PXC5.E003 Datasheet en

Uploaded by

nmtinh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Topics covered

  • Safety regulations,
  • User profiles,
  • Ethernet switch,
  • PXC5.E003,
  • Ambient conditions,
  • Battery backup,
  • Conformity,
  • Installation instructions,
  • Power supply,
  • System controller
0% found this document useful (0 votes)
94 views14 pages

PXC5.E003 Datasheet en

Uploaded by

nmtinh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Topics covered

  • Safety regulations,
  • User profiles,
  • Ethernet switch,
  • PXC5.E003,
  • Ambient conditions,
  • Battery backup,
  • Conformity,
  • Installation instructions,
  • Power supply,
  • System controller

Desigo™

System controller
PXC5.E003

System controller for integration of BACnet/MSTP, Modbus, and KNX PL-Link


devices
● System controller to integrate BACnet MS/TP, Modbus, and KNX PL-Link devices
● BACnet/IP communication (BTL certified)
● BACnet Secure Connect communication
● 2-port Ethernet switch for low-cost cabling
● KNX PL-Link bus to connect sensors and operator units (including bus power)
● Integration of Modbus data points via RTU and / or TCP
● Integration of BACnet MS/TP devices
● WLAN interface for engineering and commissioning
● Operating voltage AC 24 V
● Mounted on standard rails or on the wall
● Plug-in screw terminal blocks

A6V11646020_en--_i Smart Infrastructure


2023-05-30
Functions
Freely programmable system controller.
● System functions (alarming, scheduling, trending, access protection with individually
definable user profiles and categories)
● System controller for system networks with PXC3, PXC4, PXC5, PXC7 and DXR
controllers over BACnet/IP, BACnet/SC, or BACnet MS/TP
● Integrates third-party devices and systems
● The following functions are available with KNX PL-Link bus:
– Communication with room operator units and sensors
– Plug-and-play connection of Siemens field devices with KNX PL-Link
● Generic object viewer for data points of several assigned devices via embedded web
interface
● Generic object viewer for local data points and assigned devices via embedded web
interface
● Engineering and commissioning with the ABT Site Tool using graphical function charts
● BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC) or MS/TP, in
compliance with the BACnet standard including B-BC profile (Rev. 1.16)
● IT security including HTTPS and BACnet Secure Connect
● BACnet Secure Connect support as BACnet/SC hub
● Wireless connection for engineering and commissioning
● Cloud connectivity for remote access
● Integration of Modbus data points via RTU and / or TCP
● DIN rail or screw mounting
● Plug-in screw terminal blocks

Type summary

Type PXC5.E003
Order number S55375-C103 1)
Number of integration data points up to 500
(Modbus TCP and / or RTU)
Number of digital inputs for potential-free contacts for signaling functions NO or NC 1
(onboard)
Number of BACnet/MSTP devices per RS485 interface up to 60 2)
Number of BACnet/SC devices as a BACnet/SC hub up to 100
Number of KNX PL-Link devices up to 64
Number of configurable RS485 interfaces either for integration of Modbus RTU or BACnet 2
MS/TP

1)
For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435.
2)
Depending on the behavior of the third-party MS/TP devices.

Onboard inputs

DI Digital inputs for potential-free contacts for signaling functions (NO, NC)

2
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Equipment combinations

KNX PL-Link devices

Description Type Data sheet


Wall-mounted temperature sensor QMX3.P30 CM2N1602
Wall-mounted temperature and humidity sensor QMX3.P40
Wall-mounted temperature, humidity, and CO2 sensor QMX3.P70
Wall-mounted temperature sensor and room operator unit QMX3.P34
Wall-mounted temperature and humidity sensor and room operator QMX3.P44
unit
Wall-mounted temperature, humidity, and CO2 sensor and room QMX3.P74
operator unit
Wall-mounted temperature sensor and room operator unit QMX2.P33 A6V10733768
Wall-mounted temperature and humidity sensor and room operator QMX2.P43
unit
Flush-mounted room sensors base- and front modules: CE1N1411
● Base module for temperature and / or humidity measurement 1) ● AQR2570
● Base module for CO2 measurement 1) ● AQR2576
● Front module for base module without sensor ● AQR2530NNW
● Front module for base module with temperature sensor ● AQR2532NNW
● Front module for base module with humidity and temperature ● AQR2535NNW
sensor ● AQR2535NNWQ
● Front module for base module with humidity, temperature
sensor, and CO2 indicator LED
Passive infrared presence detector UP 258D12 A6V10489489
Presence detector WIDE with temperature sensor UP 258D31 A6V11894530
Presence detector WIDE with temperature and humidity sensor UP 258D41
Presence detector WIDE with temperature, humidity, and CO2 UP 258D51
sensor
Presence detector WIDE with temperature sensor and ultrasound UP 258D61

1)
Physical data points on the base module AQR257.. for use in HVAC functions:
- 2 x Binary potential-free contacts (NO, NC)
- 1 x Passive sensor NTC10K (Type II / Beta (0-50 °C) = 3892 K)
For details see PXC4, PXC5 & PXC7 Planning overview A6V13054435 and data sheets.

