RMA

-FRIEND
O
C

L
E

Y
RE
S
A

F
G R
T IG
RA N E

AIR-WATER CHILLERS AND HEAT PUMPS


FOR OUTDOOR INSTALLATION

TECHNICAL MANUAL
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mi-
stakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.

2
TABLE OF CONTENTS

GENERAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

TECHNICAL DATA AND PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10


Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
NOMINAL performances - Base setting up (VB) - Standard plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
NOMINAL performances - Base setting up (VB) - Radiant plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
NOMINAL performances - Low noise setting up (AS) - Standard plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
NOMINAL performances - Low noise setting up (AS) - Radiant plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
COOLING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
HEATING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Plant side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operating limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Noise levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Minimum operating area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

3
4
GENERAL FEATURES

Unit description

This series of air-water chillers and heat pumps satisfies the co- that allows the units to operate with low outdoor temperatures in
oling and heating requirements of residential plants of small and cooling and high outdoor temperature in heating and permits to
medium size. reduce noise emissions in such operating conditions.
All the units are suitable for outdoor installation and can be ap- The low noise acoustic setting up (AS) is obtained, starting from
plied to fan coil plants, radiant floor plants and high efficiency the base setting up (AB), reducing the rotational speed of the
radiators plants. fans and mounting sound jackets on the compressors.
The refrigerant circuit, contained in a compartment protected All the units are supplied with an outdoor temperature sensor, al-
from the air flow to simplify the maintenance operations, is ready installed on the unit, in order to realize the climatic control.
equipped with scroll compressor mounted on damper supports, All the units are provided with a phase presence and correct
brazed plate heat exchanger, thermostatic expansion valve, re- sequence controller device.
verse cycle valve, axial fans with safety protection grilles, finned All the units are accurately built and individually tested in the
coil made of copper pipes and aluminium louvered fins. The cir- factory. Only electric and hydraulic connections are required for
cuit is protected by high and low pressure switches and differen- installation.
tial pressure switch on the plate heat exchanger.
The plate heat exchanger and all the hydraulic pipes are ther-
mally insulated in order to avoid condensate generation and to
reduce thermal losses.
All the units can be equipped with variable speed fans control

Unit identification code

The codes that identify the units and the meaning of the letters used are described below.

RMA IP 26.1 VB AB 0M5

Unit type

IR - Unit suitable for hydronic plant in-


stallation operating as chiller Power supply
IP - Unit suitable for hydronic plant in-
stallation operating as reversible heat 5 - 400 V - 3N - 50 Hz
pump
BR - Unit suitable for hydronic plant in-
stallation with brine solutions operating
as chiller
BP - Unit suitable for hydronic plant in-
Operating range
stallation with brine solutions operating
as reversible heat pump
M - Medium temperature.
The unit is suitable to be instal-
led in temperate climates.

Unit model
Refrigerant type

0 - R410A
N° compressors

Acoustic setting up
Unit version
AB - Base setting up
VB - Base version AS - Low noise setting up
VP - Pump version
VA - Tank version

5
GENERAL FEATURES

Description of components

External structure. Basement, supporting structure and lateral pressure switches in order to assure the compressor to
panels are made of galvanized and painted sheet-steel (colour operate inside the permitted limits, 4 way reverse cycle valve
RAL 7035) to guarantee good resistance to atmospheric agents. (6) to allow operating mode change reversing the refrigerant flow
Accessibility to internal parts is possible removing the frontal (only heat pump models), liquid receiver (7) to compensate the
panel. For extraordinary manteinances also the rear panel can different refrigerant charge required in heating and in cooling
be removed. mode (only heat pump models) and pressure connections
SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket and
blind nut, as required for the use of R410A refrigerant (they
allow the complete check of the refrigerant
3 circuit: compressor
inlet pressure, compressor outlet pressure and thermostatic
expansion valve upstream pressure).
7
The axial fans (8) are contained in a sheet nozzle and are
2
equipped with a safety grille. The fans rotational speed can
be modulated continuosly by an inverter (option) to control the
condensation pressure (in cooling) and the evaporation pressure
(in heating) in order to extend the operating limits of the unit and
to reduce noise emissions. 6

4
Hydraulic circuit. All the pipes are thermally insulated to avoid
condensate generation and minimize thermal losses. The circuit
can be equipped with different kind of circulation 5 pump (option).
In that case the circuit is also equipped with expansion vessel
and air vents. It is also possible to integrate inside the unit a buffer
tank arranged as buffer on the flow towards the plant (option). In
that case the circuit is equipped
8 not only with expansion
1 vessel
and air vents, but also with safety valve, automatic air vent and
drain cock.

