Specifications Sheet No.

SPEC-1244E (1st Edition)

EC5900R Digital Programmer/Controller

OUTLINE
Model EC5900R are digital programmer/controller offering
flexible control by storing programs of 400 steps (maximum
100 steps per pattern) and maximum 19 patterns.
Sufficient comments displayed in the display of 16 character ×
4-line at the center of unit allows easy-to-operate and highly
functions. The graphic indication of a program pattern makes
you keep directly tracking the progress of a process.

FEATURES
Human friendly display and operability
LCD (wide temperature range product) display of Number of patterns :
16-character and 4-line Max 19 ······························· EC5900R
Graphic display of program pattern Max 38 (19×2programs) ···· EC5950R
Superb operability by comments display Number of steps: Max 400 (Max 100/ pattern)
Simultaneous display of process variable, setpoint, Setting method: X-Y type by settings of time and target
residual time and other related data setpoint
It is lineup about one channel type and two channel Setting range:
types Setpoint; Whole input range width
1 channel-type basic model : EC5900R Time setting; 0h00min to 399h59min or
2 channel-type basic model : EC5950R 0h00min00s to 5h59min59s
The program function of fullness (switching type)
The mass program of a maximum of 400 steps and 19 Repeat range: Maximum 999 repeats
patterns PV start: Enabled
DO : A maximum of 15 points, DI : A maximum of 12 Link between patterns: Enabled
points Guaranteed soak: Enabled
Time Units : Enables to switch time unit (minute/second) Pattern selection: Keys, DI or external communication
of programs Operation: RUN/STOP, ADVANCE and RESET
It is easy edit about a program pattern by 7-segment LED display: PV, pattern No. and step No.
deletion/insertion function of a step, and deletion/copy LED lamps: ALM, OUT, COMM, MAN, RUN
function of a pattern LCD display: SP, TIME, OUT, graphic pattern
High accuracy : ± (0.1% + 1 digit) display, Comment display, data
Multi-Input (Thermocouple, RTD, Voltage or Current), display
Multi-Output (Current, SSR drive, Relay)
Anti-overshoot control Input
Multi-PID, Programmed PID, Multi-output limit, Points: 1 ········ EC5900R
Programmed output limit 2 ········ EC5950R
Easy replace from EC5600S/EC5900A (They are Range: Multi-range system (limited in a range groupe)
following and terminal-arrangements community Refer to the range table.
about a function and operability) Resolution: Five columns: 0.1°C
(Part of the range;0.01°C)
Four columns: 1°C
SPECIFICATIONS Accuracy rating: ± (0.1% + 1 digit)
Programs However, TC input does not include
Number of programs: 1 (1program-2controls) or reference-junction compensation error.
(EC5950R) 2 (2programs-2controls : 2ch independent (Refer to Range and Accuracy Table)
control) Input polygonal line approximation:
mV, V, mA input (10 polygonal lines)
Burn out: TC/ mV input ········ Upscale
Sensor correction: Applicable to TC/RTD input
0.0 ~ ± 100.0°C
Input filter: First-order lag filter 0 ~ 20 seconds or moving Output limit:
average 1 ~ 8 times Switching system of single output limit/multi-output
Scaling: a) With setting range limiter for ranges of TC/RTD limit/programmed output limit
b) Rages of mV/mA; Scaling enabled Note; 2nd output always uses same output limit.
Four columns: -1999 ~ 1999 Single output limit····· It always uses same output limit
Five columns: -19999 ~ 19999 Multi-output limit······· Selection of 1set from 8 sets for
Signal source resistance: each Hi and Lo on a step basis
TC/mV Input; Effect of about 0.13µV/Ω Programmed output limit·····Proportional computation
RTD; Lead wire resistance 5Ω or less system by 3 reference
Input resistance: V Input ················· Approx.500kΩ points
Current Input ······· Approx.250Ω Auto/Manual: Switching of bump-less and balance-less
CMRR: 140 dB or more Direct/reverse action:
NMRR: 60 dB or more Setting up by front keys (dual output type: reverse action
fixed)
Range and Accuracy Table Cycle time: 1 ~ 120 seconds
(When the output is set to the relay output or the SSR
drive output)
CONT STOP (C STOP):
When the control action is stopped, a preset value is
output.
Preset output:
0.0 ~ 100.0% (Within an output limit, ON or OFF is
selectable.)
C STOP, when the power interruption for about 50ms or
more is recovered, the action shown in the list below is
taken.

