Ordering data

DATA SHEET

PM572, PM573, PM582, PM583, PM585, PM590, PM591,


PM592
Processor module

1 Ordering data
Processor Part no. Description Product life cycle phase *)
modules for
AC500 1SAP 130 200 R0200 PM572, processor module, memory Classic
(Standard) V2 128 kB, 24 V DC, memory card slot,
products interfaces 2 RS-232/485 (programming,
Modbus/CS31), 1 FBP, display
1SAP 130 300 R0271 PM573-ETH, processor module, memory Active
512 kB, 24 V DC, memory card slot,
interfaces 2 RS-232/485 (programming,
Modbus/CS31), 1 FBP, display, onboard
Ethernet TCP/IP with web server, SNTP,
IEC60870-5-104 protocols
1SAP 330 300 R0271 PM573-ETH-XC, processor module, Active
memory 512 kB, 24 V DC, memory
card slot, interfaces 2 RS-232/485
(programming, Modbus/CS31), 1 FBP,
display, onboard Ethernet TCP/IP with
web server, SNTP, IEC60870-5-104
protocols, XC version
1SAP 140 200 R0201 PM582, processor module, memory Active
512 kB, 24 V DC, memory card slot,
interfaces 2 RS-232/485 (programming,
Modbus/CS31), 1 FBP, display

2024/01/05 3ADR010064, 11, en_US 1


Part no. Description Product life cycle phase *)
1SAP 340 200 R0201 PM582-XC, processor module, memory Active
512 kB, 24 V DC, memory card slot,
interfaces 2 RS-232/485 (programming,
Modbus/CS31), 1 FBP, display,
XC version
1SAP 140 300 R0271 PM583-ETH, processor module, memory Active
1024 kB, 24 V DC, memory card slot,
interfaces 2 RS-232/485 (programming,
Modbus/CS31), 1 FBP, display, onboard
Ethernet TCP/IP with web server, SNTP,
IEC60870-5-104 protocols
1SAP 340 300 R0271 PM583-ETH-XC, processor module, Active
memory 1024 kB, 24 V DC, memory
card slot, interfaces 2 RS-232/485
(programming, Modbus/CS31), 1 FBP,
display, onboard Ethernet TCP/IP with
web server, SNTP, IEC60870-5-104
protocols, XC version
1SAP 140 500 R0271 PM585-ETH, processor module, memory Active
1024 kB, 24 V DC, memory card slot,
interfaces 2 RS-232/485 (programming,
Modbus/CS31), 1 FBP, display, onboard
Ethernet TCP/IP with web server, SNTP,
IEC60870-5-104 protocols
1SAP 150 000 R0261 PM590-ARCNET, processor module, Active
memory 2 MB, 24 V DC, memory
card slot, interfaces 2 RS-232/485
(programming, Modbus/CS31), 1 FBP,
display, integrated communication
module ARCNET
1SAP 150 000 R0271 PM590-ETH, processor module, memory Active
2 MB, 24 V DC, memory card slot,
interfaces 2 RS-232/485 (programming,
Modbus/CS31), 1 FBP, display, onboard
Ethernet TCP/IP with web server, SNTP,
IEC60870-5-104 protocols
1SAP 150 100 R0271 PM591-ETH, processor module, memory Active
4 MB, 24 V DC, memory card slot,
interfaces 2 RS-232/485 (programming,
Modbus/CS31), 1 FBP, display, onboard
Ethernet TCP/IP with web server, SNTP,
IEC60870-5-104 protocols
1SAP 150 100 R0277 PM591-2ETH, processor module, Active
memory 4 MB, 24 V DC, memory
card slot, interfaces 1 RS-232/485
(programming, Modbus/CS31), display,
2 onboard Ethernet TCP/IP with
web server, SNTP, IEC60870-5-104
protocols
1SAP 350 100 R0271 PM591-ETH-XC, processor module, Active
memory 4 MB, 24 V DC, memory
card slot, interfaces 2 RS-232/485
(programming, Modbus/CS31), 1 FBP,
display, onboard Ethernet TCP/IP with
web server, SNTP, IEC60870-5-104
protocols, XC version

