GIS Substation Interlocking Logic Guide

Interlock logic diagram for bus coupler feeder

Uploaded by

Neel Atiq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views9 pages

GIS Substation Interlocking Logic Guide

Interlock logic diagram for bus coupler feeder

Uploaded by

Neel Atiq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

NORMAL CLOSING

DS -QB1 CLOSED
INTERLOCK
=1
DS -QB1 OPEN

DS -QB2 CLOSED
=1
DS -QB2 OPEN

& MAINTENANCE CLOSING


DS -QB1 OPEN INTERLOCK
-QB51A MAINTENANCE
-BA5A & CLOSING
ENABLED
-QC51A M DS -QB2 OPEN
C1 C2 C3 NORMAL
DS -QB1 CLOSED OR CLOSING
BUS-IA ENABLED

DS -QB2 CLOSED

BUS-2A INTERLOCK SEL. SW BYPASSED

-QC52A M

-QB1 -QB2

-QC1 -QC2

-QB52A

-BA6A MANDATORY
-QA1 M
INTERLOCK
C1 C2 C3 SF6 STAGE-1 HEALTHY

SF6 STAGE-2 HEALTHY


BUS COUPLER-A
TCS-1 HEALTHY & CB READY

TCS-2 HEALTHY

SPRING CHARGED

CB QA1 CLOSE LOGICS


BUS SECTION-1
-QA1 M

-QC1A -QC1B

-QB1A QB1B MANDATORY BLOCKING

FOR INTERLOCK OF BUS COUPLER-B)


INTERLOCK INTERLOCK
BUS-IA BUS-IB FEEDER-1 DS -QB1 CLOSED

(*** FEEDERS OF BUS 1B & 2B


&

FEEDERS OF BUS 1A & 2A


FEEDER-1 DS -QB2 CLOSED

FEEDER-2 DS -QB1 CLOSED


SF6 STAGE-2 HEALTHY CB READY
BUS-2A BUS-2B &
FEEDER-2 DS -QB2 CLOSED
OR
-QB1 -QB2 -QB2A -QB2B -QB1 -QB2

-QC1 -QA1 M
-QC2 -QC2A -QA1 M
-QC2B -QC1 -QA1 M
-QC2

FEEDER-N DS -QB1 CLOSED


BUS COUPLER-A BUS SECTION-2 BUS COUPLER-B &
FEEDER-N DS -QB2 CLOSED
OPEN
OR INHIBIT
BUS SECTION-1 CLOSED

BUS SECTION-2 CLOSED

FOR INTERLOCK OF BUS COUPLER-B)


FEEDER-1 DS -QB1 CLOSED &

(*** FEEDERS OF BUS 1A & 2A


FEEDERS OF BUS 1B & 2B &
FEEDER-1 DS -QB2 CLOSED

FEEDER-2 DS -QB1 CLOSED


&
LEGENDS: NOTES: FEEDER-2 DS -QB2 CLOSED
TCS: TRIP CIRCUIT SUPERVISION 1. Logics have to be established in CRP by bringing statuses of all relevant OR
A/R: AUTO RECLOSE devices; wiring among the switching devices are not allowed.
CA: CONTROL AUTHORITY SWITCH 2. More than one device will not be allowed to move at the same time.
M1FP: MAIN-1 FEEDER PROTECTION RELAY 3. Closing from LCC will be for maintenance purpose only; all CB internal
M2FP: MAIN-2 FEEDER PROTECTION RELAY blocking such as SF6 Stage-1 & 2 alarm, spring discharge etc. will be
BUFP: BACK-UP FEEDER PROTECTION RELAY applicable for such closings. FEEDER-N DS -QB1 CLOSED
BCU: BAY CONTROL UNIT 4. CA is a 4 (Four) position switch having the positions of &
BCPU: BAY CONTROL & PROTECTION UNIT OFF/MIMIC/BCU/REMOTE which will be installed in CRP. FEEDER-N DS -QB2 CLOSED
SAS: SUBSTATION AUTOMATION SYSTEM 5. If BCU/SAS is not available in the substation, the CA will be a 3 (Three)
LCC: LOCAL CONTROL CUBICLE position switch having the positions of OFF/LOCAL/REMOTE which will
be installed in CRP.
6. LOCAL/REMOTE selector switch of LCC, CA (Control Authority) switch
of CRP can be in only one position at any given time.
7. INTERLOCK BYPASS switch will be installed in CRP.
& AND GATE- OUTPUT IS 1 WHEN ALL INPUTS ARE 1
8. For MIMIC CONTROL, Synchrocheck will be performed by M2FP.
9. For BCU CONTROL, Synchrocheck will be performed by BCU internally.
OR OR GATE- OUTPUT IS 1 WHEN ANY OF THE INPUTS IS 1 10. Independent and identical interlocking/blocking conditions have to be
established for MIMIC and BCU control. For MIMIC control,
interlocking/blocking conditions will be hardware based and established
=1 XOR GATE- OUTPUT IS 1 WHEN INPUTS ARE DIFFERENT
in CRP; for BCU control, they will be software based and established
internally in BCU.
11. LOCAL/REMOTE selector switch in BCU is optional.
CB -QA1 OPEN LOGICS
NOT GATE- OUTPUT IS 1 INPUT IS 0