Auto-tuning: Available
Anti-overshoot: ON/OFF
Types of control output
a) 1st output (multi-output): Current, SSR drive, Relay
Control Current output; 4 ~ 20mADC (Max. 600Ω)
Control computation cycle: 0.1 second 0 ~ 5mADC (Max. 2kΩ) ···· option
Control mode: PID control, PD control, ON-OFF control, SSR drive output; ON······ 15VDC (Max. 20mA)
3-positon control (Dual output only) OFF···· 0VDC
PID: Switching system of single PID/multi-PID/programmed PID Relay contact output;
Single PID ······· It always uses same PID Form-a contact 250VAC 3A (resistive load)
Multi-PID ········· Selection of 1set from 8 sets of b) 2nd output: Optional combinations from the current
PID parameters on a step basis output, the SSR drive and the relay contact
Programmed PID ···· Proportional computation system by Ratings are same as a).
3 reference points c) Servo drive output(option):
Control constants: Power source for control equipments;
Proportional band(P); 0.1 ~ 999.9% 24 ~ 100VAC, 50/60Hz
Integral(reset) time(I); 0.01 ~ 99.99 minutes Output; SSR 1AAC Max.
Derivative(rate) time(D); 0.00 ~ 20.00 minutes For single-phase capacitor motor
Manual reset(b); Feedback resistance; 100 ~ 2.5kΩ
(Available when the control mode is set to PD control) Free auto-calibration type
0.0 ~ 100.0% Deadband; 0.5 ~ 10.0% adjustable
D.BAND (Dead band coefficient);
± (0 ~ 0.500) (available only with dual output) Alarms
HYSTERESIS (Hysteresis band in 2-position or 3-position Types: PV alarm; (High limit, Low limit)
control); 0.00 ~ 20.00% SP alarm; (High limit, Low limit)
Deviation alarm; (High limit, Low limit)
Deviation absolute value
Heater monitoring alarm (option)
Setting range: PV alarm···· Whole input range Display
SP alarm···· Whole input range DI/DO (Configurable by key entry)
Deviation alarm
High limit; 0 ~ input range width
Low limit; input range width ~ 0
Deviation absolute value alarm····
0 ~ input range width
Alarm output hysteresis width:
Enables to set 0 to input range width
Pause function:
The pause function enabled or disabled is selectable.
Not available in SP alarm

Contact output (DO) Note 1: Selection from ALM, RUN, END, MAN, DO, Timing
Number of outputs: Max. 5 points (2 points; standard, DO, FAIL and CONT STOP
2 points; option, 1 point; When the relay Note 2: Selection from RUN, END, MAN, DO, Timing DO,
is not used for the control output, it is and CONT STOP
possible to specify it.) Note 3: Selection from RUN, ADV, RST, COND, MAN,
It is one side commonness excluding the CONT STOP and PTN SELECT
control output. When DI and DO are used in a program, up to 4 contacts
Alarm output: Refer to the alarm shown above. for each of DI and DO can be used in one step.
Status outputs: Types: 7-segment LED
AUTO/MAN status (ON when the status is MAN) PV (green) 5 digit
RUN/STOP status (ON when the status is RUN) Pattern No. (orange) 2-digit
FAIL alarm (ON when the CPU is abnormal) Step No. (orange) 2-digit
CONT STOP (ON when the control action is STOP) LED lamp [ RUN (green), MAN (orange), OUT
END (ON when the program is END) (orange) , ALM (red), COMM (green),
DO 1CH (green), 2CH (green)]
Timing DO (1 ~ 999 seconds) LCD····· 16-character × 4-line (Backlight: green)
Form-1a contact × 4 Operation screen 1······Current setpoint (SP)
(common to COM terminal (The control output relay is Target setpoint (SP)
excluded.)) Step residual time
(Max. 5 outputs from the alarm types and the status 1st output value
output shown above are selectable.) Graphic pattern display
Contact rating: 250VAC 1A (resistive load) (left side)
Operation screen 2······2nd output value
Contact input (DI) (available with dual output)
Signal assignment: Status display
ON signal ········when the input circuit is closed Display update: 0.2 seconds
OFF signal·······when the input circuit is open Auto restoration:
Number of inputs: 4 points If no key is pressed within 2 minutes, the display will
Input condition: 15VDC 1mA to drive a photo-coupler automatically return to the operation screen.
Types: RUN/STOP (Program RUN (STOP) when the signal is
ON (OFF)) Common specifications
ADV (The running step No. is advanced each time All reset: Enabled
when the signal is turned ON) Key lock: Enabled
RST (The running step No. is set to 00 each time Memory backup: Non-volatile memory (Fe-RAM)
when the signal is turned ON) Front panel: Dust-proof and Drip-proof front panel conforming
AUTO/MAN (MAN (AUTO) when the signal is ON to IP65.
(OFF)) Polyester sheet
CONT STOP (CONT STOP (CONT RUN) when the Key switch with click
signal is ON (OFF)) Failsafe: When the instrument becomes abnormal, the output
PTN SELECT (ON: enabled) will change to 0% or a preset value by a watch-dog
CONDITION (ON: step progressing condition) timer and various self-diagnosis functions. FAIL
output enabled (when the CPU is abnormal or when
a self-diagnosis function is abnormal)
Operating temperature range: -10 ~ 55°C Extension I/F (ARCNET):
Power supply: Voltage rating at 100 to 240VAC, 50/60Hz LAN for extended functions
Mass: Approx. 500g Token-bus N: N communication
Power consumption: 30VA Max. Transmission speed 2.5 Mbps
Attachments: Mounting brackets, instruction manual 20 nodes/ network
255 nodes max (using HUB)
Safety and EMC standards Application······ Heater monitoring function
(The agreement evaluation is done.) Connection to EC5500R or EC5800R
Electrical safety: IEC61010-1 * ARCNET is a registered trademark of Datapoint
Emissions: EN61326-1 Corporation, USA.
Immunity: EN61326-1 Sensor power: 24VDC 24mA Max.
DI/DO connector:
Option DI; 8 points Contact input
Analog retransmission: DO; 10 points Open collector output
0 ~ 20mADC or 4 ~ 20mADC for a setting scale is (30 VDC, 20mA)
selectable. DI/DO connector cable;
Process variable (PV), setpoint (SP), or output value WMSU0243A* 01:1m, 02: 5m, sold separately
(OUT), is selectable. DI/DO expansion adapter (CA2005A02; sold separately):
Accuracy rating; ± 0.1% DI; 7 points Contact input
Resolution; 0.05% or less DO; 8 points Form-1a 250VAC 1A (resistive load)
Load resistance; Max. 600Ω (current output) Power supply; 100V/110VAC or 200V/230VAC
Communication function: RS-232C, RS-422A, RS-485 ower consumption; Approx. 3VA/ 100VAC
(Communication modules and communication cables are Mass; Approx. 1.9kg
sold separately. RS-485 has the type with built-in the
main body. )

