Stucor Be3254 KG
Stucor Be3254 KG
➢ The large devices and systems it is more practical to express the bases in
kVA/MVA and kV. Then equation (4) is written as
➢ When (MVA)B and (kV)B are modified, the new pu impedance is given by
(kV)B = Line-to-line kV
VOLTAGE REGULATION
10. Explain the voltage regulation of a transformer and state its significance.
➢ The regulation of the transformer is defined as the reduction in magnitude of the
terminal voltage due to load, with respect to the no-load terminal voltage.
% Regulation = x 100
21
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
➢ For an ideal transformer, regulation is 0% since voltage drops, due to R1, X1, R2,
X2 are negligible.
% Regulation = x 100
% Regulation = x 100
% Regulation = x 100
22
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
Where,
V2 - secondary terminal voltage at load
I2 - secondary current at load.
Cos ϕ - Power factor of the load.
Iron loss, Pi = Wo, determined from OC test.
Copper loss Pcu =Ws, determined from SC test at full load.
At full load n =1
At half load n = 1/2
Copper loss at a load n times the full load = n2Pcu.
Condition for maximum efficiency :
𝑂𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟 = 𝑉2 𝐼2 𝐶𝑂𝑆𝜙2
➢ If R02 is the total resistance of the transformer referred to secondary, then
Total copper loss Pcu = 𝑅02
➢ For maximum value of efficiency for given cosФ2, the denominator must have the
least value.
➢ The condition for maximum efficiency is obtained by differentiating the
denominator and equating it to zero.
(denominator) = 0
=0
(- )=0
= Pcu
24
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
➢ Since the core losses are constant independent of the load, the all-day efficiency of
a transformer is dependent upon the load cycle; but no prediction can be made on
the basis of the load factor (average load/peak load).
➢ It is an important figure of merit for distribution transformers which feed daily
load cycle varying over a wide load range.
➢ Higher energy efficiencies are achieved by designing distribution transformers to
yield maximum (power) efficiency at less than full load (usually about 70% of the
full load).
➢ This is achieved by restricting the core flux density to lower values by using a
relatively larger core cross-section. (It means a larger iron/copper weight ratio.)
DETERMINATION OF PARAMETERS OF CIRCUIT MODEL OF TRANSFORMER
14. Explain OC and SC test of single phase transformers. (or) write short note on
open circuit test on transformer.
1. Open circuit test
2. Short circuit test
(i) Open circuit test:
Open circuit test is useful to determine:
1. Core loss.
2. No-load current.
3. R0 and X0.
➢ One winding of the transformer usually high voltage winding is left open and the
other winding is connected to the supply of normal voltage and frequency.
➢ The applied voltage V1 is measured by a voltmeter, the no-load current I0 by an
ammeter and no load input power W0 by a wattmeter.
➢ As the normal rated voltage is applied to the primary, normal iron loss will occur in
the transformer core.
25
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
0 =
No-load resistance
𝑅0 = =
No-load reactance
𝑋0 = =
Thus open circuit gives no load loss Pi, Iw, Iμ, R0, X0.
(ii) Short circuit test:
The short circuit test is useful to find:
1. Full-load copper loss.
2. Equivalent resistance and reactance referred to any side.
26
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
➢ In this test, the secondary winding (usually low voltage winding) is short circuited
by a thick conductor and variable low voltage is applied to the primary winding.
➢ The input voltage is gradually raised with the help of a variac till Isc full load
current flows in the primary winding.
➢ There is no output from the transformer under short circuit conditions. Since
applied voltage is very low, flux linking with the core is very small and therefore
iron losses are so small that these can be neglected and so the reading of the
wattmeter gives total copper loss at full load.
Pcu = ( 𝑅1 + ) =( 𝑅01 )
X01 =
Thus short circuit test gives full load cu loss, X01, R01 and cosФs.
27
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
28
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
➢ Any two legs of the three phase winding will act as the return for the third just as
in a 3 phase system any two conductors act as the return for the current in the
third conductor.
➢ Main drawback in a 3 phase transformer is that if any one phase becomes
disabled, then the whole transformer has to be ordinarily removed from service for
repairs.
Advantages of three phase transformer
➢ As compared to a bank of 3 – single phase transformers, the main advantages of a
single 3 phase transformer are that it occupies less floor space for equal rating,
weighs less, costs about 15 % less.
➢ Saving in iron can be achieved in constructing a single 3 phase transformer.
Saving in iron is due to the joint use of the magnetic paths between the coils.
➢ The overall bus bar structure, switchgear and installation of single phase three
phase unit is simpler.
➢ It can be transported easily.
➢ In case of three single phase units, six terminals are required to be brought while
in case of single three phase unit, only three terminals are required to be brought
out.
Three phase transformer connections
➢ Star - star connection
➢ Delta – Delta connection
➢ Star – Delta connection
➢ Delta – Star connection
AUTO TRANSFORMER
17. What is meant by auto transformer? Explain the principle of operation of an
auto transformer with neat sketch.(May 18)
➢ An auto transformer is similar to a two winding transformer but differ in the way
the primary and secondary winding are interrelated.
➢ On load condition, a part of the load current is obtained directly from the supply
and the remaining part is obtained by transformer action.
29
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
Principle of Operation
➢ In auto transformer the primary and the secondary windings are connected
magnetically as well as electrically.
➢ In fact, a part of the single continuous winding is common to both primary and
secondary.
➢ In one type of transformer, there is continuous winding with the taps brought out
at convenient points determined by desired secondary voltage and in another type
of auto transformer, there are two or more distinct coils which are electrically
connected to form a continuous winding.
➢ The primary winding AB from which a tapping at C is taken, such that CB acts as
a secondary winding.
➢ The supply voltage is applied across AB, and the load is connected across CB. The
tapping may be fixed or variable.
➢ When an AC voltage V1 is applied across AB, an alternating flux is set up in the
core, as a result, an e.m.f E1 is induced in the winding AB. A part of this induced
e.m.f is taken in the secondary circuit.
Let,
V1 – primary applied voltage
V2 – secondary voltage across the load
I1 – primary current
I2 – load current
N1 – number of turns between A and B
N2 – number of turns between C and B
30
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
➢ Equation (1) and (2) shows that the ampere turns due to section BC and AC
balance each other which is characteristic of the transformer action.
18. Derive an expression for saving of copper when an auto transformer is used.
➢ The weight of the copper is proportional to the length and area of a cross section
of the conductor.
➢ The length of the conductor is proportional to the number of turns, and the cross
section is proportional to the product of current and number of turns.
➢ Now, from the above figure (B) shown of the auto transformer, the weight of
copper required in an auto transformer is
➢ If the same duty is performed with an ordinary two winding transformer shown
above in the figure (A).
31
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
Therefore,
Now, the ratio of the weight of the copper in an auto transformer to the weight of
copper in an ordinary transformer is given as
Therefore,
32
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
secondary terminal which is dangerous to the operator and the equipment. So the
auto transformer should not be used to for interconnecting high voltage and low
voltage system.
➢ Used only in the limited places where a slight variation of the output voltage from
input voltage is required.
Applications of Auto transformer
➢ It is used as a starter to give up to 50 to 60% of full voltage to the stator of a
squirrel cage induction motor during starting.
➢ It is used to give a small boost to a distribution cable, to correct the voltage drop.
➢ It is also used as a voltage regulator
➢ Used in power transmission and distribution system and also in the audio system
and railways.
HARMONICS ON TRANSFORMERS
➢ The transformer does not generate harmonics.
➢ The transformer has primary and secondary winding which are inductive in
nature.
➢ The inductive load draws current linearly with the applied voltage.
➢ However, the transformer generates harmonics in two conditions.
Condition: 1
• When transformer is energized the magnetizing current drawn by it is non linear
and it generates harmonics.
• This is because, when transformer is energized the back emf is zero and
transformer draws huge magnetizing current which is not sinusoidal.
• The magnetizing current is rich in the 2nd order harmonic current.
Condition: 2
• The over excitation of the transformer. The over excitation means the transformer
is operated at increased flux density than its rated flux density.
• Under over excitation of transformer the 5th order harmonic current is produced.
• The above two conditions happen for a short period of time and thus the 2nd and
5th order harmonics is not a serious problem.
➢ The transformer primary function is to feed power to the load. The nature of load
decides whether the load current waveform has harmonics or not.
➢ If the load is linear, no harmonics is produced and if the load is non linear the
harmonics are produced in the electrical network.
33
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
➢ The transformer is supposed to feed the sinusoidal current at its rated kVA.
➢ However, if the current flowing through the transformer winding it adversely
affects the transformer performance.
➢ If the magnitude of the harmonic current is more, it also distorts the input voltage
of the transformer. The harmonics cause following adverse effects on the
transformer performance.
Effect of Harmonics on Iron Loss
➢ The core or iron loss of the transformer is the loss occurs due to eddy current loss
and hysteresis loss.
➢ The hysteresis loss is directly proportional to the frequency and, eddy current loss
is directly proportional to the square of the frequency.
➢ Thus, it is clear that the iron loss gets increased with increase in frequency.
➢ The harmonic current is the integral multiples of the fundamental frequency and
harmonic current may have frequency of 100 Hz, 150Hz, 200Hz, 250 Hz and so
on.
➢ Thus the iron loss of the transformer gets increased if harmonic rich current flow
through the transformer.
Effect of Harmonics on Copper Loss
➢ The tendency of flowing of current at the outer surface of the conductor is known
as skin effect.
➢ The higher frequency current tends to flow at the outer surface of the conductor.
When the current flows at the outer surface of the conductor, the effective cross
section area of the conductor gets reduced.
➢ The reduction in effective cross section area leads to increase in the conductor
resistance. The higher resistance of the conductor cause the more copper
loss(I^2R) in the transformer.
➢ Thus, the copper loss of the transformer gets increased with increase in the
harmonic current.
Effect of Harmonics on Efficiency of Transformer
➢ The efficiency of the transformer is defined as the ratio of output power to input
power.
➢ Efficiency = Output Power/ Input Power
= Input power- Losses/ Input Power
= 1 – Losses/Input Power
➢ With increase of losses in the transformer due to harmonics, the efficiency of the
transformer gets decreased.
34
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
***************************************************************************************
TWO MARKS
35
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
36
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
But in case of real transformer, ratio is fixed but voltage ratio is varied because
of voltage drop due to resistance and leakage reactance. That is why, the real
transformer V1:V2 ≠ N1:N2
With a change in frequency, iron and copper loss, regulation, efficiency & heating
varies so the operation of transformer is highly affected.
19. List the arrangement of stepped core arrangement in a transformer?
➢ To reduce the space effectively.
➢ To obtain reduce length of mean turn of the winding.
➢ To reduce I2R loss.
20. Why are breathers used in transformers?
➢ Breathers are used to entrap the atmospheric moisture and thereby not allowing it
to pass on to the transformer oil.
➢ It permits the oil inside the tank to expand and contract as its temperature
increases and decreases.
21. What is the function of transformer oil in a transformer?
➢ It provides good insulation
➢ Cooling.
37
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
%Z=
% Regulation up = *100
38
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
28. State the condition for maximum efficiency of a transformer. Then what is the
corresponding output current?
Iron loss= copper loss (or) constant loss = Variable loss.
Hence efficiency of a transformer will be maximum when copper losses are equal to
iron loss. The load current corresponding to maximum efficiency is given by I2=
31. Define regulation and efficiency of the transformer.(Or) Give the expression for
percentage voltage regulation of a single phase transformer.[Nov/Dec 2003,13]
(Or) Define voltage regulation of a transformer.[May 18]
The regulation of the transformer is defined as the reduction in magnitude of the
terminal voltage due to load, with respect to the no-load terminal voltage.
% Regulation = *100
39
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
34. Why the open circuit test on a transformer is conducted at rated voltage?
The open circuit on a transformer is conducted at a rated voltage because core
loss depends upon the voltage. This open circuit test gives only core loss or iron loss
of the transformer.
35. What are the necessary tests to determine the equivalent circuit of the
transformer?
➢ Open circuit test
➢ Short circuit test
36. Why is the range of efficiency in transformer higher than those of other
electrical machines?
The range of efficiency in transformer is higher than those of other electrical
machine because there are no rotating parts in the transformer. i.e., rotational loss is
zero.
37. Mention the two different components of core loss in a transformer.
➢ Hysteresis loss
➢ Eddy current loss
38. Give the expression for the load current when the transformer operates at its
maximum efficiency. Nov/Dec 2006.
I2=
Where,
I2=load current,
Pi=Iron loss,
R02=Equivalent resistance to secondary.
39. Explain why the wattmeter in OC test on transformers reads core loss and that
in SC test reads copper loss at full load.
➢ In OC test, the transformer secondary is open. The transformer is operated at
rated voltage. Here only iron loss occurs in transformer core.
➢ In SC test, the transformer secondary winding is short circuited. The transformer
is operated at rated current. Here the input voltage is low. The full load current
depends upon the copper loss.
40. Why is the short circuit test on a transformer performed on HV side?
The short circuit test is normally conducted on transformer HV side and LV side is
short circuited, because on the high voltage side, the current rating is low. So we
have to use normally available meter range.
41. Under what type of power factor a transformer gives zero voltage regulation?
Under leading power factor a transformer gives zero voltage regulation.
40
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
41
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
42
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
43
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – I: TRANSFORMER
44
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
UNIT-II
DC MACHINES
1
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
INTRODUCTION:
A dc generator is a machine that converts mechanical energy into electrical energy (dc
voltage and current) by using the principle of magnetic induction.
Construction:
The construction of DC generator and DC motor are the same. Any DC generator can be
run as a DC Motor and vice-versa. All DC machines have a stator and Rotor.
The stator consist of
• Yoke or Magnetic frame.
• Field system poles - Field winding, Inter-poles.
The Rotor has the following parts
• Armature-Armature core, Armature winding.
• Commutator.
• Brushes, Bearing.
Yoke:
• It acts as a protecting cover for DC machine.
• It provides mechanical support for the poles.
• It carries the magnetic flux produced by the poles.
• Material used:
Small machine: cast iron
Large machine: cast steel
Pole core, pole shoes:
• Pole core carries field winding which is necessary to produce the flux.
• Pole shoes spread out the flux in the air gap and also to reduce the reluctance.
• They support the exciting coils.
Material used:
Small machine: cast iron
Large machine: cast steel
2
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
Inter poles:
• Inter poles or the commutating poles are fixed to the frame in between main poles.
