Power Systems T - D (Q - Bank - Transmission)
Power Systems T - D (Q - Bank - Transmission)
4. If for a 50Hz transmission line the sending end voltage is 440 V, then the receiving end
voltage under lagging load condition is
7. A cable of length 10km has an insulation resistance of 20M. If the cable length is
increased to 20 km, then the insulation resistance is __________ M.
9. If the diameter of each strand in a stranded conductor is 5 cm, then the total diameter of 4
layer stranded conductor is _____________ cm.
10. If for a 50 km transmission line, the sending end voltage is 440V and the receiving end
voltage is 400V, then the percentage voltage regulation is ______________ .
11. If the frequency of a transmission system is changed from 50 Hz to 100 Hz, then the
string efficiency of the insulator
12. In capacitance grading method, three insulating materials A, B & C having permittivity’s
3, 4 & 5 and dielectric strengths of materials 40kV/cm, 15kV/cm, and 30kV/cm respectively.
Then with respect to the core of the cables the materials are arranged in the order.
(a) A, B, C (b) C, A, B
(c) B, C, A (d) C, B, A
15. A 3- 50 Hz transmission line has its conductors placed at the corners of equilateral
triangle of side 3m and the radius of each conductor is 1 cm. The capacitive reactance per
phase for 100 km transmission line is ___________ k.
16. In a 3-disc string insulator, the peak voltage of the disk is 10kV and the self-capacitance
of the string is 10 times of shunt capacitance. The string efficiency is _________ %.
17. If Q is the reactive power of shunt inductor under normal voltage and frequency, when
the frequency and voltage increased by 10%, then the reactive power
18. The value of cosL for the following shunted capacitor is _____________ lag.
19. For LT and HT lines, which of the following insulators are used respectively?
20. In Grading of cables, the ratio of d to D such that grading will increase the safe working
voltage by 100% is ______________.
21. In a short transmission line, if resistance and reactance are found to be equal and
regulation appears to be zero, then the load will
23. Consider a distribution system having three loads at UPF and having feeding point at
one end. The length doubles and current halves successively for each load from the feeding
point. If the length of feeder to first load and current in the first load are 100m and 100A
respectively and resistance of the distributor is 20/m, then the total voltage drop
_____________ kV.
24. What will be area of cross section of distributor and the resistance, if the operating
voltage is increased by 2 times?
25. Four sub-conductors are arranged in such a manner that they form the corners of a
square. The radius of each sub conductor is 1cm and the adjacent distance between the two
sub conductors is 50 cm. The self GMD of the sub-conductor configuration is
________________ cm.
X
1. ratio of distribution line must be greater than 1.0
R
2. Inductor per phase of unsymmetrical configuration is slightly greater than symmetric
configuration for same operating voltage.
3. Earth can be treated as one of the conductor in AC
4. Due to current flowing through earth only C will be influenced
27. In underground cables, to prevent the entry of moisture into the outside surface of the
insulation ____________ is used.
28. From below statements which one is not possible by using bundled conductors?
(a) Interference with communication lines will be reduced.
(b) Corona is reduced
(c) Capacitance per phase in transmission line is reduced
(d) Inductance per phase in transmission line is reduced
29. For a short transmission line, the transfer matrix is given by:
1 Z 1 0
(a) (b)
0 1 1 Z
1 Z 1 1
(c) (d)
0 0 Z 1
31. For a given transmission line the expression for voltage regulation is given by
Vs VR
100% . Hence
VR
32. The shunt admittance of a transmission line is 3 micro mho. Its complex notation in mho
is
33. The selection of size of conductors for a distribution in a distribution system is governed
by
34. The insulation level of a 400kV, EHV overhead transmission line is decided on the basis of
(a) Lightning over voltage
(b) Switching over voltage
(c) Corona inception voltage
(d) Radio & TV interference
38. A 500kV, 50Hz, 200km long three phase transmission line supplies a load of 600MW at
0.85 power factor lagging. The per phase per km line inductance & capacitance are 0.87mH
and 0.012F respectively. Assuming the line is Lossless, the surge impedance (in k) of line
is ______________.
