Control and Protection Scheme For DC-Link of Solar PV Based Microgrid
Control and Protection Scheme For DC-Link of Solar PV Based Microgrid
2, MARCH/APRIL 2024
Abstract—This article presents the inclusive DC-link voltage generally reverse-direction-connected diodes and insulated-gate
control and protection scheme for the DC-link of the microgrid. transistors (IGBTs) which allow bi-directional power flow. Low
The proposed inclusive scheme is proposed to control the DC-link
voltage DC-power is generated by the solar-based DERs which
voltage during load-switching or AC-side faults scenarios, and
protect the DC-link when short-circuit fault emerges at DC-link. To is required to be raised to a specified DC-bus voltage level by
examine the proposed inclusive scheme, the microgrid test system is boost-converter, then a voltage source inverter (VSI) converts
created according to the IEEE-1547 standard in PSCAD/EMTDC DC-bus voltage into pulsating-AC voltage as shown in Fig. 1 [4].
based software system. Then the designed microgrid is examined The basic VSI architecture has a DC-link along with a DC
under various fault scenarios to confirm the performance of the capacitor [5].
developed scheme. Results show that the presented control and
protection scheme can maintain the DC-link voltage under faults A capacitor bank is connected at DC-link between the inverter
on the AC or DC sides in grid-connected and islanding modes of and boost converter to balance the instantaneous power and
operation. The proposed scheme has the ability to ensure the voltage recognize the DC interface. DC-capacitors are inserted into the
regulation and protection of the DC-link of the microgrid under boost converter side of the DC-link to compensate for the instan-
different operating conditions and faults. taneous power variation between the rear stages and converter
Index Terms—Microgrid, control, DC-link, protection, short- front which can store high power and have a large capacitance [6]
circuit fault, voltage regulation, PSCAD/EMTDC. function. Normally, voltage ripples minimization and DC-link
voltage stability are maintained through DC-link capacitors
I. INTRODUCTION when DC-link voltage disturbances occur due to load change,
RID-CONNECTED microgrid is formed by the inte- faults, intermittent sources, or PWM inverter switching [6], [7].
G gration of renewable-based distributed energy resources
(DERs) with the distributed power system. The basic network
After VSI, a filter is connected to remove pulsating waves.
DC power flow direction changes and inverter gates turn ON
topology of conventional power systems varies due to the power and OFF to generate these pulsating waves [8]. The DC-link
conversion between AC and DC by converters and bi-directional microgrid test system is shown in Fig. 1.
power flow between DERs and utility-grid. DERs can be of DC-bus or DC-link-based microgrids have many protection
different types such as wind, solar, fuel cells, micro-hydro- challenges despite various benefits. One of the critical challenges
turbines, bio-gas, and gas turbines [1], [2], [3]. Inverters are during the islanded mode, a limited amount of fault current
is provided by inverter-based DER and overcurrent relay in-
Manuscript received 20 January 2023; revised 21 August 2023; accepted capability with single-setting in the hybrid AC-DC microgrid
13 November 2023. Date of publication 12 December 2023; date of current protection system. Along this, there are two more DC-link or
version 21 March 2024. Paper 2022-PSPC-1289.R1, presented at the 2022 DC-bus microgrid protection challenges; grounding strategy and
IEEE Industry Applications Society Annual Meeting, Detroit, MI, USA, Oct.
09–14, and approved for publication in the IEEE TRANSACTIONS ON INDUSTRY absence of zero-crossing current. In DC-link or DC-bus-based
APPLICATIONS by the Power Systems Protection Committee of the IEEE Industry microgrids, the grounding scheme is a major issue because it
Applications Society [DOI: 10.1109/IAS54023.2022.9939872]. (Correspond- may cause a short circuit transient current and over-voltage
ing author: Muhammad Waseem Altaf.)
Muhammad Waseem Altaf, Mohammad Taufiqul Arif, Shama Naz Islam, which affects its fault-detection and protection capabilities [9],
Mohammad Kamruzzaman Khan Prince, and Md. Enamul Haque are with the [10], [11], [12]. The grounding strategies for DC power systems
Renewable Energy & Electric Vehicle (REEV) Lab, Centre for Smart Power & can be distinguished by three types of configuration that are
Energy Research (cSPER), Deakin University, Geelong, VIC 3216, Australia (e-
mail: [email protected]; [email protected]; [email protected]; ungrounded, solidly grounded, and resistive grounded method
[email protected]; [email protected]). in the middle point.