• They are used for improve commutation.
Field winding:
• The field winding is placed on the pole core.
• To carry the current and to produce the magnetic flux. Material used: It is made
up of aluminium or copper.
Armature:
• It is further divided into two parts namely:
• Armature core
• Armature winding
3
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
Armature winding:
• The armature windings are placed into the slots on the armature surface.
• The ends of the coils are soldered with commutator segments.
Functions: When the armature rotates an emf is induced in the armature conductors
in case of generators.
Material used: Copper.
Commutator:
• The basic nature of emf induced in the armature conductor is alternating.
• This needs rectification in case of DC generator, which is made possible by a
device called commutator.
Material used: Copper.
Brushes & Bearings:
• The function of brushes is to collect current from commutator.
DC GENERATOR:
INTRODUCTION:
• An electrical generator is a device that converts mechanical energy to electrical
energy, generally using the principle of electromagnetic induction.
• According to Faraday's Laws of Electro-Magnetic Induction, when a conductor or a
coil is rotated in a magnetic field in such a way, to cut the magnetic lines of flux, an
e.m.f is induced in a conductor or in the coil.
Input Output
Where ‘N’ is the number of turns, ‘ ’ is the flux and ‘t’ is the time
5
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• The induced emf in the coil can be increased by
(i) increasing the flux density(B) and
(ii) by increasing the angular velocity ( ).
• The current flowing in the external resistance to a D.C generator is made
unidirectional by connecting the coil side to a slip ring.
• The slip ring is split into two segments a and b and the segments are insulated
from each other and from shaft.
• The coil sides AB is always attached to the segment a and likewise CD to b.
• The brushes B1 and B2touch these segments and are meant to collect the current.
6
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
E = EMF induced in any parallel path in the armature in volts
A = Number of parallel paths.
According to Faraday’s law, the induced emf is proportional to the rate of change of
the magnetic flux.
i.e.,
Let us consider a single conductor moving during one revolution. The flux produced by it
is given by,
𝑑𝜑 = 𝜑𝑃weber
EMF generated/conductor,
Volts
Volts
7
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
4. Explain the Circuit Model of a dc machine.
• The parallel paths of dc machine armature are symmetrical and each has an
induced emfEa and a resistance Rp. as shown in Fig below for A = 4.
• Its Thevenin equivalent is drawn by the side in which
• The armature can be represented by the symbol as shown in Fig with Ea within
circle and the series resistance Ra written by its side.
• The armature resistance is quite small so as to limit the copper- loss to an
acceptable value. Figure 7.16 also shows the field circuit of the machine and the field
coil axis is placed at 90° to the brush axis.
• Since most of the time steady-state dc behaviour of the machine will be
considered.
The armature induced emf
Machine torque
• The voltage drop at brush-commutator contact is fixed (1–2 V), independent of
armature current as the conduction process is mainly through numerous short arcs.
• This voltage being small is modelled as linear resistance and lumped with Ra.
Generating Mode
• The machine operates in generating mode (puts out electrical power) when Ia is in
the direction of induced emfEa as in Fig. (a). For the armature circuit
• Thus a dc machine is generating if its armature induced emf (Ea) is more than its
terminal voltage (Vt).
• The electromagnetic power converted from mechanical to electrical from is
8
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• Thus a DC machine is motoring if armature terminal voltage (Va) is more than its
induced emf (Ea).
• The electromagnetic power converted from mechanical to electrical from is
9
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
Lap Versus Wave Winding
• Consider a P pole machine having flux/pole Φ and rotating at rad/s. It has a
total of Z conductors and maximum permissible conductor current is Ic.
• Let us derive the expression for power converted and torque developed.
Torque developed
Or
• Find that the power converted and torque developed are independent if the
number of parallel paths.
• It means that these values are that same whether the conductors are lap
connected or wave. These in fact depend on number of conductors and permissible
conductor current.
11
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
Only a part of armature current flowsthrough shunt field winding and
the rest flows through the load.It is a “constant speed” machine.
12
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• Series field current, 𝐼𝑠𝑒= 𝐼𝑎= 𝐼𝐿+ 𝐼𝑠ℎ
7. Explain the open circuit and load circuit characteristics of separately excited
DC generator (OR) performance characteristics[NOV/DEC 2009](OR) Explain the
internal and external characteristics of DC generators.[APR/MAY 2015]
There are three types of characteristics in DC generator.
➢ Open circuit characteristics (OCC) (or) Magnetization characteristics [EgVs If]
➢ Internal characteristics (or) Total characteristics [E VsIa)
➢ External characteristics (or) Voltage regulated characteristics [V Vs IL]
These three characteristics are applicable for both self-excited and separately excited DC
generator.
SEPARATELY EXCITED DC GENERATOR:
From generator emf equation,
• It is clear that the induced emf is proportional to the flux. If the speed is kept
constant, and the flux is varied, then the induced emf also varies.
𝐸𝑔∝𝜑𝑁
Open circuit characteristics:
• If N is constant, Φ increases Eg increases Fig. shows the separately excited circuit
diagram for OCC.
• The variation of flux with the induced emf is called the no-load magnetization
curve (or) saturation curve of the generator. Measurement of flux is difficult, instead the
curve is plotted between field current (If) and induced emf (Eg).
14
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
Internal and External Characteristics:
• The internal and external characteristics are obtained due to armature reaction
drop and armature resistance drop.
Internal Characteristics
• This curve is drawn between the emf (E) and armature current (Ia). By increasing
the Ia induced emf, E will decrease due to armature reaction is shown in Fig. This is
represented as curve (2).
External Characteristics
• This curve is drawn between the terminal voltage (V) and armature current (Ia).By
increasing Ia, the induced emf again decreases due to armature resistance. This is
represented as curve (3).
(i)DC Shunt Generator Characteristics:
• This is one type of self-excited DC generator. If the armature and field winding are
connected in parallel it is called shunt excitation.
a) Open Circuit Characteristics (OCC):
15
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• Ia increases causing a drop of voltage in the armature resistance Ra, Drop in the
brush contact resistance and Drop due to armature reaction.
The above three factors cause a decrease in the induced emf. It is expressed by the
following equation.
16
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• The curve (3) represents the external characteristics. Here, the drop is due to
armature resistance and series field resistance. By increasing the load current, the
terminal voltage decreases.
• It is seen from characteristics shown in Fig. that the series generator has a rising
characteristic (i.e.,) voltage increases with increase in load.
Compound Generator:
D.C MOTOR
INTRODUCTION
• A machine that converts electrical energy into mechanical energy is known as dc
motor.
• Its operation is based on the principle that when a current carrying conductor is
placed in a magnetic field, the conductor experiences a mechanical force.
• The fundamental principles and construction of the DC motors are identical with
the DC generators.
• A DC machine that runs as a motor will also operate as a generator.
Input Output
17
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
The force whose direction is given by Fleming’s Left-Hand Rule and whose magnitude is
given by
F=BILNewtons
B=Magnetic field intensity in wb/m2
I=Current in Amperes
L=Length of the conductor in meter.
OPERATION:
• When voltage is applied to the loop of wire a current flows, and a magnetic field is
created that will interact with the field of the magnet.
• Repulsion and attraction of the fields will cause the loop to turn.
• The loop moves away from the strong field toward the weak field.
• The direction of the rotation can be determined by “the right-hand rule”.
Fig 3.16: Interaction of two fluxes and forces experienced by the conductor
• In a dc motor, the stator poles are supplied by dc excitation current, which
produces a dc magnetic field.
• The rotor is supplied by dc current through the brushes, commutator and coils.
• The interaction of the magnetic field and rotor current generates a force that drives
the motor.
• A current is supplied to the coil by a battery and the torque acting on the current-
carrying coil causes it to rotate.
18
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
9. Derive the Torque and Speed Equations of the DC Motor.
• Torque is turning or twisting moment of a force about an axis. It is measured by
the product of the force and the radius at which this force acts.
• Consider a pulley of radius ‘r’ meter acted upon by a circumferential force of ‘F’
newton which causes it to rotate at speed N rpm.
Torque, T = F × r (Nm)
Work done by this force in one revolution = Force x distance
=Fx joules.
And P = Power developed = Work done/time
P=Tx watts
Where
T = Torque in Nm
= Angular speed in rad/sec =
P= watts
19
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
(Or)
10. Explain in detail the various types of dc motor with suitable diagram.
DC MOTOR TYPES
The types of DC motors are
1. DC Series motor
2. DC Shunt motor
3. DC Compound motor
DC series motor:
In DC series motor means the field winding is connected in series with armature.
Same current flows through field as armature.
20
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• 𝑉 = 𝐸𝑔 − (𝐼𝑎𝑅𝑎 + 𝐼se𝑅𝑠𝑒 + 𝑉𝑏𝑟𝑢𝑠ℎ)
• 𝐼𝑎= 𝐼𝐿= 𝐼𝑠𝑒
• Hence 𝑉 = 𝐸𝑔 −𝐼𝑎(𝑅𝑎 + 𝑅𝑠𝑒)+ 𝑉𝑏𝑟𝑢𝑠ℎ
• 𝐼𝑎𝑅𝑎= Voltage drop in the armature resistance
• 𝐼𝑎𝑅𝑠𝑒= Voltage drop in the series field winding resistance
• 𝑉𝑏𝑟𝑢𝑠ℎ= Voltage drop at connects of the brush
NormallyVbrush is neglected and hence 𝑉 = 𝐸𝑔 − (𝑅𝑎 + 𝑅𝑠𝑒)
DC Shunt motor:
In DC shunt motor, the field winding is connected across the armature.
22
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
Industrial use:
• Lathes
• Drills
• Boring mills
• Shapers
• Spinning and Weaving machines.
23
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• The motor in which the field winding is connected in series with the armature is
called series motor.
∵ 𝜑∝𝐼𝑎
• From the above equation it is clear that by, increasing the armature current, speed
will decrease. It is shown in figure.
• DC Series motor should never be started without some load. Otherwise the motor
speed will rise to a dangerous value and get damaged.
ii) Torque – armature current characteristics
• We know that, 𝑇∝𝜑𝐼𝑎.
• In DC series motor, flux is directly proportional to armature current,
𝜑∝𝐼𝑎
𝑇∝𝐼𝑎2 (𝐵𝑒𝑓𝑜𝑟𝑒𝑠𝑎𝑡𝑢𝑟𝑎𝑡𝑖𝑜𝑛
𝑇∝𝐼𝑎 (𝐴𝑓𝑡𝑒𝑟𝑠𝑎𝑡𝑢𝑟𝑎𝑡𝑖𝑜𝑛
• At light load, armature current, 𝐼𝑎 and hence flux is small. But as 𝐼𝑎 increases,
torque increases as the square of the current. Hence this characteristic is a parabola. It
is shown in the figure.
• After saturation, the flux is constant. i.e. is independent of 𝐼𝑎, hence torque is
directly proportional to armature current. So the curve becomes a straight line
24
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
iii) Speed-torque characteristics
• This characteristics can be got from the above two characteristics. Here the DC
series motor speed is high, the torque is low and vice- versa. It is shown in figure.
DC SHUNT MOTOR
• The shunt motor field winding is connected in parallel to the armature winding.
• Shunt motor normally called as constant speed motor. In DC shunt motor
𝐼𝐿 = 𝐼𝑎 + 𝐼𝑓
• Since, the field winding is directly connected to supply voltage ‘v’ which is also
constant, the field current If is also constant.
i) Speed - armature current characteristics:
• The speed equation of the DC motor is
25
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
ii) Torque – armature characteristics:
• It is also called electrical characteristics. The DC shunt motor torque is directly
proportional to flux and armature current.
T Ia
Here, is constant
Ia
• So when the armature current increases, the torque also increases. It is shown in
the figure.
• Here, when the load torque increases, the speed slightly decreases.
26
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
would take an armature current of 220/0.5 = 440 A which is 22 times the full-load
current.
• This high starting current may result in:
(i) Burning of armature due to excessive heating effect,
(ii) Damaging the commutator and brushes due to heavy sparking,
(iii) Excessive voltage drop in the line to which the motor is connected. The result is that
the operation of other appliances connected to the line may be impaired and in
particular cases, they may refuse to work.
• In order to avoid excessive current at starting, a variable resistance (known as
starting resistance) is inserted in series with the armature circuit. This resistance is
gradually reduced as the motor gains speed (and hence Eb increases) and eventually it is
cut out completely when the motor has attained full speed.
• Starting current is limited to 1.25 to 2 times the full-load current.
Two-Point Starter:
• A two-point starter is used for starting dc motor which has the problem of over-
speeding due to loss of load from its shaft. Such a starter is shown in fig(3.23).
• DC motor starting, two and three point starter. Here for starting the motor,the
control arm is moved clockwise from its OFF position to the ON position against the
spring tension.
27
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• The control arm is held in the ON position by an electromagnet. The hold-on
electromagnet is connected in series with the armature circuit.
• If the motor losses its load,current decreases and hence the strength of the
electromagnet also decreases.The control arm returns to the OFF position due to spring
tension,this preventing the motor from overspeeding.
Four-Point Starter
• In a four-point starter, the no-volt release coil is connected directly across the
supply line through a protective resistance R.
• Fig. (3.25) shows the schematic diagram of a 4-point starter for a shunt motor
(over-load release coil omitted for clarity of the figure.
• Now the no-volt release coil circuit is independent of the shunt field circuit.
Therefore, proper speed control can be exercised without affecting the operation of no
volt release coil.
• Note that the only difference between a three-point starter and a four-point starter
is the manner in which no-volt release coil is connected.
30
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• It is based on the fact that by varying the flux , the motor speed canbe
• The shunt field rheostat reduces the shunt field current Ish and hence the flux Φ.
• Therefore, only raise the speed of the motor above the normal speed .
31
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• Generally, this method permits to increase the speed in the ratio 3:1.Wider speed
ranges tend to produce instability and poor commutation.
Advantages
• This is an easy and convenient method.
• It is an inexpensive method since very little power is wasted in the shuntfield
rheostat due to relatively small value of Ish.
• The speed control exercised by this method is independent of load on themachine.
Disadvantages
• Only speeds higher than the normal speed can be obtained since the totalfield
circuit resistance cannot be reduced below Rsh—the shunt fieldwinding resistance.
• There is a limit to the maximum speed obtainable by this method. It isbecause if
the flux is too much weakened, commutation becomes poorer.