39. In a 400 kV network, 360 kV is recorded at 400 kV bus. The reactive power absorbed by
a shunt reactor is 50 MVA for 360 kv , for 400 kV connected bus, the reactive power is
____________ MVAR.
40. A cable has the following characteristics: L = 0.201 H/m and C = 196.2pF/m. The
velocity of wave propagation through the cable is ___________ m/s.
41. The corona loss on a particular system with 50 Hz is 1 kW/phase/km. The corona loss on
the same system with supply frequency 25 Hz will be ___________ kW/phase/km.
42. Which of the following transmission line model results in higher sending end voltage for
lagging load?
(a) Sending end ‘C’ model (b) Load end ‘C’ model
(c) Nominal (d) Nominal T
43. Which of the following connection reduces Ferranti effect under no load condition?
(a) Series reactor at sending end (b) Series capacitor at sending end
(c) Series reactor at receiving end (d) None
44. For a lossless network more maximum power transfer capability is possible with
45. Which of the following expression gives per phase no load power loss in long
transmission line, where ‘IC’ is charging current carried by line and ‘R’ is per phase resistance
for total length.
I2cR
(a) I 2cR (b)
2
I2cR IR2
(c) (d) c
3 4
46. A transmission line with sending end and receiving end voltage |Vs| and | VR |0. If
line reactance is capacitive in nature then what are the limits on to make system in stable
mode.
(a) 0 < < 90 (b) 90 < < 180
(c) 180 < < 90 (d) 90 < < 0
47. A two disc insulator string has each disc capacitance ‘C’ and shunt capacitance between
metal link and ground is 0.2C the top most unit voltage is 10kV. The line voltage of insulator
string is ____________ (in kV)
48. If frequency of operation increases, then which of the following statements are correct
with respect to ABCD parameters for a lossless long transmission line?
(a) A , B , C , D
(b) A , B , C , D
(c) A , B , C , D
(d) A , B , C , D
49. A long transmission line operating under no load condition has leakage current
magnitude through shunt conductance in
51. A 1- composite conductor system shown in figure. r1 = 2 cm, r2 = 1.155 cm. Conductor
‘a’ forms forward path and b1, b2, b3 forms return path. Inductance of forward path will
52. An AC 2-wire distributor with concentrated loads and then section impedance are shown
in below figure.
Z1 = Z2 = 2 + j0.5 (both forward and return conductors)
If Vx = 4000o then the angle for Vs voltage will be
(a) – 1.09o
(b) + 1.09o
(c) – 5.18o
(d) +5.18o
53. A loss less short transmission line is shown. At the midpoint of the transmission, reactive
power compensator employed so that the midpoint voltage is maintained as 0.95 p.u. The
power delivered to the receiving end is ____pu.
(a) 2.12
(b) 2.46
(c) 2.49
(d) 2.10
54. A 3-, 400kV transmission line has a string insulator with 20 discs, maximum voltage
across any unit is 15kV. The string efficiency will be
(a) 92.8% (b) 84.6%
(c) 76.9% (d) 66.9%
55. Which of the following apparatus used to connect at receiving end side of transmission
line to maintain its voltage magnitude to be equal to sending end voltage magnitude under
loading less than ideal loading condition
56. A 1-, 2-wire system has conductor radius of 2 cm, spacing between conductors of 2m.
What is loop reactance for 20km length, 50Hz operation?
57. A 60 Hz loss less overhead long line has inductance per phase per km as 1.0 mH/km.
The capacitance per phase per km will be approximately
58. A cable ‘B’ of surge impedance 50 is used to connect two transmission Lines A and C
having surge impedances 200 and 500. A surge voltage of 10 kV injected on Line-A
travels towards cable – B and Line-C. What is the first refracted voltage at junction of cable B
and line-C.