Refrigerant circuit. It is contained inside a compartment Electrical panel. It contains all the power, control and security
separated from the air flow to simplify1maintenance and control
DESCRIZIONE DESCRIZIONE
components necessary 2 unit to work properly.
to guarantee the
operations. The unit is managed by a microprocessor controller to which all
The hermetic scroll compressor (1) is mounted on damper the electrical loads and the control devices are connected. The
supports and is protected against overtemperatures and user interface, placed on the frontal panel, allows to view and to
overcurrents. It is equipped with an electrcal heater, that is modify, if necessary, all the parameters of the unit.
activated when the compressor turns off, to keep the compressor All the units are supplied with an outdoor temperature sensor,
crankcase oil temperature high enough to prevent migration of already installed on the unit, in order to realize the climatic
the refrigerant during winter stops and to evaporate any liquid control.
present in the crankcase, in order to prevent possible liquid
rushes on starting (only heat pump models).

3
The plant side heat exchanger (2) is a brazed stainless steel
plate heat exchanger, properly insulated to avoid condensate
generation and to minimize thermal losses, and protected by a 7
differential pressure switch that detects whatever water flow lack.
It is moreover protected against freeze danger by an antifreeze
electrical heater.
2

The source side heat exchanger (3) is a finned coil realized with
grooved copper pipes and aluminium fins with notched profile to 6
increase the heat exchange coefficient. A tray is obtained in the
basement to collect the condensate generated in heating mode. 4

The expansion device (4), a thermostatic expansion valve with 5


external equalizer, allows the unit to adjust itself to the different
operating conditions keeping steady the set superheating.

The refrigerant circuit of each unit contains moreover solid 8 1


core hermetic filter dryer (5) to restrain impurity and moisture
residuals that could be present in the circuit, high and low

6
DESCRIZIONE 1 DESCRIZIONE 2
GENERAL FEATURES

Control system

The unit is managed by a microprocessor controller to which, - pump management


through a wiring board, all the electrical loads and the control - integrative electrical heaters management in heating mode
devices are connected. The user interface is realized by a (2 step logic)
display and four buttons that allow to view and, if necessary,
- compressor and pump operating hours recording
modify all the operating parameters of the unit. It's available, as
an accessory, a remote control that reports all the functionalities - serial communication through Modbus protocol
of the user interface placed on the unit. - remote stand by
The main functions available are : - remote cooling-heating
- water temperature management (through set point - general alarm digital output
adjustment)
- adaptive function
- climatic control in heating and in cooling mode (automatic set
mode
point adjustment according to outdoor air temperature)
- dynamic defrost cycle management according to outdoor air
°C
temperature
- alarm memory management and diagnostic
- fans management by means of continuous rotational speed
disp
control 1 2 1 2

Versions

Each model can be supplied in three different versions to satisfy the application requirements of the plants. The unit is always
supplied assembled, wired and factory tested.
The version is automatically identified by the option "Storing and pumping module" selected.

Base Version - VB Pump Version - VP Tank Version - VA


vb vb vb VP VP VP
The unit does not contain neither The unit contains a circulating pump, air The unit contains a tankVA (arranged
VA VAas
circulating pump nor tank. Therefore vents, expansion vessel and drain cock. buffer on the flow towards the plant),
a proper water flow through the plate safety valve, circulating pump, air vents,
heat exchanger must be guaranteed to expansion vessel and drain cock.
prevent internal safety devices activation. The tank is also arranged for the
In any case the pump, if properly sized, installation of antifreeze or integrative
can be connected to the electrical panel electrical heaters.
of the unit and managed by the controller
of the unit.

