Power System Security
The power system needs to be secured, we need to protect it from the black
out or any internal or external damage.
The operation of the power system is set to be normal only when the flow of
power and the bus voltages are within the limits even though there is a
profitable change in the load or at the generation side.
From this we can say that the security of the power system is an important
aspect with respect to the continuation of its operation.
Security function are of two type as follows:
Security control: - It determines the exact and proper security constraint
scheduling which is required to obtain the maximized security level.
Security assessment: - It gives the security level of the system in the
operating state.
Power system security assessment is the assessment of the operating network
in a manner so as to identify the possible failure/s that may occur in the
system, its consequences and its
remedial actions.
The power system may be assumed as being operated under two sets of
constraints: load constraints and operating constraints. The load constraints
impose the requirement that the load demand must be met by the system. The
operating constraints impose maximum or minimum
operating limits on system variables and are associated with both steady state
and stability limitations. Mathematically, the load constraints can be expressed
in the form of the familiar
load flow equations. The operating constraints can be expressed in the form of
inequalities such as an equipment loading, bus voltage, phase angle differences,
generator real and reactive powers etc. The operating conditions of the power
network can then be categorized into three operating states (refer Fig 1):
• Normal (or Preventive) State
• Emergency State
• Restorative State
1. A system is in the normal state when the load and operating constraints are
satisfied. It is reasonable to assume that in the normal state the power
system is in a quasi-steady state condition. For any given time, the
intersection of the load constraints and the operating constraints defines
the space of all feasible normal operating states. The power system may be
operated anywhere in this space.
A normal operating point can be classified as being either secure or insecure
with reference to an arbitrary set of disturbances or next contingencies. A
normal system is said to be secure, i.e. at a secure operating point, if it can
undergo any contingency in the next-contingency set without getting in to an
emergency condition.
On the other hand, if there is at least one contingency in the next
contingency set which would bring about an emergency, the normal system
would be called insecure or in an alert state.
2. A system is in the emergency state when the operating constraints are not
completely satisfied. Two types of emergency may be noted. One is when
only steady state operating constraints are being violated, e.g. an equipment-
loading limit is exceeded or the voltage at a bus is below a given level.
The other is when a stability operating constraint is violated and as a result
of which the system cannot maintain stability. The first type of emergency
may be called “Steady State emergency” and the second type, “dynamic
emergency”.
3. A system is in the restorative state when the load constraints are not
completely satisfied. This means a condition of either a partial or a total
system shutdown. When the extreme emergency (extremis state) comes
into action there is occurrence of extreme disturbance.
In this case the power system is in up stable state and may lead to shutting
down of the major parts of the power system. Control action should be
powerful such that the shedding of the load of the unimportant load are
needs to be done. In case of a partial shutdown the reduced system may be
in an emergency state.
This is the start of a cascading situation and, if uncorrected, would lead to a
further deterioration of the system.
Contingency Analysis. Preventive Control and Emergency Control-:
For a power system to be secure, it must have continuity in supply without a loss
of load. For this security analysis is performed to develop various control
strategies to guarantee the avoidance and survival of emergency conditions and
to operate the system at lowest cost.
Whenever the pre specified operating limits of the power system gets violated
the system is said to be in emergency condition. These violations of the limits
result from contingencies occurring in the system.
A contingency is the unexpected failure of a transmission line, transformer,
or generator. Usually, contingencies result from occurrence of a fault, or short-
circuit, to one of these components.
When such a fault occurs, the protection systems sense the fault and remove
the component, and therefore also the fault, from the system.
Of course, with one less component, the overall system is weaker, and
undesirable effects may occur.
For example, some remaining circuit may overload, or some bus may experience
an undervoltage condition.
These are called static security problems. Dynamic security problems may also
occur, including uncontrollable voltage decline, generator overspeed (loss of
synchronism), or undamped oscillatory behaviour.
Contingency analysis technique is being widely used to predict the effect of
outages like failures of equipment, transmission line etc, and to take necessary
actions to keep the power system secure and reliable. The contingency analysis
is divided into three different stages
1. Contingency definition – It comprise of set of contingencies that occur in
the power system.
2. Selection – The process of identifying the contingencies that actually leads
to the violation of the operational limits is known as contingency selection. Thus,
this process removes the unimportant contingencies and hence the contingency
list is shortened.
3. Evaluation – In this process it involves the necessary security action or
control to function in order to remove the effect of contingency.
Preventive Control and Emergency Control
The first function of security analysis (SA) is to determine whether the normal
system is secure or insecure. The second function is to determine what
corrective action strategy should be taken when the system is insecure.
The first function commonly classifies under contingency definition and
selection since, by definition, the security of a system is determined with
reference to a set of next contingencies.
The second part of security analysis is “Corrective Action Strategy”. whether
the system would respond in an acceptable manner and reach an acceptable
state following any one of a pre-defined contingency set. That is, if the system
is insecure, can it be made secure? If so, how and at what cost? Conditions
improve? Suppose the system is now insecure and there is no way of making it
secure, how much load would be shed.
Preventive Control:
If a system operator infers from the operating data that a system is in an alert
state, then he takes preventive control actions to bring the system back to a
normal state.
If the state is normal, then a system operator may wish to do some minor
changes in real and reactive scheduling (from an economic perspective), if such
flexibility exists. However, if any such change cannot bring the system out of
the secure state, the system is not secure (alert), then the operator has to try
to steer it into the secure state by real or reactive power rescheduling
(Preventive Control).
However, re-scheduling is only done to improve security and may result in higher
cost if cheaper generators are asked to "back down" their generated power
while costlier ones are ramped up.
Therefore, even if preventive control is to be done, it should be done in a way
which will minimize any cost increase while simultaneously ensuring security.
Emergency Control: If a system operator infers from the operating data that a
system is in an alert state, then he takes preventive contrl actions to bring the
system back to a normal state.
However, it is possible that the system operator is unable to act in time before
a contingency actually occurs or a grid may even operate insecurely (in an alert
state) due to high cost of preventive control or due to inadequate reserve
margins.
In such situations, a system in an alert state may cascade into an emergency and
subsequently into a total blackout if no control actions
are taken. Emergency control measures can be used to retrieve such situations.
Since most equipment can withstand a short-time thermal overload, there is a
small window of time in which some manual emergency measures can be
executed.
For other emergency situations (like instability), time may be too short and
predesigned automatic emergency measures are necessary. Some emergency
control actions that can be taken are:
a) Control of generation (reducing or increasing as per requirement).
b) Tripping of generation or load shedding.
c) Control of voltage and Re-routing of power flows.
What is meant by corrective rescheduling?
It is basically defined as the measures taken to avoid the faults after it has
occurred i.e.to isolate the defective fault from the non-faulty part of the
power system and then further rectify the fault.
After the rectification of the fault in the power system it is then restored in
the power system from where it was isolated.