TITLE: INTERLOCKING LOGIC OF ALL VOLTAGE GIS SUBSTATION IN DOUBLE SHEET


BUSBAR FOR BUS COUPLER FEEDER (BUS COUPLER-A) 1
STANDARD DOCUMENT
0 09.05.2020
DATE
FIRST PREPARATION NUMBER: 64 POWER GRID COMPANY OF BANGLADESH LTD. DOCUMENT ID: A0-DB-G0-BC-IL NEXT SHT 2
REVISION REMARKS
NLDC SAS CONTROL/PROTECTION PANEL GIS LOCAL CONTROL CUBICLE

SAS HMI IN REMOTE

SAS HMI IN LOCAL &


ORDER FROM NLDC
OR BCU
SAS HMI IN LOCAL
CA IN REMOTE
-QB51A SAS HMI IN REMOTE &
-BA5A
CA IN BCU
ORDER FROM SAS &
CA IN MIMIC
C1 C2 C3 -QC51A M

BCU SW IN REMOTE
BUS-IA
BCU SW IN LOCAL
OR
CA IN BCU
BUS-2A
CA IN MIMIC

-QC52A M CA IN REMOTE
&
BCU SW IN LOCAL
-QB1 -QB2

-QC1 -QC2
BCU SW IN REMOTE
-QB52A ORDER FROM BCU &
-BA6A

-QA1 M
C1 C2 C3

NORMAL CLOSING *) Note-1


ENABLED
BUS COUPLER-A
*) Note-1
CB READY

SYNCHROCHECK *) Note-12 OR
RELEASE
REMOTE CONTROL &
LOCAL CONTROL
CA IN MIMIC
BUS SECTION-1
-QA1 M CA IN BCU LOCAL CONTROL OR
CA IN REMOTE REMOTE CONTROL
-QC1A -QC1B
&
-QB1A QB1B ORDER FROM MIMIC NORMAL MODE
SELECTED &
BUS-IA BUS-IB NORMAL CLOSING *) Note-1, 2
ENABLED FROM CRP ORDER FROM LCC

SYNCHROCHECK *) Note-11
BUS-2A BUS-2B
RELEASE FROM MFP

-QB1 -QB2 -QB2A -QB2B -QB1 -QB2


NORMAL CLOSING
-QC1 -QC2 -QC2A -QC2B -QC1 -QC2
-QA1 M -QA1 M -QA1 M ENABLED FROM GIS LCC

BUS COUPLER-A BUS SECTION-2 BUS COUPLER-B


&

PROTECTION PANEL

CB -QA1 LOCKOUT-1 RESET COMMAND


OR TO CB
CB -QA1 LOCKOUT-2 RESET
LEGENDS: NOTES:
TCS: TRIP CIRCUIT SUPERVISION 1. Logics have to be established in CRP by bringing statuses of all relevant
A/R: AUTO RECLOSE devices; wiring among the switching devices are not allowed.
CA: CONTROL AUTHORITY SWITCH 2. More than one device will not be allowed to move at the same time.
M1FP: MAIN-1 FEEDER PROTECTION RELAY 3. Closing from LCC will be for maintenance purpose only; all CB internal *) Note-1, 2
M2FP: MAIN-2 FEEDER PROTECTION RELAY blocking such as SF6 Stage-1 & 2 alarm, spring discharge etc. will be CB READY
BUFP: BACK-UP FEEDER PROTECTION RELAY applicable for such closings.
BCU: BAY CONTROL UNIT 4. CA is a 4 (Four) position switch having the positions of LOCAL CONTROL
BCPU: BAY CONTROL & PROTECTION UNIT OFF/MIMIC/BCU/REMOTE which will be installed in CRP.
SAS: SUBSTATION AUTOMATION SYSTEM 5. If BCU/SAS is not available in the substation, the CA will be a 3 (Three)
LCC: LOCAL CONTROL CUBICLE
REMOTE CONTROL
position switch having the positions of OFF/LOCAL/REMOTE which will
be installed in CRP. *) Note-9
6. LOCAL/REMOTE selector switch of LCC, CA (Control Authority) switch MAINTENANCE MODE SELECTED
of CRP can be in only one position at any given time. *) Note-5
&
7. INTERLOCK BYPASS switch will be installed in CRP. ORDER FROM LCC
& AND GATE- OUTPUT IS 1 WHEN ALL INPUTS ARE 1
8. For MIMIC CONTROL, Synchrocheck will be performed by M2FP.
9. For BCU CONTROL, Synchrocheck will be performed by BCU internally. *) Note-3
OR OR GATE- OUTPUT IS 1 WHEN ANY OF THE INPUTS IS 1 10. Independent and identical interlocking/blocking conditions have to be MAINTENANCE
established for MIMIC and BCU control. For MIMIC control, CLOSING ENABLED
interlocking/blocking conditions will be hardware based and established
=1 XOR GATE- OUTPUT IS 1 WHEN INPUTS ARE DIFFERENT
in CRP; for BCU control, they will be software based and established
internally in BCU.
NOT GATE- OUTPUT IS 1 INPUT IS 0 11. LOCAL/REMOTE selector switch in BCU is optional.
CB -QA1 CLOSE CONTROL AUTHORITY
TITLE: INTERLOCKING LOGIC OF ALL VOLTAGE GIS SUBSTATION IN DOUBLE SHEET
BUSBAR FOR BUS COUPLER FEEDER (BUS COUPLER-A) 2
STANDARD DOCUMENT
0 09.05.2020 FIRST PREPARATION NUMBER: 64 POWER GRID COMPANY OF BANGLADESH LTD. DOCUMENT ID: A0-DB-G0-BC-IL NEXT SHT 3
REVISION DATE REMARKS
NLDC SAS CONTROL/PROTECTION PANEL GIS LOCAL CONTROL CUBICLE