2 3ADR010064, 11, en_US 2024/01/05


Dimensions

Part no. Description Product life cycle phase *)


1SAP 150 200 R0271 PM592-ETH, processor module, Active
memory 4 MB / 4 GB flash disk,
24 V DC, memory card slot, interfaces
2 RS-232/485 (programming, Modbus/
CS31), 1 FBP, display, onboard
Ethernet TCP/IP with web server, SNTP,
IEC60870-5-104 protocols
1SAP 350 200 R0271 PM592-ETH-XC, processor module, Active
memory 4 MB / 4 GB flash disk,
24 V DC, memory card slot, interfaces
2 RS-232/485 (programming, Modbus/
CS31), 1 FBP, display, onboard
Ethernet TCP/IP with web server, SNTP,
IEC60870-5-104 protocols, XC version

*) Modules in lifecycle Classic are available from stock but not recommended for
planning and commissioning of new installations.

2 Dimensions

1 Din rail 15 mm
2 Din rail 7.5 mm

2024/01/05 3ADR010064, 11, en_US 3


Technical data

The dimensions are in mm and in brackets in inch.

3 Technical data
The system data of AC500 and S500 are applicable to the standard version Ä Chapter 4 “System
data AC500” on page 11.
The system data of AC500-XC are applicable to the XC version Ä Chapter 5 “System data AC500-
XC” on page 14.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.

Processor Parameter Value


module and
terminal base Connection of the supply voltage 24 V Removable 5-pin terminal block with spring connec-
DC at the terminal base of the processor tion
module
Current consumption from 24 V DC PM57x: 50 mA
PM57x-ETH: 110 mA
PM58x: 50 mA
PM58x-ETH: 110 mA
PM58x-ARCNET: 110 mA
PM59x: 90 mA
PM59x-ETH: 150 mA
PM59x-2ETH: 150 mA
PM59x-ARCNET: 150 mA
Slots on the terminal bases TB511: 1 processor module, 1 communication module
TB521: 1 processor module, 2 communication
modules
TB523: 1 processor module, 2 communication
modules
TB541: 1 processor module, 4 communication
modules
Processor module interfaces at the terminal I/O bus, COM1, COM2, FBP
bases TB5x1
Processor module interfaces at the terminal I/O bus, COM1
bases TB5x3
Processor module network interfaces at the TB5x1-ETH / AC500 CPU with Ethernet interface
terminal bases
TB5x3-ETH / AC500CPU with two Ethernet interfaces
TB5x1-ARCNET / AC500 CPU with ARCNET
Connection system See 'Connection and Wiring'
Weight (processor module without terminal PM582: 135 g
base)
PM58x-ETH: 150 g

4 3ADR010064, 11, en_US 2024/01/05


Parameter Value
PM59x: 135 g
PM59x-ETH: 150 g
PM59x-2ETH: 150 g
PM59x-ARCNET: 160 g
Mounting position Horizontal or vertical

Detailed data Table 1: PM57x


Processor Module PM572 PM573-ETH
Program memory flash EPROM and 128 kB 512 kB
RAM
Data memory, integrated 128 kB, incl. 12 kB buf- 512 kB, incl. 288 kB buffered
fered
Expandable memory None None
Integrated mass storage memory None None
Pluggable memory card for:
User data storage x x
Program storage x x
Firmware update x x
Processor type Freescale ARM Processor 32-bit
Processor clock speed 50 MHz
Cycle time for 1 instruction:
Binary Min. 0.06 µs Min. 0.06 µs
Word Min. 0.09 µs Min. 0.09 µs
Floating point Min. 0.70 µs Min. 0.70 µs
Max. number of central inputs and outputs (up to 7 exp. modules): (1)
Digital inputs 224 224
Digital outputs 224 224
Analog inputs 112 112
Analog outputs 112 112
Max. number of central inputs and outputs (10 exp. modules):
Digital inputs 320 320
Digital outputs 320 320
Analog inputs 160 160
Analog outputs 160 160
Number of decentralized inputs and Depends on the fieldbus used
outputs
(as an info on the CS31 bus: up to 31 stations with up to 120
DI / 120 DO each)
Data backup Battery
Data buffering time at +25 °C Typ. 3 years without power supply
Battery low indication Warning issued about 2 weeks before the state of charge
becomes critical

