cMT-G03 series
Installation Instruction
1 Installation and Startup Guide
This document covers the installation of cMT-G03 Series HMI, for the detailed specifications and
operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all
warnings, precautions, and instructions on the device carefully before use.
Install Environment:
The HMI product has been tested to conform to European CE requirements. This 4 Power Connections
Electrical means that the circuitry is designed to resist the effects of electrical noise. This
Environment does not guarantee noise immunity in severe cases. Proper wire routing and Power Connector Specifications:
Wire AWG: 24~12
grounding will insure proper operation. Wiring Conductor Minimum Temperature: 75°C
(1) Make sure that the units are installed correctly and that the operating limits Screw Torque: 4.5 lbf-in (max.)
are followed. Avoid installing units in environments where severe Copper conduct only.
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to Spécifications du connecteur d'alimentation:
flammable gases, vapors or dusts. AWG de fil: 24 ~ 12
Environmental Température minimale du conducteur de câblage: 75°C
(3) Do not install the unit where acid gas, such as SO2 exists.
Considerations Couple de vis: 4.5 lbf-in (max.)
(4) This device should be mounted in the vertical position and for use on the flat
Conducteur en cuivre seulement
surface enclosure.
(5) Conform to UL 61010-2-201 safety requirement for use in Pollution Degree NOTE:
2 Environment and dry location. 1. Connect positive DC line to the ‘+’ terminal and the DC
(6) Relative Humidity: 10% ~ 90% (non-condensing) ground to the ‘-’ terminal.
Cleaning Clean the device using dry cloths. Do not use liquid or spray detergents for
Considerations cleaning.
IP rating IP 20
5 System Settings
Protection impairment if used in a manner not specified by the manufacturer.
Warning Déficit de protection si utilisé d'une manière non spécifiée par le fabricant.
2 Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the supplier.
NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it
fall may cause damage.
The package includes:
(1) Installation Instruction, 2-sided A4 *1
(2) cMT-G03 *1
(3) Power Connector *1
(4) COM Port Terminal 16-pole
3 Installation Instructions
Rail mounting: DIN rail 35mm
Panel mounting: Use two M4 or #8 panhead screws, mounting hole size is 4.6mm
Plan for adequate space around the unit and inside the enclosure, for ventilation and cables. Consider
the heat from other devices inside the enclosure. The ambient temperature around the unit must be 0 ~
50°C
cMT-G03 can be configured by the following ways.
Way1. Connect cMT-G03 with a PC, and on the PC NOTE: Make sure that all local and national electrical standards are met when
open a web browser and then enter: CAUTION installing the unit. Contact your local authorities to determine which codes apply.
http://169.254.0.1, Use power output that meets SELV (Safety Extra-Low Voltage) requirements. The unit can be
password: 111111. powered by DC power only, voltage range: 10.5~28VDC, compatible with most controller DC
Power
systems. The power conditioning circuitry inside the unit is accomplished by a switching power
Way2. Find cMT-G03 IP in Utility Manager, and supply. The peak starting current can be as high as 500mA.
then use web browser on PC to log in.
If the Power LED does not light up immediately after power up, remove power. A resettable
Fusing Require-
The page opened can be used to download /upload fuse will protect against overcurrent faults in DC circuit and the resetting will take place after a
ments period of time. Check wiring for proper connections and try to power up again.
project files, change network IP or password, and
more. A resettable fuse will prevent damage for overcurrent condition however it isn’t guaranteed.
High Voltage DC voltage sources should provide proper isolation from main AC power and similar hazards.
6 EasyBuilder Pro Software Settings A Hard-wired EMERGENCY STOP should be fitted in any system using an HMI to comply with
Emergency Stop
ICS Safety Recommendations.
Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download
dialog box: Select Ethernet > IP tab > Enter your HMI IP > Click Download to download this project Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
Supply Voltage
file to HMI. ( Please refer to EasyBuilder Pro User Manual for software operation details ) power supply. Note: The 12 or 24 VDC output from some controllers may not have enough
Condition current to power the unit.
7 Communication Connections
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the
COM1 [RS232-2W;RS-485-2W/4W],
impedance matching.
COM2 [RS232-2W;RS-485-2W/4W] c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression
COM1 COM2 COM1 COM2 Wire Routing devices.
[RS485] [RS485] d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
PIN# [RS232] [RS232] PIN#
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
2W 2W 4W 2W 4W 2W supply and the frame ground. This provides a path for static and high frequency
1 RXD1 2 Rx1- Data1- dissipation. Typical values to use are 1M Ohm and 4700pF.
3 TXD1 4 Rx1+ Data1+
DANGER
5 FG 6 Tx1-
The system designer should be aware that devices in Controller systems could fail and
7 GND 8 Tx1+
thereby create an unsafe condition. Furthermore, electrical interference in an operator
9 RXD2 10 Rx2- Data2- interface can lead to equipment start-up, which could result in property damage and/or
11 TXD2 12 Rx2+ Data2 physical injury to the operator.
Hardware
13 FG 14 Tx2- + If you use any programmable control systems that require an operator, be aware that this
Considerations potential safety hazard exists and take appropriate precautions. Although the specific design
15 GND 16 Tx2+ steps depend on your particular application, the following precautions generally apply to
installation of solid-state programmable control devices, and conform to the guidelines for
installation of Controllers recommended in NEMA ICS 3-304 Control Standards.
8 Restore Factory Default
To conform to ICS Safety Recommendations, checks should be placed in the controller to
Press and hold on the Default button on the unit for more than 15 seconds to restore default IP Setting.
ensure that all writable registers that control critical parts of plant or machinery have limit
LAN: DHCP Programming
checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of
Please note that the projects and data stored in the unit are all cleared after pressing this button. Considerations personnel.
GMECMG300_cMT-G03_Installation_180629
9 Battery Replacement
Battery Specification: UL Certification Battery, Type CR1220, Rated 3V, Max. Abnormal Charging
Limited Warranty
Current 10mA, Working Temperature: max. 70°C
Battery replacement shall be performed by qualified personnel (engineer) only and care must be taken This product is limited warranted against defects in design and manufacture.
when handling lithium batteries. For more information on battery replacement and disposal The proven defective product will either be repaired or replaced, at Weintek’s discretion.
considerations, please refer to the following link: This warranty shall not cover any product which is
http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf (a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.