Note:The field of a shunt motor in operation should never be opened because itsspeed
will increase to an extremely high value.
Armature control method
• This method is based on the fact that by varying the voltage available across
thearmature, the back e.m.f and hence the speed of the motor can be changed.
• This is done by inserting a variable resistance RC (known as controller resistance)
inseries with the armature as shown in Fig.
32
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• The speed varies widely with load since the speed depends upon thevoltage drop in
the controller resistance and hence on the armature currentdemanded by the load.
• The output and efficiency of the motor are reduced.
• This method results in poor speed regulation.Due to above disadvantages, this
method is seldom used to control the speed ofshunt motors.
Note:The armature control method is a very common method for the speedcontrol of d.c
series motors. The disadvantage of poor speed regulation is notimportant in a series
motor which is used only where varying speed service isrequired.
Advantages
(a) The speed of the motor can be adjusted through a wide range withoutresistance
losses which results in high efficiency.
(b) The motor can be brought to a standstill quickly, simply by rapidlyreducing the
voltage of generator G. When the generator voltage is reducedbelow the back e.m.f. of the
motor, this back e.m.f. sends current throughthe generator armature, establishing
dynamic braking. While this takes place, the generator G operates as a motor driving
motor A which returnspower to the line.
(c) This method is used for the speed control of large motors when a d.c.supply is not
available.
Disadvantage
• The disadvantage of the method is that a special motor-generator set is requiredfor
each motor and the losses in this set are high if the motor is operating underlight loads
for long periods.
34
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
(i) Field diverters
In this method, a variable resistance (called field diverter) is connected in parallel with
series field winding as shown in Fig.
• Any desired amount of current can be passed through the diverter by adjusting its
resistance.
• Hence the flux can be decreased and consequently the speed of the motor is
increased. The minimum speed is obtained by completely removing the resistance in the
diverter circuit.
Now for a given load, if Ia isdecreased, the flux Φ must increase .Since ,
35
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
(iv) Paralleling field coils.
This method is usually employed in the case of fanmotors. By regrouping the field coils
as shown in Fig. (5.9), several fixedspeeds can be obtained.
Armature-resistance control
• In this method, a variable resistanceis directly connected in series withthe supply
to the complete motor asshown in Fig.
• This reducesthe voltage available across thearmature and hence the speed falls.
• By changing the value of variableresistance, any speed below thenormal speed can
be obtained.
• Thisis the most common methodemployed to control the speed of d.c. series
motors.
• when full load current of the motor passes through this resistance, there is a
considerable loss of power in it.
Speed Control of Compound Motors:
• Speed control of compound motors may be obtained by any one of the
methodsdescribed for shunt motors.
• Speed control cannot be obtained throughadjustment of the series field since such
adjustment would radically change theperformance characteristics of the motor.
36
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
UNIVERSAL MOTOR
17. Explain the construction and working of an universal motor.
• An universal motor is a special type of motor which is designed to run on either
DC or single phase AC supply.
• However, the whole magnetic path (stator field circuit and also armature) is
laminated. Lamination is necessary to minimize the eddy currents which induce while
operating on AC.
• The rotary armature is of wound type having straight or skewed slots and
commutator with brushes resting on it.
• The commutation on AC is poorer than that for DC, because of the current
induced in the armature coils. For that reason brushes used are having high resistance.
37
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
Working Of Universal Motor
• A universal motor works on either DC or single phase AC supply. When the
universal motor is fed with a DC supply, it works as a DC series motor.
• When current flows in the field winding, it produces an electromagnetic field. The
same current also flows from the armature conductors.
• When a current carrying conductor is placed in an electromagnetic field, it
experiences a mechanical force. Due to this mechanical force, or torque, the rotor starts
to rotate. The direction of this force is given by Fleming's left hand rule.
• When fed with AC supply, it still produces unidirectional torque. Because,
armature winding and field winding are connected in series, they are in same phase.
Hence, as polarity of AC changes periodically, the direction of current in armature and
field winding reverses at the same time.
• Thus, direction of magnetic field and the direction of armature current reverses in
such a way that the direction of force experienced by armature conductors remains
same. Thus, regardless of AC or DC supply, universal motor works on the same principle
that DC series motor works.
Speed Torque Characteristics
38
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
STEPPER MOTOR
18. Explain the construction and working principle of different types of stepper
motors. (MAY 2018)
• A stepper Motor is basically a synchronous Motor. In a stepper motor, there are no
brushes.
• This motor does not rotate continuously; instead it rotates in the form of pulses or
in discrete steps. That is why it is called stepper motor.
• There are different types of motors available on the basis of steps per rotation, for
example-12 steps per rotation, 24 steps per rotation etc.
• We can control or operate Stepper motor with the feedback or without any
feedback. A simple image of stepper motor is shown in above picture.
Types of Stepper Motor:
The Stepper Motors are of following types:
• Permanent Magnet
• Variable Reluctance.
• Hybrid Stepper Motor
39
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
40
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• The rotor of this type of motor is made up of two rotors joining like a shaft of
motor.
• One of them is for north and other is for South Pole. These poles arrange in
alternative manner as they designed in such a manner.
Applications of stepper motors:
• Linear actuators, linear stages, rotation stages, goniometers, and mirror mounts
• Commercially, stepper motors are used in floppy disk drives, scanners, computer
printers, plotters, slot machines, image scanners, compact disc drives, intelligent
lighting, camera lenses, CNC machines and, more recently, in 3D printers.
BRUSHLESS DC MOTOR
19. Explain the construction and working principle of Brushless DC motor.
• Conventional dc motors are highly efficient and their characteristics make them
suitable for use of servomotors.
• However their only drawback is that they need a commutator and brushes which
are subject to wear and require maintenance.
• When the functions of commutator and brushes were implemented by solid state
switches, maintenance free motors were realized.
• These motors are known as brushless dc motors.
CONSTRUCTION:
• The construction of modern brushless motor is very similar to the ac motor known
as the permanent magnet synchronous motor. The main parts of brushless dc motor are
• Stator
• Rotor
Stator:
• Stator is made up of silicon steel stampings with slots in its inner periphery.
• The slots are accommodated either in closed or open distributed armature
winding.
41
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• This winding is to be wound for a specified number of poles.
• The winding is connected to DC supply through power electronic switching
circuits.
Rotor:
• Rotor is made up of permanent magnet. The number of poles of the rotor is same
as the number of poles of the stator.
• The rotor shaft carries a rotor position sensor.
• A position sensor provides information about the position of the shaft at any
instant for the controller which sends signals to the electronic commutator.
Principle of operation:
• The schematic diagram of the brushless dc motor is shown in the figure. It also
shows the three phases of the stator and rotor with d and q axes.
• The stator is connected to a variable voltage current source through an indicator
and an inverter comprising six SCRs (S1 to S6).
• Diodes are connected across SCRs to protect these from the voltage induced in the
armature coil undergoing commutation position sensors placed on the rotor.
• Which cause the SCRs to be fired in sequence so as to be in synchronism with the
rotors mechanical position.
42
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
• The armature winding of a stator draws the current from the inverter circuit. The
current distributions in the stator winding depend upon rotor position and the devices
turn on.
• The m.m.f perpendicular to the permanent magnet flux is setup. Then the
armature conductor experiences a force. The reactive force develops a torque in the rotor.
• If the torque is more than the opposing fractional and load torque, the motor
starts. It is self-starting motor.
• As the motor picks up, then there exists a relative speed between permanent field
and armature conductors.
• As per faraday’s law of electromagnetic induction, emf is induced in the
conductors. This emf oppose a cause, as a result, the developed torque is reduced.
• Finally the rotor will attain a steady state when the developed torque is equal to
the opposing load torque. Thus the motor attains steady state condition.
Advantages:
• They require little or no maintenance.
• They have a much larger operating life.
• No field winding.
• Better ventilation.
• Regenerative braking is possible.
• High speed operation.
• No mechanical commutator.
Disadvantages:
• Require rotor position sensors.
• Motor field cannot be controlled.
• Require power semiconductor switching circuits.
Applications:
• Laser printer
• Hard disk drive
• Automotive applications.
• Robotics applications.
• Textile and glass industries.
*********************************************************************************************
43
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
2MARKS:
1. State the law of conservation of energy.
According to the law of conservation of energy, “Energy can neither be created nor
destroyed, but it can be converted from one form to another form”.
2. Classify the two types of DC machines.
DC machines can be classified into two types.
✓ DC generator
✓ DC motor
3. What is a DC generator?
A DC generator is an electromechanical device which converts mechanical energy
into electrical energy.
4. What is the principle of generator?
When the armature conductor cuts the magnetic flux, emf is induced in the
conductor.
5. State Faraday’s first law of electromagnetic induction.
It states that “whenever the magnetic flux linking a conductor changes, an emf is
always induced in it”.
6. State Fleming’s Right hand rule.
The thumb, forefinger & middle finger of right hand are held so that these fingers
are mutually perpendicular to each other, then forefinger gives the direction of the
lines of flux, thumb gives the direction of the relative motion of conductor and middle
finger gives the direction of the emf induced.
7. How will you find the direction of force produced using Fleming’s left hand
rule?
The thumb, forefinger & middle finger of left hand are held so that these fingers
are mutually perpendicular to each other, then forefinger gives the direction of
magnetic field, middle finger gives the direction of the current and thumb gives the
direction of the force experienced by the conductor.
8. The outer frame of a DC machine serves double purposes, what are they?
• It acts as a mechanical support for the machine
• Magnetic circuit is formed through the core
9. List the main constituents of stator of DC machine.
• Stator
• Rotor
Stator parts
1. Yoke
2. Pole core
44
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
3. Pole shoe
4. Field coils
Rotor parts
1. Armature
2. Commutator
3. Brushes
10. What is the purpose of yoke in DC machine?
• It acts as a protecting cover for the whole machine and provides mechanical support
for the poles
• It carries magnetic flux produced by the poles
11. Express the emf equation of DC generator (OR) write the equation for emf
induced DC machine.[MAY 2018]
EMF generated in DC generator
45
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
14. What is a DC compound generator?
Compound generator is one of the self-excited DC generators. In that, there are
two field windings, one of them is connected across the armature and other is
connected in series with the armature winding.
15. List the conditions of self-excitation of DC generator.
There must be a sufficient residual flux in the field poles.
The field terminals must be connected in such a way that the field current
increases flux in the direction of residual flux.
The field circuit resistance should be less than the critical field resistance.
The generator should run at the rated speed.
16. State the conditions under which a DC shunt generator fails to excite.
There may not be any residual magnetism in the field system.
The field winding connection may be such that it may not assist the voltage to get
build up.
The total field circuit resistance is more than the critical field resistance.
The break or opening in the field or armature circuit.
17. Compare lap winding and wave windings used for DC machine armature.
46
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
21. What is the purpose of Commutator?
Commutator is used to convert the alternating emf (AC) generated in the armature
winding into direct voltage (DC).
22. Differentiate self and separately excited DC generators.
The field winding is excited by an emf The field winding is excited by separate DC
induced in the armature conductors. source.
23. Give the circuit model for DC shunt generator and write down the current
and voltage equation.
Ia=IL+Ish
Eg= V+IaRa+Brush drop
V=Eg-IaRa- Brush drop
24. What are the causes for drop in terminal voltage?
Eg= V+IaRa+Brush drop
V=Eg-IaRa- Brush drop
1. Armature circuit resistance drop.
2. Brush contact drop.
3. Demagnetizing effect of armature reaction.
4. Weakening of field current.
25. What is the function of carbon brush used in DC generators?
The function of the carbon brush is to collect current from commutator and supply
to external load circuit and to load.
26. Why is the emf not zero when the field current is reduced to zero in DC
generator?
Even after the field current is reduced to zero, the machine is left out with some
flux as residue so emf is available due to residual flux.
27. Name any two application of DC series generator.
o Booster
o Constant illumination
o Constant current source
in determining heating, temperature rise, rating & efficiency of transformers, machines &
other A.C run magnetic devices.
28. How does DC motor differ from DC generator in construction?
➢ Generators are normally placed in closed room and accessed by skilled operators
only. Therefore on ventilation point of view they may be constructed with large opening
in the frame.
47
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
➢ Motors have to be installed right in the place of use which may have dust,
dampness, inflammable gases, chemical etc. to protect the motors against these
elements the motor frames are used partially closed or totally closed or flame proof.
29. Define armature reaction in DC machines? What are its effects?
The interaction between the main flux and armature flux cause disturbance called as
armature reaction.
30. Define pole pitch.
It is the distance measured in terms of number of armature slots (or armature
conductors) per pole.
31. Define back pitch.
It is the distance measured in terms of armature conductors between the two sides of a
coil at the back of the armature.
32. Define front pitch.
It is the distance measured in terms of armature conductors between the coil sides
attached to any one commutator segment.
33. Define commutator pitch.
The commutator pitch is the number of commutator segments spanned by each coil of
the winding. It is denoted by YC.
34. Why the external characteristics of DC shunt generator is more drooping
than that of a separately excited generator?
In separately excited generator, Ia= IL and , Ish is not supplied by armature. In DC shunt
generator, Ia = IL +Ish hence the drop IaRa is more than in separately excited generator.
Hence the external characteristics of DC shunt generator is more drooping than that of a
separately.
35. What is a DC motor?
A DC motor is an electromechanical device which converts electrical energy into
mechanical energy.
36. What is the principle of motor?
When a current carrying conductor is placed in a magnetic field it experiences a force
tending to move it.
37. How will you find the direction of force produced using Fleming’s left hand
rule?
The thumb, forefinger & middle finger of left hand are held so that these fingers are
mutually perpendicular to each other, then forefinger gives the direction of magnetic
field, middle finger gives the direction of the current and thumb gives the direction
of the force experienced by the conductor.
48
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
38. Mention the significance of back emf.
Eg= V-IaRa.
Ia=
49
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
Applied voltage control
44. Write the expression for speed of a Dc motor.[NOV/DEC 2015]
armature resistance
Speed is directly proportional to back e.m.f(Eb) and inversely proportional to flux/pole
(Ф)
45. What is a self-excited DC machine?
The excitation current is needed for producing magnetic field in DC machine.
If the exciting current is drawn from the same source (armature) itself, then it is called
self excited Dc machine.
46. What for field coils are provided in DC machines?
In Dc machine, we are in need of magnetic field to produce e.m.f(generator) or force
(motor) in the conductor. Permanent magnet is not employed for this purpose in Dc
machines. Electromagnets are used.
