3-Phase Energy Meter with Modbus
3-Phase Energy Meter with Modbus
www.sbc-support.com
Main features
ff 3-phase energy meter, 3 × 230/400 VAC 50 Hz
ff Direct measurement up to 65 A
ff Display of active power, voltage and current for every phase
ff Display of active power for all phases
ff Modbus RTU Interface to query the data
ff Reactive power for every and/or all Phases available
through interface
ff Up to 247 meters can be connected to the Modbus Interface
ff 7-digits display for 1 or 2 tariffs
ff Lead seal possible with cap as accessory
ff Accuracy class B according to EN50470-3,
accuracy class 1 according to IEC62053-21
Order Number
Standard Version: ALE3D5FD10C2A00
MID Version: ALE3D5FD10C3A00
Sealing caps: 4 104 7485 0
Dimension drawings
70
70
57,7
57.7 62
62
22,7
22.7 31
31
30,5
30.5 9 9
9 4,5
4.5 27
27
9
CT Select
69,5
69.5
8282
45
68
68
35
35 11
11 4,5
4.5
66
7
55xx11.7
11,7 ==(58,5)
[58.5] 6
2 | www.sbc-support.com Energy meter ALE3 with integrated Serial Modbus interface | Datasheet
Menu to display the values on the LCD
Start
T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
L1
L2
>3s L1
L2
L1
L2
ALE3D5F
ALE3D5F
ALE3D5F
T1 total
L3 L3 L3
Class B Class B Class B
Error U(V) I(A) Error U(V) I(A) Error U(V) I(A)
T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
>3s
L1 L1 L1 L1
L2 L2 L2 L2
ALE3D5F
ALE3D5F
ALE3D5F
ALE3D5F
T1 part
L3 L3 L3 L3
Class B
Error U(V) I(A)
Class B
Error U(V) I(A) building
Class B
Error U(V) protocol
I(A) (VISI+) energy- heating remote
Class B
Error U(V)alarming
I(A)
management (VISI+)
tele- temperature
>sheduler
20 s alarming
L2
lighting
ALE3D5F
T2 total
L3
Class B communication (VISI+)
Error U(V) I(A)
Start
T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
water treatment lift ventilation sanitation graphic editor (VISI+)
>3s
L1 L1 L1
L2 L2 L2
ALE3D5F
ALE3D5F
ALE3D5F
T2 part
L3 L3 L3
Class B Class B Class B
Error U(V) I(A) Error U(V) I(A) Error U(V) I(A)
T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
L1 L1
L2 L2
setpoint access control trending
Instan.
ALE3D5F
ALE3D5F
L3 L3
Class B Class B
Power P
Error U(V) I(A) Error U(V) I(A)
L2
ALE3D5F
L3
Class B
Error U(V) I(A)
L2
ALE3D5F
L3
Class B
Error U(V) I(A)
L2
ALE3D5F
L3
Class B
Error U(V) I(A)
T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
L1 L1
L2 L2
Voltage
ALE3D5F
ALE3D5F
L3 L3
Class B Class B
U
Error U(V) I(A) Error U(V) I(A)
L2
ALE3D5F
L3
Class B
Error U(V) I(A)
L2
ALE3D5F
L3
Class B
Error U(V) I(A)
T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
L1 L1
L2 L2
Current
ALE3D5F
ALE3D5F
L3 L3
Class B Class B
I
Error U(V) I(A) Error U(V) I(A)
L2
ALE3D5F
L3
Class B
Error U(V) I(A)
L2
ALE3D5F
L3
Class B
Error U(V) I(A)
Start
Datasheet | Energy meter ALE3 with integrated Serial Modbus interface www.sbc-support.com | 3
Wiring diagram
max. 1200 m
Terminals E1 and E2
Connection for the control signal of the
ripple control receiver for tariff switching
L2
ALE3D5F
L3
Class B
Error U(V) I(A)
3 × 230/400 VAC
L1
L2
L3
N
(PEN)
4 | www.sbc-support.com Energy meter ALE3 with integrated Serial Modbus interface | Datasheet
Technical data Modbus
Protocol Modbus RTU according to IDA specification
Bus system RS-485 Serial line
Transmission rate (bps) 4800-9600-19'200-38'400-57'600-115'200.
The transmission Baud rate is automatically detected
Transmission mode E ven parity: 8 data bits, 1 stop bit
Odd parity: 8 data bits, 1 stop bit
No parity: 8 data bits, 2 stop bits
The parity is automatically detected
Bus cable Twisted, shielded, 2×0.5 mm2, 1200 m max.
Response time typ. 5 character times
max. 60 ms
Data transmission
ff Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized.
ff Up to 20 Registers can be read at a time.
ff The device supports broadcast messages.
ff In accordance with the Modbus protocol, a register R is numbered as R - 1 when transmitted.
ff The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM (transmission rate, etc.)
Exception Responses
ff ILLEGAL FUNCTION [01]: The function code is not supported.
ff ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range
or more than 20 registers have been requested.
ff ILLEGAL DATA VALUE [03]: The value in the data field is invalid for the referenced register.
Datasheet | Energy meter ALE3 with integrated Serial Modbus interface www.sbc-support.com | 5
Registers
For double registers (4–5, 16–17, 28–29, 30–31, 32–33, 34-35) the high register is sent first (big_Endian).
Partial counters (30–31, 34–35) can be reset by writing 0 in both registers in the same message.