7
GENERAL FEATURES

Options

Standard pump Allows the circulation of the water on the plant side.

Allows the circulation of the water on the plant side and guarantees a higher avai-
High head pump
lable static head, suitable for high pressure drop plants.

Allows the circulation of the water on the plant side with the possibility to set the
Modulating pump rotational speed of the pump in order to get the requested flow rate without the
necessity to install other setting devices.

Allows the circulation of the water on the plant side.


Tank and
Storing The thermal inertia of the buffer tank allows to reduce the number of compressor
standard pump
and pumping starts and to guarantee a more stable flow temperature.
module
Allows the circulation of the water on the plant side and guarantees a higher avai-
Tank and lable static head, suitable for high pressure drop plants.
high head pump The thermal inertia of the buffer tank allows to reduce the number of compressor
starts and to guarantee a more stable flow temperature.

Allows the circulation of the water on the plant side with the possibility to set the
rotational speed of the pump in order to get the requested flow rate without the
Tank and
necessity to install other setting devices.
modulating pump
The thermal inertia of the buffer tank allows to reduce the number of compressor
starts and to guarantee a more stable flow temperature.

Integrate or replace the heating power supplied by the heat pump and are managed
Integrative
by the unit controller with a 2 step logic.
electrical Standard in the tank
They are also activated as antifreeze electrical heaters.
heaters
Available only for the VA version.

Soft starter Reduces the compressor start current.

Allows to reduce the phase shift between the absorbed current and the power sup-
Compressor power factor correction
ply voltage keeping it above the value of 0,9.

Modulating control The fans rotational speed can be modulated continuosly by an inverter to control
Fans control (condensation / evaporation the condensation pressure (in cooling) and the evaporation pressure (in heating)
control) in order to extend the operating limits of the unit and to reduce noise emissions.

Fuses Allows to protect the electrical loads with fuses.


Electrical loads
protection Thermal magnetic Allows to protect the electrical loads with thermal magnetic circuit breakers simpli-
circuit breakers fying the maintenance operations.

Chiller (IR) without options (VB) Heat pump (IP) without options (VB)

8
GENERAL FEATURES

Option "Storing and pumping module"

Standard, high head or modulating pump Tank and standard, high head or modulating pump
(VP version) (VA version)

Option "Integrative electrical heaters"

Standard in the tank


(only for VA version)

Accessories

Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor
Rubber vibration dampers
and by the fans in their normal operating mode.

Coil protection grille Protects the external surface of the finned coil..

Tank antifreeze Activated together with the antifreeze electrical heater of the plate heat exchanger, it has the task to keep the water
electrical heater in the buffer tank at a temperature high enough to avoid ice generation during winter.

It is suitable for wall mounting and reports all the control and visualization functions available on the user interface
Remote control
placed on the unit. It therefore allows the complete remote control of the unit.

It allows to communicate with the unit controller and to view the operating conditions of the unit through Modbus
Modbus serial interface
communication protocol. The RS485 serial line ensures the signal quality up to distances of about 1200 meters (that
on RS485
can be extended by means of proper repeaters).

It allows the unit to be turned on and off according to a set program, through the digital input available on the unit
Programmer clock
wiring board (remote stand by).

Phase sequence and It checks not only the presence and correct order of the power supply phases but also the voltage level on each
voltage controller phase and avoid the unit to operate with voltage levels outside the permitted limits.

Allows to detect the water flow lack through the plate heat exchanger and operates as an integration of the protecion
Water flow switch
offered by the differential pressure switch (standard).

9
TECHNICAL DATA AND PERFORMANCES

Technical data

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1 U.M.

