Data sheet

www.sbc-support.com

3 phase energy meters


with integrated Serial Modbus interface

Energy meters with an integrated Serial RS-485 Modbus


interface allow direct reading of all relevant data, such as
energy (Total and partial), current and voltage for every
phase and active and reactive power for every phase and
for the three phases.

Main features
ff 3-phase energy meter, 3 × 230/400 VAC 50 Hz
ff Direct measurement up to 65 A
ff Display of active power, voltage and current for every phase
ff Display of active power for all phases
ff Modbus RTU Interface to query the data
ff Reactive power for every and/or all Phases available
through interface
ff Up to 247 meters can be connected to the Modbus Interface
ff 7-digits display for 1 or 2 tariffs
ff Lead seal possible with cap as accessory
ff Accuracy class B according to EN50470-3,
accuracy class 1 according to IEC62053-21

Order Number
Standard Version: ALE3D5FD10C2A00
MID Version: ALE3D5FD10C3A00
Sealing caps: 4 104 7485 0

Technical Data Mounting


Precision class B according to EN50470-3 Mounting On 35mm rail, according to EN60715TH35
1 according to IEC62053-21
Terminal connections Conductor cross-section 1.5–16 mm2.
Operationg voltage 3×230 / 400 VAC, 50 Hz Main circuit Screwdriver Pozidrive no. 1
Tolerance –20%/+15% Slot no.2, torque 1.5–2 Nm
Reference / maximum Iref = 10 A, Imax = 65 A Terminal connections Conductor cross-section max. 2.5 mm2.
current Control circuit Screwdriver Pozidrive no. 0.
Slot no. 2, torque 0.8 Nm
Starting / minimum current Ist = 40 mA, Imin = 0.5 A
Insulation – 4 kV/50 Hz test according to VDE0435
Power consumption Active 0.4 W per phase characteristics for Energy Meter part
Counting range 00’000,00…99’999,99 – 6 kV 1.2/50 µs surge according to IEC255-4
100’000,0…999’999,9 – 2 kV/50 Hz test according to VDE0435 for Interface
– Device protection class II
Display LCD backlit, digits 6 mm high
Ambient temperature –25°…+55°C
Display without Capacitor based LCD
mains power Max. 2 times over 10 days Storage temperature –30°…+85°C
Environment Mechanical M2
Pulses per kWh LED 1000 Imp./kWh
Electromagnetic E2
Relative humidity 75%, without condensation
EMC/ – Surge according to IEC61000-4–5 at main circuit 4 kV,
interference immunity at Modbus interface, 1 kV
– Burst according to IEC61000-4-4, at main circuit, 4 kV,
at Modbus interface 1 kV
– ESD according to IEC61000-4-2,
contact 8 kV, air 15 kV
Error display
Example: Connection error at L3 Example: Connection error at L1 and L3

Dimension drawings

70
70
57,7
57.7 62
62
22,7
22.7 31
31

30,5
30.5 9 9
9 4,5
4.5 27
27
9

CT Select
69,5
69.5

8282

45
68
68

35
35 11
11 4,5
4.5
66
7

55xx11.7
11,7 ==(58,5)
[58.5] 6

Display elements, direct measurement

 T1 total Shows the total consumption tariff 1


 T1 part Shows the partial consumption for tariff 1, this value
can be reset
 T2 total Shows the total consumption tariff 2
 T2 part Shows the partial consumption for tariff 2, this value
can be reset
 P (kW) Shows the instantaneous power per phase or for all
phases
 U (V) Shows the voltage per phase
 I (A) Shows the current per phase
 kWh Shows the unit kWh for consumption display
 L1/L2/L3 For P, U, I or error message display,
the corresponding phase is displayed
 Error In the absence of phase or incorrect current direc-
tion. The corresponding phase is also displayed.

2 | www.sbc-support.com Energy meter ALE3 with integrated Serial Modbus interface | Datasheet
Menu to display the values on the LCD

Start
T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
L1

L2
>3s L1

L2
L1

L2

ALE3D5F
ALE3D5F

ALE3D5F
T1 total
L3 L3 L3
Class B Class B Class B
Error U(V) I(A) Error U(V) I(A) Error U(V) I(A)

visualization combined heat cooling IT / Data


(VISI+) and power station

T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )

>3s
L1 L1 L1 L1

L2 L2 L2 L2
ALE3D5F

ALE3D5F

ALE3D5F

ALE3D5F
T1 part
L3 L3 L3 L3
Class B
Error U(V) I(A)
Class B
Error U(V) I(A) building
Class B
Error U(V) protocol
I(A) (VISI+) energy- heating remote
Class B
Error U(V)alarming
I(A)

management (VISI+)

T1tota l T1part . T2total T2part. P(kW )


L1

tele- temperature
>sheduler
20 s alarming
L2
lighting
ALE3D5F

T2 total
L3
Class B communication (VISI+)
Error U(V) I(A)