47. How does a series motor develop high starting torque?
A dc series motor is always started with some load. Therefore the motor armature
current increases. Due to this, series motor develops high starting torque.
48. What is the need for starter in dc motors?
When a dc motor is directly switched on, at the time of starting, the motor back
e.m.f is zero. Due to this, the armature current is very high.
Due to the very high current, the motor gets damaged. To reduce the starting
current of the motor a starter is used.
49. What is prime mover?
The basic source of mechanical power which drives the armature of the generator is
called prime mover.
50. Mention the applications of series motor.
Series motors are used where the load is directly attached to the shaft and where
there is no danger of the load is being thrown off.
50
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
It is used in electric trains, where the self weight of the train acts as load and for
cranes, hoists, fans, blowers, conveyors, lifts etc.
51. Mention the applications of compound motor.
Compound motors are used for driving heavy machine tools for intermittent loads
shears, punching machines.
52. State the various applications of DC motors.
Type of Characteristics Applications
Motor
Shunt Approximately constant For driving constant speed line
speed. Speed can be shafting lathes, centrifugal
controlled. Medium starting pumps, machine tools, Blowers
torque. (Up to 1.5 full load and fans, Reciprocating pumps.
torque)
Series Variable speed. Speed can For traction work. i.e. electric
be controlled. High Starting locomotives rapid transit systems
torque. trolley cars etc. cranes and hoists
Conveyors.
Cumulative Compound Variable speed. For intermittent high torque
Speed can be controlled. loads, for shears and punches,
High Starting torque. elevators, conveyors, heavy
planners, rolling Mills, ice
machines, printing press, air
compressors .
P= Number of poles.
Z = Number of conductors.
A= Number of parallel paths
Ia= Armature current.
51
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
55. Why a dc series motor used to start heavy loads? Why DC series motor is
never started on no load?
In case of a d.c. series motor, and on no load as is small hence flux
produced is also very small. According to speed equation,
As Eb is almost constant.
So on very light load or no load as flux is very small, the motor tries to run at
dangerously high speed which may damage the motor mechanically.
This can be seen from the speed-armature current and the speed-torque
characteristics that on low armature current and low torque condition motor shows a
tendency to rotate with dangerously high speed.
56. State the function of no volt coil of the starter.
As the handle is gradually moved over to the final stud, the starting resistance is
cut out of the armature circuit in steps. The handle is now held magnetically by the no-
volt release coil which is energized by shunt field current.
The no-volt coil is demagnetized and the handle is pulled to the OFF position by
the spring. Thus, the motor is automatically disconnected from the supply.
57. Mention the factor affecting the speed of DC motor.
The factors affecting the speed of a DC motor are,
The flux Φ.
The voltage across the armature.
The applied voltage V.
58. State the advantages of flux control method used for controlling speed of DC
shunt motor.
This is an easy and convenient method.
It is an inexpensive method since very little power is wasted in the shunt field
rheostat due to relatively small value of Ish.
The speed control exercised by this method is independent of load on the machine.
59. State the disadvantages of flux control method used for controlling speed of
DC shunt motor.
Only speeds higher than the normal speed can be obtained since the total field
circuit resistance cannot be reduced below Rsh—the shunt field winding resistance.
There is a limit to the maximum speed obtainable by this method. It is because if
the flux is too much weakened, commutation becomes poorer.
52
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
60. State the disadvantages of armature control method used for controlling
speed of DC shunt motor.
A large amount of power is wasted in the controller resistance since it carries full
armature current Ia.
The speed varies widely with load since the speed depends upon the voltage drop
in the controller resistance and hence on the armature current demanded by the load.
The output and efficiency of the motor are reduced.
This method results in poor speed regulation. Due to above disadvantages, this
method is seldom used to control the speed of shunt motors.
61. State the methods of speed control in DC series motor.
Rheostat control.
Applied voltage control.
Flux control.
i. Flux diverter.
ii. Armature diverter.
iii. Tapped field.
iv. Series-parallel grouping of field coil.
62. Why DC series motor is not suitable for belt driven loads?
For belt driven loads, there is possibility of breaking of a belt causing no load condition
for the series motor. But on no load, dc series motor tries to run at dangerously high
speed and may get damaged. To avoid such situation, dc series motor is not suitable for
belt driven loads.
63. What is stepper motor?
➢ A stepper Motor is basically a synchronous Motor. In a stepper motor, there are
no brushes.
➢ This motor does not rotate continuously; instead it rotates in form of pluses or in
discrete steps. So, it is called as stepper motor.
64. Define step angle.
Step angle is defined as the angle through which the motor rotates for each
command pulse.it is denoted as β.
Β = (Ns-Nr/Ns.Nr) 360
65. Define resolution
It is defined as the no.of steps needed to complete one revolution of the shaft.
Resolution = no. of steps /revolution
66. Mention some applications of stepper motor.
➢ Floppy disc drives
53
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
➢ Full step operation or single phase on mode is the one in which at a time only one
Quartz watch
➢ Camera shutter operation
➢ Dot matrix and line printers
➢ Small tool application i.e. robotics
67. What are the advantages and disadvantages of stepper motor?
Advantages:
➢ It can be driven in open loop without feedback
➢ It is mechanically simple
➢ It requires little or no maintenance.
Disadvantages:
➢ Low efficiency
➢ Fixed step angle
➢ Limited power output
68. What is meant by full step operation?
Phase winding is energized, due to which one stator winding is energized and
causes the rotor to rotate some angle.
69. What is meant by two phase mode of operation?
Two phase on mode is the one in which two phase windings are energized at a time,
due to which two stator windings are energized and causes the rotor to rotate through
some angle.
70. What is synchronism in stepper motor?
It is the one to one correspondence between the number of pulses applied to the
stepper motor and the number of steps through which the motor has actually moved.
71. What are the types of stepper motor?
The Stepper Motors are of following types:
• Permanent Magnet
• Variable Reluctance.
• Hybrid Stepper Motor
72. What is meant by micro stepping in stepper motor?
The methods of modulating currents through stator windings so as to obtain
rotation of stator magnetic field through a small angle to obtain micro stepping action
are known as micro stepping.
73. What are the advantages of micro stepping?
➢ Improvement in resolution.
➢ Dc motor like performance.
➢ Elimination of mid frequency resonance.
54
BE3254 – ELECTRICAL AND INSTRUMENTATION ENGINEERING UNIT – II: DC MACHINES
;
➢ Rapid motion at micro stepping rate..
74. What are the advantages of brushless dc motors drives?
➢ They require little or no maintenance.
➢ They have a much larger operating life.
➢ No field winding.
➢ Better ventilation.
➢ Regenerative braking is possible.
➢ High speed operation.
➢ No mechanical commutator.
75. What are the disadvantages of brushless dc motors drives?
➢ Require rotor position sensors.
➢ Motor field cannot be controlled.
➢ Require power semiconductor switching circuits.
76. What are the applications of brushless dc motors?
➢ Laser printer
➢ Hard disk drive
➢ Automotive applications.
➢ Robotics applications.
➢ Textile and glass industries.
77. Define mechanical commutators.
➢ Its arrangement is located in the rotor.
➢ No of commutator segments are very high.
78. Define electronic commutators.
➢ Its arrangement is located in the stator.
➢ No of switching devices limited to six.
79. Why the BLDC motor is called electronically commutated motor?
The BLDC motor is also called electronically commutated motor because the phase
windings of BLDC motor is energized by using power semiconductor switching circuits.
Here the power semiconductor switching circuits act as a commutator.
55
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
UNIT-III
AC ROTATING MACHINES
1
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ All these bars are joined at each end by metal rings called end rings. This forms a
permanently short-circuited winding.
➢ The rotor is not connected electrically to the supply but has current induced in it
by transformer action from the stator.
3
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
(ii) The rotating field passes through the air gap and cuts the stationary rotor
conductors.Due to the relative speed between the rotating flux and the stationary
rotor, e.m.f.s are induced in the rotor conductors. Since the rotor circuit is short-
circuited, currents start flowing in the rotor conductors.
(iii) The current-carrying rotor conductors are placed in the magnetic field produced by
the stator. Mechanical force acts on the rotor conductors. The sum of the mechanical
forces on all the rotor conductors produces a rotating torque.It moves the rotor in the
same direction as the rotating field.
(iv) According to Lenz’s law, the direction of rotor currents will be such that they tend to
oppose the cause producing them. Now, the cause producing the rotor currents is the
relative speed between the rotating field and the stationary rotor conductors.
To reduce this relative speed, the rotor starts running in the same direction as that of
stator field and tries to catch it.
2. Explain the principle of operation of 3-phase induction motor and explain how
the rotating magnetic field is produced by three- phase currents.
PRODUCTION OF ROTATING MAGNETIC FIELD
➢ If a balanced 3 phase supply is given to a balanced 3 phase winding, it produces
rotating magnetic field of constant amplitude. This speed is called as
synchronous speed.
➢ The speed of the rotating magnetic field is given by
NS =
5
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
6
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
7
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
RRemarks:
i) The resultant flux is of constant value. .
8
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
Fig.4.6
➢ The secondary is connected to the load, which draws electrical power. But in case
of induction motor the secondary / rotor is short circuited.
➢ The stator of the induction motor is represented by an equivalent circuit as shown
in above fig.
From fig,
V1 – supply voltage per phase
E1 – induced EMF in stator
E2 – induced EMF in rotor
R1 – stator resistance/ phase
X1 – stator reactance/ phase
X2r – rotor reactance / phase
R2r – rotor induced EMF in running condition/phase
When the induction motor operates under no load condition, it draws some current
from the supply.
It is to produce the flux in the air gap and to supply iron losses. Normally the no
load current consists of two components, (i.e) Iw and Iµ.
= +
Where,
Iw – working component which supplies no load losses.
Iµ - magnetizing component which sets up the flux in core and air gap
9
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ From this equation, rotor circuit consists of fixed reactance X2 in series with
= + -
10
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
= + = +
i) The part R2 is rotor resistance itself which represents that part where rotor
copper loss takes place.
K = transformation ratio=
= =
= = =
11
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
= +
Fig.4.11
X01= equivalent reactance referred to stator
= +
12
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
= +
= +
= +
The equivalent circuit (referred stator) is shown in below figures.
In DC motor, torque is proportional to the product of the armature and flux per pole
i.e., T Ia.
Incase of induction motor, the flux and rotor current, the rotor power factor has also
been taken into account. Hence,
………….(1)
Where,
let E2 be the rotor induced emf per phase under standstill condition and X2 be the
rotor reactance per phase under standstill condition.since the rotor frequency at a
slip is fr = sf.
X2 = sX2
Also ………(2)
13
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
14
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ When the supply voltage V is constant, E2 is also constant and running torque is
given by,
➢ If a curve is drawn between the torque and slip for a particular value of rotor
resistance R2, the graph thus obtained is called torque-slip characteristic.
15
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
Hence, torque slip curve is a straight line from zero slip to a slip that
corresponds to full-load.
(iii)As slip increases beyond full load slip, the torque increases and becomes maximum
at s = R2/X2. This maximum torque in an induction motor is called pull-out
torque or break-down torque.
Its value is at least twice the full-load value when the motor is operated at rated
voltage and fiequency.
When is X2 maximum, term increases rapidly so that may be neglected.
➢ This large starting current produces a large voltage drop in the line, which may
affect the operation of other devices connected to the same line.
➢ Hence, it is not advisable to start induction motors of higher ratings (generally
above 25kW) directly from the mains supply.
Types of starters:
➢ DOL(Direct On Line) starter
➢ Rotor resistance starter.
➢ Autotransformer starter.
➢ Star to Delta starter.
7. Describe with a neat sketch, the principle and working of a DIRECT ON LINE
starter of a 3-phase induction motor. (16) (NOV/DEC 2011)
➢ This method is also known as the DOL method for starting the three-phase squirrel
cage induction motor.
➢ In this method, we directly switch the stator of the three-phase squirrel cage
induction motor on to the supply mains.
➢ The motor at the time of starting draws very high starting current (about 5 to 7
times the full load current) for the very short duration.
➢ Such a high value of current causes sudden undesirable voltage drop in the supply
voltage.
➢ A live example of this sudden drop of voltage is the dimming of the tube lights and
bulbs in our homes at the instant of starting of refrigerator motor.
➢ The buttons which may be installed in a convenient place away from the starter.
The start button is held open by a spring.
➢ On pressing the star pushbutton S1, the contactor C is energized from two line
conductors L1 and L2.
➢ The three main contacts M and the auxiliary contact A are closed. The terminals a
and b are short-circuited. The motor is then connected to the supply mains.
➢ The S1 button moves back under the spring action as soon as the pressure is
released. The coil C remains energized through ab.
➢ Thus, the main contact M remains closed, and the motor continues to get supplies.
➢ Therefore, contact A is known as Hold-On-Contact. The stop button S2 is normally
held closed by the spring.
➢ If the S2 button is pressed to stop the motor, the supply through the contactor coil
C is disconnected.
17
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ As the coil C is de-energized, the main contacts M and the auxiliary contact A are
opened. The supply to the motor is disconnected, and the motor is stopped.
Under voltage Protection
➢ When the voltage falls below a certain value or when the supply fails or disrupted
during the operation of the motor, the coil C is de-energized.
➢ Hence, the motor is disconnected from the supply overload Protection
➢ The motor is overloaded one or all the overload coils (O.L.C) are energized.
➢ The normally closed contact D is opened, and the contactor coil C is de-energized
to disconnect the supply from the motor. Fuses are provided in the circuit for short
circuit protection.
➢ In Direct on line starting the starting current may be as large as ten times the full
load current, and the starting torque is equal to full load torque.
➢ Such a large starting current produces an excessive voltage drop in the line which
supplies power to the motor.
18
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ In this article, we will discuss on the starting method and characteristics of slip
ring induction motors with its applications.
➢ Unlike cage motors, the speed of the slipring motor can be controlled.
➢ The stators of the slipring motors are same as those of squirrel cage motors.
➢ But the rotor of a slipring motor consists of a three-phase winding formed out of
copper conductors, and set into a laminated soft iron core.
➢ The rotor sliprings are connected to three terminals through three sets of brushes.
A starter unit, connected to the terminals, completes the rotor circuit externally.
➢ The starter unit consists of three variable resistances connected in star.
➢ It is connected to the three slipring terminals so that each phase of the rotor
winding has variable resistance in series with it, as shown in Fig.
