ELECTRICAL & ALLIED WORKS
S. No. Description Qty Unit Rate
0.0 Power Sources
0.1 Installation of Oil Type Distribution Transformer 11KV 1 Nos.
0.2 / 415 Volt 400 kVA (On Prime Rating). 1 Nos
0.3 Diesel Generator Set. 1 Set
Only installation at designated location, connection of cables,
testing and commissioning of owner supplied water cooled NEW
diesel genset with canopy and other necessary arrangement,
complete in all respects.
Intsallation of Diesel Gen Set 220 kVA as per SLD.
Standby Source - Inverter (UPS)
Inverter (UPS - Un-interruptible Power Supply)
Only installation at designated location, connection of cables,
testing and commissioning of Owner Supplied Inverter (UPS)
with Dry Batteries Bank (as specified below), complete in all
respects.
UPS With deep discharged, GEL type Dry Batteries Set.
Amount
-
-
-
Description Qty Unit Rate
1.0 LT Panel Boards
1.01 LT SWITCHGEARS / BOARDS
1.02 General Cubicle Guidelines:
Fabrication, supply at site, installation at designated location,
testing and commissioning of Meter Panel Board (MPB)
comprising of cubicles, frame made of sheet steel 12 SWG and
doors of 14 SWG, with flexible earthing straps, degreased and
de-rusted, finished with electro-static powder coating of 50
micron thickness in approved color, panel housing to
comply with protection class IP-54, indoor floor mounting, in
free standing design, with hinged door, lockable handle, all
auxiliaries, internal wiring, designation labels on MCCBs,
earthing bar, numbering beads on the control wires, panel
suitable for system Voltage 415 V, 50 Hz, 3 Phase and neutral, bus
bars of 99.8% purity electrolytic copper, including cost of cable
termination lugs, brass cable glands for incoming & outgoing
cables, wiring from breakers, indication lamps, instruments
and control all accessories complete in all respects.
All incoming and outgoing breakers shall be accessible by
opening the front door having additional M.S. sheet cover.
Gaskets shall also be provided where necessary. All MCCBs
shall be suitable to operate without any de- rating at 50°C
ambient temperature and shall be of one make only and not a
mixture of more than one make. The front and back sides of
LTMPB shall also have louvers at bottom and sides of
panel for hot air exhaust. The panel shall have a front
access. Circuits’ layout shall conform to the single line
diagrams. Low Tension Main Panel Board & Sub Main Panel
Board shall be manufactured by any one of the manufacturer
as mentioned in list of manufacturers.
Main Panel Boards (MPB-GF)
Confirming to general specification mentioned in 1.01 but
equipped with following:
Incoming:
01 - MCCB TP 630 Amp Adj. MCCB (15 KA)
01 - Energy Analyzer (Smart Control) 03 - CTS 630/5 accuracy class
0.5
03 - Voltmeter 0 - 500V (Smart Control) 03 - Amp 0 - 630 (Smart
Control)
03- Phase Indication Lights (RYB) 02- ON/OFF Indication Lights
4 - Bus bar Cu Strip/phase comprises on [1x(40x10)] Size
1 - bus bar Cu Strip (PC) Size = [1x(20x10)]
1.03 Outgoing : 1 Nos
1.04 01 - MCCB Adj. TP pole 400 Amp 15KA 1 Nos
03 - MCCB TP pole 100 Amp 15KA 1 Each
02 -MCCB TP pole 60 Amp 15KA
01 - MCCB TP pole 30 Amp 15KA
01 - MCB DP pole 40 Amp 15KA
Complete in all respect as per single line diagram.
ATS With AMFP Panel
Confirming to general specification mentioned in 1.01 but
equipped with following:
Incoming:
02 - MCCB TP 630 Amp Adj. MCCB (15 KA)
01 - MCCB FP 400 Amp MCCB (15 KA)
01 - Magnetic Contactor AC3 Rated TP 600 Amp 01 - Magnetic
Contactor AC3 Rated FP 300 Amp 03 - CTS 630/5 accuracy class
0.5
03 - CTS 300/5 accuracy class 0.5
06 - Voltmeter 0 - 500V (Smart Control) 03 - Amp 0 - 400 (Smart
Control)
03 - Amp 0 - 630 (Smart Control) 06- Phase Indication Lights (RYB)
04- ON/OFF Indication Lights
01- AMFP with ATS Module (Deepsea 8610 / Lovato /
Datakom / equivalent)
01- Electrical/Mechanical Interlocking
01 Set- Battery Charger , Batteries, Aux Relay and allied
accessories
4 - bus bar Cu Strip/phase comprises on [1x(40x10)] Size
1 - bus bar Cu Strip (PC) Size = [1x(20x10)]
Outgoing :
01 - MCCB Adj. TP pole 630 Amp 15KA
Complete in all respect as per single line diagram.