(a) 4 kV
(b) 5.33 kV
(c) 7.27 kV
(d) 10 kV
59. A one km long 11kV, 3-core, 3- metal sheath cable, save the following test results;
(i) Capacitance between any two conductors when other conductor connected to sheath;
0.4F
(ii) Capacitance between all three cores bunched together and sheath 0.9F;
60. A loss less transmission line has ABCD as A A 0o , B= B 90o , C= C 90o ,
D D 0o. To avoid Ferranti effect under No load a -connected shunt reactor connected
at receiving end, what will be each reactor reactance in
B B
(a) (b)
3 1 A 1 A
3B
(c) (d) none
1 A
61. A single load draws a current of 1060o with voltage 100130o. A shunt reactor added
across the load then the source current (Is) and source power factor (coss) variations will be
62. A single phase AC distributor supply two single phase loads as shown in the figure.
Voltage at point ‘B’ is 200+j0 volts. What is source power factor?
64. A single line diagram of a two bus power system network shown below. Voltage at buses
|V1| = |V2| = 1 p.u. If generator supplies a reactive power of 0.1 p.u then what is the reactive
power to be supplied by capacitor bank placed at bus (1)
1. String efficiency for suspension type string is always less as compared to strain type
string.
2. If ratio between self-capacitance to shunt capacitance reduces then string efficiency will
increase.
3. String efficiency of a 3-disc insulator string for 20 kV supply is 78%. String efficiency of
same string for 40 kV supply is more than 78%.
66. A short length of cable connected between dead end tower and substation at the end of
transmission line. Which of the following statement is correct if surge wave enters from
overhead line to cable?
For this transmission line steady state stability limit, if the shunt admittance is assume to be
zero and series resistance is neglected is ________ MW (consider two terminal voltages are
held constant at 110 kV)
68. For a single circuit transmission line delivering a 3-phase load of 50 MVA at 110 kV and
p.f 0.8 lagging. Find the sending end voltage and sending end current per phase.
69. In a transmission line both sending end and receiving end voltages are maintained at
same magnitude and there is a real power flow from sending end to receiving end. The
reactive power flow will be
(a) Delivered by both buses into the line
(b) Absorbed by both buses from the line
(c) Delivered by sending end bus
(d) No reactive power flow between buses
70. A 220 kV, 3- transmission line suspended by a string insulator has a string efficiency
80% with maximum voltage across any unit as 15kV. The number of units will be
(a) 10 (b) 11
(c) 12 (d) 13
71. A loss less short transmission line model has a voltage regulation of 10% with maximum
power transfer capability 2 p.u. If angular difference between sending end and receiving end
voltages is very low then reactive power delivered by side in per unit us _______
72. Three transmission lines connected in parallel where each line has a surge impedance of
400. At the sending end of this parallel line combination a cable of surge impedance 100
is connected. If a surge voltage of ‘V’ was placed on cable travels towards junction of cable
and parallel lines then what is transmitted voltage at junction
4 8
(a) V (b) V
7 7
7
(c) V (d) V
8
73. A flat spacing conductors single phase line operating at 50Hz with spacing between
conductors is 6m and external inductance of each conductor is 1.0 mH/km. The physical
diameter of each conductor is
(a) 4.04 cm (b) 8.08 cm
(c) 5.18 cm (d) 10.37 cm
74. A DC two wire distributor fed from both sides supplying two load as shown below. Each
wire in the distributor has a resistance of 0.2 for 100 m length. If VA = VD = 200V then the
minimum voltage at any point on the distributor is _________ V.
75. The line constants of a 200 km, 3 phase, 50 Hz transmission line are given as following
The sending end voltage is 230 kV. The value of line charging current when the load is
disconnected will
76. A loss less 200 km, 400 kV, 50 Hz, long transmission line has a natural impedance of
250. The generalized circuit constant ‘B’ will be ______________ s/ph.
77. A single core cable 5 km long has an insulation resistance of 0.4 MΩ. The core diameter
is 20 mm and the diameter of the cable over the insulation is 50 mm. The resistivity of the
insulating material is
78. The A surge of 15 kV magnitude travels along a cable towards its junction with an
overhead line. The inductance and capacitance of the cable and overhead line are
respectively 0.3 mH, 0.4 μF and 1.5 mH, 0.012 μF per km. The voltage rise at the junction due
to the surge is
79. A typical line has the following parameters; A = D = 0.961.0° and B = 10080° Ω
The maximum power that can be transmitted if the sending and receiving end line voltages
are 120 kV and 110 kV respectively is __________ MW.
