FM Approved Sprinkler Types and Ratings
FM Approved Sprinkler Types and Ratings
Automatic sprinkler protection is recommended for industrial and other buildings having combustible construction or combustible
occupancies.
There are many FM Approved types of automatic sprinklers. Typical examples include: upright, pendent, flush, recessed, concealed,
sidewall, dry-pendent, dry-upright, extended coverage, corrosion resistant, and rack storage.
A sprinkler operates automatically when the heat-actuated element is heated to, or above, its thermal rating.
Selection of the proper temperature rating for automatic sprinklers is important. The proper rating provides a factor of safety designed
to prevent premature operation. The rating should be selected from the following table:
625°F
Ultra High 650°F(343°C) Orange/Tag
(329°C)
*Some manufacturers paint the frame arms of 135°F (57°C) sprinklers black.
Sprinklers of "very extra high" and "ultra high" ratings are primarily used for internal protection of chambers such as ovens and dryers
having working temperatures above 300°F (149°C). When the sprinklers are normally heated to the working temperature of the oven
or dryer, under accidental fire conditions they will operate fast enough for safe protection. However, when the sprinklers are initially at
the same temperature as a cold oven or dryer, operation may be so severely retarded that the oven or dryer is virtually without internal
sprinkler protection.
Specially coated sprinklers are available for use where corrosion resistance is desired and decorative coated or plated sprinklers are
available for areas where improved appearance is desired. For corrosion resistance, wax is satisfactory except in extreme
atmospheres. Wax has too low a melting point for higher temperature rated sprinklers, whereas a bituminous coating affords some
protection. A lead coating protects against certain mild corrosive atmospheres. Wax-over-lead provides good sprinkler protection.
Corrosion resistant sprinklers such as those manufactured from stainless steel or other corrosion resistant materials currently afford
the best available protection. Common decorative finishes are bright brass, chrome, paint, or polyester coating. These finishes are for
decorative purposes only and are not FM Approved for corrosion resistance.
Only sprinklers supplied by the listed manufacturers are FM Approved. Any change in the device after it leaves the manufacturer voids
the Approval. Coated, plated and painted sprinklers rated above 165°F (74°C) have the standard temperature color code either on the
frame arms or on the compression screws, except in the case of bulb type decorative coated sprinklers in which the bulb fluid color
indicates the temperature rating per the following table:
155° Red
(68°)
400°-650° Black
(204°-343°)
When selecting a specific type of sprinkler, refer to the FM Global Property Loss Prevention Data Sheets to ensure that the sprinkler
selected is capable of providing adequate fire protection for the intended occupancy. In addition, working plans of proposed layouts,
showing all details with respect to location of sprinklers and piping, description of the occupancy and details of construction, should be
sent to your insurance company for review before the materials are fabricated. The plans will be accepted or changes will be
recommended to assure that the work will be done according to the best practice and to avoid the possibility of later requests for changes.
Unless otherwise noted, automatic sprinkler system components have a rated working pressure of 175 psi (12.1 bar).
In this section, the following conventions are used:
The sprinkler nominal discharge coefficient (K-factor) is expressed in US customary units of gal/min/(psi)1⁄2 .
Following is a cross reference of standard US vs. Metric K-factors for FM Approved sprinklers
Nominal Metric
K-factor K-factor
[gal/min (psi) 1/2 ] [l/min (bar)1/2 ]
2.8 40
5.6 80
8.0 115
11.2 160
14.0 200
16.8 240
19.6 280
22.4 325
25.2 365
Nominal Metric
K-factor K-factor
[gpm/(psi)1/2 ] [lpm/(bar)1/2 ]
3.8 55
5.8 84
6.9 99
SR Standard Response
Heat responsive elements are identified as either Fusible or, in the case of bulb type elements, with the nominal bulb diameter in
millimeters (e.g., 2.5 mm, 3 mm, etc.)
Nominal thread sizes are expressed using American National Standard Taper Pipe Threads (NPT). Sprinklers intended for sale
outside the United States shall have threads which are in compliance with other national or international standards as permitted at the
sole discretion of FM Approvals.