Power supply 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz

Refrigerant
Type R410A R410A R410A R410A R410A R410A -
Compressor
Type scroll scroll scroll scroll scroll scroll -
Quantity 1 1 1 1 1 1 n°
Power steps 0 - 100 0 - 100 0 - 100 0 - 100 0 - 100 0 - 100 %
Oil charge 2,51 3,25 3,25 3,25 3,25 3,25 kg
Plant side heat exchanger
stainless steel stainless steel stainless steel stainless steel stainless steel stainless steel
Type brazed plates brazed plates brazed plates brazed plates brazed plates brazed plates -
Quantity 1 1 1 1 1 1 n°
Water volume 1,90 1,90 2,56 2,56 3,33 3,33 l
Source side heat exchanger
finned finned finned finned finned finned
Type coil coil coil coil coil coil -
Quantity 1 1 1 1 1 1 n°
Frontal surface 1,45 1,45 1,45 1,75 1,75 1,75 m2
Fans
Type axial axial axial axial axial axial -
Quantity 1 1 1 1 1 1 n°
Diameter 630 630 630 800 800 800 mm
Maximum rotational speed 900 900 900 900 900 900 rpm
Total installed power 0,6 0,6 0,6 1,8 1,8 1,8 kW
Plant side hydraulic circuit
Expansion vessel volume 10 10 10 10 10 10 l
Tank volume - VA 85 85 85 85 85 85 l
Safety valve set - VA 6 6 6 6 6 6 bar
Standard pump (option)
centrifugal centrifugal centrifugal centrifugal centrifugal centrifugal
Type pump pump pump pump pump pump -
Installed power 0,7 0,7 0,7 0,7 1,0 1,0 kW
High head pump (option)
centrifugal centrifugal centrifugal centrifugal centrifugal centrifugal
Type pump pump pump pump pump pump -
Installed power 1,2 1,2 1,2 1,2 1,6 1,6 kW
Modulating pump (option)
centrifugal pump centrifugal pump centrifugal pump centrifugal pump centrifugal pump centrifugal pump
Type with inverter with inverter with inverter with inverter with inverter with inverter -
Installed power 0,7 0,7 0,7 0,7 1,0 1,0 kW
Integrative electrical heaters in the tank (option)
Installed power 6,6 6,6 6,6 6,6 6,6 6,6 kW
Power steps 2 2 2 2 2 2 n°

10
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - Base setting up (VB) - Standard plants

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1 U.M.

Power supply 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz

Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,9 22,1 25,8 30,8 35,6 40,2 kW
Power input 6,82 7,50 8,76 10,8 12,3 13,9 kW
IR
EER 2,92 2,95 2,95 2,85 2,89 2,89 -
Water flow rate plant side 3432 3809 4444 5319 6143 6932 l/h
Pressure drops plant side 26 31 26 36 31 38 kPa

Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,5 21,7 25,3 30,2 34,9 39,4 kW
Power input 6,75 7,42 8,66 10,7 12,2 13,8 kW
EER 2,89 2,92 2,92 2,82 2,86 2,86 -
Water flow rate plant side 3363 3741 4358 5216 6023 6795 l/h
Pressure drops plant side 25 30 25 35 29 37 kPa
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 21,0 23,3 27,1 32,5 37,6 42,4 kW
Power input 6,49 7,14 8,33 10,3 11,7 13,4 kW
IP
COP 3,24 3,26 3,25 3,16 3,21 3,16 -
Water flow rate plant side 3568 3961 4610 5515 6386 7188 l/h
Pressure drops plant side 27 33 27 38 33 41 kPa
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 17,4 19,3 22,5 26,8 31,0 35,0 kW
Power input 6,40 7,03 8,21 10,1 11,5 13,2 kW
COP 2,72 2,75 2,74 2,65 2,70 2,65 -
Water flow rate plant side 2954 3278 3825 4559 5276 5942 l/h
Pressure drops plant side 19 23 19 27 23 28 kPa

Data declared according to EN 14511. The values are referred to units without options and accessories.

NOMINAL performances - Base setting up (VB) - Standard plants - EUROVENT certified data

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1 U.M.

Power supply 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz

Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 20,0 22,2 25,9 31,0 35,8 40,4 kW
IR EER 2,97 3,00 2,99 2,92 2,96 2,95 -
Pressure drops plant side 26 31 25 36 30 38 kPa
ESEER 3,36 3,39 3,38 3,30 3,34 3,33 -

Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,6 21,8 25,4 30,4 35,1 39,6 kW
EER 2,94 2,98 2,97 2,90 2,93 2,91 -
Pressure drops plant side 25 30 25 34 29 37 kPa
IP ESEER 3,32 3,37 3,36 3,28 3,31 3,29 -
Heating A7W45 (air 7 °C bs - 6 °C bu / water 40 - 45 °C )
Heating capacity 20,9 23,2 27,0 32,3 37,4 42,1 kW
COP 3,27 3,30 3,29 3,20 3,25 3,21 -
Pressure drops plant side 28 34 27 39 33 41 kPa

11
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - Base setting up (VB) - Radiant plants

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1 U.M.