Muhammad Naveed Naz is with the School of Engineering and Built Envi- However, the operation of the circuit breaker (CB) in DC
ronment, Nathan Campus, Griffith University, Brisbane, QLD 4111, Australia
(e-mail: [email protected]). and AC power systems is led by the mechanism of AC-CB, arc
Aman Maung Than Oo is with the School of Engineering, Macquarie Uni- phenomenon, and AC zero-crossing that makes it possible to
versity, Macquarie Park, NSW 2109, Australia (e-mail: [email protected]). observe and quench the arc after tripping during the half-cycle.
Color versions of one or more figures in this article are available at
https://doi.org/10.1109/TIA.2023.3341848. But, DC-power disruption is the main issue due to the absence of
Digital Object Identifier 10.1109/TIA.2023.3341848 zero-crossing current in the DC power system which may cause
0093-9994 © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.
ALTAF et al.: CONTROL AND PROTECTION SCHEME FOR DC-LINK OF SOLAR PV BASED MICROGRID 2707
a serious threat to worker’s safety and also becomes a cause and power output quality depends on the controller and filter.
of circuit breaker erosion which reduces the lifetime of circuit Harmonics distortion in the voltage may reduce the inverter
breakers [13], [14]. Nowadays, fuses and circuit breakers are output power quality. The voltage and current control-loop for
commercially available for DC power system protection [15]. network voltage stability are shown in Fig. 1. Undistorted current
The absence of zero-crossing and grounding problem mitigation or power output can be supplied by the proper design of the
solutions is available in PSCAD/EMTDC software tools to test inverter controller. During normal operation, control strategies
and analyze the protection scheme’s effectiveness. work efficiently without any fault. More current flows at the
DC-bus or DC-link voltage level should be constant because fault point when short-circuit faults occur at DC-link [20].
VSI delivers constant voltage output or equal to the real-time The capacitor at the DC-link discharges in milliseconds to-
voltage at the AC-side. DC-link voltage variation changes the wards the point of fault due to overcurrent. An inductor can
output of VSI which results in the reactive power flow (reactive be incorporated to limit the overcurrent due to a short circuit
power flow occurs due to the AC-side voltage and VSI output proposed in [21].
voltage difference) [16]. So, the protection and voltage regula- An overcurrent protection challenge in VSI is analyzed
tion at DC-link is very vital during islanded and grid-connected in [22]. Inverters protection against overcurrent and overvoltage
modes. faults must be ensured especially in the motor-drive system [23].
The load requirement is fulfilled by the DERs of the micro- Despite having diverse natures, faults of both types have dam-
grid with the additional support of the utility-grid during the aging effects on the inverter power stage and motor winding.
grid-connected mode. The voltage regulation is ensured by the But the existing control strategies for DC-link voltage failed to
additional support of the utility-grid. The controlled power ex- stabilize the voltage at DC-link which may damage the microgrid
port is ensured by an inverter with stable voltage at the DC-link. when DC-link or AC-side faults due to short circuits occur during
The sending controlled power depends on the stability of the the grid-connected mode. So, DC-link protection and a voltage
in-phase current component at the d-axis and q-axis respectively. control scheme are needed for microgrid protection and voltage
The load demand is represented by the current demand that is regulation at DC-link.
measured by the voltage amplitude which is achieved by the The microgrid operation without a utility-grid supply requires
3Φ locked-loop (PLL-3 ph) [17]. The voltage at DC-link is setting up the voltage and frequency reference values. Hence,
maintained by the information on power demand received at during microgrid islanded mode operation, the DERs inverter
a main controller that also operates the DER accordingly [18], must provide voltage and frequency reference levels which are
[19]. The current is controlled by the closed-loop inverter to the inverter’s main function. The VSI is shown in Fig. 1, despite
fulfill the power demand. The closed-loop inverter generates an a few problems that have been observed due to high transient
accurate reference current by the supply requirement of active fault currents that can damage the semiconductor devices and
and reactive power. Fig. 1 represents the control strategy of the components for voltage measurement across capacitors. To han-
inverter, where output power is delivered by the closed-loop dle these shortcomings, a cascade control strategy should be
current controller, and reference current is also determined by incorporated. This inverter-based control strategy should be able
the controller. The main controller sets the current and power to regulate the voltage during unintentional islanding [2] or
requirement and each inverter is accountable for that. The current heavy load loss.