R Read Write Description Unit
1 X Firmware-Version Ex: 11 = FW 1.1
2 X Number of supported registers Will give 52
3 X Number of supported flags Will give 0
4–5 X Baudrate Ex: Baudrate High = 1; Baudrate Low = 49'664
1 × 65'536 + 49'664 = 115'200 bps
6 Not Used Will give 0
7 X Type / ASN function Will give «AL»
8 X Type / ASN function Will give «E3»
9 X Type / ASN function Will give «D5»
10 X Type / ASN function Will give «FD»
11 X Type / ASN function Will give «10»
12 X Type / ASN function Will give «Cx»
x : 2 = Non MID
x : 3 = MID
13 X Type / ASN function Will give «A0»
14 X Type / ASN function Will give «0»
15 X HW vers. Modif. Ex: 11 = HW 1.1
16–17 X Serial number Low Unique 32 bit serial number
18 X Serial number High Unique 32 bit serial number
19 Not Used Will give 0
20 Not Used Will give 0
21 Not Used Will give 0
22 X Status 0 = no Problem
1 = problem with last communication request
23 X Reponse Timeout ms
24 X X1)
Modbus Address Range 1–247
25 X Error register 0 : No error
1 : Error Phase 1
2 : Error Phase 2
3 : Error Phase 1 and 2
4 : Error Phase 3
5 : Error Phase 1 and 3
6 : Error Phase 2 and 3
7 : Error Phase 1, 2 and 3
26 X Not Used Will give 0
27 X Tariff register 0 is Tariff 1
4 is tariff 2
28–29 X WT1 total 10 –2 kWh (multiplier 0,01)
Counter Energy Total Tariff 1 Ex: W T1 total High = 13; WT1 total Low = 60'383
13 × 65'536 + 60'383 = 912'351 = 9123.51 kWh
30–31 X X WT1 partial 10 –2 kWh (multiplier 0,01)
Counter Energy Partial Tariff 1 Ex: W T1 partial High = 13; WT1 partial Low = 60'383
13 × 65536 + 60383 = 912351 = 9123.51 kWh
32–33 X WT2 total 10 –2 kWh (multiplier 0,01)
Counter Energy Total Tariff 2 Ex: W T2 total High = 13 WT2 total Low = 60'383
13 × 65'536 + 60'383 = 912'351 = 9123.51 kWh
6 | www.sbc-support.com Energy meter ALE3 with integrated Serial Modbus interface | Datasheet
R Read Write Description Unit
34–35 X X WT2 partial 10 –2 kWh (multiplier 0,01)
Counter Energy Partial Tariff 2 Ex: W T2 partial High = 13; WT2 partial Low = 60'383
13 × 65'536 + 60'383 = 912'351 = 9123.51 kWh
36 X URMS phase 1 V
Voltage of Phase 1 Ex: 230 = 230 V
37 X IRMS phase 1 10 –1 A (multiplier 0,1)
Current of Phase 1 Ex: 314 = 31.4 A
38 X PRMS phase 1 10 –2 kW (multiplier 0,01)
Active Power of Phase 1 Ex: 1545 = 15,45 kW
39 X QRMS phase 1 10 -2kvar (multiplier 0,01)
Reactive Power of Phase 1 Ex: 1545 = 15,45 kvar
40 X cos phi phase 1 10 –2 (multiplier 0,01)
Ex: 67 = 0,67
41 X URMS phase 2 V
Voltage of Phase 2 Ex: 230 = 230 V
42 X IRMS phase 2 10 –1 A (multiplier 0,1)
Current of Phase 2 Ex: 314 = 31.4 A
43 X PRMS phase 2 10 –2 kW (multiplier 0,01)
Active Power of Phase 2 Ex: 1545 = 15,45 kW
44 X QRMS phase 2 10 –2 kvar (multiplier 0,01)
Reactive Power of Phase 2 Ex: 1545 = 15,45 kvar
45 X cos phi phase 2 10 –2 (multiplier 0,01)
Ex: 67 = 0,67
46 X URMS phase 3 V
Voltage of Phase 3 Ex: 230 = 230 V
47 X IRMS phase 3 10 –1 A (multiplier 0,1)
Current of Phase 3 Ex: 314 = 31.4 A
48 X PRMS phase 3 10 –2 kW (multiplier 0,01)
Active Power of Phase 3 Ex: 1545 = 15,45 kW
49 X QRMS phase 3 10 –2 kvar (multiplier 0,01)
Reactive Power of Phase 3 Ex: 1545 = 15,45 kvar
50 X cos phi phase 3 10 –2 (multiplier 0,01)
Ex: 67 = 0,67
51 X PRMS total 10 –2 kW (multiplier 0,01)
Active Power of all phases Ex: 1545 = 15,45 kW
52 X QRMS total 10 –2 kvar (multiplier 0,01)
Reactive power of all phases Ex: 1545 = 15,45 kvar
1)
The Modbus Address register is not writable with a broadcast message.
Datasheet | Energy meter ALE3 with integrated Serial Modbus interface www.sbc-support.com | 7
Saia-Burgess Controls AG
Bahnhofstrasse 18 | 3280 Murten, Switzerland
T +41 26 580 30 00 | F +41 26 580 34 99
www.saia-pcd.com
support@saia-pcd.com | www.sbc-support.com
PP26-527 ENG05 05.2017 Subjects to change without notice