Desigo Control Point

Description Type Data sheet


BACnet touch panels with integrated data storage and web server A6V11664137
functionality: PXM30.E
7.0 " PXM40.E
10.1 " PXM50.E
15.6 "
TCP/IP client touch panels with data storage in web server A6V11664139
PXG3.Wx00-2: PXM30-1
7.0 " PXM40-1
10.1 " PXM50-1
15.6 "
BACnet/IP web server with standard functionality PXG3.W100-2 A6V12304192
BACnet/IP web server with extended functionality PXG3.W200-2

3
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Technical and mechanical design
The compact build allows for mounting the devices on a standard rail or a wall.

5 6 7 8 4 Service button (network login and WLAN on/off)


5 2-port Ethernet switch with 2 LEDs per port for
display purposes
6 Plug-in terminal block with screw terminals
KNX PL-Link
1
7 Plug-in terminal block with screw terminals
2 Power supply
3 8 Plug-in terminal blocks with screw terminals
Digital input
4
9 Plug-in terminal block with screw terminals
Date/Series M-bus, for future use
S/N

10 Plug-in terminal block with screw terminals


WLAN
Default COM1 / COM2 (MS/TP or Modbus)
11 DIP switches for bus termination and polarization
COM1 / COM2
15 16 11 10 12 11 10 13 9 14 12 Slider for mounting on standard mounting rails
13 Eyelets for cable ties
1 Plastic housing 14 Holes for wall mounting
2 Front cover 15 Date / Series and Serial number
3 LEDs for communication and state 16 QR code for default WLAN access
Description see Technical data

4
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
LED displays

Activity LED Color Activity Function


Ethernet Green Continuously ON Link active
1/2 Continuously OFF No connection
Flashing Network traffic
Yellow Continuously ON Link 100 Mbps
Continuously OFF Link 10 Mbps
RUN Green Continuously ON Device operational
Continuously OFF Device not operational
Flashing Start-up or program halted
Red Continuously OFF OK
Continuously ON HW or SW fault
Rapid flashing Firmware or application missing/corrupted
Blue Continuously ON Connection to the cloud OK
Continuously OFF No connection to the cloud
BAT Red Continuously OFF Optional battery OK
Continuously ON Optional battery empty - replace
COM… Yellow Flashing Communication
Continuously OFF No communication to subsystem
KNX Yellow Flashing Communication
Continuously OFF No communication to subsystem
SVC Red Continuously OFF OK
Flashing Device is not configured
Flashing per wink Identification of the device after receipt of
command wink command

5 Hz 5 Hz

2s 1s 2s 1s

WLAN Blue Steady OFF WLAN inactive


Steady ON WLAN active and at least one WLAN client
connected
Flashing WLAN active and no WLAN client
connected
Service Press 0.2 ... 1 s Identification in the network
button Press 1 ... 3 s Enable/disable WLAN
WLAN is disabled automatically after 10 min
if no client is connected
As per description Do the following to reset the device to
factory state:
1. Power off the device.
2. Power on the device.
3. Wait until all LEDs light up and turn off
again, then press the Service button.
4. Keep the Service button pressed until
all LEDs light up, then release the
button.
All LEDs go off, the device restarts.
5. Wait until the device has fully started –
unconfigured (green RUN LED and red
SVC LED are flashing)

5
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Product documentation
Related documents such as the environmental declarations, declarations of conformity, etc.,
can be downloaded from the following Internet address:
www.siemens.com/bt/download

Notes
Safety

CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
● Observe national provisions and comply with the appropriate safety regulations.

Mounting position and ambient temperature


The devices can be snapped onto standard rails or screwed onto a flat surface.
Plug-in screw terminals connect power and interfaces.

Ambient temperature -5...50 °C (23...122 °F) Ambient temperature -5...45 °C (23...113 °F)
● Wall, horizontal ● Overhead
– From left to right ● Wall, vertically

– From right to left – From top to bottom


– From bottom to top
● On a horizontal surface

Installation

WARNING
Electric shock
Incorrect installation of the device may lead to electric shock injuries when touching the
device!
● Install the device in a lockable cabinet or use terminal covers.
● Do not install the device in locations where children are likely to be present.
● Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply with the
requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS 60695-11-21.

Disposal

This symbol or any other national label indicate that the product, its
packaging, and, where applicable, any batteries may not be disposed of as
domestic waste. Delete all personal data and dispose of the item(s) at
separate collection and recycling facilities in accordance with local and
national legislation.
For additional details, refer to Siemens information on disposal.