Power supply 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz

Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 24,6 27,3 31,9 38,1 44,1 49,6 kW
Power input 7,09 7,81 9,11 11,2 12,8 14,6 kW
IR
EER 3,47 3,50 3,50 3,40 3,45 3,40 -
Water flow rate plant side 4259 4723 5513 6595 7625 8604 l/h
Pressure drops plant side 39 47 38 54 46 58 kPa

Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 24,2 26,8 31,3 37,4 43,2 48,7 kW
Power input 7,01 7,73 9,01 11,1 12,7 14,4 kW
EER 3,45 3,47 3,47 3,37 3,40 3,38 -
Water flow rate plant side 4173 4637 5410 6475 7471 8432 l/h
Pressure drops plant side 37 45 37 52 44 56 kPa
Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 21,4 23,8 27,7 33,2 38,4 43,3 kW
Power input 5,48 6,03 7,03 8,71 9,91 11,3 kW
IP
COP 3,91 3,95 3,94 3,81 3,87 3,83 -
Water flow rate plant side 3651 4063 4731 5657 6549 7371 l/h
Pressure drops plant side 29 35 29 40 34 43 kPa
Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 17,8 19,8 23,0 27,5 31,8 35,9 kW
Power input 5,39 5,92 6,90 8,54 9,72 11,1 kW
COP 3,30 3,34 3,33 3,22 3,27 3,23 -
Water flow rate plant side 3034 3377 3926 4697 5434 6120 l/h
Pressure drops plant side 20 25 20 28 24 30 kPa

Data declared according to EN 14511. The values are referred to units without options and accessories.

12
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - Low noise setting up (AS) - Standard plants

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1 U.M.

Power supply 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz

Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,1 21,2 24,8 29,6 34,2 38,6 kW
Power input 7,34 8,09 9,42 11,6 13,3 15,0 kW
IR
EER 2,60 2,62 2,63 2,55 2,57 2,57 -
Water flow rate plant side 3295 3655 4273 5113 5903 6658 l/h
Pressure drops plant side 24 29 24 33 28 36 kPa

Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 18,7 20,8 24,3 29,1 33,6 37,8 kW
Power input 7,27 8,00 9,33 11,4 13,1 14,9 kW
EER 2,57 2,60 2,60 2,55 2,56 2,54 -
Water flow rate plant side 3226 3586 4187 5010 5783 6520 l/h
Pressure drops plant side 23 28 23 32 27 34 kPa
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 19,9 22,2 25,8 31,0 35,8 40,3 kW
Power input 6,22 6,85 7,98 9,88 11,3 12,8 kW
IP
COP 3,20 3,24 3,23 3,14 3,17 3,15 -
Water flow rate plant side 3381 3773 4388 5259 6078 6847 l/h
Pressure drops plant side 25 30 25 35 30 37 kPa
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 16,4 18,3 21,3 25,5 29,5 33,2 kW
Power input 6,13 6,74 7,87 9,73 11,1 12,6 kW
COP 2,68 2,72 2,71 2,62 2,66 2,63 -
Water flow rate plant side 2800 3107 3620 4337 5020 5651 l/h
Pressure drops plant side 17 21 17 24 21 26 kPa

Data declared according to EN 14511. The values are referred to units without options and accessories.

NOMINAL performances - Low noise setting up (AS) - Standard plants - EUROVENT certified data

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1 U.M.