PFI PLANT :
Fabrication, supply, installation & commissioning of sheet
metal clad totally enclosed free standing, front excess Power
factor improvement plant to be installed with Main LT Switch
Board, fabricated from 12 SWG
M.S. sheet steel & doors from 14 SWG M.S. sheet steel with
electrostatic paint of approved color, 415 volts, 3 phase,
50Hz, power factor improvement plant of automatically /
manually controlled. complete with air contactors, HRC fuses for
short circuit protection
On/Off push buttons, On/Off indication light, PFI relay, make
NOKIAN/Entes for switching in & out out the capacitors in
12 steps, HRC fuses, control fuses, auto/manual selector
switch, 415 volts 3 phase delta connected capacitors
Amount
-
-
-
-
Description Qty Unit Rate
1.05 DISTRIBUTION BOARDS
i Supply installation and commissioning of recessed wall mounting
ii type Distribution Boards fabricated from 16 SWG sheet steel
with electrostatic paint of approved color and with back box,
comprising of incoming 3 phase moulded case circuit
breakers or earth leakage circuit breakers (as specified) and
outgoing single phase Miniature circuit breakers (having
magnetic & thermal trip devices) as given below, complete
with internal wiring earthing , neutral link, termination
blocks and cable chamber at the top of incoming 3 phase
moulded case circuit breakers or earth leakage circuit
breakers (as specified) and outgoing single phase Miniature
circuit breakers (having magnetic & thermal trip devices) ,
complete with internal wiring earthing, neutral link,
termination blocks and cable chamber at the top of the DB.
Each D.B. shall have Digital Voltmeter, Voltmeter /
Selector switch, LED Phase indication lights & control fuses
on incoming. All breakers & instrumentation and other
materials shall be as listed in Annexure “A” it shall be
manufactured by any one of the manufacturers as mentioned in
Annexure ”A” and conforming to single line diagram.
Distribution Board (DB-GF)
Conforming to same constructional specification as 1.03 but
equipped with following:
Incoming
1-100 ATP MCCB
(10 KA)
03- Phase Indication Light
01 - Voltmeter 0 - 500V (Smart Control) with Selector Switch
Outgoing:
12-10/16 ASP MCB (6 KA)
12-20 ASP MCB (6 KA)
2-20 ATP MCB (6 KA)
3- MCB Single Pole - Spaces For Futures
Distribution Board (DBAC-GF)
Conforming to same constructional specification as 1.03 but
equipped with following:
Incoming
1-400 ATP MCCB (10 KA)
1 Nos
Amount
-
-
Description Qty Unit Rate
iii 03- Phase Indication Light 1 Nos
iv 01 - Voltmeter 0 - 500V (Smart Control) with Selector Switch 1 Nos
v Outgoing: 1 Nos
15-20 ASP MCB (6 KA) 1 Nos
08-50 ATP MCCB (6 KA)
04-20 ATP MCB (6 KA)
02-150 ATP MCCB (10 KA)
6- MCB Single Pole - Spaces For Futures
Distribution Board (DB-1F)
Conforming to same constructional specification as 1.03 but
equipped with following:
Incoming
1-100 ATP MCCB (10 KA)
03- Phase Indication Light
01 - Voltmeter 0 - 500V (Smart Control) with Selector Switch
Outgoing:
12-10/16 ASP MCB (6 KA)
12-20 ASP MCB (6 KA)
2-20 ATP MCB (6 KA)
3- MCB Single Pole - Spaces For Futures
Distribution Board (DBU-GF)
Conforming to same constructional specification as 1.03 but
equipped with following:
Incoming
1-40 ADP MCCB (10 KA)
01- Phase Indication Light
01 - Voltmeter 0 - 240V (Smart Control)
Outgoing:
15-10/16 ASP MCB (6 KA)
3- MCB Single Pole - Spaces For Futures
Distribution Board (DB-KITCHEN)
Conforming to same constructional specification as 1.03 but
equipped with following:
Incoming
1-100 ATP MCCB (10 KA)
03- Phase Indication Light
01 - Voltmeter 0 - 500V (Smart Control) with Selector Switch
Outgoing:
9-10/16/20 ASP MCB (6 KA)
3-40 ATP MCB (6 KA)
3- MCB Single Pole - Spaces For Futures
SUB TOTAL SECTION (1.0)
2.0 CIRCUIT POINT WIRING
2.01 Note:- For list of approved manufacturer's see 15 Each
2.02 Annexure "A". Furthermore, flexible pipe ,where req,will be 4 Each
2.03 corrugated. And all the connectors will be non- flammable 24 Each
2.04 type. 30 Each
2.05 Supply and wiring of light circuit from DB to 11 Each
2.06 switchboard with 2x2.5mm single core insulated 300/500
2
174 Each
2.07 volt grade cables and 2.5mm2 cable as protective 4 Each
conductor (PC) in & including PVC conduit installed recessed
in walls / R.C.C. Slab, installed on ceiling or as required as
per site conditions. Complete with all conduit accessories
junction boxes, pull boxes as required complete in all respects as
per specifications and drawings.
