Load Alternator + Timer E1ZMLA10 24-240V AC/DC
ENYA series
5 functions
7 time ranges
Wide input voltage range
1 change over contact
Width 17.5 mm (0.69 in)
Installation design
Technical data
1. Functions 6. Output circuit
The funktion can be selected at anytime if connected to the supply 1 isolated change over contact (1 CO)
voltage. Contact material: AgNi
Rated voltage: 250V a.c.
E ON delay Switching capacity: 2000VA (8A / 250V a.c.)
R OFF delay Fusing: 8A fast acting
L1 Manual OFF Mechanical life: 20 x 106 operations
LA Load Alternator (Pump Changer) Electrical life: 1 x 105 operations
L2 Manual ON at 1000VA resistive load
Switching frequency: max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
2. Time ranges Overvoltage category: III (in accordance with IEC 60664-1)
Time range Adjustment range Rated surge voltage: 4kV
1s 50 ms 1s
10 s 500 ms 10 s 7. Control input
1 min 3s 1 min Input not potential free: terminals A1-B1
10 min 30 s 10 min Loadable: yes
1h 3 min 1h Max. line length: 10 m
10 h 30 min 10 h Trigger level (sensitivity): automatic adaption to supply voltage
100 h 5h 100 h Min. control pulse length: d.c. 50 ms / a.c. 100 ms
3. Indicators 8. General data
Green LED U/t ON: indication of supply voltage Degree of protection: Basic insulation
Green LED U/t flashes: indication of time period Insulation test voltage:
Yellow LED R ON/OFF: indication of relay output Supply circuit - Output circuit: 1680V
4. Mechanical design Interference immunity: Class A
Self-extinguishing plastic housing, rated IP40. Prospective current value: 1000A / 8A
Mounted on DIN-rail TS 35 according to EN 60715
Mounting position: any 8. Accuracy
Shockproof terminal connection according to VBG 4 (PZ1 required). Base accuracy: ±1 % of maximum scale value
Terminals are rated IP20 Adjustment accuracy: <5 % of maximum scale value
Tightening torque: max. 1 Nm (0.74 ft lbs) Repetition accuracy: <0.5 % or ±5 ms
Terminal capacity: Voltage influence: -
1 x 0.5 to 2.5 mm² (1 x 20 to 14 AWG) Temperature influence: ≤0.01 % / °C
with/without multicore cable end
1 x 4 mm² (1 x 12 AWG) 9. Ambient conditions
without multicore cable end Ambient temperature: -25 to +55 °C (-13 to +131 °F)
2 x 0.5 to 1.5 mm² (2 x 20 to 16 AWG) Storage temperature: -25 to +70 °C (-13 to +158 °F)
with/without multicore cable end Transport temperature: -25 to +70 °C (-13 to +158 °F)
2 x 2.5 mm² (2 x 14 AWG) Relative humidity: 15 % to 85 %
flexible without multicore cable end (in accordance with IEC 60721-3-3
class 3K3)
5. Input circuit Pollution degree: 2 (in accordance with IEC 60664-1)
Supply voltage: 24 to 240V a.c./d.c.
Terminals: A1(+)-A2 10. Weight
Tolerance: 24V -15% to 240V +10% Single packing: 80 g (2.82 oz)
Rated consumption: 4VA (1.5W)
Rated frequency: a.c. 48 to 63 Hz
Duty cycle: 100 %
Reset time: 100 ms
Residual ripple for d.c.: 10 %
Drop-out voltage: >30 % of minimum rated supply voltage
Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 4kV
www.tele-online.com
E1ZMLA10 24-240V AC/DC
Functions
Load Alternator - Pump Changer (LA) OFF delay (R)
In this mode, every falling edge toggles the output relay R (flip-flop) from The supply voltage U must be constantly applied to the device (green
L1 to L2 or L2 to L1 whatever position is defined by the previous status. LED U/t illuminated). When the control contact S is closed, the output
On Power-Up the relay R stays in off condition until the first falling edge is relay R switches into on-position (yellow LED illuminated). If the control
detected on S Terminal B1. contact is opened, the set interval t begins (green LED flashes). After
To ensure a safe and optimal function, please turn both timing controllers the interval t has expired (green LED U/t illuminated) the output relay
on the front to the most left position (CCW), which equals 50 msec. switches into off-position (yellow LED not illuminated). If the control
In this operation mode, a minimum delay/de-bump time of 50 msec is contact is closed again before the interval t has expired, the interval
applied from the falling edge of the control input until relay R is changing already expired is erased and is restarted.
its state.
Is a longer delay time as 50 msec is set, a short pulse on the „S“ input
resets the times. The timer is restarted with the next falling edge signal on U
„S“ input again. If you wish to apply longer delay times, set the according
time selectors to the required values or contact your application engineer. LED U/t
S <t
R t <t
Manual OFF (L1)
If the function selector indicates function L1, the output relay R remains
in the off-position. If you switch from LA to L1 the relay switches into
off-position independent of the status of the control input.
Manual ON (L2)
If the function selector indicates function L2, the output relay R remains
in on-position as long as the supply voltage is available. If you switch
from LA to L2 the relay switches into on-position independent of the
status of the control input.
ON delay (E)
When the supply voltage U is applied, the set interval t begins (green
LED U/t flashes). After the interval t has expired (green LED U/t
illuminated) the output relay R switches into on-position (yellow LED
illuminated). This status remains until the supply voltage is interrupted.
If the supply voltage is interrupted before the expiry of the interval t,
the interval already expired is erased and is restarted when the supply
voltage is next applied.
U
LED U/t
R t <t
www.tele-online.com
E1ZMLA10 24-240V AC/DC
Connections Dimensions
with control input without control input
OFF Delay (R) ON Delay (E)
(+) (+)
U~ U~
(-) (-)
15 S 15
A1 B1 A1 B1
A1 15 A1 15
R R
A2 16 18 A2 16 18
A2 A2
16 18 16 18
Load Alternator - Pump Changer (LA)
Ordering information
Type Functions Supply voltage Art. No.
E1ZMLA10 24-240V AC/DC E, R, LA, L1, L2 24-240V a.c. / d.c. 110218
This device is subject to the Waste Electrical and Electronic Equipment Regulation (WEEE) and may not be disposed of with normal domestic
waste. The device is made of materials that can be recycled by specialized recycling companies. The device must be disposed of according to
the national electronic scrap regulations.