Aux Boiler Feed Water VV Sipart PS2-Manual
Aux Boiler Feed Water VV Sipart PS2-Manual
138
Tolerance band "Down" Change gearing (4).
9
violated. Continue using:
-
238
+
o
33
Linear actuator or adjust friction clutch (5) up to
display shows d_0_u:
5
4
5 3.1 3.2 2 3.2
2 Linear actuator -
1 Display 3.1 Restrictor Y1 4 Transmission ratio selector external linear
2 Keys 5 Adjustment wheel for
Continue using:
3.2 Restrictor Y2 with double- potentiometer (e. g.
acting positioners friction clutch
with cylinder drives) or for 'WAY' using:
Changing the operating mode Once the friction For linear actuators:
2.) Press for > 5 s Set pick-up lever perpendicular
Display (1) clutch (5) has been
Operating mode Remaining steps carried out automatically. to the spindle:
adjusted.
P manual mode Continue using:
Position of
3.) Direction of action is determined.
potentiometer [%] Tolerance band "Up" Acknowledge message using:
Change position using: violated.
Set the next highest travel value on
Not initialized the lever.
4.) Determination of the travel. Zero point and stroke are Restart initialization.
PRST
Degrees
33° A. PST Partial Stroke Test (PST) with option -Z P02
Set transmission ratio selector (4) appropriately 90°
(see view of device)
3.YWAY 1) Range of stroke (optional setting) OFF b. DEVI Monitoring dynamic control valve behavior
5 | 10 | 15 | 20 mm
If used, the value on the actuator must correspond
(Short lever 33°, range of
to the set range of stroke on the lever arm. stroke 5 to 20 mm) C. LEAK Monitoring/compensation pneumatic leakage
Carrier pin must be set to the value of the actuator 25 | 30 | 35
travel or, if this value is not scaled, to the next (Short lever 90°, range of
larger scale value stroke 25 to 35 mm)
40 | 50 | 60 | 70 | 90 | 110 | 130 d. STIC Monitoring of stiction (slipstick)
(Long lever 90°, range of
stroke 40 to 130 mm)
4.INITA Initialization (automatic) NOINI | no / ###.# | Strt E. DEBA Monitoring of deadband
5.INITM Initialization (manual) NOINI | no / ###.# | Strt
6.SCUR Current range of setpoint 0 ... 20 mA 0 MA Monitoring of lower endstop
F. ZERO
4 ... 20 mA 4 MA
7.SDIR Setpoint direction Rising riSE
Falling FALL G. OPEN Monitoring of upper endstop
8.SPRA Setpoint split range start 0.0 ... 100.0 %
9.SPRE Setpoint split range end 0.0 ... 100.0 %
10.TSUP Setpoint ramp up Auto / 0 ... 400 s H. TMIN Monitoring the lower limit temperature
11.TSDO Setpoint ramp down 0 ... 400 s
12.SFCT Setpoint function J. TMAX Monitoring the upper limit temperature
Linear Lin
Equal percentage 1: 25, 1:33, 1:50 1 - 25 1 - 33 1 - 50
Invers equal percentage 25:1, 33:1, 50:1 n1 - 25 n1 - 33 n1 - 50
Freely adjustable FrEE L. STRK Monitoring the number of total strokes
13.SL0 2) Setpoint turning point at 0%
etc. ... etc. to 0.0 ... 100.0 %
33.SL20 100 % O. DCHG Monitoring the no. of changes in direction
34.DEBA Deadband of closed-loop controller Auto / 0.1 ... 10.0 %
35.YA Start of manipulated variable limit 0.0 ... 100.0 % P. PAVG Monitoring the position average value
36.YE End of manipulated variable limit 0.0 ... 100.0 %
37.YNRM Standardization of To mechanical travel MPOS Parameter
Function
Parameter values Unit Notes
manipulated variable To flow FLoW name (bold = factory setting)