Same as item # 2.01, circuit point wiring from switch board
to switch board (Loop Circuit).
Supply and wiring of first light / wall / Exhaust fan point
consisting of one point controlled by one switch with
2x1.5mm (P+N) PVC insulated 300/500 volt grade wire in
2
and including PVC conduits recessed in walls/R.C.C. slab, or
installed on ceilings including all conduit accessories junction
boxes, pull boxes, pull wire, 2.5mm2 cable as PC. complete
with 10 Amp. Single way switch make CLIPSAL / MK /
Legrand / ABB or approved equivalent installed on &
including 16 SWG sheet steel boards recessed in
wall/column complete in all respects as per drawing
&
Same as item No. 2.03 above but point to point wiring.
Same as item No. 2.01 above but first light point
controlled by MCB in DB.
Same as item above but point to point wiring.
Same as item No. 2.03 above but wiring of ceiling fan point
including cost of M.S. fan hook box and fan dimmer make
CLIPSAL or approved equivalent fitted on plastic plates installed
on 16 SWG sheet steel boards recessed in wall/column.
2.08 Supply and wiring of first 3 pin 10 Amps light plug socket 8 Each
2.09 outlet point from nearest switch board with single core 38 Each
2.10 2x1.5mm2(P+N) PVC insulated 300/500 volt grade cable in & 103 Each
including PVC conduit recessed in walls/R.C.C. slab, or
installed on surface of Ceiling including all conduits
accessories, junction boxes, pull boxes etc. 2.5mm2 cable as PC 2
pin 10 Amps switch & socket out let make CLIPSAL / MK /
Legrand / ABB or approved equivalent installed on &
including 16 SWG sheet steel board recessed in walls
complete in all respects and as per specifications & drawings.
Same as item No.2.08 above but wiring of one sockets outlet
for with 3x4mm2(P+N+E) 5A,13A,15A single core cables from
DB to point s including cost of one Nos. 5A,13A,15A.3 pin
switch socket outlet with make CLIPSAL / MK / Legrand /
ABB or approved equivalent installed on & including 16 SWG
sheet steel boards recessed in walls/columns, Complete in all
respects.
Same as item No.2.08 above but loop wiring of
5A,13A,15A sockets outlet with 3x4mm2(P+N+E) single core
cables from point to point including cost of 5A,13A,15A
3 pin switch sockets outlets with make CLIPSAL / MK /
Legrand
/ ABB or approved equivalent installed on & including
16 SWG sheet steel boards recessed in walls
/columns, complete in all respects.
2.13 Same as item No.2.08 above but wiring of one No. 20 Amps AC 11 Each
2.14 Plug with 2x 4mm2 single core cables (P+N) from DB to the 4 Each
2.15 point and 4mm2 as CPC including cost of one no. 20 Amps AC 2 Each
2.16 Power switch sockets outlets make CLIPSAL / MK / Legrand / 2 Each
2.17 ABB or approved equivalent installed on & including 16 SWG 1 Each
sheet steel boards recessed in walls /columns.
Same as item No.2.08 above but wiring of one No. Floor
Mounted AC Cabinet with 4 core 16 mm from DB to the point
2
and 10mm2 as CPC.
Same as item No.2.08 above but wiring of one No. Floor
Mounted AC Unit ( PACU) at roof, with 4 core 35 mm2
cables (3P+N) and 16mm2 as CPC from DB to the point .
Same as item No.2.08 above but wiring of one No. Floor
Mounted Exhaust Fan at roof, with 4 core 25 mm2 cables
(3P+N) and 16mm2 as CPC from DB to the point .
Same as item No.2.08 above but wiring of one No. wall
Mounted I solator 4 pole for L i f t , with 4 core 35 mm2 cables
(3P+N) and 16mm2 as CPC from MPB to the point .
SUB TOTAL SECTION (2.0)
Amount
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-