SAS HMI IN REMOTE

SAS HMI IN LOCAL &


-QB51A

-BA5A ORDER FROM NLDC

C1 C2 C3 -QC51A M OR BCU
SAS HMI IN LOCAL CA IN REMOTE
BUS-IA

SAS HMI IN REMOTE & CA IN BCU


&
ORDER FROM SAS CA IN MIMIC
BUS-2A
BCU SW IN REMOTE

BCU SW IN LOCAL
-QC52A M

OR
-QB1 -QB2

-QC1 -QC2
CA IN BCU
-QB52A

-BA6A CA IN MIMIC
-QA1 M
C1 C2 C3 CA IN REMOTE
&
BCU SW IN LOCAL
BUS COUPLER-A &
BCU SW IN REMOTE

ORDER FROM BCU


*) Note-1
OPEN INHIBIT

BUS SECTION-1 *) Note-1


-QA1 M CB READY
OR

-QC1A -QC1B

-QB1A QB1B

BUS-IA BUS-IB
REMOTE CONTROL
CA IN MIMIC LOCAL CONTROL &
CA IN BCU
BUS-2A BUS-2B
&
CA IN REMOTE
-QB1 -QB2 -QB2A -QB2B -QB1 -QB2
ORDER FROM MIMIC
-QC1 -QA1 M
-QC2 -QC2A -QA1 M
-QC2B -QC1 -QA1 M
-QC2

*) Note-1, 2
CB READY OR
BUS COUPLER-A BUS SECTION-2 BUS COUPLER-B

PROTECTION PANEL
CB -QA1 LOCKOUT-1 TRIP

CB -QA1 LOCKOUT-2 TRIP &


&
50BF RETRIP FROM BBP BU-1

50BF RETRIP FROM BBP BU-2

*) Note-1, 2
OPEN INHIBIT
COMMAND
OR TO CB
LEGENDS: NOTES:
TCS: TRIP CIRCUIT SUPERVISION 1. Logics have to be established in CRP by bringing statuses of all relevant
A/R: AUTO RECLOSE devices; wiring among the switching devices are not allowed.
CA: CONTROL AUTHORITY SWITCH 2. More than one device will not be allowed to move at the same time.
M1FP: MAIN-1 FEEDER PROTECTION RELAY 3. Closing from LCC will be for maintenance purpose only; all CB internal
M2FP: MAIN-2 FEEDER PROTECTION RELAY blocking such as SF6 Stage-1 & 2 alarm, spring discharge etc. will be
BUFP: BACK-UP FEEDER PROTECTION RELAY applicable for such closings.
BCU: BAY CONTROL UNIT 4. CA is a 4 (Four) position switch having the positions of LOCAL CONTROL
BCPU: BAY CONTROL & PROTECTION UNIT OFF/MIMIC/BCU/REMOTE which will be installed in CRP.
SAS: SUBSTATION AUTOMATION SYSTEM 5. If BCU/SAS is not available in the substation, the CA will be a 3 (Three)
LCC: LOCAL CONTROL CUBICLE position switch having the positions of OFF/LOCAL/REMOTE which will
REMOTE CONTROL &
be installed in CRP. *) Note-5
6. LOCAL/REMOTE selector switch of LCC, CA (Control Authority) switch
ORDER FROM LCC
of CRP can be in only one position at any given time.
7. INTERLOCK BYPASS switch will be installed in CRP.
& AND GATE- OUTPUT IS 1 WHEN ALL INPUTS ARE 1
8. For MIMIC CONTROL, Synchrocheck will be performed by M2FP.
9. For BCU CONTROL, Synchrocheck will be performed by BCU internally.
OR OR GATE- OUTPUT IS 1 WHEN ANY OF THE INPUTS IS 1 10. Independent and identical interlocking/blocking conditions have to be
established for MIMIC and BCU control. For MIMIC control,
interlocking/blocking conditions will be hardware based and established
=1 XOR GATE- OUTPUT IS 1 WHEN INPUTS ARE DIFFERENT
in CRP; for BCU control, they will be software based and established
internally in BCU.
NOT GATE- OUTPUT IS 1 INPUT IS 0 11. LOCAL/REMOTE selector switch in BCU is optional.
CB -QA1 OPEN CONTROL AUTHORITY
TITLE: INTERLOCKING LOGIC OF ALL VOLTAGE GIS SUBSTATION IN DOUBLE SHEET
BUSBAR FOR BUS COUPLER FEEDER (BUS COUPLER-A) 3
STANDARD DOCUMENT
0 09.05.2020 FIRST PREPARATION NUMBER: 64 POWER GRID COMPANY OF BANGLADESH LTD. DOCUMENT ID: A0-DB-G0-BC-IL NEXT SHT 4
REVISION DATE REMARKS
DS -QB1 NORMAL OPEN/CLOSE DS -QB1 MAINTENANCE OPEN/CLOSE
INTERLOCK INTERLOCK