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.
2708 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 60, NO. 2, MARCH/APRIL 2024
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.
ALTAF et al.: CONTROL AND PROTECTION SCHEME FOR DC-LINK OF SOLAR PV BASED MICROGRID 2709
Vco = Vci /(1 − D) (2) The VSI at the grid-side stabilizes the DC-link voltage, re-
active power, and active power. The VSI control diagram at the
where Vci , D, and Vco are DC-DC bidirectional-converter input- grid-side is shown in Fig. 4. The voltage parameter at DC-link
voltage, duty-cycle ratio, and converter output-voltage respec- Vdc is measured by a voltage sensor and the measured value is
tively. The battery and SC components are combined in ESS sent to the comparator. The measured value is compared with
∗
to overcome the transients in DC-link that are arisen due to the reference voltage Vdc level. The reference DC-link voltage
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.
2710 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 60, NO. 2, MARCH/APRIL 2024
is calculated by (6).
√
∗ 6Vgln
Vdc = (6)
ma
In (6), Vgln is the RMS value of the grid line to ground voltage
and ma is the modulation index. The modulation index is set to
0.85 leaving 15% adjustments for the grid side transients and
faults. The measured value of the DC-link voltage follows the
∗
reference value Vdc . This can be understood by (7).
1.5Vdg .idg = Vdc .idc (7)
Vqg=0
In (7), Vdg and Idg are the d-axis grid voltage and current,
respectively, Vdc and Idc are the DC-link voltage and current.
Equation (7) assumed no loss in the grid-side voltage source
inverter (VSI) and the q-axis grid voltage is zero, that is, Vqg =
0. According to (7) the DC power input to the grid side VSC
equals the AC power output. The DC-link current depends on
the available renewable energy in the microgrid. Therefore the
d-axis grid current idg reflects the operating conditions.
The deviation of the measured value Vdc from the reference Fig. 5. Proposed DC-link protection and DC-link voltage control scheme flow
∗ chart [1].
value Vdc is also called an error. The error eVdc is sent to the
proportional-integral (PI) regulator. The control signal DB1k
enables the VSI regulator. The grid d-axis reference current
i∗dg is generated by the PI regulator. The i∗dg is presented in synchronous reference frame-angular-speed and Lt is the sum
mathematical form as (8) [1] of filter inductances including inductances of the inverter-side
and grid-side.
i∗dg (t) = eVdc (t) KPdc + KIdc (8) The 3-phase control signals are generated by sending the
control signals dd1 , and dq1 through the dq0/abc block in the
In (8), KIdc and KPdc are integral and proportional gains for the abc stationary reference frame. For grid-side VSI switching, the
outer voltage control loop of the voltage regulator at the DC-link. PWM modulator block is generating six switching signals by
The reference current d-axis is sent to the current control inner using these three-phase control signals. The VSI is enabled by
loop where the error eidg is measured by the comparator. The the switching pulses to stabilize the grid currents at dq-axes to
d-axis pulse control dd is generated by sending error eidg to the controller’s reference setting.
another PI regulator. In this article, reactive power towards the
grid is regulated to be zero during normal operation.
D. Proposed DC-Link Voltage Control and DC-Link
Q∗g = 0 (9) Protection Scheme Algorithm Flow Chart
The error between measured and reference Qg reactive power The developed DC-link protection and voltage control strat-
is received by the PI regulator that generates the grid q-axis egy algorithm flowchart is shown in Fig. 5. The microgrid is
reference current i∗qg . The q-axis control signal dq is generated by designed as per the standard of IEEE-1547. The under/over
another PI regulator that compares the measured and reference voltage-based protection strategy at DC-link is proposed with an
q-axis grid-current iqg . The terms vdg , vqg are called com- adjusted threshold level and a control strategy based on voltage
pensation terms and ωLt iqg , ωLt iqg are called speed-induced is designed to regulate the DC-link voltage at 780 V DC. The
voltage terms that are inserted in the controller to produce the DC-link circuit breaker (CB) threshold limits is set based on
control pulses dd1 , and dq1 at dq axes. Where vdg and vqg are under voltage which is 760 V and rate of change of over current
the q-axis and d-axis components of the grid-voltage, ω is the which may increase to 2 kA/ms [28].