Start
T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
water treatment lift ventilation sanitation graphic editor (VISI+)
>3s
L1 L1 L1

L2 L2 L2
ALE3D5F

ALE3D5F

ALE3D5F
T2 part
L3 L3 L3
Class B Class B Class B
Error U(V) I(A) Error U(V) I(A) Error U(V) I(A)

presence shade control traffic control Logistic energy


system

T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
L1 L1

L2 L2
setpoint access control trending
Instan.
ALE3D5F

ALE3D5F

L3 L3
Class B Class B

Power P
Error U(V) I(A) Error U(V) I(A)

T1tota l T1part . T2total T2part. P(kW )


L1

L2
ALE3D5F

L3
Class B
Error U(V) I(A)

T1tota l T1part . T2total T2part. P(kW )


L1

L2
ALE3D5F

L3
Class B
Error U(V) I(A)

T1tota l T1part . T2total T2part. P(kW )


L1

L2
ALE3D5F

L3
Class B
Error U(V) I(A)

T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
L1 L1

L2 L2

Voltage
ALE3D5F

ALE3D5F

L3 L3
Class B Class B

U
Error U(V) I(A) Error U(V) I(A)

T1tota l T1part . T2total T2part. P(kW )


L1

L2
ALE3D5F

L3
Class B
Error U(V) I(A)

T1tota l T1part . T2total T2part. P(kW )


L1

L2
ALE3D5F

L3
Class B
Error U(V) I(A)

T1tota l T1part . T2total T2part. P(kW ) T1tota l T1part . T2total T2part. P(kW )
L1 L1

L2 L2

Current
ALE3D5F

ALE3D5F

L3 L3
Class B Class B

I
Error U(V) I(A) Error U(V) I(A)

T1tota l T1part . T2total T2part. P(kW )


L1

L2
ALE3D5F

L3
Class B
Error U(V) I(A)

T1tota l T1part . T2total T2part. P(kW )


L1

L2
ALE3D5F

L3
Class B
Error U(V) I(A)

Start

Datasheet | Energy meter ALE3 with integrated Serial Modbus interface www.sbc-support.com | 3
Wiring diagram

D /D Modbus over RS-485 serial line

max. 1200 m

Terminals E1 and E2
Connection for the control signal of the
ripple control receiver for tariff switching

T1tota l T1part . T2total T2part. P(kW )


L1

L2
ALE3D5F

L3
Class B
Error U(V) I(A)
3 × 230/400 VAC

L1
L2
L3
N
(PEN)

4 | www.sbc-support.com Energy meter ALE3 with integrated Serial Modbus interface | Datasheet
Technical data Modbus
Protocol Modbus RTU according to IDA specification
Bus system RS-485 Serial line
Transmission rate (bps) 4800-9600-19'200-38'400-57'600-115'200.
The transmission Baud rate is automatically detected
Transmission mode E ven parity: 8 data bits, 1 stop bit
Odd parity: 8 data bits, 1 stop bit
No parity: 8 data bits, 2 stop bits
The parity is automatically detected
Bus cable Twisted, shielded, 2×0.5 mm2, 1200 m max.
Response time typ. 5 character times
max. 60 ms

ff The interface works only if the Phase 1 is connected.


ff The communication is ready 30 s after the Power On.
ff Refresh Time for the data is 10 s. Therefore the delay between reads of the same data should be at least 10 s.
ff The use of Energy meters in Bus with intensive communication can increase the data refresh time.
ff 247 devices can be connected to the Modbus. Over 128 devices, a repeater should be used.
ff The interface don’t have a terminal resistor, this should be provided external.
ff For a description of the used registers please look at the Register Page.

Data transmission
ff Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized.
ff Up to 20 Registers can be read at a time.
ff The device supports broadcast messages.
ff In accordance with the Modbus protocol, a register R is numbered as R - 1 when transmitted.
ff The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM (transmission rate, etc.)

Exception Responses
ff ILLEGAL FUNCTION [01]: The function code is not supported.
ff ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range
or more than 20 registers have been requested.
ff ILLEGAL DATA VALUE [03]: The value in the data field is invalid for the referenced register.