HSES -QC51A OPEN HSES -QC51A CLOSED

CB -QA1 OPEN CB -QA1 OPEN


& &
ES -QC2 CLOSED ES -QC2 CLOSED
NORMAL MAINTENANCE
ES -QC1 OPEN ES -QC1 CLOSED
*** IF -QB1 & -QC1 ARE OR OPEN/CLOSE *** IF -QB1 & -QC1 ARE OR OPEN/CLOSE
-QB51A SEPARATE DEVICES ENABLED SEPARATE DEVICES ENABLED
-BA5A

INTERLOCK SEL. SW BYPASSED INTERLOCK SEL. SW BYPASSED


C1 C2 C3 -QC51A M

BUS-IA
DS -QB2 NORMAL OPEN/CLOSE DS -QB2 MAINTENANCE OPEN/CLOSE
INTERLOCK INTERLOCK

HSES -QC52A OPEN HSES -QC52A CLOSED


BUS-2A

CB -QA1 OPEN CB -QA1 OPEN


& &
-QC52A M ES -QC1 CLOSED ES -QC1 CLOSED
NORMAL MAINTENANCE
ES -QC2 OPEN ES -QC2 CLOSED
-QB1 -QB2 *** IF -QB2 & -QC2 ARE OR OPEN/CLOSE *** IF -QB2 & -QC2 ARE OR OPEN/CLOSE
SEPARATE DEVICES ENABLED SEPARATE DEVICES ENABLED
-QC1 -QC2

-QB52A
INTERLOCK SEL. SW BYPASSED INTERLOCK SEL. SW BYPASSED
-BA6A

-QA1 M
C1 C2 C3

BUS COUPLER-A

BUS SECTION-1
-QA1 M

-QC1A -QC1B

-QB1A QB1B

BUS-IA BUS-IB

BUS-2A BUS-2B

-QB1 -QB2 -QB2A -QB2B -QB1 -QB2

-QC1 -QA1 M
-QC2 -QC2A -QA1 M
-QC2B -QC1 -QA1 M
-QC2

BUS COUPLER-A BUS SECTION-2 BUS COUPLER-B

LEGENDS: NOTES:
TCS: TRIP CIRCUIT SUPERVISION 1. Logics have to be established in CRP by bringing statuses of all relevant
A/R: AUTO RECLOSE devices; wiring among the switching devices are not allowed.
CA: CONTROL AUTHORITY SWITCH 2. More than one device will not be allowed to move at the same time.
M1FP: MAIN-1 FEEDER PROTECTION RELAY 3. Closing from LCC will be for maintenance purpose only; all CB internal
M2FP: MAIN-2 FEEDER PROTECTION RELAY blocking such as SF6 Stage-1 & 2 alarm, spring discharge etc. will be
BUFP: BACK-UP FEEDER PROTECTION RELAY applicable for such closings.
BCU: BAY CONTROL UNIT 4. CA is a 4 (Four) position switch having the positions of
BCPU: BAY CONTROL & PROTECTION UNIT OFF/MIMIC/BCU/REMOTE which will be installed in CRP.
SAS: SUBSTATION AUTOMATION SYSTEM 5. If BCU/SAS is not available in the substation, the CA will be a 3 (Three)
LCC: LOCAL CONTROL CUBICLE position switch having the positions of OFF/LOCAL/REMOTE which will
be installed in CRP.
6. LOCAL/REMOTE selector switch of LCC, CA (Control Authority) switch
of CRP can be in only one position at any given time.
7. INTERLOCK BYPASS switch will be installed in CRP.
& AND GATE- OUTPUT IS 1 WHEN ALL INPUTS ARE 1
8. For MIMIC CONTROL, Synchrocheck will be performed by M2FP.
9. For BCU CONTROL, Synchrocheck will be performed by BCU internally.
OR OR GATE- OUTPUT IS 1 WHEN ANY OF THE INPUTS IS 1 10. Independent and identical interlocking/blocking conditions have to be
established for MIMIC and BCU control. For MIMIC control,
interlocking/blocking conditions will be hardware based and established
=1 XOR GATE- OUTPUT IS 1 WHEN INPUTS ARE DIFFERENT
in CRP; for BCU control, they will be software based and established
internally in BCU.
NOT GATE- OUTPUT IS 1 INPUT IS 0 11. LOCAL/REMOTE selector switch in BCU is optional.
MOTORIZED DS OPEN/CLOSE LOGICS

TITLE: INTERLOCKING LOGIC OF ALL VOLTAGE GIS SUBSTATION IN DOUBLE SHEET


BUSBAR FOR BUS COUPLER FEEDER (BUS COUPLER-A) 4
STANDARD DOCUMENT
0 09.05.2020 FIRST PREPARATION NUMBER: 64 POWER GRID COMPANY OF BANGLADESH LTD. DOCUMENT ID: A0-DB-G0-BC-IL NEXT SHT 5
REVISION DATE REMARKS
NLDC SAS CONTROL/PROTECTION PANEL GIS LOCAL CONTROL CUBICLE