Sprinkler finishes are identified as follows:
Finish Description
Brass Unfinished, Plain Brass or Bronze
Wax Over Lead Wax Over Lead Coated (for extra corrosion protection in some atmospheres)
Wax Over Polyester Wax Over Polyester Coated (for extra corrosion protection in some atmospheres)
Sprinkler nominal temperature ratings are expressed in degrees Fahrenheit (°F) followed by the equivalent in degrees Celsius (°C).
General Information
Automatic sprinkler protection is recommended for industrial and other buildings having combustible construction or combustible
occupancies.
When selecting a specific type of sprinkler, refer to the FM Global Property Loss Prevention Data Sheets to ensure that the sprinkler
selected is capable of providing adequate fire protection for the intended occupancy. Projects that are specific to FM Global insured
clients, working plans of proposed layouts, showing all details with respect to location of sprinklers and piping, description of the
occupancy and details of construction, should be sent to the local FM Global engineering office for review and acceptance before the
materials are fabricated. The plans will be accepted or changes will be recommended to assure that the work will be done according
to the best practice and to avoid the possibility of later requests for changes.
Nominal thread sizes are expressed using American National Standard Taper Pipe Threads (NPT). Sprinklers intended for sale
outside the United States shall have threads which are in compliance with other national or international standards as permitted at the
sole discretion of FM Approvals.
Unless otherwise noted, automatic sprinklers have a rated working pressure of 175 psi (12.1 bar).
Sprinkler Categories
There are three categories of FM Approved automatic sprinklers: Storage, Non-Storage and Special Protection sprinklers based on
the type of occupancy hazard they are intended to protect. Within these three categories are various different types of orientations
(such as pendent, upright, horizontal sidewall, vertical sidewall, flush, recessed, concealed, dry pendent, dry upright, etc.), thermal
response ratings (i.e. quick response or standard response), nominal temperature ratings (see table below), K-factors (see table
below) and spacings (i.e. standard or extended coverage).
The sprinkler nominal discharge coefficient (K-factor) is expressed in US customary units of gal/min/(psi)0.5 . See the table below for
nominal K-factor values of currently Approved sprinklers.
5.6 80
8.0 115
11.2 160
14.0 200
16.8 240
19.6 280
22.4 320
25.2 360
The following table provides the nominal K-factor values of currently Approved Special Protection (Residential) sprinklers.
5.8 85
6.9 100
A sprinkler operates automatically when the heat-actuated element is heated to, or above, its thermal rating. Selection of the proper
temperature rating for automatic sprinklers is important as it provides a factor of safety designed to prevent premature operation. See
the table below as well as the occupancy-specific FM Global data sheet to ensure the proper nominal temperature rating for the
sprinkler is chosen based on the hazard being protected as well as the expected ambient temperature conditions. Factory coated,
plated and painted sprinklers rated above 165°F (74°C) have the standard temperature color code either on the frame arms or on the
compression screws, except in the case of bulb type decorative coated sprinklers in which the bulb fluid color indicates the
temperature rating per the following table:
Nominal Temperature Ratings of Sprinklers Based on Maximum Ambient Temperature at Sprinkler Level
Maximum
Nominal Temperature Color and
Ambient Temperature Color of
Temperature Range of Temperature
Temperature Classification Sprinkler
Rating of Nominal of Sprinkler
at Sprinkler of Sprinkler Frame
Sprinkler* Rating** Glass Bulb
Level
Orange,
135°F (55°C) 100°F (38°C) 135°F (57°C) Ordinary Unpainted
135°F (57°C)
Yellow, 175°F
175°F (80°C) 150°F (66°C) 175°F (79°C) Intermediate White
(79°C)
Green, 200°F
200°F - 220°F & 225°F
212°F (100°C) 150°F (66°C) Intermediate White
(93°C - 104°C) (93°C &
107°C)
Mauve, 325°F
325°F -375°F
& 360°F
350°F (175°C) 300°F (149°C) (163°C - Extra High Red
(162°C &
191°C)
182°C)
Black, 400°F -
400°F -475°F
Very Extra 650°F
425°F (220°C) 375°F (191°C) (204°C - Green
High (204°C –