Change the Modbus address direct on device


ff To modify the Modbus address, press 3 s on  touch
ff In menu,  increase address by 10,  increase by 1
ff Once the address is selected wait for the root menu to come back

Datasheet | Energy meter ALE3 with integrated Serial Modbus interface www.sbc-support.com | 5
Registers
For double registers (4–5, 16–17, 28–29, 30–31, 32–33, 34-35) the high register is sent first (big_Endian).
Partial counters (30–31, 34–35) can be reset by writing 0 in both registers in the same message.
R Read Write Description Unit
1 X Firmware-Version Ex: 11 = FW 1.1
2 X Number of supported registers Will give 52
3 X Number of supported flags Will give 0
4–5 X Baudrate Ex: Baudrate High = 1; Baudrate Low = 49'664
1 × 65'536 + 49'664 = 115'200 bps
6 Not Used Will give 0
7 X Type / ASN function Will give «AL»
8 X Type / ASN function Will give «E3»
9 X Type / ASN function Will give «D5»
10 X Type / ASN function Will give «FD»
11 X Type / ASN function Will give «10»
12 X Type / ASN function Will give «Cx»
x : 2 = Non MID
x : 3 = MID
13 X Type / ASN function Will give «A0»
14 X Type / ASN function Will give «0»
15 X HW vers. Modif. Ex: 11 = HW 1.1
16–17 X Serial number Low Unique 32 bit serial number
18 X Serial number High Unique 32 bit serial number
19 Not Used Will give 0
20 Not Used Will give 0
21 Not Used Will give 0
22 X Status 0 = no Problem
1 = problem with last communication request
23 X Reponse Timeout ms
24 X X1)
Modbus Address Range 1–247
25 X Error register 0 : No error
1 : Error Phase 1
2 : Error Phase 2
3 : Error Phase 1 and 2
4 : Error Phase 3
5 : Error Phase 1 and 3
6 : Error Phase 2 and 3
7 : Error Phase 1, 2 and 3
26 X Not Used Will give 0
27 X Tariff register 0 is Tariff 1
4 is tariff 2
28–29 X WT1 total 10 –2 kWh (multiplier 0,01)
Counter Energy Total Tariff 1 Ex: W T1 total High = 13; WT1 total Low = 60'383
13 × 65'536 + 60'383 = 912'351 = 9123.51 kWh
30–31 X X WT1 partial 10 –2 kWh (multiplier 0,01)
Counter Energy Partial Tariff 1 Ex: W T1 partial High = 13; WT1 partial Low = 60'383
13 × 65536 + 60383 = 912351 = 9123.51 kWh
32–33 X WT2 total 10 –2 kWh (multiplier 0,01)
Counter Energy Total Tariff 2 Ex: W T2 total High = 13 WT2 total Low = 60'383
13 × 65'536 + 60'383 = 912'351 = 9123.51 kWh

6 | www.sbc-support.com Energy meter ALE3 with integrated Serial Modbus interface | Datasheet
R Read Write Description Unit
34–35 X X WT2 partial 10 –2 kWh (multiplier 0,01)
Counter Energy Partial Tariff 2 Ex: W T2 partial High = 13; WT2 partial Low = 60'383
13 × 65'536 + 60'383 = 912'351 = 9123.51 kWh
36 X URMS phase 1 V
Voltage of Phase 1 Ex: 230 = 230 V
37 X IRMS phase 1 10 –1 A (multiplier 0,1)
Current of Phase 1 Ex: 314 = 31.4 A
38 X PRMS phase 1 10 –2 kW (multiplier 0,01)
Active Power of Phase 1 Ex: 1545 = 15,45 kW
39 X QRMS phase 1 10 -2kvar (multiplier 0,01)
Reactive Power of Phase 1 Ex: 1545 = 15,45 kvar
40 X cos phi phase 1 10 –2 (multiplier 0,01)
Ex: 67 = 0,67
41 X URMS phase 2 V
Voltage of Phase 2 Ex: 230 = 230 V
42 X IRMS phase 2 10 –1 A (multiplier 0,1)
Current of Phase 2 Ex: 314 = 31.4 A
43 X PRMS phase 2 10 –2 kW (multiplier 0,01)
Active Power of Phase 2 Ex: 1545 = 15,45 kW
44 X QRMS phase 2 10 –2 kvar (multiplier 0,01)
Reactive Power of Phase 2 Ex: 1545 = 15,45 kvar
45 X cos phi phase 2 10 –2 (multiplier 0,01)
Ex: 67 = 0,67
46 X URMS phase 3 V
Voltage of Phase 3 Ex: 230 = 230 V
47 X IRMS phase 3 10 –1 A (multiplier 0,1)
Current of Phase 3 Ex: 314 = 31.4 A
48 X PRMS phase 3 10 –2 kW (multiplier 0,01)
Active Power of Phase 3 Ex: 1545 = 15,45 kW
49 X QRMS phase 3 10 –2 kvar (multiplier 0,01)
Reactive Power of Phase 3 Ex: 1545 = 15,45 kvar
50 X cos phi phase 3 10 –2 (multiplier 0,01)
Ex: 67 = 0,67
51 X PRMS total 10 –2 kW (multiplier 0,01)
Active Power of all phases Ex: 1545 = 15,45 kW
52 X QRMS total 10 –2 kvar (multiplier 0,01)
Reactive power of all phases Ex: 1545 = 15,45 kvar
1)
The Modbus Address register is not writable with a broadcast message.

Datasheet | Energy meter ALE3 with integrated Serial Modbus interface www.sbc-support.com | 7