Power supply 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz

Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,2 21,3 24,9 29,8 34,4 38,8 kW
IR EER 2,64 2,67 2,67 2,61 2,63 2,62 -
Pressure drops plant side 24 29 24 33 28 35 kPa
ESEER 2,98 3,02 3,02 2,95 2,97 2,96 -

Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 18,8 20,9 24,4 29,2 33,7 38,0 kW
EER 2,61 2,64 2,64 2,58 2,59 2,59 -
Pressure drops plant side 23 28 23 32 27 34 kPa
IP ESEER 2,95 2,98 2,98 2,92 2,93 2,93 -
Heating A7W45 (air 7 °C bs - 6 °C bu / water 40 - 45 °C )
Heating capacity 19,8 22,1 25,7 30,8 35,6 40,1 kW
COP 3,22 3,28 3,26 3,17 3,21 3,18 -
Pressure drops plant side 25 31 25 35 30 38 kPa

13
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - Low noise setting up (AS) - Radiant plants

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1 U.M.

Power supply 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz

Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 23,7 26,2 30,7 36,7 42,4 47,7 kW
Power input 7,62 8,41 9,79 12,0 13,8 15,6 kW
IR
EER 3,11 3,12 3,14 3,06 3,07 3,06 -
Water flow rate plant side 4087 4534 5307 6354 7333 8261 l/h
Pressure drops plant side 36 43 36 50 43 54 kPa

Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 23,2 25,7 30,1 35,9 41,5 46,7 kW
Power input 7,55 8,32 9,69 11,9 13,7 15,5 kW
EER 3,07 3,09 3,11 3,02 3,03 3,01 -
Water flow rate plant side 4002 4448 5204 6217 7179 8089 l/h
Pressure drops plant side 34 42 34 48 41 51 kPa
Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 20,3 22,6 26,3 31,6 36,5 41,2 kW
Power input 5,24 5,77 6,73 8,34 9,49 10,9 kW
IP
COP 3,87 3,92 3,91 3,79 3,85 3,78 -
Water flow rate plant side 3463 3857 4491 5383 6223 7011 l/h
Pressure drops plant side 26 32 26 37 31 39 kPa
Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 16,8 18,8 21,8 26,2 30,2 34,0 kW
Power input 5,16 5,67 6,61 8,19 9,32 10,6 kW
COP 3,26 3,32 3,30 3,20 3,24 3,21 -
Water flow rate plant side 2880 3206 3720 4474 5160 5811 l/h
Pressure drops plant side 18 22 18 26 22 27 kPa

Data declared according to EN 14511. The values are referred to units without options and accessories.

14
TECHNICAL DATA AND PERFORMANCES

COOLING performances

Cooling capacity

1.5 The graphs allow to get the corrective factors to


be applied to the nominal performances in order
to obtain the real performances in the selected
1.4
operating conditions.
1.3
The reference nominal condition is :
1.2 A35W7
source : air in 35°C d.b.
1.1 plant : water in 12°C out 7°C

1.0
Outlet temperature
0.9
plant side :
A = 24°C
0.8 B = 18°C
C = 12°C
0.7
D = 7°C

0.6 A B C D

0.5
15 20 25 30 35 40 45 50

Inlet air temperature d.b. [°C]

Power input EER

1.5 2.0

1.4 A
1.8

1.3
B
1.6
1.2
C
B 1.4
1.1
D
1.0
A 1.2
D
0.9
1.0
C
0.8
0.8
0.7

0.6
0.6

0.5 0.4
15 20 25 30 35 40 45 50 15 20 25 30 35 40 45 50

Inlet air temperature d.b. [°C] Inlet air temperature d.b. [°C]

15
TECHNICAL DATA AND PERFORMANCES

HEATING performances

Heating capacity

1,5
The graphs allow to get the corrective factors to
be applied to the nominal performances in order
1,4 to obtain the real performances in the selected
operating conditions.
1,3 A
The reference nominal condition is :
1,2
B A7W35
1,1
source : air in 7°C d.b. 6°C w.b.
C plant : water in 30°C out 35°C
1,0

D Outlet temperature
0,9 plant side :
A = 55°C
0,8
B = 45°C
0,7 C = 35°C
D = 25°C
0,6

0,5
-15 -10 -5 0 5 10 15 20

Inlet air temperature w.b. [°C]