SAS HMI IN REMOTE

SAS HMI IN LOCAL &


ORDER FROM NLDC
OR BCU
SAS HMI IN LOCAL
CA IN REMOTE
-QB51A SAS HMI IN REMOTE &
-BA5A
CA IN BCU
ORDER FROM SAS &
CA IN MIMIC
C1 C2 C3 -QC51A M

BCU SW IN REMOTE
BUS-IA
BCU SW IN LOCAL
OR
CA IN BCU
BUS-2A
CA IN MIMIC

-QC52A M CA IN REMOTE
&
BCU SW IN LOCAL
-QB1 -QB2

-QC1 -QC2
BCU SW IN REMOTE
-QB52A ORDER FROM BCU &
-BA6A

-QA1 M
C1 C2 C3

BUS COUPLER-A

OR
NORMAL CLOSING *) Note-1
ENABLED REMOTE CONTROL &
LOCAL CONTROL
CA IN MIMIC
BUS SECTION-1
CA IN BCU
-QA1 M

CA IN REMOTE &
-QC1A -QC1B OR
ORDER FROM MIMIC
-QB1A QB1B

NORMAL CLOSING *) Note-1, 2


BUS-IA BUS-IB
ENABLED FROM CRP
LOCAL CONTROL

REMOTE CONTROL
BUS-2A BUS-2B
NORMAL MODE & &
SELECTED
-QB1 -QB2 -QB2A -QB2B -QB1 -QB2

-QC1 -QA1 M
-QC2 -QC2A -QA1 M
-QC2B -QC1 -QA1 M
-QC2 ORDER FROM LCC

BUS COUPLER-A BUS SECTION-2 BUS COUPLER-B


NORMAL OPEN/CLOSE
OR
ENABLED FROM GIS LCC

LOCAL CONTROL

REMOTE CONTROL
*) Note-9
MAINTENANCE MODE SELECTED
*) Note-5
&
ORDER FROM LCC
COMMAND
MAINTENANCE *) Note-3 & TO DS
OPEN/CLOSE ENABLED
LEGENDS: NOTES:
TCS: TRIP CIRCUIT SUPERVISION 1. Logics have to be established in CRP by bringing statuses of all relevant
A/R: AUTO RECLOSE devices; wiring among the switching devices are not allowed.
CA: CONTROL AUTHORITY SWITCH 2. More than one device will not be allowed to move at the same time.
M1FP: MAIN-1 FEEDER PROTECTION RELAY 3. Closing from LCC will be for maintenance purpose only; all CB internal
M2FP: MAIN-2 FEEDER PROTECTION RELAY blocking such as SF6 Stage-1 & 2 alarm, spring discharge etc. will be
BUFP: BACK-UP FEEDER PROTECTION RELAY applicable for such closings.
BCU: BAY CONTROL UNIT 4. CA is a 4 (Four) position switch having the positions of
BCPU: BAY CONTROL & PROTECTION UNIT OFF/MIMIC/BCU/REMOTE which will be installed in CRP.
SAS: SUBSTATION AUTOMATION SYSTEM 5. If BCU/SAS is not available in the substation, the CA will be a 3 (Three) MECHANICAL INTERLOCK WITH
LCC: LOCAL CONTROL CUBICLE position switch having the positions of OFF/LOCAL/REMOTE which will ADJACENT ES SATISFIED
be installed in CRP. *** DEPENDING UPON
6. LOCAL/REMOTE selector switch of LCC, CA (Control Authority) switch MANUFACTURER'S DESIGN
of CRP can be in only one position at any given time.
7. INTERLOCK BYPASS switch will be installed in CRP.
& AND GATE- OUTPUT IS 1 WHEN ALL INPUTS ARE 1
8. For MIMIC CONTROL, Synchrocheck will be performed by M2FP.
9. For BCU CONTROL, Synchrocheck will be performed by BCU internally.
OR OR GATE- OUTPUT IS 1 WHEN ANY OF THE INPUTS IS 1 10. Independent and identical interlocking/blocking conditions have to be
established for MIMIC and BCU control. For MIMIC control,
interlocking/blocking conditions will be hardware based and established
=1 XOR GATE- OUTPUT IS 1 WHEN INPUTS ARE DIFFERENT
in CRP; for BCU control, they will be software based and established
internally in BCU.
NOT GATE- OUTPUT IS 1 INPUT IS 0 11. LOCAL/REMOTE selector switch in BCU is optional.
MOTORIZED DS CLOSE/OPEN CONTROL AUTHORITY
TITLE: INTERLOCKING LOGIC OF ALL VOLTAGE GIS SUBSTATION IN DOUBLE SHEET
BUSBAR FOR BUS COUPLER FEEDER (BUS COUPLER-A) 5
STANDARD DOCUMENT
0
REVISION
09.05.2020
DATE
FIRST PREPARATION NUMBER: 64 POWER GRID COMPANY OF BANGLADESH LTD. DOCUMENT ID: A0-DB-G0-BC-IL NEXT SHT 6
REMARKS
MANUAL DS -QB51A OPEN/CLOSE MANUAL DS -QB52A OPEN/CLOSE
INTERLOCK INTERLOCK