19
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ A slipring motor can be made to run below its maximum speed by leaving parts of
the external resistances in series with the rotor windings.
➢ These motors are usually started with full line voltage applied across its terminals.
➢ As these motors have external resistance connected to its rotor circuit, the value of
starting current is adjusted or kept minimum, by increasing the resistance of the
rotor circuit.
➢ This external resistance can be assumed to be a form of rheostat, connected in
star.
➢ The rheostat is at its maximum when the motor starts and gradually cut-out as the
motor gathers speed.
➢ The controlling rheostat may be of either stud or contactor type. It may be either
hand operated or sometimes automatic.
➢ The 3-phase supply to the stator has a switching contactor along with over-load
and no or low-voltage protective devices.
➢ There might be also an interlock provided to ensure the proper sequential
operation of the control gear and starting devices.
9. With neat diagrams, explain the working of (i) Auto Transformer Starter
(ii) Star-Delta Starter for 3 phase induction motor. (16) (NOV/DEC 2016)
Auto Transformer Starter:
➢ A three-phase star connected autotransformer can be used to reduce the voltage
applied to the stator. Such a starter is called an autotransformer starter.
➢ The schematic diagram of autotransformer starter. The schematic diagram of
autotransformer starter is shown in the Fig.
➢ It consists of a suitable change over switch.
➢ When the switch is in the start position, the stator winding is supplied with
reduced voltage. This can be controlled by tappings provided with autotransformer.
➢ The reduction in applied voltage by the fractional percentage tappings x, used for
an autotransformer.
➢ When motor gathers 80% of the normal speed, the changeover switch is thrown
into run position.
➢ Due to this, rated voltage gets applied to stator winding.
➢ The motor starts rotating with normal speed. Changing of switch is done
automatically by using relays.
20
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ The power loss is much less in this type of starting. It can be used for both star
and delta connected motors. But it is expensive than stator resistance starter.
21
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ In this method, induction motor is connected in star during start and delta while
running with rated speeds.
➢ These starters are designed to run on delta connected stator of an induction motor.
The schematic diagram of this starter is shown in Figure.
➢ This starter uses a TPDT (triple pole double throw) switch and it connects the
stator winding in star during the starting condition.
➢ Due to this star connection, the applied voltage to the motor is reduced by the
factor 1/√3. This reduced voltage results the less current through the motor.
➢ When the motor picks up the speed, the TPST switch is thrown automatically on
the other side by using relays such that the winding is now connected in delta
across the supply.
➢ So, the normal voltage is applied to the motor (because in delta connection voltage
is same, (VL =VP) and hence the motor runs at normal speed.
➢ This method is cheap and maintenance free as compared to other methods.
➢ However, this is suitable only for delta connected motors and also the factor by
which starting voltage reduced, i.e., 1/√3 cannot be altered.
SINGLE PHASE INDUCTION MOTOR
➢ The motors which work on single phase a.c. supply is very popularly in use in
shops, offices, houses, schools etc. These a.c. motors are called single phase
induction motors.
➢ The numerous domestic applications use single phase motors. The power rating of
such motors is very small.
➢ Some of them are even fractional horse power motors, which are used in
applications like small toys, small fans, hair dryers etc.
10. Explain with neat diagram the construction of single phase Induction Motors.
➢ Similar to a d.c. motor, single phase induction motor has basically two main parts.
One is rotating and other is stationary.
➢ The stationary part in single phase induction motors is called stator while the
rotating part is called rotor.
➢ The stator has laminated construction, made up of stampings. The stampings are
slotted on its periphery to carry the winding called stator winding or main winding.
➢ This is excited by a single phase a.c. supply. The laminated construction keeps
iron losses to minimum.
22
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ The stampings are made up of material like silicon steel which minimizes the
hysteresis loss. The stator winding is wound for certain definite number of poles
means when excited by single phase a.c. supply, stator produces the magnetic field
which creates the effect of certain definite number of poles.
➢ The number of poles for which stator winding is wound, decides the synchronous
speed of the motor.
➢ The synchronous speed is denoted as Ns and it has a fixed relation with supply
frequency f and number of poles P. The relation is given by,
➢ The induction motor never rotates with the synchronous speed but rotates at a
speed which is slightly less than the synchronous speed.
➢ The rotor construction is of squirrel cage type. In this type, rotor consists of
uninsulated copper or aluminum bars, placed in the slots.
➢ The bars are permanently shorted at both the ends with the help of conducting
rings called end rings.
➢ The entire structure looks like cage hence called squirrel cage rotor. The
construction and symbol is shown in the Fig.4.18.
23
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
by two resolving fluxes each equal to the half the value of ( ) the alternating flux
Fig 4.20
➢ Fig 4.20 shows the vectors when they have been rotated by an angle + to – .
24
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
Fig 4.21
Fig 4.22
Fig 4.23
➢ After three quarters of cycle of, again the resultant is zero.
Fig 4.24
➢ So flux variation is ,0,- ,0.the flux variation with respect to is plotted which
is shown in the figure below.
25
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
Fig 4.25
➢ With respect to the forward rotating flux (i.e., one which rotates in the same
direction as rotor).
➢ The slip with respect to the backward flux is
Sb = = 1+ = 1+1-s = 2-s
Sb = 2-s
➢ Each of the two component fluxes while revolving around the stator cuts the rotor
induces an emf and produces its own torque. The two torques are oppositely
directed so that the net torque is zero i.e., resultant torque is equal to their
differences.
26
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ Now depending upon these additional means the single-phase induction motors are
classified as:
(i) Split phase induction motor.
(ii) Capacitor start induction motor.
(iii) Capacitor start capacitor run induction motor (two value capacitor method).
(iv) Shaded pole induction motor.
winding is highly inductive in nature so, the current flowing in running winding
lags behind applied voltage by large angle.
➢ The resultant of these two currents is I. The resultant of these two currents
produces rotating magnetic field which rotates in one direction.
➢ In split phase induction motor the starting and main current get split from each
other by some angle so this motor got its name as split phase induction motor.
Applications:
➢ Fans,
➢ Blowers,
➢ Centrifugal pumps,
➢ Washing machine,
➢ Grinder,
➢ Lathes,
➢ Air conditioning fans, etc.
28
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ We are familiar with this fact that the current flowing through the capacitor leads
the voltage. So, in capacitor start inductor motor and capacitor start capacitor run
induction motor we are using two winding.
➢ They are the main winding and the starting winding. With starting winding we
connect a capacitor so the current flowing in the capacitor i.e Ist leads the applied
29
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
30
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ It has salient poles on the stator excited by single-phase supply and a squirrel cage
rotor as shown in Fig. (4.30).
➢ A portion of each pole is surrounded by a short-circuited turn of copper strip called
shading coil.
31
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
32
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ Record players,
➢ Small fans,
➢ Electric clocks etc.
THREE PHASE ALTERNATOR (OR) SYNCHRONOUS GENERATOR
14. Describe construction and working of an alternator (or) synchronous
generator.
➢ An alternator has 3-phase winding on the stator and a DC field winding on the
rotor.
➢ The individual field pole windings are connected in series in such a way that when
the field winding is energized by the D.C. exciter, adjacent poles have opposite
polarities.
34
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
If Kp and Kd are the pitch factor and distribution factor of the armature winding, then,
35
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
Sometimes the turns (T) per phase rather than conductors per phase are specified, in
that case, eq. becomes:
where,
kp = cos
The line voltage will depend upon whether the winding is star or delta connected.
i.e.,EL= Er.m.s/phase
Kd=
Kp =
kp = cos
PROBLEM : A 3-phase, 12-pole, 500 rpm star connected alternator has 144 slots
with 8 conductors per slot. The coils are full pitched and flux per pole is 0.08wb.
36
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
Determine the phase and line EMF’s. What will be the phase voltage if the coils are
connected to form a balanced two-phase winding?(15)(NOV/DEC 2018)
Solution:
Emf per phase 4.44fɸ
Since the coils are full pitched i.e, the coil span factor 1
No. of slots/pole/phase,
No. of slots/pole,
Angular displacement ,
Emf/Phase, 3265.88 V
37
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
5656.67 V
VOLTAGE REGULATION
16. Define Voltage regulation. Explain the two methods used to determine voltage
regulation of alternators.
➢ The voltage regulation of an alternator is defined as the rise in voltage when full
load is thrown off, assuming field current and speed remaining the same.
➢ The percentage regulation is defined as the ratio of change in terminal voltage from
full load to no load terminal voltage.
% Regulation = * 100
ZS =
E0=
E0 =
% Regulation = * 100
Fig.4.35
b) The ampere turn or MMF method
39
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ This method of finding voltage regulation considers the opposite view to the
synchronous impedance method. It assumes the armature leakage reactance to be
additional armature reaction.
➢ Suppose the alternator is supplying full-load current Ia at operating voltage V and
p.f. cos ϕ lagging. The procedure for finding Voltage regulation for AT method is as
under:
(i) From the O.C.C., field current OA required to produce the operating load
voltage V (or V + IaRa cos ϕ) is determined [See Fig. (4.36)]. The field current OA
is laid off horizontally as shown in Fig. (4.36).
(iv) This method gives a regulation lower than the actual performance of the
machine. For this reason, it is known as Optimistic Method.
c) Zero power factor method or portier method:
➢ This method is based on the separation of armature leakage reactance drop and
the armature reactance effect.
➢ The experimental data required are, no load curve, full load zero power factor curve
also called wattles load characteristics.
40
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ It is the curve of terminals volts against excitation, when armature is delivering full
load current at zero pf. The reduction in voltage due to armature reaction is found
from the above.
➢ Voltage drop due to armature leakage reactance XL is found from both by
combining these two, E0 can be calculated if we vectorially add to V the drop due to
resistance and leakage reactance XL. We get E.
➢ If to E is further added the drop due to armature reaction then we get E0.
➢ The zero power factor lagging curves can be obtained.
➢ If a similar machine is available this may be driven at no load as a synchronous
motor at practically zero pf or by adding alternator with pure reactors.
➢ By connecting the alternator with pure reactors.
➢ By connecting the alternator to a three phase line with ammeter and wattmeter
connected for measuring current and power.
➢ By so adjusting the field current that we get full load armature current with zero
wattmeter reading.
➢ Point B was obtained when wattmeter was reading zero.
➢ Point A is obtained from short circuit test with full load armature current.
➢ Hence OA represents field current which is equal and opposite to the
demagnetizing armature reaction ands for balancing.
% Regulation = *100
Procedural Steps
➢ Suppose we are given V the terminal Voltage.
➢ We will be given or else we can calculate Armature leakage reactance XL and hence
can calculate IXL.
➢ Adding IXL vectorially to V, we get voltage E.
➢ We will next find N-L curves, field excitation for voltage E. Let it be If1.
41
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
SYNCHRONOUS MOTOR
17. Explain briefly principle operation of synchronous motor?
➢ Consider a 3-phase synchronous motor having two rotor poles NR and SR. Then the
stator will also be wound for two poles NS and SS. The motor has direct voltage
applied to the rotor winding and a 3-phase voltage applied to the stator winding.
➢ The stator winding produces a rotating field which revolves round the stator at
synchronous speed NS (= 120 f/P). The direct (or zero frequency) current sets up a
two-pole field which is stationary so long as the rotor is not turning.
➢ Thus, we have a situation in which there exists a pair of revolving armature poles
(i.e., NS - SS) and a pair of stationary rotor poles (i.e., NR-SR).
➢ Suppose at any instant, the stator poles are at positions A and B as shown in Fig.
(4.38 (i)). It is clear that poles NS and NR repel each other and so do the poles SS
and SR.
➢ Therefore, the rotor tends to move in the anti- clockwise direction. After a period of
half-cycle (1/2 f = 1/100 second), the polarities of the stator poles are reversed but
the polarities of the rotor poles remain the same as shown in Fig. (4.38 (ii)).
42
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ Now SS and NR attract each other and so do NS and SR. Therefore, the rotor tends
to move in the clockwise direction.
➢ Since the stator poles change their polarities rapidly, they tend to pull the rotor
first in one direction and then after a period of half-cycle in the other. Due to high
inertia of the rotor, the motor fails to start.
➢ Hence, a synchronous motor has no self-starting torque i.e., a synchronous motor
cannot start by itself.
➢ If the rotor poles are rotated by some external means at such a speed that they
interchange their positions along with the stator poles, then the rotor will
experience a continuous unidirectional torque.
➢ Suppose the stator field is rotating in the clockwise direction and the rotor is also
rotated clockwise by some external means at such a speed that the rotor poles
interchange their positions along with the stator poles.
➢ Suppose at any instant the stator and rotor poles are in the position shown in Fig.
(4.39 (i)). It is clear that torque on the rotor will be clockwise.
➢ After a period of half-cycle, the stator poles reverse their polarities and at the same
time rotor poles also interchange their positions as shown in Fig. (4.39 (ii)).
➢ The result is that again the torque on the rotor is clockwise. Hence a continuous
unidirectional torque acts on the rotor and moves it in the clockwise direction.
➢ Under this condition, poles on the rotor always face poles of opposite polarity on
the stator and a strong magnetic attraction is set up between them.
43
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ This mutual attraction locks the rotor and stator together and the rotor is virtually
pulled into step with the speed of revolving flux (i.e., synchronous speed).
➢ If now the external prime mover driving the rotor is removed, the rotor will
continue to rotate at synchronous speed in the clockwise direction because the
rotor poles are magnetically locked up with the stator poles.
➢ It is due to this magnetic interlocking between stator and rotor poles that a
synchronous motor runs at the speed of revolving flux i.e., synchronous speed.
18. Explain the operation of torque equation of synchronous motor.
➢ Except for very small machines, the armature resistance of synchronous motor is
negligible as compared to its synchronous reactance.
➢ Hence, the equivalent circuit for the motor becomes as shown in Fig. 4.40 (a). From
the phasor diagram of Fig. 4.40 (b). It is seen that
……………………..(1)
……………..(2)
……………(3)
Pin =
Now
Since stator Cu losses have been neglected, Pin also represents the gross
mechanical power (Pm) developed by the motor.
44
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
= N—m
Ns in rpm.
19. Discuss the methods of starting and procedure for starting synchronous
motor.
45
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ Once the rotor attains the synchronous speed, the d.c. excitation to the rotor is
switched on.
➢ Once the synchronism is established pony motor is decoupled.
➢ The motor then continues to rotate as synchronous motor.