Power input COP

1.5 2.0

1.4
1.8 D
1.3
1.6 C
1.2

1.4 B
1.1

1.0 1.2 A

0.9
1.0

0.8
0.8
0.7

0.6 A B C D 0.6

0.5 0.4
-15 -10 -5 0 5 10 15 20 -15 -10 -5 0 5 10 15 20

Inlet air temperature w.b. [°C] Inlet air temperature w.b. [°C]

16
TECHNICAL DATA AND PERFORMANCES

Plant side hydraulic performances

Pressure drops - unit without options

60

30.1
50

26.1
Pressure drops [ kPa ]

40
22.1

30 19.1
40.1
20
35.1

10

0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000

Flow rate [ l/h ]

Available static head - unit with option “Storing and pumping module” :
“Standard pump” or "Tank and standard pump"

320

280 19.1

22.1
Available static head [ kPa ]

240

26.1
200
30.1
160
35.1

120 40.1

80

40

0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000

Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

17
TECHNICAL DATA AND PERFORMANCES

Available static head - unit with option “Storing and pumping module” :
“High head pump” or "Tank and high head pump"

320

280
35.1

40.1
Available static head [ kPa ]

240

200

160 19.1

22.1
120

80 26.1

30.1
40

0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000

Flow rate [ l/h ]

Available static head - unit with option “Storing and pumping module” :
“Modulating pump” or "Tank and modulating pump"

320

280 19.1

22.1
Available static head [ kPa ]

240

26.1
200
30.1
160
35.1

120 40.1

80

40

0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000

Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

18
TECHNICAL DATA AND PERFORMANCES

Operating limits

The graphs reported below show the operating area inside which the correct working of the unit is guaranteed.

COOLING
35

30
Outlet temperature - plant side [°C]

25

20 Modulating fans
control
15
(condensation
10 control)
5

0
BRINE units (BR and BP)
-5

-10

-15
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

Inlet air temperature d.b. [°C]

HEATING

65

60

55
Outlet temperature - plant side [°C]

50

45

40

35

30

25

20

15

10

-5
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

Inlet air temperature d.b. [°C]

Temperature difference between unit inlet and outlet Plant side


DT max Maximum value 8 °C

DT min Minimum value 3 °C

19
TECHNICAL DATA AND PERFORMANCES

Electrical data

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1 U.M.

Unit
Power supply 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 V-ph-Hz

F.L.A. Maximum total current input 18,8 20,8 22,9 25,9 29,9 34,0 A

F.L.I. Maximum total power input 10,8 12,1 13,4 15,8 18,4 21,0 kW

Maximum total start current 98 114 121 129 144 178 A


M.I.C. Maximum total start current
55 64 68 73 82 102 A
with soft starter (option)

Integrative electrical heaters standard in the tank (option)


Power supply 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 V-ph-Hz

F.L.A. Maximum total current input 9,5 9,5 9,5 9,5 9,5 9,5 A

F.L.I. Maximum total power input 6,6 6,6 6,6 6,6 6,6 6,6 kW

Standard pump (option)


Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 V-ph-Hz

F.L.A. Maximum total current input 3,6 3,6 3,6 3,6 5,1 5,1 A

F.L.I. Maximum total power input 0,7 0,7 0,7 0,7 1,0 1,0 kW

High head pump (option)


Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 V-ph-Hz

F.L.A. Maximum total current input 6,1 6,1 6,1 6,1 8,2 8,2 A

F.L.I. Maximum total power input 1,2 1,2 1,2 1,2 1,6 1,6 kW

Modulating pump (option)


Power supply 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 V-ph-Hz

F.L.A. Maximum total current input 3,6 3,6 3,6 3,6 5,1 5,1 A

F.L.I. Maximum total power input 0,7 0,7 0,7 0,7 1,0 1,0 kW

20
TECHNICAL DATA AND PERFORMANCES

Noise levels

Base setting up (AB)


Sound pressure level
Sound power levels [dB] Sound power
Model by octave bands [Hz] level at 1 metre at 5 metres at 10 metres