246°C)
343°C)
Black, 400°F -
500°F -575°F
650°F
525°F (275°C) 475°F (246°C) (260°C - Ultra High Orange
(204°C –
302°C)
343°C)
Black, 400°F -
650°F
650°F (345°C) 625°F (329°C) 650°F (343°C) Ultra High Orange
(204°C –
343°C)
*The values indicated for nominal temperature ratings of sprinkler in this table are based on values indicated in FM Global data sheets
**The values indicated are based on the actual (marked or marked nominal) temperature ratings of currently Approved sprinklers
Sprinklers of "very extra high" and "ultra high" ratings are primarily used for internal protection of chambers such as ovens and dryers
having working temperatures above 300°F (149°C). When the sprinklers are normally heated to the working temperature of the oven
or dryer, under fire conditions they will operate fast enough for proper protection. However, when the sprinklers are initially at the
same temperature as a cold oven or dryer, operation may be so severely retarded that the oven or dryer is virtually without internal
sprinkler protection.
The thermal sensing elements of the sprinkler are identified as either Fusible or, in the case of bulb type elements, nominal bulb
diameter in millimeters (e.g., 2.5 mm, 3 mm, etc.).
Approved sprinklers are also available with factory-applied special coatings for resistance to corrosive environments; such sprinklers
are listed under the Special Protection sprinkler category. For corrosion resistance, wax is satisfactory except in extreme
atmospheres. Wax has too low a melting point for high temperate rated sprinklers, whereas a bituminous coating affords some
protection. A lead coating protects against certain mild corrosive atmospheres. Wax-over-lead provides good sprinkler protection.
Corrosion resistant sprinklers such as those manufactured from stainless steel or other corrosion resistant materials currently afford
the best available protection. See the FM Global occupancy-specific data sheet to determine when a corrosion resistant sprinkler is
needed and, if so, which type offers the best resistance for the environmental conditions.
FM Approved sprinklers are available with common decorative finishes such as factory-applied bright brass, chrome, paint, or
polyester coating. Note that these finishes are for decorative purposes only and are not FM Approved specifically for corrosive
environments.
Finishes of currently Approved Storage and Non-Storage sprinklers are included in the following table.
Finish Description
Black Plated Black Plated
Finishes of currently Approved Special Protection (Corrosive Environment) sprinklers are included in the following table. Note that FM
Approved Special Protection (Corrosive Environment) sprinklers are also acceptable for use as Non-Storage sprinklers, unless
indicated otherwise by the occupancy-specific FM Global data sheet.
Finishes of Approved Special Protection (Corrosive Environment) Sprinklers
Finish Description
Lead Coated (for extra corrosion protection in some
Lead
atmospheres)
Orientation
Adjustable dry horizontal sidewall sprinklers are dry-type sprinklers in which the sprinklers attached to the nipple extension are of the
horizontal sidewall orientation. They are intended for installation near a wall/ceiling interface and are equipped with a special deflector
which discharges most of the water in a horizontal plane so that the water is directed onto adjacent walls as well as the protected
area. These types of sprinklers are typically used to protect areas subject to freezing and are connected to water-filled sprinkler piping
located adjacent to the protected area in a location not susceptible to freezing. They are also sometimes used on dry type sprinkler
systems where the installed sprinkler must be of the sidewall orientation. The sprinklers are generally intended for locations such as
offices, hotel lobbies and dining rooms, where the installation of Non-Storage pendent or upright sprinklers with the usual ceiling
spacing and pipe location may be objectionable because of appearance. They are also installed for special circumstances where their
directional properties are desirable.
Dry Adjustable Pendent
A dry-type sprinkler consists of a sprinkler permanently attached to an extension nipple which has a closure at the inlet end to prevent
system water from entering the nipple until the sprinkler operates.