2024/01/05 3ADR010064, 11, en_US 5


Processor Module PM572 PM573-ETH
Real-time clock:
With battery backup x x
Accuracy Typ. ± 2 s / day at +25 °C
Program execution:
Cyclic x x
Time-controlled x x
Multitasking x x
Protection of the user program by a x x
password
Serial interface COM1:
Physical link Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s)
pluggable terminal block, spring connection for programming,
Connection as Modbus (master/slave), as serial ASCI communication, as
Usage CS31 Master
Serial interface COM2 (not for PM5xy-2ETH models):
Physical link Configurable for RS-232 or RS-485 (from 0.3 to 187.5 kB/s)
D-sub for programming, as Modbus (master/slave), as serial
Connection ASCII communication
Usage
Integrated communication module:
ETH = Ethernet - ETH onboard with web server,
SNTP and IEC60870-5-104 protocol
RJ45 -
ARCNET = ARCNET BNC -
Number of external communication Up to 4 communication modules like PROFIBUS DP,
modules Ethernet, CANopen. There are no restrictions concerning
the communication module types and communication module
combinations (e.g. up to 4 PROFIBUS DP communication
modules are possible)
Ethernet - 10/100 base-TX, 1x RJ45 socket,
provided on TB5x1-ETH
LEDs, LCD display, 8 function keys For RUN/STOP switchover, status displays and diagnosis
Number of timers Unlimited
Number of counters Unlimited
Programming languages:
Structured Text ST x x
Instruction List IL x x
Function Block Diagram FBD x x
Ladder Diagram LD x x
Sequential Function Chart x x
SFC
Continuous Function Chart x x
CFC
1): up to 7 I/O terminal units before PS501 V1.2 and processor module firmware before V1.2.0.

6 3ADR010064, 11, en_US 2024/01/05


Table 2: PM58x
Processor Module PM582 PM583-ETH PM585-ETH
Program memory flash EPROM and RAM 512 kB 1024 kB 1024 kB
Data memory, integrated 416 kB, incl. 288 1024 kB, incl. 1536 kB, incl.
kB buffered 288 kB buf- 512 kB buf-
fered fered
Expandable memory None None None
Integrated mass storage memory None None None
Pluggable memory card for:
User data storage x x x
Program storage x x x
Firmware update x x x
Processor type Freescale ARM Processor 32-bit
Processor clock speed 84 MHz 400 MHz
Cycle time for 1 instruction:
Binary Min. 0.05 µs Min. 0.004 µs
Word Min. 0.06 µs Min. 0.008 µs
Floating point Min. 0.50 µs Min. 0.008 µs
Max. number of central inputs and outputs (up to 7 exp. modules): 1)
Digital inputs 224
Digital outputs 224
Analog inputs 112
Analog outputs 112
Max. number of central inputs and outputs (10 exp. modules):
Digital inputs 320
Digital outputs 320
Analog inputs 160
Analog outputs 160
Number of decentralized inputs and outputs Depends on the fieldbus used
(as an info on the CS31 bus: up to 31 stations with
up to 120 DI / 120 DO each)
Data backup Battery
Data buffering time at +25 °C Typ. 3 years without power supply
Battery low indication Warning issued about 2 weeks before the state of
charge becomes critical
Real-time clock:
With battery backup x
Accuracy Typ. ±2 s / day at +25 °C
Program execution:
Cyclic x
Time-controlled x
Multitasking x
Protection of the user program by a password x