2. Using Damper Winding
➢ In a synchronous motor, in addition to the normal field winding, the additional
winding consisting of copper bars placed in the slots in the pole faces.
➢ The bars are short circuited with the help of end rings. Such an additional winding
on the rotor is called damper winding.
➢ This winding as short circuited, acts as a squirrel cage rotor winding of an
induction motor. The schematic representation of such damper winding is shown
in the Fig.4.41.
46
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
47
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ Many a times, a large synchronous motor is provided with a coupled d.c. machine.
This machine is used as a d.c. motor to rotate the synchronous motor at a
synchronous speed.
➢ Then the excitation to the rotor is provided. Once motor starts running as a
synchronous motor, the same d.c. machine acts as a d.c. generator called exciter.
The field of the synchronous motor is then excited by this exciter itself.
20. Explain V and inverted V curves.
➢ Excitation can be increased by increasing the field current passing through the
field winding of synchronous motor.
➢ If the graph of armature current drawn by the motor (Ia) against field current (If) is
plotted, then its shape looks like English alphabet letter V.
➢ If such graphs are obtained at various load conditions we get family of curves, all
looking like V. such curves are called as V-curves of synchronous motor.
48
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
Observation table:
S.No VL (V) IL (A) W1(W) W2(W) (If) excitation(A)
1
2
3
Now IL = Ia , per phase value can be determined, from the stator winding
connections.
cos ɸ =
Result table:
50
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
The speed at which the revolving flux rotates is called synchronous speed Ns and is
given by
9. Write an expression for the slip of an induction motor. Define slip of induction
motor. (NOV/DEC 2010) (NOV/DEC 2013) (NOV/DEC 2012)
Slip of an induction motor is the speed difference between synchronous speed and
motor speed expressed as percentage of synchronous speed.
Where,
15. Write down the condition to get maximum torque under running condition?
(APR/MAY 2016) (NOV/DEC 2015)
The rotor resistance and rotor reactance should be equal for developing maximum
torque
i.e.
Where s is the slip–under running conditions.
and X2 are the rotor resistance and reactance.
16. What are the advantages and disadvantages of three phase induction
motor?(MAY 2018)
Advantages:
➢ It has simple and rugged construction.
➢ It is relatively cheap.
➢ It requires little maintenance.
➢ It has high efficiency and reasonably good power factor.
➢ It has self-starting torque.
Disadvantages:
➢ It is essentially a constant speed motor and its speed cannot be changed easily.
➢ Its starting torque is inferior to a d.c. shunt motor.
17. What are the applications of three phase induction motors?
52
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
53
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
54
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
55
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
34. List the applications of single phase induction motors? (APR/MAY 2011)
Some of the common applications of single phase induction motor are
➢ Motor of refrigerator
➢ Water pump motor
➢ Cooler motor
➢ Drilling machines
➢ Small fans
➢ Used in small toys, hair dryers, ventilators, clock etc.
35. What are the advantages of retaining the capacitor in the circuit?
➢ It improves the running torque.
➢ It improves the overall power factor of the motor.
36. Mention the applications of split phase induction motor.
➢ Fans,
➢ Blowers,
➢ Centrifugal pumps,
➢ Washing machine,
➢ Grinder,
➢ Lathes,
➢ Air conditioning fans, etc.
37. List out the applications of capacitor start capacitor run induction motor.
➢ Conveyors,
➢ Grinder,
➢ Air conditioners,
➢ Compressor, etc.
38. State the application of shaded pole motor.
56
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
➢ Hair dryers,
➢ Toys,
➢ Record players,
➢ Small fans,
➢ Electric clocks etc.
39. State the limitations of shaded pole motors. [APRIL/MAY-2015]
➢ Starting torque is poor
➢ Power factor is very low.
➢ Due to copper losses in the shading ring the efficiency is very low.
➢ Speed reversal is very difficult
➢ Size and power rating is very small.
44. What are the two types of synchronous machines? (OR) What are the types of
rotor in alternator
The classification synchronous machines are:
➢ Salient pole or projecting pole rotor type
➢ Non-salient pole or Cylindrical rotor type
45. Why the stator core is laminated? (APR/MAY 2011)
Stator core is laminated to reduce the eddy currents loss.
57
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
46. How can you distinguish between the two types of large synchronous generator
from their appearance?
S.NO Salient Pole Type Smooth Cylindrical Type
1 Poles are projecting out from the surface Poles are non-projecting
2 Air gap is non-uniform Air gap is uniform
3 Large diameter and small axial length Small diameter and large axial length
4 Mechanically weak Mechanically strong
5 Preferred for low speed alternator Preferred for high speed alternator
47. What are the advantages of salient pole type of construction used for
synchronous machines?
➢ They allow better ventilation.
➢ The pole faces are so shaped radial air gap length increases from the pole center to
the pole tips so that flux distribution in the air gap is sinusoidal in shape which
will help to generate sinusoidal emf.
➢ Due the variable reluctance, the machine develops additional reluctance power,
which is independent of excitation.
48. Write the emf equation of the synchronous generator (OR) alternator.
Emf per phase 4.44fɸ
Where, f = frequency of supply in Hz,
ɸ = flux per pole in wb,
Tph= turns per phase,
Kp = Pitch factor,
Kd = distribution factor.
49. Define voltage regulation.
The percentage regulation is defined as the ratio of change in terminal voltage from
full load to no load terminal voltage.
% Regulation = * 100
58
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – III: AC ROTATING
MACHINES
SYNCHRONOUS MOTOR
52. What is a synchronous motor?
A synchronous electric motor is an AC motor which, at steady state, the rotation of
the shaft is synchronized with the frequency of the supply current; the rotation period
is exactly equal to an integral number of cycles.
53. What are the advantages of synchronous motor?[APRIL/MAY 2011]
➢ The speed is constant and independent of load.
➢ These motor usually operate at higher efficiencies.
➢ Electromagnetic power varies linearly with the voltages.
54. What are the disadvantages of synchronous motor?
➢ Higher cost.
➢ Necessity of a DC excitation source.
➢ Greater initial cost
➢ High maintenance cost.
55. Give the torque equation of a synchronous motor.
The torque developed by the motor is,
60
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
UNIT-IV
1
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
MEASUREMENT:
A measurement of any quantity either physical or electrical gives meaning when it is
compared with predefined standard quantity.
The basic requirements of the measurement:
❖The standard used for comparison purposes must be accurately defined and should be
commonly accepted.
❖The apparatus used and the method must be provable.
The two methods of measurement are:
❖Direct method
❖Indirect method
Direct method of measurement:
The unknown quantity which is known as measurand is directly compared against a
standard. The result is expressed as a numerical number and unit.
Indirect method of measurement:
The unknown quantity is converted into some other form and then it is compared
against a standard.
The types of measurement are:
❖Primary measurement
❖Secondary measurement
❖Tertiary measurement
Primary measurements:
Primary measurements are direct method of measurements without involving conversion
of the measured quantity. E.g.: measurement of length of a bar using scale.
Secondary measurements:
Secondary measurements are the indirect method of measurements which involve one
conversion of the quantity to be measured. Eg: Measurement of pressure of manometers.
Tertiary measurements:
Tertiary measurements are the indirect method of measurements which involve two
conversions of the quantity to be measured.
2
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
• Here the variable conversion element and variable manipulation element are collectively
called as data conditioning element.
Data transmission element:
• The transmission of data from one another is done by the data transmission element.
• In case of space crafts the control signals are sent from the control stations by using radio
signals.
• The stage that follows the signal conditioning element and data transmission element
collectively is called the intermediate stage.
Data presentation element:
• The display or readout devices which display the required information about the
measurement, forms the data presentation element.
• The information of the measurand has to be conveyed for monitoring, control process.
✓ In case of data to be monitored, visual display devices are needed like ammeters,
voltmeters.
✓ In case of data to be recorded, recorders like magnetic tapes, TV equipment and storage
type CRT, printers are used.
• The final stage in a measurement system is known as terminating stage.
• When a control device is used for the final measurement stage, it is necessary to apply
some feedback to the input signal to accomplish the control objective.
Example: Bourdon tube pressure gauge
• Due to pressure, closed end of tube is displaced. Pressure is converted to displacement.
• The closed end is linked to mechanical linkage to a gearing arrangement.
• The gearing arrangement amplifies the small displacement and makes the pointer to
rotate through a large angle.
2. Discuss the static and dynamic characteristics of measuring instrument.(MAY
2018) (13 marks)
STATIC CHARACTERISTICS:
• The static characteristics of an instrument are, in general, considered for instruments
which are used to measure an unvarying process condition.
• All the static performance characteristics are obtained by one form or another of a process
called calibration.
• Desirable static characteristics are:
i. Accuracy
ii. Reproducibility
4
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
iii. Sensitivity
iv. Linearity
• Undesirable static characteristics are:
i. Drift
ii. Dead zone
iii. Static error
iv. Hysteresis
Accuracy:
• It is the degree of closeness of a measurement compared to true value.
• The accuracy of any instrument system is measured in terms of its error.
• It is the ability of instrument to indicate true value. It is calibration against a standard.
Static sensitivity:
• Static sensitivity is defined as the ratio of the magnitude of the output signal to the
magnitude of input signal to be measured.
• Low sensitivity meter produces more loading effect.
• Meter with high sensitivity will give more reliable result. Eg: Milli-ammeter, Galvanometer.
Linearity:
Fig 4.1
• The ability to produce the input characteristics symmetrically is known as Linearity.
• It can be expressed as straight line.
• It is a measure of maximum deviation of any one of the calibration points from straight
line which is drawn by using the method of least square from the given calibration data.
• Any departure from straight line relationship is known as non-linearity.
Reproducibility:
• It is defined as the degree of closeness with which a given value may be repeatedly
measured.
5
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
6
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
7
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
8
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
• Some of the reasons of the appearance of these errors are known but still some reasons
are unknown.
• Hence, we cannot fully eliminate these kinds of errors.
Sources of Errors:
• Noise
• Design limitations
• Weakening of measuring system.
Limiting Error:
• The accuracy and precision of an instrument depends upon its design, material used and
workmanship. The choice depends upon accuracy.
• The manufacturer has to specify the deviations from the nominal value of a particular
quantity.
• The limits of these deviations from specified value are defined as Limiting errors.
• Absolute error is the difference between true value and measured value of a company.
• Relative error is defined as the ratio of the error to the specified magnitude of a quantity.
CLASSIFICATION OF STANDARDS:
• International standards
• Primary standards
• Secondary standards
• Working standards
International standards of instruments:
10
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
International standards are defined on the basis of International agreement. They are
regularly evaluated and checked by absolute measurements in terms of fundamental
units. The standardized units are:
1) International ohm.
2) International amperes.
Primary standards:
• They are maintained at National standards laboratories in different countries.
• The function of primary standards is the calibration and verification of secondary
standards.
• The standardized units are:
✓ Quite stable.
✓ Independent.
✓ Invariant.
• The following points are considered in primary standards:
✓ Accuracy of machining.
✓ Rigidity of construction.
✓ Low temp Coefficient.
Secondary standards:
• They are basic reference standards used by measurement and calibration laboratories in
industries.
• Each laboratory sends its secondary standards to national standard laboratory standard
for calibration and compare with primary standards.
• Then the secondary standards are sent back to the industrial user by the national
laboratories with a certification as regards their measured value in terms of primary
standards.
Working standards:
• These standards are used to check and calibrate laboratory instrument for accuracy and
performance.
5. Give an introduction about measuring instruments.
Electrical instruments may be divided into two categories, which are,
i. Absolute instruments
ii. Secondary instruments
11
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
12
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
SPRING CONTROL:
• When the pointer is deflected one spring unwinds itself while the other is twisted.
• This twist in the spring produces restoring (controlling) torque, which is proportional
to the angle of deflection of the moving systems.
GRAVITY CONTROL:
• In gravity controlled instruments, a small adjustable weight is attached to the spindle
of the moving system such that the deflecting torque produced by the instrument has
to act against the action of gravity.
• Thus a controlling torque is obtained.
• This weight is called the control weight.
• Another adjustable weight is also attached in the moving system for zero adjustment
and balancing purpose. This weight is called balance weight.
Where, Kg is a constant.
13
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
DAMPING TORQUE:
• Due to inertia, pointer moves from point ‘a’ to point ‘b’.
• This action produces oscillations and pointer will take some amount of time for
settling.
• To damp or to make these oscillations disappear some force or torque is required, this
torque is called damping torque.
• This damping torque is produced by any one of the four damping system.
Air friction damping:
✓ Aluminum piston attached to the spindle moves over the air chamber produces
damping by air friction.
Fluid friction damping:
✓ In this type oil is used instead of air because viscosity of oil is greater.
✓ A disc attached to the moving system is dipped into the oil pot.
✓ The disc moves in the oil and produces friction drag.
✓ This produces damping.
Eddy current damping:
✓ A conductor is attached to the moving system and made to move in the magnetic field
produced by a permanent magnet.
✓ The conductor is aluminium circular disc.
14
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
✓ When the moving system oscillates, the disc moves and cuts the magnetic flux.
✓ An emf is induced in the disc, since the disc has several closed path, a current flows.
This current is called eddy current.
✓ This eddy current interacts with the magnetic field, produces a torque which opposes
the spindle motion.
✓ This type of damping is called eddy current damping.
Electromagnetic damping:
✓ The deflecting system makes the coil to move in a magnetic field, produces a torque
which produces the current in the coil.
✓ By lenz law, this current produces a torque which opposes the movement of the coil,
and damps the oscillations of the moving system.
✓ This is called electromagnetic damping.
6. Explain the working of permanent magnet moving coil.
• The principle operation of PMMC is based upon the principle of “current carrying
conductor is placed in a magnetic field it is acted upon by the force which tends to
move it.”
Construction:
• A coil of thin wire is mounted on an aluminium spindle positioned between the poles
of a U shaped permanent magnet which is made up of magnetic alloys like alnico.
• The coil is pivoted on the jewel bearings and thus the coil is free to rotate.
Operation:
• When a current flows through the coil, it generates a magnetic field which is
proportional to the current in case of an ammeter.
• The deflecting torque is produced by the electromagnetic action of the current in the
coil and the magnetic field.
• The controlling torque is provided by two phosphor bronze hair springs.
• Damping is caused by the current set up in the aluminium coil which prevents the
oscillation of the coil.
Torque equation
Where,
Tc= controlling torque in N-m
KS= spring constant in Nm/rad or Nm/deg.