6
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Warranty
The application-specific technical data is guaranteed only in combination with the Siemens
products listed in the 'Device combinations' section. If third-party products are used, any
guarantee provided by Siemens will be invalidated.

Technical data
Power supply

Operating voltage (24 V~, ⏊, ) AC 24 V -15 / +20 % (PELV)


AC 24 V Class 2 (US)
48…63 Hz
Functional ground (US) The terminal for the functional ground must be
Functional earth connected on the installation side with the building
grounding system (PE).
Screw terminals for wire cross sections up to Max. 2.5 mm2 (14 AWG)
Internal fusing 3.15 A irreversible / non-replaceable
External supply line fusing (EU) Non-renewable fuse max. 10 A slow-blow
or
circuit breaker max. 13 A
Tripping characteristic B, C, D per EN 60898
or
Power supply with current limitation of max. 10 A

Power consumption (for transformer planning)

Full load 19 VA / 0.8 A


Base load (without loading by KNX PL-Link and M-Bus) 12 VA / 0.5 A
KNX PL-Link supply 4 VA / 0.17 A
M-Bus supply, for future use 3 VA / 0.13 A

Function data

Hardware information
Processor NXP i.MX8 DualX, 1 GHz
Storage 1 GByte RAM
8 GByte eMMC

Data backup in the event of power failure


Energy reserve (supercapacitor) to support real-time clock (7 days).
Energy reserve to support real-time clock can be extended using optional battery CR2032: depending on the life
time of the battery and use, typically 10 years.
(Battery safety requirement and specification for CR2032 according to IEC 60086-4 or UL1642.
Battery must be rated for ambient temperature 70 °C (158 °F))
Low power of battery will be indicated by LED and a system alarm will be generated
Data available if stored to flash memory: Every 5 minutes.
The interval of 5 minutes is only valid for change log but not for trending.
In case of a power failure, trend log data can be lost up to 30 minutes.

7
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Interfaces

Ethernet interface
Plug 2 x RJ45, shielded
Interface type 10Base-T / 100Base-TX, IEEE 802.3 compatible
Bit rate 10/100 Mbps, autosensing
Protocol BACnet/IP on UDP/IP, BACnet/SC on TCP/IP, and
HTTPS on TCP/IP
Cabling (in-house cabling only), cable type 10 Mbps: Min. CAT3, shielded cable is recommended
100 Mbps: Min. CAT5, shielded cable is recommended
Cable length Max. 100 m (330 ft)

Screw terminals, plug-in


Cu-wire or Cu-strand with wire end sleeve 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.0 mm2 (22 to 18 AWG)
Cu-strand without wire end sleeve 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.5 mm2 (22 to 16 AWG)
Stripping length 6...7.5 mm (0.24...0.29 in)
Screwdriver Slot screws, screwdriver size 1 with shaft ø = 3 mm
Max. tightening torque 0.6 Nm (0.44 lb ft)

The two COM interfaces can be used either for Modbus RTU or for BACnet MS/TP,
according to configuration.

Modbus RTU interface


Interface type EIA-485, electrically isolated
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, 76800, 115200 (depending on the configuration)
Internal bus termination 120 Ohm, switchable with DIP switch
Internal bus polarization 270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only) 3-wire cable, shielded cable recommended (shield must
Cable length be connected to building earth in the mounting panel)
Max. 1000 m (3300 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V

BACnet MS/TP interface


Interface type EIA-485, electrically isolated
Baud rate 9600, 19200, 38400, 76800, 115200 (depending on the
configuration)
Internal bus termination 120 Ohm, switchable with DIP switch
Internal bus polarization 270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only) 3-wire cable, shielded
Distance between 2 devices Max. 500 m (1650 ft)
Length of the MS/TP line Max. 1000 m (3300 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V

8
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
WLAN interface
Interface type Wireless access point
Supported standards IEEE 802.11b/g/n
Frequency band 2.4…2.462 GHz
WLAN channels 1…11
Maximum radio-frequency power 16.4 dBm
Distance (unobstructed field) Min. 5 m (16 ft)
Device pairing Activation / deactivation with service button
Automatic switch off after 10 minutes if no WLAN-client
is connected.
Optionally, for cyber security reasons, the WLAN can be
permanently disabled via configuration.
Default SSID and WLAN password: Scan the QR code.
It will display something like WIFI:S:PXC5.E003_0000550;T:WPA;P:1400052738;;
Then SSID = PXC5.E003_0000550 and password = 1400052738
Determine manually: Use the information from the Date/Series/SN block It will display something like:
Date/Series: 20190423A0000550
S/N: 1400052738
SSID = <ASN>_<Running number after the series letter> and password = <S/N>

KNX PL-Link interface


Type KNX TP1 PL-Link, galvanic isolation
Baud rate: 9.6 kbps
Cabling (in-house cabling only) 2-wire cable, 0.75 mm2 / AWG20
or 1 mm2 / AWG18
Cable length With internal supply: Max. 80 m (262 ft)
With external supply: Max. 1000 m (3300 ft)
Internal bus power Max. 50 mA
When using external bus power for KNX PL-Link, switch
off the internal bus power via the ABT Site Tool.