2024/01/05 3ADR010064, 11, en_US 7


Processor Module PM582 PM583-ETH PM585-ETH
Serial interface COM1:
Physical link Configurable for RS-232 or RS-485 (from 0.3
to 187.5 kB/s) pluggable terminal block, spring
Connection connection for programming, as Modbus (master/
Usage slave), as serial ASCI communication, as CS31
master
Serial interface COM2 (not for PM5xy-2ETH models):
Physical link Configurable for RS-232 or RS-485 (from 0.3 to
187.5 kB/s) D-sub for programming, as Modbus
Connection (master/slave), as serial ASCII communication
Usage
Integrated communication module:
ETH = Ethernet - ETH onboard with web server,
SNTP and IEC60870-5-104 pro-
RJ45 - tocol
ARCNET = ARCNET BNC -
Number of external communication modules Up to 4 communication modules like PROFIBUS
DP, Ethernet, CANopen. There are no restrictions
concerning the communication module types and
communication module combinations (e.g. up to 4
PROFIBUS DP communication modules are pos-
sible)
Ethernet - 10/100 base-TX, 1x RJ45
socket,
provided on TB5x1-ETH
LEDs, LCD display, 8 Function Keys For RUN/STOP switchover, status displays and
diagnosis
Number of timers Unlimited
Number of counters Unlimited
Programming languages:
Structured Text ST x
Instruction List IL x
Function Block Diagram FBD x
Ladder Diagram LD x
Sequential Function Chart SFC x
Continuous Function Chart (CFC) x
1): up to 7 I/O terminal units before PS501 V1.2 and processor module firmware before V1.2.0.

8 3ADR010064, 11, en_US 2024/01/05


Table 3: PM59x 2)
Processor Module PM59x-ETH PM59x- PM59x-ETH
ARCNET
PM59x-2ETH
Program memory flash EPROM and RAM PM590: 2048 kB
PM591/PM592: 4096 kB
Data memory, integrated PM590: 2560 kB, PM590: 3072
kB,
PM591: 3584 kB, incl. 1536 kB buf-
fered PM591/592:
5632 kB, incl.
1536 kB buffered
Expandable memory None None None
Integrated mass storage memory None None PM592-ETH: 4
GB flash disk
Pluggable memory card for:
User data storage x x x
Program storage x x x
Firmware update x x x
Processor type Freescale ARM Processor 32-bit
Processor clock speed 400 MHz
Cycle time for 1 instruction:
Binary Min. 0.002 µs Min. 0.002 µs Min. 0.002 µs
Word Min. 0.004 µs Min. 0.004 µs Min. 0.004 µs
Floating point Min. 0.004 µs Min. 0.004 µs Min. 0.004 µs
Max. number of central inputs and outputs (up to 7 exp. modules): 1)

Digital inputs 224 224 224


Digital outputs 224 224 224
Analog inputs 112 112 112
Analog outputs 112 112 112
Max. number of central inputs and outputs (10 exp. modules):
Digital inputs 320 320 320
Digital outputs 320 320 320
Analog inputs 160 160 160
Analog outputs 160 160 160
Number of decentralized inputs and outputs Depends on the fieldbus used
(as an info on the CS31 bus: up to 31 stations with up
to 120 DI / 120 DO each)
Data backup Battery
Data buffering time at +25 °C Typ. 3 years without power supply
Battery low indication Warning issued about 2 weeks before the state of
charge becomes critical
Real-time clock:
With battery backup x x x
Accuracy Typ. ±2 s / day Typ. ±2 s / day Typ. ±2 s / day
at +25 °C at +25 °C at +25 °C