PART NAMES AND FUNCTION

Process variable (PV) display

Pattern No. display

Step No. display


Displays setpoint (SP), output
value (OUT), program data,
running Information
AUTO/ MAN key
Channel lamp
Mode switching key
ALM lamp
Setting digit shift key
Output status lamp

Remote status lamp Display back key

MAN operation lamp

Setting item/ entry key


Program RUN lamp

Program RUN/STOP key


Dial
Program advance key

Program reset key

Pattern selection key


Types of operation screens
Operation (Main) screen Operation (Sub) screen
SP 100.0 °C SP 100.0 °C
T.SP 1000.0
0h00min Back key
3 sec.
OUT1 100.0
Disp key
Disp key Setup screen
Parameter screen
1: PID CHECK
2: OUTPUT LIMIT DIGIT 5
3: REF POINT
4: ALARM 1 Disp key
5 sec.
Disp key

Program (Main) screen Program (Sub) screen


1:STEP DELETE
PATTERN 1 2:STEP INSERT
CHECK/WRT CHECK Back key 3:PTN DELETE
3 sec. 4:PTN COPY 1

Display examples of operation screens

Main screen Program control/ constant Sub screen


1 SP 100.0 °C value control Running SP 5 SP 100.0 °C Running SP
T.SP 1000.0 Step target SP
1h00min Step remaining time
OUT1 100.0 1st output value
BACK key ENT key BACK key ENT key
2 6
R1
Input range
T.SP 1000.0
OUT2 100.0 2nd output value 0.0 ~ 1760.0
Control Mode
0h00min
COND ABCD Remaining condition contact No. ON-OFF REV. °C Direct/ reverse
DO OUT1
1234 100.0 Current sequence contact No. SINGLE mA Output type
BACK key ENT key BACK key ENT key
3
ALARM STATUS Alarm activation status 7 HEATER
A: V.H B: DV.L Displays alarms being 1: 99.99Ω 500.0A
C: PV.H D: PV.L currently activated. Heater monitoring
A blank at right side of alarm
2: 99.99Ω 500.0A
unit data
E: No. (A, B, C, D, E) indicates 3: 99.99Ω 500.0A
BACK key ENT key that no alarm is activated.
BACK key ENT key
4
CHECK Communication remote/local 8 CHECK
COMM LOCAL status/ setting HEAT ALARM HOLD Heater monitoring
KEY LOCK UNLOCK key lock status/ setting HOLD unit alarm hold/ release