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.
ALTAF et al.: CONTROL AND PROTECTION SCHEME FOR DC-LINK OF SOLAR PV BASED MICROGRID 2711
Fig. 6. (a) RMS voltage level at AC-side, (b) RMS current level at AC-side,
and (c) voltage level at DC-link, (d) current level at DC-link during stable grid-
connected mode without any fault [1].
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.
2712 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 60, NO. 2, MARCH/APRIL 2024
Fig. 9. (a) RMS voltage level at AC-side, (b) RMS current level at AC-side, (c)
voltage level at DC-link, and (d) current level at DC-link during grid-connected Fig. 11. (a) RMS voltage level at AC-side, (b) RMS current level at AC-
mode with AC-side fault and without DC-link voltage control [1]. side, (c) voltage level at DC-link, and (d) current level at DC-link during grid-
connected mode with AC-side fault and with DC-link voltage control [1].
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.
ALTAF et al.: CONTROL AND PROTECTION SCHEME FOR DC-LINK OF SOLAR PV BASED MICROGRID 2713
Fig. 12. (a) id and idref inverter currents, (b) iq and iqref inverter currents, and
(c) inverter reactive, and active power level during grid-connected mode with Fig. 14. (a) id and idref inverter currents, (b) iq and iqref inverter currents, and
AC-side fault and with DC-link voltage control [1]. (c) inverter reactive, and active power level during grid-connected mode with
DC-link fault and without DC-link voltage protection [1].
Fig. 13. (a) RMS voltage level, (b) RMS current level at AC-side, (c) voltage
level at DC-link, and (d) current level at DC-link during grid-connected mode Fig. 15. (a) RMS voltage level, (b) RMS current level at AC-side, (c) voltage
with DC-link fault and without DC-link protection [1]. level at DC-link, and (d) current level at DC-link during grid-connected mode
with DC-link fault and with DC-link protection [1].
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.
2714 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 60, NO. 2, MARCH/APRIL 2024
before and after islanded mode. The DC-link fault occur at 1.5 s,
the current and the voltage level is shown in Fig. 17(c) and (d)
without DC-link protection action respectively. It can be seen
from Fig. 17(c) and (d) the current rises and voltage drop due
to the DC-link fault. Fig. 17(e) and (f) represents the DC-link
current and voltage levels during islanded mode when DC-link
short-circuit fault occurs at 1.5 s of simulation time with DC-link
protection and voltage control action. It can also be seen from
Fig. 17(e) and (f) that the DC-link developed protection strategy
successfully detects and isolates the fault by the action of the
circuit breaker at the DC-link. Similarly, if an AC-side fault
occurs during the islanded mode, then the protection system
at the AC-side should take action and the faulty area should
be isolated otherwise DC-link protection system operates by a
circuit breaker at DC-link action when a fault occurs at AC-side
near the VSI to protect it along with other components of the
microgrid.
From the discussed simulation results, it is concluded that
the DC-link developed protection and DC-link voltage control
Fig. 16. (a) id and idref inverter currents, (b) iq and iqref inverter currents, and strategy successfully controls the DC-link voltage during AC-
(c) inverter reactive, and active power level during grid-connected mode with side faults and protects the DC-link when faults take place at
DC-link fault and with DC-link voltage protection [1]. DC-link itself.
V. CONCLUSION
The proposed protection and voltage control strategy is pre-
sented to regulate the DC-link voltage and protect the DC-link
during AC and DC fault events which are implemented to test
on battery energy storage, solar PV based microgrid. The devel-
oped strategy is tested during both islanded and grid-connected
modes by creating faults both at DC-link and AC-side. Results
show the effectiveness of the proposed scheme by regulating
the DC-link voltage during AC side faults, and protecting the
DC-link when short-circuit fault occurs at DC-link during both
islanded and grid-connected modes. In future, this scheme can
be implemented on wind-turbine based energy system.