2024/01/05 3ADR010064, 11, en_US 9


Processor Module PM59x-ETH PM59x- PM59x-ETH
ARCNET
PM59x-2ETH
Program execution:
Cyclic x x x
Time-controlled x x x
Multitasking x x x
Password protection of user program x x x
Serial interface COM1:
Physical link Configurable for RS-232 or RS-485 (from 0.3 to 187.5
kB/s) pluggable terminal block, spring connection for
Connection programming, as Modbus (master/slave), as serial
Usage ASCII communication, as CS31 master
Serial interface COM2 (not for PM5xy-2ETH models):
Physical link Configurable for RS-232 or RS-485 (from 0.3 to 187.5
kB/s) D-sub for programming, as Modbus (master/
Connection slave), as serial ASCII communication
Usage
Integrated communication module:
ETH = Ethernet ETH ARCNET ETH onboard
with web server,
RJ45 ETH ARCNET SNTP and
ARCNET = ARCNET BNC ETH ARCNET IEC60870-5-104
protocol
Number of external communication modules Up to 4 communication modules like PROFIBUS
DP, Ethernet, CANopen. There are no restrictions
concerning the communication module types and
communication module combinations (e.g. up to 4
PROFIBUS DP communication modules are possible)
Ethernet 10/100 base-TX, - PM59x-ETH:
1x RJ45 socket 10/100 base-TX,
1x RJ45 socket,
provided on
TB5x1-ETH
PM591-2ETH:
10/100 base-TX,
independent
interfaces, 2x
RJ45 socket,
provided on
TB521-2ETH
LEDs, LCD display, 8 Function Keys For RUN/STOP switchover, status displays and diag-
nosis
Number of timers Unlimited Unlimited Unlimited
Number of counters Unlimited Unlimited Unlimited
Programming languages:
Structured Text ST x x x
Instruction List IL x x x
Function Block Diagram FBD x x x
Ladder Diagram LD x x x
Sequential Function Chart SFC x x x

10 3ADR010064, 11, en_US 2024/01/05


System data AC500
Environmental conditions

Processor Module PM59x-ETH PM59x- PM59x-ETH


ARCNET
PM59x-2ETH
Continuous Function Chart (CFC) x x x
1): up to 7 I/O terminal units before PS501 V1.2 and processor module firmware before V1.2.0.
2): For PM595 see device description for PM595 .

4 System data AC500


4.1 Environmental conditions
Table 4: Process and supply voltages
Parameter Value
24 V DC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
100 V AC...240 V AC wide-range supply
Voltage 100 V ... 240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply, according to EN 61131-2
DC supply Interruption < 10 ms, time between 2 interrup-
tions > 1 s, PS2
AC supply Interruption < 0.5 periods, time between 2 inter-
ruptions > 1 s

NOTICE!
Risk of damaging the PLC due to improper voltage levels!

– Never exceed the maximum tolerance values for process and supply voltages.
– Never fall below the minimum tolerance values for process and supply voltages.
Observe the system data Ä Chapter 4 “System data AC500” on page 11 and the
technical data of the module used.

NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
– AC voltage above 264 V
– Frenquency below 47 Hz or above 62.4 Hz

NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable
temperature classification.

2024/01/05 3ADR010064, 11, en_US 11


Power supply units

Parameter Value
Temperature
Operating 0 °C ... +60 °C: Horizontal mounting of modules.
0 °C ... +40 °C: Vertical mounting of modules.
Output load reduced to 50 % per group.
Storage -40 °C ... +70 °C
Transport -40 °C ... +70 °C
Humidity Max. 95 %, without condensation
Air pressure
Operating > 800 hPa / < 2000 m
Storage > 660 hPa / < 3500 m

4.2 Creepage distances and clearances


The creepage distances and clearances meet the requirements of the overvoltage category II, pollu-
tion degree 2.

4.3 Power supply units

AC500 and AC500-eCo PLC devices are Class II/Class III devices and do not require
a Protective Earth (PE) connection.
For proper EMC performance, all metal parts, DIN rails, mounting screws, and cable
shield connection terminals are connected to a common ground and provide Func-
tional Earth (FE). This is typically connected to a common reference potential, such
as equipotential bonding rails.
Signal Grounds (SGND or GND) are used for signal reference and must not be
connected to cable shields, FE or other signals unless otherwise specified in the
specific device description.