80. The power factor of a 120 kW group load is 0.8 lagging. This p.f. is to be improved to 0.9
by means of shunt capacitors. The KVAR of capacitors required is _____ KVAR.
81. The overhead lines are connected in parallel to supply a load of 10 MW at 0.8 pf
(lagging) and 30 kV. The resistance and reactance of one line (A) are 5.5 Ω and 13.5 Ω,
respectively; those of the other line (B) are 6 Ω and 11 Ω respectively. The KVA supplied by
line B is
(a) 6,730 KVA a. at pf 0.83 lagging
(b) 7,120 KVA at pf 0.77 lagging
(c) 7,860 KVA at pf 0.77 lagging
(d) 6,020 KVA at pf 0.83 lagging
82. The three conductors of a 3-phase line are arrange at the corners of a triangle of sides
2m, 2.5m and 4.5m. The inductance per phase per meter, if the diameter of each conductor is
1.24 cm and conductors are regularly transposed is
(a) 1.04 H (b) 2.1 H
(c) 1.27 H (d) 2.8 H
83. A single phase ring distributor ABC is fed at A. The loads at B and C are 20A at 0.8 pf
lagging and 15 A at 0.6 pf lagging respectively, both expressed with reference to voltage at
A. The total impedance of the section AB, BC and CA are (1+j1), (1+j2) and (1+j3) ohm’s
respectively. The current in section BC is
(a) (2.6 + j1.5) A (b) (2.4 + j3.2) A
(c) (2.6 j1.5) A (d) (2.4 j3.2) A
84. The voltage at the receiving end of a 3-phase feeder delivering 100 KVA varies between
475 V and 525 V. For what KVA capacity must an induction regulator be designed to
maintain the voltage M constant at 500 V?
(a) 4 KVA (b) 5 KVA
(c) 6 KVA (d) 7 KVA
86. An interconnector cable having a reactance of j0.05 pu links two generating stations G1
and G2 as shown below, where |V1| = |V2| = 1 pu. The load demand at two buses are
SD1=15+j5 pu and SD2=25+j15 pu. The total reactive power at the generating station G1 when
generator G2 is working on unity power factor and δ=15° is ____________ p.u.
(a) 25.36
(b) 24.58
(c) 12.56
(d) 21.36
87. In a two bus AC system, the sending end voltage |Vs| and the receiving end voltage |Vr|
for the line is 1 pu. The line reactance is j 0.05 pu and resistance is neglected. If the real
power flow through the line is 10 pu then the reactive power absorbed by the line is
_______________ p.u.
88. A conductor consists of seven identical strands each having a radius of r as shown below.
Determine the factor by which r should be multiplied to obtain the self GMD of strand one
for calculation of capacitance?
(a) 2.34
(b) 2.67
(c) 3.12
(d) 3.46
89. The corona loss on a particular system at 50Hz is 2KW/km/ph. The corona loss at 60 Hz
would be ________ KW/km/ph.
90. A uniformly distributed load on a distributor of length 500 m is rated at 1A per metre
length. The distributor is fed from one end at 220V. The voltage drop at a distance of 400
metres from the feeding point is ________ V.