38.YDIR Direction of manipulated variable Rising riSE U. PRES 5) Pressure monitoring On / OFF
for display and position feedback Falling FALL
39.YCLS None no U1.PUNIT Pressure unit bAr / PSI / MPA
Tight closing / fast closing with
manipulated variable Tight closing Up uP U2.P_HYS Hysteresis for limits 0.200 ... 1.000 bar
Tight closing Down do 2.90 ... 14.50 psi
Tight closing Up and Down uP do 0.020 ... 0.100 MPa
Fast closing Up Fu
Fd U3.PFRLL Behavior lower limit PZ Cont / HoLd
Fast closing Down
Fast closing Up and Down Fu Fd
Tight closing Up and fast closing Down uP Fd U4.PFRUL Behavior upper limit PZ Cont / HoLd
Fast closing Up and tight closing Down Fu do
40.YCDO Lower value for tight closing / fast closing 0.0 ... 0.5 ... 100.0 % U5.PZMLL Lower limit PZ 1.400 ... 7.000 bar
20.30 ... 101.52 psi
41.YCUP Upper value for tight closing / fast closing 0.0 ... 99.5 ... 100.0 % 0.140 ... 0.700 MPa
42.DI1 3) Function of digital input DI1 NO contact NC contact
U6.PZMUL 1.400 ... 7.000 bar
Upperlimit PZ
None OFF 20.30 ... 101.52 psi
Message only on -on 0.140 ... 0.700 MPa
Block configuration bLoc 1
U7.PCL Limit actuating pressure Y1 0.000 ... 7.000 bar
Block configuration and manual bLoc 2 00.00 ... 101.52 psi
Move process valve to position YE uP -uP 0.000 ... 0.700 MPa
Move proces valve to position YA doWn -doWn
Block movement StoP -StoP U8.LRL Limit +/- Leakage 0.000 ... 7.000 bar
Partial Stroke Test PSt -PSt 00.00 ... 101.52 psi
0.000 ... 0.700 MPa
43.DI2 3) Function of digital input DI2 NO contact NC contact
None OFF U9.TPMT Time pressure measurement Y1 1 ... 100 s
Message only on -on
Move process valve to position YE uP -uP
Move process valve to position YA doWn -doWn
Block movement StoP -StoP
Partial Stroke Test PSt -PSt
44.AFCT 4) Alarm function Normal Inverted
None OFF
A1=Min, A2=Max
A1=Min, A2=Min
A1=Max, A2=Max
45.A1 Response threshold of alarm 1 0.0 ... 10.0 ... 100.0 %
46.A2 Response threshold of alarm 2 0.0 ... 90.0 ... 100.0 %
47. FCT 4) Function fault message output Normal Inverted
Fault
Fault + not automatic
Fault + not automatic + DI
("+" means logical OR combination)
48. TIM Monitoring period for setting of fault message s
'Control deviation'
Auto / 0 ... 100
49. LIM Response threshold for fault message 'Control
deviation'
Auto / 0 ... 100 %
50.PRST Preset
Reset all parameters which can ALL HINTS:
be reset by 'Init', 'PArA' and 'diAg'.
Reset initialization parameters '1.YFCT' 1) Parameter only appears with 'WAY', '-WAY', 'ncSLL', and '-ncLL'
Init 2) Turning points only appear with selection 12.SFCT = 'FrEE'.
to '5 INITM'.
Reset parameters '6.SCUR' to '49. LIM'. 3) NC contact means: action with opened switch or Low level
PArA
Reset param. A to U of the extended diagnostics NO contact means: action with closed switch or High level
diAg 4) Normal means: High level without fault
function as well as parameter '52.XDIAG'.
Inverted means: Low level without fault
51.PNEUM Pneumatics type
Standard pneumatic block Std 5) Only with built-in pressure option -Z P01 / -Z P02
Fail in Place pneumatic block FIP
Operation with boosters booSt
52.XDIAG Activating for extended diagnostics Off OFF
Single-stage alarm On1
Two-stage alarm On2
Three-stage alarm On3 A5E00074670-06 10/2020