For the supply of the modules, power supply units according to SELV or PELV specifications must be
used.

Safety Extra Low Voltage (SELV) and Protective Extra Low Voltage (PELV)
To ensure electrical safety of AC500/AC500-eCo extra low voltage circuits, 24 V DC
supply, communication interfaces, I/O circuits, and all connected devices must be
powered from sources meeting requirements of SELV, PELV, class 2, limited voltage
or limited power according to applicable standards.

12 3ADR010064, 11, en_US 2024/01/05


Electromagnetic compatibility

WARNING!
Improper installation can lead to death by touching hazardous voltages!
To avoid personal injury, safe separation, double or reinforced insulation and separa-
tion of the primary and secondary circuit must be observed and implemented during
installation.
– Only use power converters for safety extra-low voltages (SELV) with safe galvanic
separation of the primary and secondary circuit.
– Safe separation means that the primary circuit of mains transformers must be
separated from the secondary circuit by double or reinforced insulation. The pro-
tective extra-low voltage (PELV) offers protection against electric shock.

4.4 Electromagnetic compatibility


Table 5: Electromagnetic compatibility
Parameter Value
Device suitable only as Control Equipment for Industrial Applications, including marine applications.
IEC 61131-2, zone B
Ä Chapter 4.6 “Approvals and certifications” on page 14
Radiated emission according to Yes
IEC 61000-6-4 CISPR11, class A
Conducted emission according to Yes
IEC 61000-6-4 CISPR11, class A
Electrostatic discharge (ESD) according to Air discharge: 8 kV
IEC 61000-4-2, criterion B Contact discharge: 6 kV
Fast transient interference voltages (burst) Power supply (DC): 2 kV
according to
Digital inputs/outputs (24 V DC): 1 kV
IEC 61000-4-4, criterion B
Digital inputs/outputs (240 V AC): 2 kV
Analog inputs/outputs: 1 kV
Communication lines shielded: 1 kV
High energy transient interference voltages Power supply (DC):
(surge) according to
- Line to ground: 1 kV
IEC 61000-4-5, criterion B
- Line to line: 0,5 kV
Digital inputs/outputs/relay:
(24 V DC):
- Line to ground: 1 kV
(AC):
- Line to ground: 2 kV
- Line to line: 1 kV
Analog inputs/outputs:
- Line to ground: 1 kV
Communication lines:
- Line to ground: 1 kV

2024/01/05 3ADR010064, 11, en_US 13


System data AC500-XC
Environmental conditions

Parameter Value
Influence of radiated disturbances Test field strength: 10 V/m
IEC 61000-4-3, criterion A
Influence of line-conducted interferences Test voltage: 10 V
IEC 61000-4-6, criterion A
Power frequency magnetic fields 30 A/m 50 Hz
IEC 61000-4-8, criterion A 30 A/m 60 Hz

4.5 Mechanical data


Parameter Value
Mounting Horizontal/Vertical
Wiring method Spring/screw terminals
Degree of protection PLC system: IP 20
● with all modules or option boards plugged in
● with all terminals plugged in
● with all covers closed
Housing Classification V-2 according to UL 94
Vibration resistance (sinusoidal) acc. to IEC All three axes
60068-2-6
2 Hz ... 8.4 Hz, 3.5 mm peak,
8.4 Hz ... 150 Hz, 1 g
Shock test acc. to IEC 60068-2-27 All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules:
Mounting Rail Top Hat according to IEC 60715 35 mm, depth 7.5 mm or 15 mm
Mounting with screws M4
Fastening torque 1.2 Nm

4.6 Approvals and certifications


The PLC Automation catalog contains an overview of the available approvals and certifications.