63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
19.1 82,4 83,6 80,2 74,8 71,0 65,5 59,4 53,6 87 77 61 51 46
22.1 82,6 83,8 80,4 75,0 71,2 65,7 59,6 53,8 88 77 62 51 46
26.1 83,5 84,7 81,3 75,9 72,1 66,6 60,5 54,7 89 78 62 52 47
30.1 88,2 83,4 80,0 78,2 76,5 72,3 69,5 60,5 90 81 65 55 50
35.1 88,6 83,8 80,4 78,6 76,9 72,7 69,9 60,9 91 82 66 55 50
40.1 88,9 84,1 80,7 78,9 77,2 73,0 70,2 61,2 91 82 66 56 50

Low noise setting up (AS)


Sound pressure level
Sound power levels [dB] Sound power
Model by octave bands [Hz] level at 1 metre at 5 metres at 10 metres

63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
19.1 80,3 81,5 78,1 71,7 66,9 61,2 54,9 49,1 85 74 58 48 43
22.1 80,5 81,7 78,3 71,9 67,1 61,4 55,1 49,3 85 74 59 48 43
26.1 81,4 82,6 79,2 72,8 68,0 62,3 56,0 50,2 86 75 59 49 44
30.1 86,9 82,1 78,7 75,9 73,2 68,8 65,8 56,8 89 78 62 52 47
35.1 87,5 82,7 79,3 76,5 73,8 69,4 66,4 57,4 90 79 63 53 48
40.1 87,9 83,1 79,7 76,9 74,2 69,8 66,8 57,8 90 79 63 53 48

Reference conditions
Performances referred to units operating in cooling mode at nominal conditions A35W7.
Unit placed in free field on reflecting surface (directional factor equal to 2).
The sound power level is measured according to ISO 3744 standard.
The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1/5/10 metres from the external surface of the unit.

21
TECHNICAL DATA AND PERFORMANCES

Weights

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1 U.M.

Components weights
Unit without options 220 223 241 255 278 280 kg

Standard pump 9 9 9 9 11 11 kg

High head pump 12 12 12 12 13 13 kg

Modulating pump 12 12 12 14 16 16 kg
Storing
and Tank and
31 31 31 31 33 33 kg
pumping standard pump
Options

module Tank and


34 34 34 34 35 35 kg
high head pump
Tank and
34 34 34 36 38 38 kg
modulating pump
Integrative
electrical Standard in the tank 5 5 5 5 5 5 kg
heaters

Transport weights
Unità senza opzioni 236 239 257 275 298 300 kg

Standard pump 9 9 9 9 11 11 kg

High head pump 12 12 12 12 13 13 kg

Modulating pump 12 12 12 14 16 16 kg
Storing
and Tank and
31 31 31 31 33 33 kg
pumping standard pump
Options

module Tank and


34 34 34 34 35 35 kg
high head pump
Tank and
34 34 34 36 38 38 kg
modulating pump
Integrative
electrical Standard in the tank 5 5 5 5 5 5 kg
heaters

Operating weights
Unità senza opzioni 224 227 246 260 284 286 kg

Standard pump 10 10 10 10 12 12 kg

High head pump 13 13 13 13 14 14 kg

Modulating pump 13 13 13 15 17 17 kg
Storing
and Tank and
117 117 117 117 119 119 kg
pumping standard pump
Options

module Tank and


120 120 120 120 121 121 kg
high head pump
Tank and
120 120 120 122 124 124 kg
modulating pump
Integrative
electrical Standard in the tank 5 5 5 5 5 5 kg
heaters

22
TECHNICAL DATA AND PERFORMANCES

Overall dimensions

576
D
53
60

1453
1038

2
1 2
1
215
150

131 167 202 E 288 220 53


614

Frame 1 2
Model 19.1 22.1 26.1 30.1 35.1 40.1
Plant return 1 1"1/4 F 1"1/4 F 1"1/4 F 1"1/4 F 1"1/4 F 1"1/4 F -

Plant flow 2 1"1/4 M 1"1/4 M 1"1/4 M 1"1/4 M 1"1/4 M 1"1/4 M -

D 1494 1704 mm

E 728 938 mm

Minimum operating area

Respect the free area around the unit as shown in the


figure in order to guarantee a good accessibility and
facilitate maintenance and control operations.

A 400 mm
B 600 mm
C 200 mm

A B

The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing errors.
The reserves the right to modify the products contents in this catalogue without previous notice.

23
Cod. 3QE29190