REFERENCES
[1] M. W. Altaf, M. T. Arif, S. N. Islam, M. K. K. Prince, and M. E. Haque,
Fig. 17. (a) Voltage level at DC-link, and (b) current level at DC-link without “Control and protection scheme for dc-link of solar PV based microgrid,”
any fault; (c) Voltage level at DC-link, and (d) current level at DC-link with in Proc. IEEE Ind. Appl. Soc. Annu. Meeting, 2022, pp. 1–8.
short-circuit fault and without protection system; and (e) Voltage level at DC- [2] M. W. Altaf, M. T. Arif, S. Saha, S. N. Islam, M. E. Haque, and A. M. T.
link, and (f) current level at DC-link with short circuit fault and with protection Oo, “Effective ROCOF-based islanding detection technique for different
system during islanded mode [1]. types of microgrid,” IEEE Trans. Ind. Appl., vol. 58, no. 2, pp. 1809–1821,
Mar./Apr. 2022.
[3] M. W. Altaf, M. T. Arif, S. N. Islam, M. K. K. Prince, and M. E.
microgrid operation when a DC-link fault occurs. It can be seen Haque, “Integrated control and protection scheme for seamless operation
from Fig. 16, that after DC-link fault creation, idref, id, iqref, of microgrid,” in Proc. IEEE Ind. Appl. Soc. Annu. Meeting, 2022, pp. 1–8.
[4] W. N. H. A. Alias, M. Z. Sujod, and N. A. M. Kamari, “Dc-link protection
and iq current values are disturbed and drop to zero due to the for grid-connected photovoltaic system: A review,” in Proc. ECCE, 2019,
action of the DC-link protection system. pp. 725–736.
[5] L. An and D. D.-C. Lu, “Analysis of DC bus capacitor current ripple
reduction in basic DC/DC cascaded two-stage power converters,” IEEE
G. DC-Link Short Circuit Fault and AC-Side Fault During Trans. Ind. Electron., vol. 63, no. 12, pp. 7467–7477, Dec. 2016.
Islanded Mode Without and Without DC-Link Protection [6] M. E. Meral and D. Çelik, “Mitigation of dc-link voltage oscillations to
reduce size of dc-side capacitor and improve lifetime of power converter,”
Fig. 17(a) and (b) represents the DC-link current and voltage Electric Power Syst. Res., vol. 194, 2021, Art. no. 107048.
[7] M. Fallah, J. Modarresi, H. M. Kojabadi, L. Chang, and J. M. Guerrero,
levels during the islanded mode without any DC-link fault and “A modified indirect extraction method for a single-phase shunt active
AC-side fault respectively. Fig. 17(a) and (b) depicts that DC- power filter with smaller DC-link capacitor size,” Sustain. Energy Technol.
link current and voltage levels are almost near to each other Assessments, vol. 45, 2021, Art. no. 101039.
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.
ALTAF et al.: CONTROL AND PROTECTION SCHEME FOR DC-LINK OF SOLAR PV BASED MICROGRID 2715
[8] P. Alemi, Y.-C. Jeung, and D.-C. Lee, “DC-link capacitance minimization [19] Z. Zeng, W. Zheng, and R. Zhao, “Space-vector-based hybrid PWM
in T-type three-level AC/DC/AC PWM converters,” IEEE Trans. Ind. strategy for reduced DC-link capacitor current stress in the postfault
Electron., vol. 62, no. 3, pp. 1382–1391, Mar. 2015. grid-connected three-phase rectifier,” IEEE Trans. Ind. Electron., vol. 63,
[9] M. Farhadi and O. A. Mohammed, “Protection of multi-terminal and dis- no. 8, pp. 4989–5000, Aug. 2016.
tributed DC systems: Design challenges and techniques,” Electric Power [20] B. Li, C. Li, F. Guo, and Y. Xin, “Overcurrent protection coordination
Syst. Res., vol. 143, pp. 715–727, 2017. in a power distribution network with the active superconductive fault
[10] Y. Wang, Z. Yu, J. He, S. Chen, R. Zeng, and B. Zhang, “Performance current limiter,” IEEE Trans. Appl. Supercond., vol. 24, no. 5, Oct. 2014,
of shipboard medium-voltage DC system of various grounding modes Art. no. 5602004.
under monopole ground fault,” IEEE Trans. Ind. Appl., vol. 51, no. 6, [21] F. Deng and Z. Chen, “Design of protective inductors for HVDC transmis-
pp. 5002–5009, Nov./Dec. 2015. sion line within DC grid offshore wind farms,” IEEE Trans. Power Del.,
[11] S.-L. Chen, S.-C. Hsu, C.-T. Tseng, K.-H. Yan, H.-Y. Chou, and T.-M. vol. 28, no. 1, pp. 75–83, Jan. 2013.