5 System data AC500-XC


5.1 Environmental conditions
Table 6: Process and supply voltages
Parameter Value
24 V DC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
100 V AC...240 V AC wide-range supply

14 3ADR010064, 11, en_US 2024/01/05


Environmental conditions

Parameter Value
Voltage 100 V ... 240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply, according to EN 61131-2
DC supply Interruption < 10 ms, time between 2 interrup-
tions > 1 s, PS2
AC supply Interruption < 0.5 periods, time between 2 inter-
ruptions > 1 s

NOTICE!
Risk of damaging the PLC due to improper voltage levels!

– Never exceed the maximum tolerance values for process and supply voltages.
– Never fall below the minimum tolerance values for process and supply voltages.
Observe the system data Ä Chapter 4 “System data AC500” on page 11 and the
technical data of the module used.

NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
– AC voltage above 264 V
– Frenquency below 47 Hz or above 62.4 Hz

NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable
temperature classification.

2024/01/05 3ADR010064, 11, en_US 15


Environmental conditions

Parameter Value
Temperature
Operating -40 °C ... +70 °C
-40 °C ... 0 °C: Due to the LCD technology, the
display might respond very slowly.
-40 °C ... +40 °C: Vertical mounting of modules
possible, output load limited to 50 % per group
+60 °C ... +70 °C with the following deratings:
● System is limited to max. 2 communication
modules per terminal base
● Applications certified for cULus up to +60 °C
● Digital inputs: maximum number of simultane-
ously switched on input channels limited to
75 % per group (e.g. 8 channels => 6 chan-
nels)
● Digital outputs: output current maximum
value (all channels together) limited to 75 %
per group (e.g. 8 A => 6 A)
● Analog outputs only if configured as
voltage output: maximum total output cur-
rent per group is limited to 75 %
(e.g. 40 mA => 30 mA)
● Analog outputs only if configured as current
output: maximum number of simultaneously
used output channels limited to 75 % per
group (e.g. 4 channels => 3 channels)
Storage / Transport -40 °C ... +85 °C
Humidity Operating / Storage: 100 % r. H. with condensa-
tion
Air pressure Operating:
-1000 m .... 5000 m (1080 hPa ... 620 hPa)
> 2000 m (< 795 hPa):
● Max. operating temperature must be reducted
by 10 K for each 1000 m exceeding 2000 m
● I/O module relay contacts must be operated
with 24 V nominal only
Immunity to corrosive gases Yes, according to:
ISA S71.04.1985 Harsh group A, G3/GX
IEC60068-2-60
Method 4 with following concentrations:
● H2S 100 ± 10ppb
● NO2 1250 ± 20ppb
● CL2 100 ± 10ppb
● SO2 300 ± 20ppb
Immunity to salt mist Yes, horizontal mounting only, according to IEC
60068-2-52 severity level: 1

16 3ADR010064, 11, en_US 2024/01/05


Power supply units

NOTICE!
Risk of corrosion!
Unused connectors and slots may corrode if XC devices are used in salt-mist environ-
ments.
Protect unused connectors and slots with TA535 protective caps for XC devices.

NOTICE!
Risk of malfunctions!
Unused slots for communication modules are not protected against accidental phys-
ical contact.
– Unused slots for communication modules must be covered with dummy communi-
cation modules to achieve IP20 rating.
– I/O bus connectors must not be touched during operation.

5.2 Creepage distances and clearances


The creepage distances and clearances meet the requirements of the overvoltage category II, pollu-
tion degree 2.

5.3 Power supply units

AC500 and AC500-eCo PLC devices are Class II/Class III devices and do not require
a Protective Earth (PE) connection.
For proper EMC performance, all metal parts, DIN rails, mounting screws, and cable
shield connection terminals are connected to a common ground and provide Func-
tional Earth (FE). This is typically connected to a common reference potential, such
as equipotential bonding rails.
Signal Grounds (SGND or GND) are used for signal reference and must not be
connected to cable shields, FE or other signals unless otherwise specified in the
specific device description.