91. In a string of three identical suspension insulator units supporting a transmission line
conductor, if the self-capacitance of each unit is denoted as C farads, the capacitance of each
connector pin to ground can be taken as 0.1 C farads. If the maximum permissible voltage
per unit is given as 20 KV then the string efficiency is
93. For a two machine system with losses, the transfer impedance being not purely resistive,
the maximum value of the sending end power P1 max and the maximum receiving end
power P2 max will occur at power angles (δ) in such a manner that
94. The KVA taken by a 10km long, 3-phase, 3-core, cable, if the capacitance measured
between any two cores is 0.3μF/Km when it is connected to 10 KV, 50 Hz bus-bar is
95. A 3-phase line operating at 50 Hz has the conductors arrangement as shown below, The
conductor diameter is 0.8 cm. The capacitance per phase per kilometer when the
transmission line is operating at 132 kV is
96. A single phase motor connected to 400 V, 50 Hz supply takes 31.7 A at a power factor of
0.7 lagging. The capacitance required in parallel with the motor to raise the power factor to
0.9 lagging is _______ μF.
97. The insulation resistance of a single core cable is 495 MΩ per km. If the core diameter is
2.5 cm and resistivity of insulation is 4.5 × 1014 Ω-cm, the insulation thickness is __________
cm.
98. For a single circuit transmission line delivering a load of 50 MVA at 110 KV and pf 0.8
lagging. Given A = D = 0.983°; B = 11075° Ω; and C = 0.000580o ℧ ; The sending end
line voltage is ________ kV.
99. Consider two parallel short transmission lines of impedances ZA and ZB respectively.
Currents IA and IB are both lagging and the sending end voltage is VS. If the reactance to
resistance ratio of both the impedances ZA and ZB are equal, then the total current I will
103. The receiving end power factor of a 3- short line under the condition of maximum
power transferred, having per phase impedance of (0.3+j0.4), receiving end voltage is 6.3
kV/ph and voltage regulation not be exceed 5% is.
104. Calculate string efficiency for a string of 3 insulator units, if the capacitance of each unit
to earth and line be 20% and 5% of the self-capacitance of the unit.
(a) 74.5% (b) 82.1%
(c) 86.2% (d) 91.4%
105. An installation consists of an induction motor and a heater load. The induction motor
takes 25 kVA at 0.8 lagging p.f. The rating of the heater operating at unity p.f., so that the
overall p.f. becomes 0.9 lagging is
(a) 18.21 kW (b) 14.12 kW
(c) 12.16 kW (d) 10.97 kW
106. There are 6 conductors in a double circuit line. Each conductor has a radius of 12 mm.
The six conductors are arranged horizontally. The center to center distance between the two
consecutive conductors is 2m. The sequence of conductors are from left to right as follows:
a, b, c, a’, b’, c’ . The inductance per km per phase of the system us ________ mH.
107. The GMR of the unconventional conductors shown in figure in terms of the radius ‘r’ of
an individual strand.
(a) 1.101 r
(b) 1.512 r
(c) 1.002 r
(d) 1.704 r
108. Two ideal voltage sources designated as 1 and 2 are connected as shown in figure. If E1
= 1000o V, E2 =10030o V, and z = 0 + j5. The total reactive power supplied to the
impedance is
109. An extra high voltage transmission line of length 400 km can be approximate by a
lossless line having propagation constant = 0.00112 radians/km. Then the percentage
ratio of line length to wavelength will
110. A 2-wire d.c. ring distributor is 300 m long and is fed at 240 V at point A. At point B,
150 m from A, a load of 120 A is taken and at C, 100 m in the opposite direction, a load of 80
A is taken. If the resistance per 100 m of single conductor is 0.03 ohm, the voltage at point B
is
111. A thermal power station of 1000 MW capacity is located at 400 km away from a load
centre. Select the most suitable power evacuation transmission configuration among the
following options.
112. A 3-phase overhead transmission line has its conductors horizontally spaced between
adjacent conductors equal to ‘d’. If now the conductors of the line are rearranged to form an
equilateral triangle of sides equal to ‘d’
(a) Average capacitance and inductance will increase
(b) Average capacitance will decrease and inductance will increase
(c) Average capacitance will increase and inductance will decrease
(d) Surge impedance loading of the line increase.
113. A 50 Hz, three-phase transposed line has the following parameters per phase
114. A three-phase motor is drawing 20 kVA at 0.707 power-factor lagging from a 220 V
source. A capacitor bank is added with the motor to raise the power factor to 0.90 leading.