Adjustable dry pendent sprinklers are dry-type sprinklers in which the sprinkler attached to the nipple extension is of the pendent
orientation. These types of sprinklers are typically used to protect areas subject to freezing and are connected to water-filled sprinkler
piping located above the protected area in a location not susceptible to freezing. They are also sometimes used on dry type sprinkler
systems where the installed sprinkler must be of the pendent orientation.
Adjustable Recessed Pendent
Adjustable recessed pendent sprinklers consist of a pendent sprinkler installed in a decorative recessed cup which reduces the
protrusion of the sprinkler from the ceiling. They are intended for use with concealed sprinkler piping where attractive appearance
under a ceiling is desired; such occupancies may include offices, hotel lobbies, dining rooms, clubs and similar properties. FM
Approved adjustable recessed pendent sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of
hazard occupancies as outlined in the occupancy-specific FM Global Property Loss Prevention Data Sheet. Unless indicated
otherwise by the occupancy-specific FM Global Property Loss Prevention Data Sheet, these sprinklers are FM Approved only for use
in wet systems as well as pre-action systems that qualify as a wet system.
Concealed Pendent
Concealed pendent sprinklers incorporate a cover plate which is heat activated and can be manually removed to prevent
over-painting of the cover plate. They are intended for use with concealed sprinkler piping where attractive appearance under a
ceiling is desired; such occupancies may include offices, hotel lobbies, dining rooms, clubs and similar properties. FM Approved
concealed pendent sprinklers are limited to a maximum temperature rating of 225°F (107°C) and to protection of hazard occupancies
as outlined in the occupancy-specific FM Global Property Loss Prevention Data Sheet. Unless indicated otherwise by the
occupancy-specific FM Global Property Loss Prevention Data Sheet, these sprinklers are FM Approved only for use in wet systems
as well as pre-action systems that qualify as a wet system.
Dry Concealed Pendent
A dry-type sprinkler consists of a sprinkler permanently attached to an extension nipple which has a closure at the inlet end to prevent
system water from entering the nipple until the sprinkler operates.
Dry concealed pendent sprinklers are dry-type sprinklers in which the sprinklers attached to the nipple extension are of the pendent
orientation. Dry concealed pendent sprinklers incorporate a cover plate which is heat activated and can be manually removed to
prevent over-painting of the cover plate. These types of sprinklers are typically used to protect areas subject to freezing and are
connected to water-filled sprinkler piping located adjacent to the protected area in a location not susceptible to freezing. They are also
sometimes used on dry type sprinkler systems where the installed sprinkler must be of the pendent orientation. The sprinklers are
generally intended for use with concealed sprinkler piping where attractive appearance under a ceiling is desired; such occupancies
Dry horizontal sidewall sprinklers are dry-type sprinklers in which the sprinklers attached to the nipple extension are of the horizontal
sidewall orientation. They are intended for installation near a wall/ceiling interface and are equipped with a special deflector which
discharges most of the water in a horizontal plane so that the water is directed onto adjacent walls as well as the protected area.
These types of sprinklers are typically used to protect areas subject to freezing and are connected to water-filled sprinkler piping
located adjacent to the protected area in a location not susceptible to freezing. They are also sometimes used on dry type sprinkler
systems where the installed sprinkler must be of the sidewall orientation. The sprinklers are generally intended for locations such as
offices, hotel lobbies and dining rooms, where the installation of Non-Storage pendent or upright sprinklers with the usual ceiling
spacing and pipe location may be objectionable because of appearance. They are also installed for special circumstances where their
directional properties are desirable.
Dry Pendent
A dry-type sprinkler consists of a sprinkler permanently attached to an extension nipple which has a closure at the inlet end to prevent
system water from entering the nipple until the sprinkler operates.
Dry pendent sprinklers are dry-type sprinklers in which the sprinkler attached to the nipple extension is of the pendent orientation.