OPEN/CLOSE OPEN/CLOSE
HSES -QC51A CLOSED HSES -QC52A CLOSED
ENABLED ENABLED
-QB51A

-BA5A

C1 C2 C3 -QC51A M

BUS-IA

BUS-2A

-QC52A M

-QB1 -QB2

-QC1 -QC2

-QB52A

-BA6A

-QA1 M
C1 C2 C3

BUS COUPLER-A

BUS SECTION-1
-QA1 M

-QC1A -QC1B

-QB1A QB1B

BUS-IA BUS-IB

BUS-2A BUS-2B

-QB1 -QB2 -QB2A -QB2B -QB1 -QB2

-QC1 -QA1 M -QC2 -QC2A -QA1 M -QC2B -QC1 -QA1 M -QC2

BUS COUPLER-A BUS SECTION-2 BUS COUPLER-B

LEGENDS: NOTES:
TCS: TRIP CIRCUIT SUPERVISION 1. Logics have to be established in CRP by bringing statuses of all relevant
A/R: AUTO RECLOSE devices; wiring among the switching devices are not allowed.
CA: CONTROL AUTHORITY SWITCH 2. More than one device will not be allowed to move at the same time.
M1FP: MAIN-1 FEEDER PROTECTION RELAY 3. Closing from LCC will be for maintenance purpose only; all CB internal
M2FP: MAIN-2 FEEDER PROTECTION RELAY blocking such as SF6 Stage-1 & 2 alarm, spring discharge etc. will be
BUFP: BACK-UP FEEDER PROTECTION RELAY applicable for such closings.
BCU: BAY CONTROL UNIT 4. CA is a 4 (Four) position switch having the positions of
BCPU: BAY CONTROL & PROTECTION UNIT OFF/MIMIC/BCU/REMOTE which will be installed in CRP.
SAS: SUBSTATION AUTOMATION SYSTEM 5. If BCU/SAS is not available in the substation, the CA will be a 3 (Three)
LCC: LOCAL CONTROL CUBICLE position switch having the positions of OFF/LOCAL/REMOTE which will
be installed in CRP.
6. LOCAL/REMOTE selector switch of LCC, CA (Control Authority) switch
of CRP can be in only one position at any given time.
7. INTERLOCK BYPASS switch will be installed in CRP.
& AND GATE- OUTPUT IS 1 WHEN ALL INPUTS ARE 1
8. For MIMIC CONTROL, Synchrocheck will be performed by M2FP.
9. For BCU CONTROL, Synchrocheck will be performed by BCU internally.
OR OR GATE- OUTPUT IS 1 WHEN ANY OF THE INPUTS IS 1 10. Independent and identical interlocking/blocking conditions have to be
established for MIMIC and BCU control. For MIMIC control,
interlocking/blocking conditions will be hardware based and established
=1 XOR GATE- OUTPUT IS 1 WHEN INPUTS ARE DIFFERENT
in CRP; for BCU control, they will be software based and established
internally in BCU.
NOT GATE- OUTPUT IS 1 INPUT IS 0 11. LOCAL/REMOTE selector switch in BCU is optional.
MANUAL DS OPEN/CLOSE LOGICS

TITLE: INTERLOCKING LOGIC OF ALL VOLTAGE GIS SUBSTATION IN DOUBLE SHEET


BUSBAR FOR BUS COUPLER FEEDER (BUS COUPLER-A) 6
STANDARD DOCUMENT
0 09.05.2020 FIRST PREPARATION NUMBER: 64 POWER GRID COMPANY OF BANGLADESH LTD. DOCUMENT ID: A0-DB-G0-BC-IL NEXT SHT 7
REVISION DATE REMARKS
NLDC SAS CONTROL/PROTECTION PANEL GIS LOCAL CONTROL CUBICLE