θ = angular deflection in rad or degree.
• For the final steady deflection i.e at equilibrium:
Tc= Td
Ks θ= GI
….. (2)
• Electrical energy supplied is given by, multiply I.dt on both the sides of the equation
(2),
…..(3)
19
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
…..(5)
20
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
Fixed coil:
• Fixed coils are wound with heavy wire with less number of turns in order to have low
resistance and hence low voltage drop across the meter.
• It is also called as current coil which is connected in series with the load and properly
laminated in order to avoid eddy current loss in conductor when heavy current flows.
Moving coil:
• It is generally attached to the spindle which is connected to the pointer. The moving
coil is also called as pressure coil.
• It is made up of thin wire and has more number of turns in order to have high
resistance.
Control torque:
• It is provided by springs.
Damping:
• Air friction damping is used.
Pointer and scale:
• Mirror type scale and knife edge pointer to avoid parallax error while reading.
Torque equation:
21
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
22
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
23
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
24
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
25
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
26
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
27
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
10. Explain the construction and working principle of single phase induction
type energy meter. Write short notes on any 2 adjustments required in energy
meter. (Nov/Dec 2009, May/June 2014,2017) (Nov/Dec 2018)
• Energy meter is an instrument used to measure the total power consumed over a
specific interval of time. Unit of energy is Kwh.
• Energy= power * time
• Energy meter is an integrating type of instrument which measures the energy
consumed when power is delivered at an average rate of 1000 watts for one hour.
Basic principle:
• It is an integrating type instrument which works on the principle of induction. i.e.,
in this type of instrument, alternating fluxes are produced because of 1φ AC supply.
• These alternating fluxes induce the generation of eddy current in the moving system
which interacts with each other to produce a driving torque which causes the aluminium
disc to rotate and thus records the energy.
Constructional details:
• The four main parts of induction type of energy meter are:
➢ Driving system
➢ Moving system
➢ Braking system
➢ Registering system
Driving system:
• The driving system of the energy meter consists of two electromagnets whose core
is made up of silicon steel laminations.
• The coil of one of the electromagnets which is excited by the load current is called
as current coil and the corresponding electromagnet is called as series magnet.
28
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
• The coil of the second electromagnet which is connected across the supply is
called pressure coil and the corresponding electromagnet is called shunt magnet.
Moving system:
• The moving system consists of aluminium disc mounted on a light alloy shaft.
• The disc is positioned in the air gap between the series and shunt magnets.
• The moving system is connected to a hardened steel pivot which is screwed to the
foot of the shaft.
• In this type of energy meter as there is no controlling torque, continuous
rotation of the disc is produced due to driving torque only.
Braking system:
• The braking system consists of permanent magnet positioned near the edge of the
aluminium disc.
• The aluminium disc moves in the field of this magnet and thus provides a braking
torque.
Registering system:
• The function of a registering or counting mechanism is to record continuously a
number which is proportional to the revolutions made by the moving system.
Principle of operation:
• When the pressure coil wound on the shunt magnet is connected across the supply
voltage, it carries a current IP proportional to the supply voltage, thus producing an
alternating flux φP.
29
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
• As this flux φP is alternating in nature, it indicates an emf Eep in the disc which
in turn produces eddy current Iep.
• When the current coil wound on the series magnet carries the load current I,
it produces an alternating flux φe.
• This flux φc induces an emf Eec in the disc which in turn produces eddy current
Iec.
• Now the eddy current Iep interacts with φc and produces a torque T1.
• Similarly the eddy current Iec interact with φP and produces another torque T2.
As these torques are in the opposite direction, the net torque is the difference of the above
two torques.
Let
V= supply voltage
Ip= current through the pressure coil which is proportional to supply voltage. I= load
current.
Φ= phase angle of load.
Φp= flux produced by the current through P.C Φc= flux produced by the current through
C.C
• Since Φ is the phase angle of load, load current I lags the supply voltage by the
angle Φ.
• However ΦP will be in phase with IP, as Φp is the flux produced due to current IP.
• Similarly ΦC will be in phase with I, as ΦC is the flux produced due to load current
I. Let,
T1= ΦCIepcos( angle between ΦC and Iep)
T1= ΦCIepcos(90°+90°-φ) .............................................................. (2)
T1= ΦCIepcos(180°-φ)
T2= ΦPIeccos( angle between ΦPand Iec)
T2= ΦPIeccosφ ....................................................................................... (3)
Net driving torque, 𝑇𝑑 𝖺 𝑇2 − 𝑇1
Hence 𝜑𝑃𝐼𝑒𝑐 − cos 𝜑 − 𝜑𝑐𝐼𝑒𝑝 cos(180° − 𝜑) ................................................ (4)
𝑇𝑑 𝖺 𝜑𝑃𝐼𝑒𝑐 cos 𝜑 + 𝜑𝑐𝐼𝑒𝑝 cos 𝜑 ........................................................(5)
We know that ,𝜑𝑃 𝖺 𝐼𝑃 𝖺 𝑉
31
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
11. Write short notes on two and three element energy meter.
32
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
33
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
carrying the current to be measured and therefore the primary current is dependent on
the load connected to the system whose current is to be measured.
• The secondary winding of the C.T is connected to a low range ammeter.
• In case of C.T the secondary current is less than the primary current.
• From the above equation it is clear that in order to decrease the secondary current
by 100 times, the secondary voltage should be increased by 100 times.
• If the turn’s ratio of C.T is known and the meter reading is known, the actual high
line current value can be determined.
35
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
Potential transformers:
• The primary winding is connected across the high voltage line whose voltage is to
be measured and the secondary is connected to the low range voltmeter coil.
• One end of the secondary winding is always grounded for safety purpose.
36
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
• As seen in the above figure, at first digital storage oscilloscope digitizes the analog
input signal, then the analog input signal is amplified by amplifier if it has any weak
signal.
• After amplification, the signal is digitized by the digitizer and that digitized signal
stores in memory.
• The analyzer circuit process the digital signal after that the waveform is
reconstructed (again the digital signal is converted into an analog form) and then that
signal is applied to vertical plates of the cathode ray tube (CRT).
• The cathode ray tube has two inputs they are vertical input and horizontal input.
• The vertical input signal is the ‘Y’ axis and the horizontal input signal is the ‘X’ axis.
• The time base circuit is triggered by the trigger and clock input signal, so it is going
to generate the time base signal which is a ramp signal.
• Then the ramp signal is amplified by the horizontal amplifier, and this horizontal
amplifier will provide input to the horizontal plate.
• On the CRT screen, we will get the waveform of the input signal versus time.
Working Principle
• The working principle of a Digital Storage Oscilloscope (DSO) is based on digitizing
and storing the input signals with the help of CRT (Cathode Ray Tube) and digital
memory.
• The process of digitization is the sampling of input signals at different periodic
signals.
• Here, the signal’s maximum frequency measured by the DSO depends on 2 factors,
37
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
• In linear interpolation, the dots are connected together by a straight line. It can be
used in pulsed or square wave generation but not in case of sinusoidal waves.
• In sinusoidal interpolation, the dots are connected so as to form sinusoidal
waveform. But it is not suitable for square or pulse waves.
38
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
TWO MARKS
➢ Dead zone
10. Write the main static characteristics.
➢ Accuracy
➢ Reproducibility
➢ Sensitivity
➢ Drift
➢ Static error
➢ Dead zone
➢ Resolution
40
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
RESOLUTION THRESHOLD
R0-observed reading
24. What are different types of errors in measurement system. (MAY 2018).
➢ Gross Errors
➢ Systematic Errors
(i) Instrumental Errors
(ii) Environmental Errors
(iii) Observational Errors
➢ Random errors
25. What are the reasons for gross errors?
➢ Incorrect adjustment
➢ Misreading of instrument scale
➢ Incorrect recording of experimental data
➢ Parallax error
26. What are the reasons for instrumental errors?
➢ Inherent short comings in an instrument
➢ Misuse of instrument
➢ Loading effect
27. How can we reduce the environmental errors?
➢ Air-conditioning
➢ Shielding
➢ Proper earthing
➢ Spring mounting
28. What are the causes for random errors?
➢ Hysteresis in elastic members
➢ Backlash in the movement
➢ Mechanical vibrations
29. What are the sources of errors?
➢ Energy exchanged by interaction
➢ Noise
➢ Design limitations
➢ Deterioration of measuring system.
30. Define backlash.
• It is defined as the maximum distance through which a part of the mechanical
system can be moved in one direction without applying appreciable force or motion
42
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
43
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
• If the instrument is connected to AC, the pointer cannot follow the rapid reversals
and the deflection corresponds to mean torque, which is zero.
• So these instruments cannot be used for AC.
37. Which type of instruments is called universal instrument?
The moving iron instruments are known as universal instruments, because these
instruments can be used for both AC and DC.
38. What are the errors occurring in MI (MOVING IRON) instruments?
➢ Hysteresis error
➢ Temperature error
➢ Stray magnetic field error
➢ Frequency error due to reactance of instrument coil and eddy currents.
39. What are the advantages and disadvantages of MI Instruments?
Advantages:
➢ Universal use – Suitable for the measurement of both AC and DC
➢ Less friction loss hence high torque / weight ratio
➢ Cheapness – A single type moving element could cover entire range of current
➢ Robustness – Simple and rugged construction because there is no current
Carrying moving parts.
➢ Accuracy – Capable of giving good accuracy like 2%
Disadvantages:
➢ Scale – The scale of MI instrument is not uniform and is cramped at the lower end
and therefore accurate readings are not possible at this end.
➢ Errors – these instrument are subjected to serious errors due to hysteresis,
frequency changes and stray magnetic field
➢ Difference u AC and DC calibrations – there is a difference between DC and AC
calibrations on account of effect of inductance and eddy currents when the meter is
used on AC. Hence they must be calibrated for frequency at which they are used.
40. What are the main types of instrument used as ammeters and voltmeters?
➢ Permanent magnet moving coil
➢ Moving Iron
➢ Electrodynamometer
➢ Hot wire
➢ Thermocouple
➢ Induction
44
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
➢ Electrostatic
➢ Rectifier
41. Write and explain the torque equation of moving coil.
Where
Where
𝐾 − 𝑠𝑝𝑟𝑖𝑛𝑔𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
For final steady state condition
𝑇𝑐= 𝑇𝑑
𝐺𝐼 = 𝐾𝜃
Final Deflection,
Current,
42. What are the operating forces needed for indicating instruments?
i)Deflecting force:
The force required for moving the pointer from its zero position
ii)Controlling force:
The force required to bring the pointer to final steady state position without over shoot
and to bring back the pointer to zero when deflecting force is absent.
iii)Damping force:
The force required to bring the pointer to final steady state position quickly without
oscillations.
43. What are the control systems used for producing control force?
➢ Gravity control
➢ Spring Control
44. What are the advantages of spring control over gravity control?
Advantages:
➢ Gravity control can be used only in vertically mounted instruments
➢ The scale used in gravity control type instruments is cramped at the lower end.
Hence not uniform.
45. What are the damping systems used in instrument?
➢ Air friction damping
45
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
46
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – IV: MEASUREMENTS AND
INSTRUMENTATION
➢ Damping torque
53. List the measuring instruments you known.
➢ Permanent Magnet Moving Coil (PMMC) instrument
➢ Permanent Magnet Moving Iron (PMMI) instrument
➢ Dynamometer type wattmeter
➢ Energy meter
54. Why we need damping device in indicating instruments?
• Damping device is mainly used to prevent oscillation of the moving system and
enable the latter to reach its final position quickly.
55. Compare moving coil and moving iron instruments based on any two salient
features.
48
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
UNIT-V
1
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
2
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Generating station:
In the generating station, electric power is produced by 3-phase alternators.
The usual generation voltage is 11 kV.
The generation voltage is stepped-up to 220 KV at the generating station with help of
3-phase transformers.
Advantages of high voltage transmission:
The saving of conductor material
High transmission efficiency
Disadvantages of high voltage transmission:
It introduces insulation problems
The cost of switchgear and transformer equipment is increased
The primary transmission is carried at 66 KV, 132 KV, 220 KV, 400 KV or 765 KV.
The highest transmission voltage adopted for power transmission in India is 765 KV.
Primary transmission:
The electric power at 220KV is transmitted by 3-phase, 3-wire overhead system. This
forms the primary transmission.
Secondary transmission:
The primary transmission line terminates at the receiving station (RS).
At the receiving station, the voltage is reduced to 33 KV by step-down transformers.
From this station, electric power is transmitted at 33 KV by 3-phase, 3-wire overhead
system to various sub-stations (SS). This forms the secondary transmission.
Primary distribution:
The secondary transmission line terminates at the sub-station (SS), where voltage is
reduced from 33 kV to 6.6 KV by step-down transformer.
The 6.6KV lines run along the important road sides of the city. This forms the primary
distribution.
Big consumers (>50 kW) are supplied power at 6.6KV with their own sub-stations.
Secondary distribution:
The electric power from primary distribution line (6.6KV) is delivered to distribution
sub-stations (DS).
These distribution sub-stations are located near the consumer localities.
Here, step down the voltage to 400 V, 3-phase, 4-wire for secondary distribution.
The voltage between any two phases is 400 V and between any phase and neutral is
230 V.
3
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The single-phase residential lighting load is connected between any one phase and
neutral.
3-phase, 400V motor load is connected across 3-phase lines directly.
The secondary distribution system consists of feeders, distributors and service
mains.
2. DISTRIBUTION SYSTEM:
The part of power system which distributes electric power for local use is known as
distribution system.
In general, the distribution system is the electrical system between the sub-station fed
by the transmission system and the consumer’s meters.
It generally consists of feeders, distributors and the service mains.
Fig. 1.2 shows the elements of low voltage distribution system.
Feeders:
A feeder is a conductor which connects the sub-station (or localized generating station)
to the area where power is to be distributed.
Generally, no tapings are taken from the feeder so that current in it remains the same
throughout.
The main consideration in the design of a feeder is the current carrying capacity.
Distributor:
A distributor is a conductor from which tapping’s are taken for supply to the
consumers. In Fig. 1.2, AB, BC, CD and DA are the distributors.
The current through a distributor is not constant because tappings are taken at
various places along its length.
4
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
While designing a distributor, voltage drop along its length is the main consideration
since the statutory limit of voltage variations is ± 6% of rated value at the consumer’s
terminals.
Service mains:
The service mains are generally a small cable which connects the distributor to the
consumers’ terminals.
