Refrigerant
Refrigerant
ENVIRONMENT
Surname: Rixana
Student number:222085509
Lecturer: Ms W Heuvel
Marking Criteria
Mark Allocation Student Mark
Structure 5
Abstract 5
Introduction 5
Experimental Procedure 5
Results 45
Discussion 25
Conclusion 5
Appendix 5
Total 100
Declaration
2.The adjusting of the dual pressure controller was carried out by following the subsequent
actions: the low-pressure cut-out scale was examined, and it was learned that it was fixed at
5 psi. If it was necessary, the adjustment screw was turned using a regular screwdriver. The
cut-in scale was checked to see if it was at 45 psi, and if necessary. The tone can be improved
a little bit.
3.Reset the refrigerant valves to the following positions (if necessary): V1: Open V4: Open V2:
Closed V5: Closed V3: Closed V6: Closed. The cord was located and plugged into a standard
household outlet. The notch 6 (of 8) the damper on the evaporator was closed to ¾.
4. Next the power switch was placed in the ON position. The LCD of the electronic temperature
controller showed the room (ambient) temperature, and this was recorded as our hot reservoir
temperature. Steps were taken to make sure that the electronic temperature controller was
set up on point.
5.The controller pressed the SET button This was done by pressing the up and down arrows
to select °F on the LCD. The SET button was pressed once more to fix the temperature. A set
point of 55°F was then selected with the arrow keys. However, when it hit this temperature,
the compressor kicked off.
6.The controller was set to a lower point (compared to room temperature) as this is necessary
for the machine to operate continuously. Press the SET button again and switch to temperature
difference mode. 10° F was changed with a pair of arrow keys from its original value.
7.This correction told the controller to turn on the compressor 10°F higher than what was set
i.e., 65°F (heating is only available in Active Temperature 2 stage). Enclosure TEST button
pushed once more, and unit transitioned from HEAT mode back to normal COOL mode.
8.Cooling mode was entered using the LCD arrow keys selecting"C1." The room temperature
could finally be displayed on the LCD by pressing SET, once an again. The flow meter was
found, and we made sure that the knob fully open by turning it counterclockwise. The mode
switchfulfillment was used to select the COOLING mode. The compressor clicked on, and the
blower fans started.
9.The trainer was initially allowed to run until steady-state conditions had been reached and
no bubbles were present in the flow meter. This took five to twenty minutes. The ball height
noted the flow in the flow meter It was measured from the centre of the ball as well on a scale
so to be made an appropriate record.
10. The air temperature exiting the evaporator (evaporator output temperature) was noted
before turning off the trainer. This temperature was displayed on the Electronic Temperature
control panel and represented the temperature of the cold reservoir.
11.The power switch was then turned to the OFF position after setting the mode switch to
STAND-BY to turn off the trainer.
List of Apparatus
• Condenser
• Evaporator
• Expansion Valve
• Compressor
• Refrigerant R134a
Figure 2:The flowmeter taken at steady state with no bubbles
Results
Table 1:The temperature,pressure and enthalpy at various points.
The recordings in table 1, show the temperatures and pressure as recorded by the
thermometer in the thermal system. The enthalpies were found using P-h diagram for
Refrigerant R-134a in the appendix.
• Measure the height of the ball at its center against the scale to determine the height in
millimeters (mm); the height is 21,4mm. Using Table 3, the volumetric flow rate may be
determined. The measured value is interpolated to be 0,324𝑓𝑡 3 /ℎ.
This is converted to 2,548× 10−3 𝑘𝑔/𝑠
• By multiplying the volumetric flow rate by the density at 32°C, one can determine the
mass flow rate. According to (Cengel & Boles, 2011), the density is 1163.467 kg/m3.
The mass flow rate is therefore 2,9645kg/s
Discussion
The findings indicate that the evaporator's heat duty is 71,148 kJ/hr, which is in line with
expectations given that the evaporator will draw heat from the surroundings to provide the
cooling effect. The saturated liquid in the throttle valve is evaporated by the heat. In
comparison to the energy required in the evaporation stage, the compressor's additional work
68,243kj/hr is relatively insignificant. Its purpose is to heat the saturated vapour to the
superheated temperature of 35°C. The labor done in this stage is only sufficient to fulfill the
necessary task since the overdesign guarantees that the refrigerant is entirely evaporated
when it enters the condenser.
The refrigerant is subcooled in the condenser due to an overdesign factor, which ensures that
all of the vapor has liquified. The heat released is approximately 545,468 kJ/kg, which is
slightly higher than the heat of vaporization in the evaporator because it is not desirable to
send the liquified refrigerant to the throttling valve before it is fully condensed.
The phrase "coefficient of performance," or C.O.P., is used to describe the refrigeration cycle's
performance. It was discovered that this value is 0,130.
Conclusion
The experiment was carried out using the Amatrol T7082 thermal system, and R-134a
refrigerant was chosen because of its clean nature, broad applicability, and availability of
access. The mass flow rate of refrigerant is 2,9645 kg/hr. In order to ensure full vaporization
and condensation in the evaporator and condenser, respectively, overdesign factors are
applied, which results in superheated vapour into the condenser and subcooled liquid to the
throttle valve. It is discovered that the heat is absorbed in the evaporation stage, generating
the refrigeration effect.
References
Cengel, Y. A. & Boles, M. A., 2011. THERMODYNAMICS an engineering approach. 8th ed.
New York: McGraw-Hill Education.
Emani, M. S. & Roy, R., 2017. Development of refrigerants:A brief review. Elseveir, pp.
175-181.
Evans, O., 1805. The Abortion of Young Steam Engineers Guide. Philadephia: Oliver
Evans.
To calculate the absolute pressure, covert each pressure from bar to kPa.
1𝐵𝑎𝑟 = 100𝑘𝑃𝑎
Then convert each pressure to MPa by using the conversion 1MPa = 1000kPa
(𝑋2 − 𝑋1 )
𝑋 = 𝑋1 + (𝑌 − 𝑌1 )
(𝑌2 − 𝑌1 )
0,324𝑓𝑡 3
𝑄=
ℎ
𝑚̇ = 𝜌 × 𝑄
𝑓𝑡 3 𝑚3
Conversions were made from 𝑡𝑜
ℎ 𝑠
𝑚̇ = 0,00255𝑘𝑔/𝑠
𝑄 = 0,00255(434 − 410)
𝑄 = 0,0612𝑘𝑊
3. Heat Duty of the condenser:
𝑄 = 𝑚̇ × (ℎ2 − ℎ3 )
𝑄 = 2,9645(434 − 250)
𝑄 = 545,468𝑘𝑊
𝑊 = 𝑚̇(ℎ2 − ℎ3 )
𝑊 = 2,9645(434 − 410)
𝑊 = 71,148𝑘𝑊
𝐶𝑂𝑃 = 0,130
Table 3:Determination of the Volumetric Flow rate