-QB51A

-BA5A

C1 C2 C3 -QC51A M

BUS-IA

BUS-2A

-QC52A M

-QB1 -QB2

-QC1 -QC2

-QB52A

-BA6A

-QA1 M
C1 C2 C3

BUS COUPLER-A

BUS SECTION-1
-QA1 M

-QC1A -QC1B

-QB1A QB1B

BUS-IA BUS-IB

BUS-2A BUS-2B

-QB1 -QB2 -QB2A -QB2B -QB1 -QB2

-QC1 -QA1 M -QC2 -QC2A -QA1 M -QC2B -QC1 -QA1 M -QC2

BUS COUPLER-A BUS SECTION-2 BUS COUPLER-B

ORDER FROM LCC

COMMAND
MECHANICAL INTERLOCKS
& TO
SATISFIED
LEGENDS: NOTES: MANUAL DS
TCS: TRIP CIRCUIT SUPERVISION
*** DEPENDING UPON
1. Logics have to be established in CRP by bringing statuses of all relevant
A/R: AUTO RECLOSE devices; wiring among the switching devices are not allowed. MANUFACTURER'S DESIGN
CA: CONTROL AUTHORITY SWITCH 2. More than one device will not be allowed to move at the same time.
M1FP: MAIN-1 FEEDER PROTECTION RELAY 3. Closing from LCC will be for maintenance purpose only; all CB internal
M2FP: MAIN-2 FEEDER PROTECTION RELAY blocking such as SF6 Stage-1 & 2 alarm, spring discharge etc. will be
BUFP: BACK-UP FEEDER PROTECTION RELAY applicable for such closings.
BCU: BAY CONTROL UNIT 4. CA is a 4 (Four) position switch having the positions of
BCPU: BAY CONTROL & PROTECTION UNIT OFF/MIMIC/BCU/REMOTE which will be installed in CRP.
SAS: SUBSTATION AUTOMATION SYSTEM 5. If BCU/SAS is not available in the substation, the CA will be a 3 (Three)
LCC: LOCAL CONTROL CUBICLE position switch having the positions of OFF/LOCAL/REMOTE which will
be installed in CRP. OPEN/CLOSE
6. LOCAL/REMOTE selector switch of LCC, CA (Control Authority) switch ENABLED
of CRP can be in only one position at any given time.
7. INTERLOCK BYPASS switch will be installed in CRP.
& AND GATE- OUTPUT IS 1 WHEN ALL INPUTS ARE 1
8. For MIMIC CONTROL, Synchrocheck will be performed by M2FP.
9. For BCU CONTROL, Synchrocheck will be performed by BCU internally.
OR OR GATE- OUTPUT IS 1 WHEN ANY OF THE INPUTS IS 1 10. Independent and identical interlocking/blocking conditions have to be
established for MIMIC and BCU control. For MIMIC control,
interlocking/blocking conditions will be hardware based and established
=1 XOR GATE- OUTPUT IS 1 WHEN INPUTS ARE DIFFERENT
in CRP; for BCU control, they will be software based and established
internally in BCU.
NOT GATE- OUTPUT IS 1 INPUT IS 0 11. LOCAL/REMOTE selector switch in BCU is optional.
MANUAL DS CLOSE/OPEN CONTROL AUTHORITY
TITLE: INTERLOCKING LOGIC OF ALL VOLTAGE GIS SUBSTATION IN DOUBLE SHEET
BUSBAR FOR BUS COUPLER FEEDER (BUS COUPLER-A) 7
STANDARD DOCUMENT
0
REVISION
09.05.2020
DATE
FIRST PREPARATION NUMBER: 64 POWER GRID COMPANY OF BANGLADESH LTD. DOCUMENT ID: A0-DB-G0-BC-IL NEXT SHT 8
REMARKS
ES -QC1 OPEN/CLOSE ES -QC2 OPEN/CLOSE
INTERLOCK INTERLOCK

DS -QB2 OPEN DS -QB1 OPEN


OPEN/CLOSE OPEN/CLOSE
CB -QA1 OPEN & ENABLED
CB -QA1 OPEN & ENABLED
DS -QB1 OPEN DS -QB2 OPEN
*** IF -QB1 & -QC1 ARE *** IF -QB2 & -QC2 ARE
SEPARATE DEVICES SEPARATE DEVICES
-QB51A

-BA5A

C1 C2 C3 -QC51A M HSES -QC51A OPEN/CLOSE HSES -QC52A OPEN/CLOSE


DS -QB1A OPEN INTERLOCK DS -QB2A OPEN INTERLOCK
BUS-IA
BUS-1A ALL DS -QB1 OPEN BUS-2A ALL DS -QB2 OPEN
OPEN/CLOSE OPEN/CLOSE
MANUAL DS -QB51A CLOSED & ENABLED
MANUAL DS -QB52A CLOSED & ENABLED
BUS-2A CVT -BA5A NO VOLTAGE CVT -BA6A NO VOLTAGE

CVT -BA5A MCB OK CVT -BA6A MCB OK


-QC52A M

-QB1 -QB2

-QC1 -QC2

-QB52A

-BA6A

-QA1 M
C1 C2 C3

BUS COUPLER-A

BUS SECTION-1
-QA1 M

-QC1A -QC1B

-QB1A QB1B

BUS-IA BUS-IB

BUS-2A BUS-2B

-QB1 -QB2 -QB2A -QB2B -QB1 -QB2

-QC1 -QA1 M
-QC2 -QC2A -QA1 M
-QC2B -QC1 -QA1 M
-QC2

BUS COUPLER-A BUS SECTION-2 BUS COUPLER-B

LEGENDS: NOTES:
TCS: TRIP CIRCUIT SUPERVISION 1. Logics have to be established in CRP by bringing statuses of all relevant
A/R: AUTO RECLOSE devices; wiring among the switching devices are not allowed.
CA: CONTROL AUTHORITY SWITCH 2. More than one device will not be allowed to move at the same time.
M1FP: MAIN-1 FEEDER PROTECTION RELAY 3. Closing from LCC will be for maintenance purpose only; all CB internal
M2FP: MAIN-2 FEEDER PROTECTION RELAY blocking such as SF6 Stage-1 & 2 alarm, spring discharge etc. will be
BUFP: BACK-UP FEEDER PROTECTION RELAY applicable for such closings.
BCU: BAY CONTROL UNIT 4. CA is a 4 (Four) position switch having the positions of
BCPU: BAY CONTROL & PROTECTION UNIT OFF/MIMIC/BCU/REMOTE which will be installed in CRP.
SAS: SUBSTATION AUTOMATION SYSTEM 5. If BCU/SAS is not available in the substation, the CA will be a 3 (Three)
LCC: LOCAL CONTROL CUBICLE position switch having the positions of OFF/LOCAL/REMOTE which will
be installed in CRP.
6. LOCAL/REMOTE selector switch of LCC, CA (Control Authority) switch
of CRP can be in only one position at any given time.
7. INTERLOCK BYPASS switch will be installed in CRP.
& AND GATE- OUTPUT IS 1 WHEN ALL INPUTS ARE 1
8. For MIMIC CONTROL, Synchrocheck will be performed by M2FP.
9. For BCU CONTROL, Synchrocheck will be performed by BCU internally.
OR OR GATE- OUTPUT IS 1 WHEN ANY OF THE INPUTS IS 1 10. Independent and identical interlocking/blocking conditions have to be
established for MIMIC and BCU control. For MIMIC control,
interlocking/blocking conditions will be hardware based and established
=1 XOR GATE- OUTPUT IS 1 WHEN INPUTS ARE DIFFERENT
in CRP; for BCU control, they will be software based and established
internally in BCU.
11. LOCAL/REMOTE selector switch in BCU is optional.
NOT GATE- OUTPUT IS 1 INPUT IS 0
ES & HSES OPEN/CLOSE LOGICS