5
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Advantages:
Simplest.
The initial cost is low.
Useful when the generation is at low voltage.
Preferred when the station is located at centre of the load.
Disadvantages:
The end of distributor near to the substation gets heavy loaded.
When load on the distributor changes, the consumer faces serious voltage
fluctuations.
As consumers are dependent on single feeder and distributor, a fault on any of these
two causes interruption in supply.
Drawbacks:
A distributor nearest to the substation is heavily loaded.
Due to load variation, voltage fluctuations are more at the far ends.
If any fault occurs, there is no continuity of supply.
The feeder in the ring fashion is divided into number of sections as AB, BC, CD, DE and
EA.
The various distributors are connected at A, B, C, D and E.
Each distributor is supplied by the two feeders.
7
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Advantages:
Due to load variations, the voltage fluctuation is less at the far end.
Better reliability.
It gives continuity of supply, when fault occurs at any one distributor.
Interconnected system:
When the feeder ring is energized by two or more than two generating stations or
substations is called as interconnected system.
Advantages of Interconnected System:
Better reliability.
During peak load, reserve power capacity reduces and efficiency increases.
It gives continuity of supply.
4. AC DISTRIBUTION SYSTEM:
8
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
It is that part of AC distribution system which operates at voltages higher than general
utilization.
It handles large blocks of electrical energy than the average low voltage consumer uses.
The voltage used for primary distribution depends upon the amount of power to be
conveyed and the distance of the substation required to be fed.
The most commonly used primary distribution voltages are 11 kV, 6·6 kV and 3·3 kV.
Due to economic considerations, primary distribution is carried out by 3- phase, 3-wire
system.
Electric power from the generating station is transmitted at high voltage to the
substation located in or near the city.
9
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
10
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
6. EARTHING:
The process of connecting the metallic frame (i.e., non- current carrying part) of
electrical equipment or some electrical part of the system (e.g., neutral point in a star-
connected system) to the earth is called grounding or Earthing.
The potential of the earth is to be considered zero for all practical purposes.
Earthing is to connect any electrical equipment to earth with a very low resistance wire,
making it to attain earth’s potential.
This ensures safe discharge of electrical energy due to failure of the insulation line
coming in contact with the casing, etc.
Earthing brings the potential of the body of the equipment to zero i.e., to the earth’s
potential, thus protecting the operating personnel against electrical shock.
11
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Necessity of Earthing:
The requirement for provision of earthing can be listed as follows:
To protect the operating personnel from the danger of shock.
To maintain the line voltage constant, under unbalanced load condition.
To avoid risk of fire due to earth leakage current through unwanted path.
Protection of the equipments.
Protection of large buildings and all machines fed from overhead lines against lighting.
Methods of Earthing:
The various methods of earthing in common use are,
(a) Plate earthing
12
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Earth electrode made of a GI (galvanized iron) pipe of 38mm in diameter and length of
2m (depending on the current) with 12mm holes on the surface is placed upright at a
depth of 4.75cm in a permanently wet ground.
13
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
To keep the value of the earth resistance at the desired level, the area (15 cm)
surrounding the GI pipe is filled with a mixture of salt and coal.
The efficiency of the earthing system is improved by pouring water through the funnel
periodically.
The GI earth wires of sufficient cross-sectional area are run through a 12.7mm
diameter pipe (at 60cm below) from the 19mm diameter pipe and secured tightly at the
top as shown in figure (5.10).
14
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The length of the conductor buried in the ground would give a sufficient earth
resistance and this length should not be less than 15m.
The electrodes shall be as widely distributed as possible in a single straight or circular
trenches radiating from a point.
This type of earthing is used where the earth bed has a rocky soil and excavation work
is difficult.
Selection of Earthing:
The type of earthing to be provided depends on many factors such as type of soil, type
of installation, etc.
The following table helps in selecting a type of earthing for a particular application.
Earth Resistance:
The earth resistance should be kept as low as possible so that the neutral of any
electrical system, which is earthed, is maintained almost at the earth potential.
The earth resistance for copper wire is 1Ω and that of GI wire less than 3Ω.
The typical value of the earth resistance at large power stations is 0.5Ω , major
substations is 1Ω, small sub stations is 2 Ω and in all other cases 5Ω.
The resistance of the earth depends on the following factors:
Condition of soil.
Moisture content of soil.
Temperature of soil.
15
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
16
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
b) Materials:
Materials used are tin lead or silver having low melting points. Use of copper or iron is
dangerous, though tinned copper may be used.
c) Types of Fuses:
Fuses are classified into following types,
1. Re-wireable or kit-Kat fuse
2. High rupturing capacity (H.R.C) cartridge fuse
1. Re-wireable or Kit-Kat Fuse:
Re-wireable fuse is used where low values of fault current are to be interrupted.
These fuses are simple in construction, cheap and available up to a current rating of
200A.
They are erratic in operation and their performance deteriorates with time.
An image of re-wireable fuse is as shown in figure (5.12)
When a fault occurs, the current increases and the fuse element melts before the fault
current reaches its first peak.
The heat produced in the process vaporizes the melted silver element.
The chemical reaction between the silver vapours and the filling powder results in the
formation of a high resistance substance which helps in quenching the arc.
8. CIRCUIT BREAKER:
Electrical circuit breaker is a switching device which can be operated manually and
automatically for the controlling and protection of electrical power system, respectively.
During shirt circuits fault or any other type of electrical fault, these equipments, as
well as the power network, suffer a high stress of fault current, which in turn damage
the equipment and networks permanently.
For saving these equipment and the power networks, the fault current should be
cleared from the system as quickly as possible.
Again after the cleared, the system must come to its normal working condition as soon
as possible for supplying reliable quality power to the receiving ends.
The circuit breaker is the special device all the required switching operations during
current carrying condition.
18
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
A circuit breaker essentially consists of fixed and moving contacts, called electrodes.
Under normal operating conditions, these contacts remain closed and will not open
automatically until and unless the system becomes faulty.
The contacts can be opened manually or by remote control whenever desired.
When a fault occurs in any part of the system, the trip coils of the breaker get
energized and the moving contacts are pulled apart by some mechanism, thus opening
the circuits.
The main types of circuit breakers are,
Miniature circuit breakers (MCB)
Molded Case Circuits Breakers (MCCB)
Earth leakage circuit breakers (ELCB) or Residual Current Breaker (RCCB)
Air blast Circuits Breaker (ACB)
Vacuum Circuits Breaker (VCB)
SF6 Circuits Breaker.
9. MINIATURE CIRCUIT BREAKERS (MCB)
Minimum circuit breakers are electromechanical devices which protect an electrical
circuit from over currents.
Over currents in an electrical circuit may results from short circuits overload, or faulty
design.
MCB is better alternative than fuse, since it does not require replacement once an
overload is detected.
MCB functions by interrupting the continuity of electrical flow through the circuits
once a fault is detected.
In simple terms, MCB is a switch which automatically turns off when the current
flowing through it passes the maximum allowable limit.
Generally MCB is designed to protect against over current and over temperature faults
(over heating).
Working Principle:
There are two contacts - one is fixed and the other is moveable.
When the current exceeds the predefined limit, a solenoid forces the moveable contact
to open (i.e., disconnect from the fixed contact) and the MCB turns off, thereby
stopping the current from flowing in the circuits.
19
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Operation:
An image of MCB is shown in figure (5.15) and internal parts of an MCB are shown in
figure (5.16).
It mainly consists of one bi- metallic strip, one trip coil and one hand operated on-off
lever.
Electric current carrying path of a MCB is as follows - first left hand side power
terminal-then bimetallic strip - then current coil - then moving contact - then fixed
contact and lastly right hand side power terminal, and all are arranged in series.
20
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The current coil or trip coil placed in such a manner that during SC faults, the MMF of
that coil causes its plunger to hit the same latch point and force the latch to be
displaced. Hence, the MCB will open in the same manner.
Again when operating lever of the MCB is operated by hand, that means when we
make the MCB at off position manually, the same latch point is displaced as a result
moving contact separated from fixed contact in same manner.
So, whatever may be the operating mechanism, i.e., may be due to deformation of bi-
metallic strip or may be due to increased MMF of trip coil or may be due to manual
operation - actually the same latch point is displaced and the deformed spring is
released, which is ultimately responsible for movement of the moving contact.
When the moving contacts are separated from fixed contact, there may be a high
chance of arc.
This are then goes up thorough the arc runner and enters into arc splitters and is
finally quenched.
When we switch on the MCB, we actually reset the displaced operating latch to its
previous on position and make the MCB ready for another switch off or trip operation.
These are available in single pole, double pole, triple pole, and four pole versions with
neutral poles, if required.
The normal current ratings are available from 0.5-63 A with a sym-metrical short
circuits rupturing capacity of 3-10kA, at a voltage level of 230/440v.
MCBs are generally designed to trip within 2.5 millisecond when an over current fault
arises.
In case of temperature rise or over heating it may take 2 seconds to 2 min for the MCB
to trip.
Advantages:
MCBs are replacing the re-wireable switch i.e., fuse units for low power domestic and
industrial applications.
The disadvantages of fuses, like low SC interrupting capacity (say 3kA), Etc, are
overcome with high SC breaking capacity of 10kA.
MCB is combination of all three functions in a wiring system like switching, overload
and short circuits protection. Overload protection can be obtained by using bi-metallic
strips where as shorts circuit protection can be obtained by using solenoid.
21
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Voltage –ELCB is a voltage operated circuits breakers. The device will function when
the current passes through the ELCB.
Voltage-ELCB contains relay coil and one end of the coil is connected to metallic load
body and the other end is connected to ground wire as shown in figure (5.17).
If the voltage of the equipment body rises (by touching phase to metal part or
insulation failure of equipment), which could cause the difference between earth and
load body voltage, and the danger of electric shock will occur.
This voltage difference will produce an electric current from the load metallic body and
phase through the loop to the Earth.
When voltage on the equipment metallic body rises to danger level i.e., which exceed to
50V, the flowing current through relay loop could move the relay contact by
disconnecting the supply current and avoid from any danger electric shock.
22
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The ELCB detects fault currents from line to the earth (ground) wire within the
installation it protects.
If sufficient voltage appears across the ELCB’s sensing coil, it will switch off the power,
and remain off until manually reset.
A voltage – sensing ELCB does not sense fault current from line to any other earthed
body.
MCCB are manufactured such that the end user will not have access to internal
workings of the over-current protection device.
Generally constructed of two pieces of heavy-duty electrically insulated plastic, these
halves are riveted together to form the whole.
Inside the plastic shell is series of thermal elements and a spring-loaded trigger.
When the thermal element gets too warm, from an over current situation, the spring
trips, which in turn will shut off the electrical circuits.
Operating mechanism:
At its core, the protection mechanism employed by MCCBs is based on the same
physical principles used by all type of thermal – magnetic circuit breakers.
Overload protection is accomplished by means of a thermal mechanism.
MCCBs have a bimetallic contact that expands and contacts in response to changes on
temperature.
Under normal operating conditions, the contact allows electric current through the
MCCB.
However as soon as the current exceeds the adjusted trip value, the contact will start
to heat and expend until the circuits is interrupted.
The thermal protection against overload is designed with a time delay to allow short
duration over current, which is a normal part of operation for many devices.
Fault protection is accomplished with electromagnetic induction, and the response is
instant.
Fault currents should be interrupted immediately, no matter if their duration is short
or long.
Whenever a fault occurs, the extremely high current induces a magnetic field in a
solenoid coil located inside the breaker – this magnetic induction trips a contact and
current it interrupted.
As a complement to the magnetic protection mechanism, MCCBs have internal arc
dissipation measure to facilitate interruption.
As with all types of circuit breakers, the MCCB includes a disconnection switch which
is used to trip the breaker manually.
It is used whenever the electric supply must be disconnected to carry out field work
such as maintenance or equipment upgrades.
25
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Applications:
Molded case circuits breakers can have very high current ratings, which allows them
to be used in heavy duty applications. Such as,
Main electric feeder protection
Capacitor bank protection
Generator protection
Welding applications
Low current application that require adjustable trip setting
Motor protection
26
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
Always make sure that the power source should be shut-off before performing any
work related to electricity.
For example; inspecting, installing, maintaining or repairing.
Running extension cords through the house can trip up residence; this can cause
injury and damage to the wire or outlet if it causes the cord to be ripped out of the
wall.
If you find yourself using extension cords very often, consider having an electrician
install new outlets throughout your home.
Never try repairing energized equipment. Always check that it is de-energized first by
using a tester.
When an electric tester touches a live or hot wire, the bulb inside the tester lights up
showing that an electrical current is flowing through the respective wire.
Check all the wires, the outer metallic covering of the service panel any other hanging
wires with an electrical tester before proceeding with your work.
27
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
28
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
TWO MARKS
29
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
31
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
34
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
The device features two arrangements, one for the over current and one for the over-
temperature.
39. Mention the similarity between MCB and MCCB.
They both provide an element of protection
The MCB and MCCB sense and protect the power circuit from the short circuit or
over current situation.
They are mostly used in low tension or low voltage circuit.
40. Give the advantages of MCCB.
MCCB has an adjustable trip setting.
It can interrupt very large currents.
It has a movable trip unit.
It has a very small tripping time thus fast switching during fault current.
It also offers remote ON/OFF feature.
It has a compact design & takes less space.
41. Mention the differences between the MCB and MCCB.
The MCB’s tripping circuit is fixed and is movable in the MCCB.
MCBs have less than 100 amps, while MCCBs have as high as 2,500 amps.
In MCB, the remote on/off is impossible, while in MCCB, it is possible by the use of
shunt wire.
The MCB is largely used in low circuit current, while MCCB is used for the heavy
current circuit.
The MCB is used for low energy requirements (domestic purposes), whereas the
MCCB is used in high energy requirement regions (large industries).
42. What is ELCB?
An Earth-leakage circuit breaker (ELCB) is a safety device used in electrical
installations with high earth impedance to prevent shock. It detects small stray
voltages on the metal enclosures of electrical equipment and interrupts the circuit if
the voltage level exceeds danger threshold.
43. What is the Purpose of ELCB?
The main purpose of ELCB is to detect Earth leakages and prevent injury to human
beings from electrical shocks and prevent electrical fires that are caused by short
Circuit.
35
BE3254 – ELECTRICAL & INSTRUMENTATION ENGINEERING UNIT – V: BASICS OF POWER SYSTEMS
36