These types of sprinklers are typically used to protect areas subject to freezing and are connected to water-filled sprinkler piping
located above the protected area in a location not susceptible to freezing. They are also sometimes used on dry type sprinkler
systems where the installed sprinkler must be of the pendent orientation.
Dry Recessed Horizontal Sidewall
A dry-type sprinkler consists of a sprinkler permanently attached to an extension nipple which has a closure at the inlet end to prevent
system water from entering the nipple until the sprinkler operates.
Dry recessed horizontal sidewall sprinklers are dry-type sprinklers in which the sprinklers attached to the nipple extension are of the
horizontal sidewall orientation and are installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the
wall. These types of sprinklers are typically used to protect areas subject to freezing and are connected to water-filled sprinkler piping
located adjacent to the protected area in a location not susceptible to freezing. They are also sometimes used on dry type sprinkler
systems where the installed sprinkler must be of the sidewall orientation.
Dry Recessed Pendent
A dry-type sprinkler consists of a sprinkler permanently attached to an extension nipple which has a closure at the inlet end to prevent
system water from entering the nipple until the sprinkler operates.
Dry recessed pendent sprinklers are dry-type sprinklers in which the sprinklers attached to the nipple extension are of the pendent
orientation and are installed in a decorative recessed cup which reduces the protrusion of the sprinkler from the ceiling. These types
of sprinklers are typically used to protect areas subject to freezing and are connected to water-filled sprinkler piping located above the
protected area in a location not susceptible to freezing. They are also sometimes used on dry type sprinkler systems where the
installed sprinkler must be of the pendent orientation.
Dry Upright
A dry-type sprinkler consists of a sprinkler permanently attached to an extension nipple which has a closure at the inlet end to prevent
system water from entering the nipple until the sprinkler operates.
Dry upright sprinklers are dry-type sprinklers in which the sprinklers attached to the nipple extension are of the upright orientation.
These types of sprinklers are typically used to protect areas subject to freezing and are connected to water-filled sprinkler piping
located below the protected area in a location not susceptible to freezing.
Flush Pendent
Flush pendent sprinklers are constructed with an operating element which extends a short distance below the ceiling. Upon actuation,
the sprinkler deflector drops below the ceiling level to provide a proper water distribution. They are intended for use with concealed
sprinkler piping where attractive appearance under a ceiling is desired; such occupancies may include offices, hotel lobbies, dining
rooms, clubs and similar properties. FM Approved flush pendent sprinklers are limited to a maximum temperature rating of 225°F
(107°C) and to protection of hazard occupancies as outlined in the occupancy-specific FM Global Property Loss Prevention Data
Sheet. Unless indicated otherwise by the occupancy-specific FM Global Property Loss Prevention Data Sheet, these sprinklers are
FM Approved only for use in wet systems as well as pre-action systems that qualify as a wet system.
Horizontal Sidewall
Sidewall sprinklers are sprinklers that are intended for installation near a wall/ceiling interface. They are equipped with a special
deflector which discharges most of the water in a horizontal plane so that the water is directed onto adjacent walls as well as the
protected area. The sprinklers are generally intended for locations such as offices, hotel lobbies and dining rooms, where the
installation of Non-Storage pendent or upright sprinklers with the usual ceiling spacing and pipe location may be objectionable
because of appearance. They are also installed for special circumstances where their directional properties are desirable.
Horizontal sidewall automatic sprinklers are sidewall-type sprinklers in which the axis of the sprinkler orifice is oriented horizontally.
Vertical sidewall automatic sprinklers are sidewall-type sprinklers in which the axis of the sprinkler orifice is oriented vertically. They
are FM Approved for use in both the upright and pendent positions, except where noted otherwise.
Non-Storage Sprinklers
A Non-Storage automatic sprinkler is a sprinkler that has been categorized by FM Global as acceptable for protecting
non-storage-type occupancies and/or other occupancy hazards characterized by low to moderate heat-release rate fires as
permitted in a FM Global occupancy-specific Property Loss Prevention Data Sheet.