impact Fire Services - Hudson
6350988
Building #: 21352565
30 AVALON RD
STONEHAM MA 02180
Inspection Ref #: 27076045

Deficiencies - General Questions

None

Deficiencies - General Wet System Questions

None

Deficiencies - 4” CSC
Deficiency #1

Sprinkler Type: Wet


Is the information sign in place and legible indicating any antifreeze, dry
systems, pre-action systems, auxiliary system controls valves, floor control
and sectional valves, heat tape, and low point drains?: No

Notes:

Deficiencies - Inspectors Test Connection

None

Deficiencies - Valves

None

Deficiencies - Drain Valves

None

Copyright 2023 Inspect Point


Page 6 of 7
Report of Inspection / Test
Annual NFPA 25

2023-08-07 Conducted by: Tom Frink


Property
COLONIAL PARK ELEMENTARY SCHOOL Impact Fire Services - Hudson
6350988
Building #: 21352565
30 AVALON RD
STONEHAM MA 02180
Inspection Ref #: 27076045

Client Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in
operational condition upon completion of this inspection except as noted.

Client Name Signature Date Completed

Mod 2023-08-07

Copyright 2023 Inspect Point