Safety Extra Low Voltage (SELV) and Protective Extra Low Voltage (PELV)
To ensure electrical safety of AC500/AC500-eCo extra low voltage circuits, 24 V DC
supply, communication interfaces, I/O circuits, and all connected devices must be
powered from sources meeting requirements of SELV, PELV, class 2, limited voltage
or limited power according to applicable standards.

2024/01/05 3ADR010064, 11, en_US 17


Electromagnetic compatibility

WARNING!
Improper installation can lead to death by touching hazardous voltages!
To avoid personal injury, safe separation, double or reinforced insulation and separa-
tion of the primary and secondary circuit must be observed and implemented during
installation.
– Only use power converters for safety extra-low voltages (SELV) with safe galvanic
separation of the primary and secondary circuit.
– Safe separation means that the primary circuit of mains transformers must be
separated from the secondary circuit by double or reinforced insulation. The pro-
tective extra-low voltage (PELV) offers protection against electric shock.

5.4 Electromagnetic compatibility


Table 7: Electromagnetic compatibility
Parameter Value
Device suitable only as Control Equipment for Industrial Applications, including marine applications.
IEC 61131-2, zone B
Ä Chapter 5.6 “Approvals and certifications” on page 19
Radiated emission according to Yes
IEC 61000-6-4 CISPR11, class A
Conducted emission according to Yes
IEC 61000-6-4 CISPR11, class A
Electrostatic discharge (ESD) according to Air discharge: 8 kV
IEC 61000-4-2, criterion B Contact discharge: 6 kV
Fast transient interference voltages (burst) Power supply (DC): 4 kV
according to
Digital inputs/outputs (24 V DC): 2 kV
IEC 61000-4-4, criterion B
Digital inputs/outputs (240 V AC): 4 kV
Analog inputs/outputs: 2 kV
Communication lines shielded: 2 kV
High energy transient interference voltages Power supply (DC):
(surge) according to
- Line to ground: 1 kV
IEC 61000-4-5, criterion B
- Line to line: 0,5 kV
Digital inputs/outputs/relay:
(24 V DC):
- Line to ground: 1 kV
(AC):
- Line to ground: 2 kV
- Line to line: 1 kV
Analog inputs/outputs:
- Line to ground: 1 kV
Communication lines:
- Line to ground: 1 kV

18 3ADR010064, 11, en_US 2024/01/05


Approvals and certifications

Parameter Value
Influence of radiated disturbances Test field strength: 10 V/m
IEC 61000-4-3, criterion A
Influence of line-conducted interferences Test voltage: 10 V
IEC 61000-4-6, criterion A
Power frequency magnetic fields 30 A/m 50 Hz
IEC 61000-4-8, criterion A 30 A/m 60 Hz

5.5 Mechanical data


Parameter Value
Mounting Horizontal/vertical (no application in salt mist
environment)
Wiring method Spring terminals
Degree of protection PLC system: IP 20
● with all modules or option boards plugged in
● with all terminals plugged in
● with all covers closed
Housing Classification V-2 according to UL 94
Vibration resistance (sinusoidal) acc. to IEC 2 Hz ... 8.4 Hz, 3.5 mm peak,
60068-2-6
8.4 Hz ... 500 Hz, 2 g
Vibration resistance (broadband random) acc. to 5 Hz ... 500 Hz, 1,9 g rms (operational)
IEC 60068-2-64
5 Hz ... 500 Hz, 4 g rms (non operational)
Shock resistance All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules:
Mounting Rail Top Hat according to IEC 60715 35 mm, depth 7.5 mm or 15 mm
Mounting with screws M4
Fastening torque 1.2 Nm

5.6 Approvals and certifications


The PLC Automation catalog contains an overview of the available approvals and certifications.

— —
new.abb.com/plc © Copyright 2017-2024 ABB.
We reserve all rights in this document and in the information contained
therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden.

2024/01/05 3ADR010064, 11, en_US 19

You might also like