Too, “Analysis of rail potential and stray current for Taipei metro,” IEEE [22] D. R. Lugo Núñez, “High power density and overcurrent protection
Trans. Veh. Technol., vol. 55, no. 1, pp. 67–75, Jan. 2006. challenges in the design of a three-phase voltage source inverter for motor
[12] D. Salomonsson, L. Soder, and A. Sannino, “Protection of low-voltage drive applications,” Ph.D. dissertation, Virginia Tech, Blacksburg, VA,
DC microgrids,” IEEE Trans. Power Del., vol. 24, no. 3, pp. 1045–1053, USA, 2007.
Mar. 2009. [23] Y. Son and J.-I. Ha, “Discontinuous grid current control of motor drive
[13] J.-D. Park, J. Candelaria, L. Ma, and K. Dunn, “DC ring-bus microgrid system with single-phase diode rectifier and small DC-link capacitor,”
fault protection and identification of fault location,” IEEE Trans. Power IEEE Trans. Power Electron., vol. 32, no. 2, pp. 1324–1334, Feb. 2017.
Del., vol. 28, no. 4, pp. 2574–2584, Oct. 2013. [24] Y. Xu, Y. Huang, B. Zheng, W. Zhang, Y. Li, and J. Zou, “Over-current
[14] C. Yuan, M. A. Haj-ahmed, and M. S. Illindala, “Protection strategies for protection method for PMSM VSI with small DC-link capacitor,” IET
medium-voltage direct-current microgrid at a remote area mine site,” IEEE Power Electron., vol. 11, no. 7, pp. 1231–1238, 2018.
Trans. Ind. Appl., vol. 51, no. 4, pp. 2846–2853, Jul./Aug. 2015. [25] B. Karanayil, V. G. Agelidis, and J. Pou, “Performance evaluation of
[15] S. Mirsaeidi, X. Dong, and D. M. Said, “Towards hybrid AC/DC mi- three-phase grid-connected photovoltaic inverters using electrolytic or
crogrids: Critical analysis and classification of protection strategies,” polypropylene film capacitors,” IEEE Trans. Sustain. Energy, vol. 5, no. 4,
Renewable Sustain. Energy Rev., vol. 90, pp. 97–103, 2018. pp. 1297–1306, Oct. 2014.
[16] T. Raji, “Why is the DC link voltage in a grid-connected [26] M. Hossain, H. Pota, A. Haruni, and M. Hossain, “DC-link voltage
PV system controlled to be fixed?,” 06 2018. [Online]. Avail- regulation of inverters to enhance microgrid stability during network
able: https://www.researchgate.net/post/Why_is_the_DC_link_ contingencies,” Electric Power Syst. Res., vol. 147, pp. 233–244, 2017.
voltage_in_a_grid-connected_PV_system_controlled_to_be_fixed/ [27] N. Zakzouk and R. Lotfi, “Power flow control of a hybrid bat-
5b1793ce565fba17f5215c8e/citation/download tery/supercapacitor standalone PV system under irradiance and load
[17] Y. Huang, L. Wang, S. Zhang, D. Wang, X. Deng, and G. Zhu, “Im- variations,” in Proc. IEEE 10th Int. Conf. Power Energy Syst., 2020,
pacts of phase-locked loop dynamic on the stability of DC-link volt- pp. 469–474.
age control in voltage source converter integrated to weak grid,” IEEE [28] B. Mitra, B. Chowdhury, and M. Manjrekar, “HVDC transmission for
Trans. Emerg. Sel. Topics Circuits Syst., vol. 12, no. 1, pp. 48–58, access to off-shore renewable energy: A review of technology and fault
Mar. 2022. detection techniques,” IET Renewable Power Gener., vol. 12, no. 13,
[18] X.-S. Pu, T. H. Nguyen, D.-C. Lee, K.-B. Lee, and J.-M. Kim, “Fault pp. 1563–1571, 2018, doi: 10.1049/iet-rpg.2018.5274.
diagnosis of dc-link capacitors in three-phase AC/DC PWM converters
by online estimation of equivalent series resistance,” IEEE Trans. Ind.
Electron., vol. 60, no. 9, pp. 4118–4127, Sep. 2013.
Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 23,2024 at 13:59:05 UTC from IEEE Xplore. Restrictions apply.