Conformity

Ambient conditions and protection classification


Classification as per EN 60730
Automatic action Type 1
Control function Class A
Pollution degree 2
Overvoltage category I
Protection against electric shock Protection class III
Protection degree of housing to EN 60529
Front parts in DIN cut-out IP30
Terminal part IP20
Climatic ambient conditions
● Storage / Transport (packaged for transport) as per ● Class 1K22 / 2K12
IEC EN 60721‑3‑2 Temperature -25...70 °C (-13...158 °F)
Air humidity 5...95 % (non-condensing)
● Operation as per IEC/EN 60721-3-3 ● Class 3K23
Operation in enclosed dry locations, having no
temperature or humidity control
Temperature -5...50 °C (23...122 °F)
(for details see chapter Mounting)
Air humidity 5...95 % (non-condensing)
Mechanical ambient conditions
● Transport per IEC/EN 60721-3-2 ● Class 2M4
● Operation as per IEC/EN 60721-3-3 ● Class 3M11

9
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Standards, directives, and approvals
Product standards IEC/EN 60730-1, IEC/EN 62368-1
Product family standard IEC/EN 63044-x
Electromagnetic compatibility (EMC) For residential, commercial, and industrial environments
EU conformity (CE) See CE declaration 1)
EAC conformity Eurasian compliance
RCM conformity See RCM declaration 1)
UL/cUL approbation (US / Canada) UL916, http://ul.com/database
CSA certification C22.2, http://csagroup.org/services-industries/product-
listing
FCC CFR 47 Part 15C
BACnet B-BC
AMEV profile (BACnet 2017) AS-A / AS-B 2)
KBOB profile (BACnet 2017) AS-CH 3)
Environmental compatibility 1) The product environmental declaration 1) contains data
on environmentally compatible product design and
assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).

1)
Documents can be downloaded at www.siemens.com/bt/download.
2)
AS-B pending
3)
AS-CH pending

European Union conformity


Contact for regulatory topics: (EU) Siemens AG, Berliner Ring 23, DE-76437 Rastatt

FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
● Reorient or relocate the receiving antenna.
● Increase the separation between the equipment and receiver.
● Connect the equipment into an outlet on a circuit different from that to which the receiver
is connected.
● Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions:
1. This device may not cause harmful interference, and
2. this device must accept any interference received, including interference that may cause
undesired operation
FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland
Ltd. could void user authority to operate the equipment. United States representative
https://new.siemens.com/us/en/products/buildingtechnologies/home.html

10
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Industry Canada statement
This device complies with ISED’s license-exempt RSSs. Operation is subject to the following
two conditions:
1. This device may not cause interference, and
2. This device must accept any interference received, including interference that may cause
undesired operation.

Radiofrequency radiation exposure statement


This equipment complies with FCC and IC radiation exposure limits set forth for an
uncontrolled environment. This equipment should be installed and operated with a minimum
distance of 20 cm between the radiator and your body.
This transmitter must not be co-located or operated in conjunction with any other antenna or
transmitter.
Housing

Color top / bottom 2003 Ti-Grey / 804 Black


Dimensions per DIN 43880, see Dimensions
Weight without / with packaging 351 g / 391 g

11
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Connection terminals

3 4 5 6 7 10 11

65 66 67 68 69 70 71 72

Terminal Symbol Description


1, 2 2 x RJ45 interface for Ethernet with switch

3, 4 KNX KNX PL-Link


5, 6 ~,⏊ Operating voltage AC 24 V
7 Functional ground (must be connected on the installation side with the building
grounding system (PE)).
10, 11 D, ⏊ Digital input
Term on, off Switch for bus termination
Polar on, off Switch for polarization
65, 66, 67 COM1 Interface EIA-485 (Modbus RTU, BACnet MS/TP)
68, 69, 70 COM2
71, 72 MBUS M-bus interface (for future use)

12
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Dimensions
All dimensions in mm and inches.

21.5 (0.85")

11 (0.43")
124 (4.88")

117 (4.61")

35.5 (1.40")
110 (4.33")

45 (1.77")

11 (0.43")
4 (0.16")

21.5 (0.85")
26.5 (1.04")
4.1

45 (1.77")
(
0.1
6")

49 (1.91")
129 (5.08")
65.5 (2.58")
144 (5.67")
70.5 (2.78")

13
Siemens Schweiz AG A6V11646020_en--_i
Smart Infrastructure 2023-05-30
Issued by © Siemens 2020
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies

Document ID A6V11646020_en--_i