BACK key ENT key BACK key ENT key


MODEL CODE NUMBER
1 2 3 4 5 6 7 8
EC59 R
1Control method Note4 8Special
0 1 channel 0 None
5 2 channel Z Special
21st output Note 1 7DI/DO option
1 Relay 0 None
2 SSR drive 1 DI/DO adapter terminal
3 2 DI/DO connector
4 62nd output Note 1
5 4 to 20mA
0 None
6 0 to 5mA
1 Relay
7
2 SSR drive
8 Multi-output
3
3Event relay output Note 2 4
0 2 points 5 4 to 20mA
1 4 points 6 0 to 5mA
4Built-in option Note 3 5Extension option Note 1, 4
0 None
0 None
1 Extension I/F
5 AO
2 Servo drive
8 Sensor power + AO
3 Extension I/F + Servo drive
Note1: Designating 1st output, 2nd output and servo drive 4 RS-485
5 2 channel, multi-output
Output type 1st output 2nd output
6 2 channel, multi-output, RS-485
Single output multi 8 0
7 2 channel, 0 to 5mA output
Single output 0- 5 mA 6 0
8 2 channel, 0 to 5mA output, RS-485
Dual output One of 1, 2, 5 and 6 One of 1, 2, 5 and 6
Servo drive 8 0 Note 4. Designating extension option
Note 2: When select 8 by the 1st output and do not use the relay output, point of contact Control method Extension option
output appointment becomes 5 points with 3 points, "1" with "0". EC590∗R 0, 1, 2, 3, 4
EC595∗R 0, 5, 6, 7, 8
Note 3: For the voltage output, use an external resistance HMSU3081A02 (250Ω ± 0.1%)

RANGE TABLE DEFAULT SETTINGS


Default settin g at the shipment from the factory.

Note: For V and mA input, linear scaling or square root extraction


scaling is selectable.
DIMENSIONS Unit: mm

Approx. 175

Option
(Communication module)

Option (DI/DO connector cable)

Option (DI cable)

Panel thickness 10mm Max

PANEL CUTOUT
(96 × N-1 +92) +1
-0
+0.8
92 -0 For the installation of N sets
+0.8
-0
92

120Min.

TERMINAL CONFIGURATION
1) EC5900R: DI/DO connector, ARCNET, Servo drive, 2) EC5900R: DI/DO terminal adapter, ARCNET, Servo drive,
Sensor POW, AO Sensor POW, AO
3) EC5900R: DI/DO connector, RS-485, Sensor POW, AO 4) EC5900R: DI/DO terminal adapter, RS-485, Sensor POW, AO
EC5950R: DI/DO connector, RS-485, Sensor POW, AO EC5950R: DI/DO, terminal adapter, RS-485, Sensor POW, AO

PERIPHERAL UNIT
Communication module
Type Module Remarks
1 RS-232C ZE7101A0113 EC5900R
2 RS-232C ZE7101A0114 EC5950R
EC5900R Terminal block type
3 RS-422A/ RS-485 ZE7101B0411
Up to 32 sets can be connected to a HOST.
EC5950R Terminal block type
4 RS-422A/ RS-485 ZE7101B0412
Up to 32 sets can be connected to a HOST.

For RS-232C

Cable side
Insertion side to EC5900R
For RS-422A/ 485
Communication cable
For RS-232C: Model : HMSU2255B02 With an exclusive connector for the instrument side, cable length 2m,
D-sub connector (Male) for other side
For RS-422A:Model : WMSU0075A01 (Appoint a cable length)
For RS-485: Model : WMSU0075A02 (Appoint a cable length)
DI cable
HMSU2695A01 Cable length 1m
HMSU2695A02 Cable length 5m
DI/DO connector cable
WMSU0243A01 Cable length 1m
WMSU0243A02 Cable length 5m
DI/DO expansion adapter ( CA2005A02 )

Dimensions (Unit: mm)


hole Terminal cover

Extension option External resistor


Heater monitoring unit Model: ZE7201 Model: HMSU3081A02
Note: The extension I/F is required for EC5900R. Resistance: 250Ω ± 0.1%
Use the following cable. For RS-485 (Extension option) terminator
HMSU2032A7601 (2 m ), CO-SPEV--SB (A) Model: WMSU0303A01
1P × 0.3SQ or equivalent cables Resistance: 200Ω

CAUTION
Do not install this device before consulting instruction manual
Specifications are subject to change without notice.
For further information, a quotation or a demonstration please contact to:

OHKURA ELECTRIC CO., LTD.


Head Office / Factory Saitama, JAPAN
Sales Offices Tokyo, Osaka, Nagoya, Kyushu, Tohoku
URL http://www.ohkura.co.jp/
e-mail (in English) [email protected]

Printed in Japan: .Feb. 2009