TITLE: INTERLOCKING LOGIC OF ALL VOLTAGE GIS SUBSTATION IN DOUBLE SHEET


BUSBAR FOR BUS COUPLER FEEDER (BUS COUPLER-A) 8
STANDARD DOCUMENT
0 09.05.2020 FIRST PREPARATION NUMBER: 64 POWER GRID COMPANY OF BANGLADESH LTD. DOCUMENT ID: A0-DB-G0-BC-IL NEXT SHT 9
REVISION DATE REMARKS
NLDC SAS CONTROL/PROTECTION PANEL GIS LOCAL CONTROL CUBICLE

-QB51A

-BA5A

C1 C2 C3 -QC51A M

BUS-IA

BUS-2A

-QC52A M

-QB1 -QB2

-QC1 -QC2

-QB52A

-BA6A

-QA1 M
C1 C2 C3

BUS COUPLER-A

BUS SECTION-1
-QA1 M

-QC1A -QC1B

-QB1A QB1B

BUS-IA BUS-IB

BUS-2A BUS-2B

-QB1 -QB2 -QB2A -QB2B -QB1 -QB2

-QC1 -QA1 M
-QC2 -QC2A -QA1 M
-QC2B -QC1 -QA1 M
-QC2

BUS COUPLER-A BUS SECTION-2 BUS COUPLER-B

ORDER FROM LCC

COMMAND
MECHANICAL INTERLOCK
& TO
WITH ADJACENT DS SATISFIED
LEGENDS: NOTES: HSES/ES
TCS: TRIP CIRCUIT SUPERVISION
*** DEPENDING UPON
1. Logics have to be established in CRP by bringing statuses of all relevant
A/R: AUTO RECLOSE devices; wiring among the switching devices are not allowed. MANUFACTURER'S DESIGN
CA: CONTROL AUTHORITY SWITCH 2. More than one device will not be allowed to move at the same time.
M1FP: MAIN-1 FEEDER PROTECTION RELAY 3. Closing from LCC will be for maintenance purpose only; all CB internal
M2FP: MAIN-2 FEEDER PROTECTION RELAY blocking such as SF6 Stage-1 & 2 alarm, spring discharge etc. will be
BUFP: BACK-UP FEEDER PROTECTION RELAY applicable for such closings.
BCU: BAY CONTROL UNIT 4. CA is a 4 (Four) position switch having the positions of
BCPU: BAY CONTROL & PROTECTION UNIT OFF/MIMIC/BCU/REMOTE which will be installed in CRP.
SAS: SUBSTATION AUTOMATION SYSTEM 5. If BCU/SAS is not available in the substation, the CA will be a 3 (Three)
LCC: LOCAL CONTROL CUBICLE position switch having the positions of OFF/LOCAL/REMOTE which will
be installed in CRP. OPEN/CLOSE
6. LOCAL/REMOTE selector switch of LCC, CA (Control Authority) switch ENABLED
of CRP can be in only one position at any given time.
7. INTERLOCK BYPASS switch will be installed in CRP.
& AND GATE- OUTPUT IS 1 WHEN ALL INPUTS ARE 1
8. For MIMIC CONTROL, Synchrocheck will be performed by M2FP.
9. For BCU CONTROL, Synchrocheck will be performed by BCU internally.
OR OR GATE- OUTPUT IS 1 WHEN ANY OF THE INPUTS IS 1 10. Independent and identical interlocking/blocking conditions have to be
established for MIMIC and BCU control. For MIMIC control,
interlocking/blocking conditions will be hardware based and established
=1 XOR GATE- OUTPUT IS 1 WHEN INPUTS ARE DIFFERENT
in CRP; for BCU control, they will be software based and established
internally in BCU.
NOT GATE- OUTPUT IS 1 INPUT IS 0 11. LOCAL/REMOTE selector switch in BCU is optional.
ALL ES & HSES CLOSE/OPEN CONTROL AUTHORITY
TITLE: INTERLOCKING LOGIC OF ALL VOLTAGE GIS SUBSTATION IN DOUBLE SHEET
BUSBAR FOR BUS COUPLER FEEDER (BUS COUPLER-A) 9
STANDARD DOCUMENT
0 09.05.2020 FIRST PREPARATION NUMBER: 64 POWER GRID COMPANY OF BANGLADESH LTD. DOCUMENT ID: A0-DB-G0-BC-IL NEXT SHT N/A
REVISION DATE REMARKS