The kVAR rating of the capacitor bank is _________ kVAR.
115. A single core, 1-phase cable, consisting conductor of 1 cm diameter inside a sheath of
2.8 cm diameter, is 20 km long and operates at 13 kV and 50 Hz. The relative permittivity of
the dielectric is 5. The charging current of the cable is ____________ A.
116. One circuit of a single phase transmission line is composed of three solid wires of 0.25
cm radius. The return circuit is composed of two wires of 0.5 cm radius as shown in figure.
The inductance due to the current in side ‘y’ of the line is
117. Two regional systems, each having several synchronous generators and locals are inter
connected by an ac line and a HVDC kink as shown in figure. Which of the following
statement is true in the steady state:
(d) The directions of power flow in the HVDC link (Pdc) cannot be reserved
118. Determine the voltage across the bottom unit of a string of suspension insulators
consisting of 3 similar units. The voltage between line and earth is 60 kV and the ratio of the
capacitance of each unit and the capacitance between pin to earth is 10 : 1.
119. The terminal voltage of a Y-connected load consisting of three equal impedances of
2030o is 4.4 kV line to line. The impedance in each of the three lines connecting the load
to a bus at a substation is ZL = 1.475o. The line to line voltage at the substation bus is
___________ kV.
120. A single phase transmission line and a telephone line are both symmetrically strung one
below the other, in horizontal configurations, on a common tower. The shortest and longest
distances between the phase and telephone conductors are 2.1 m and 4 m respectively. The
voltage (V/km) induced in the telephone circuit, due to 50 Hz current 80 A in the power
circuit is _____________ V/km.
121. A typical line has the following parameters; A = D = 0.961.0o and B = 10080o . If
the line supplies a load of 30 MW at 0.8 pf lag, 110 kV, the voltage regulation of the line is
Solutions
1. Ans: (a)
Solution: Three and half core cable is used for distribution system
3-core cable is used for small voltage transmission system
For bulk amount of power transmission single core cable used
2. Ans: (d)
Solution: Shackle Insulator used in distribution system for the crossing of lines and dead
end lines. The same thing is done in transmission system by using strain Insulator (or)
tension Insulator.
3. Ans: (c)
Solution: The proximity effect is nothing but when current carrying conductor creates a flux
and links the adjacent conductors then the current distribution in that conductor is non-
uniform.
4. Ans: (d)
Solution: In case of lagging pf load the voltage regulation and voltage drop is positive from
sending to the receiving end and hence the voltage at receiving end will be less than 440V.
5. Ans: (a)
Solution: In the feeder, the current is same throughout the length so the size of the feeder is
based on current carrying capacity.
7. Ans: 10
1 20 M 20 km
Solution: R R 2 10 M
length R2 10 km
8. Ans: (b)
9. Ans: 45
Solution: Total diameter of standard conductor is (2n + 1)d (2 4 + 1)5 45 cm
10. Ans: 10
VS VR 40
Solution: Voltage regulation for short transmission line 100 100 10%
VR 400
11. Ans: (c)
Solution: String efficiency is independent of frequency
voltage across the string
String efficiency =
n voltage of disc near to power conductor
16. Ans: 86 to 87
mutual capacitance 1
Solution: Solution: m
self capacitance 10
V3 m2 3m 1 V1 1.31V1
V2 m 1 V1 1.1V1
Total Voltage= V1 V2 V3 V1 1.1V1 1.31V1 3.41V1
Voltage across string
String efficiency =
Number of discs voltage across the disc near to the power conductor
3.41v1
100 86.76%
3 1.31v1
I1
Let, V2 nV1 : I2
n
I1R1 I / nR 2
100 1 100 R1 n2R 2
V1 nV1
a1 V22 n V1
2 2
1 1
a 2 2 n2 a2 2 a1
V a2 V1 V12
n
R 2 22 R1 4R1 ;
1 1
a2 a a1
2 1
2 4
25. Ans: 19 to 20
Solution: Self GMD self GMD1 4 0.778 r d d 2d
Vs
VR
Voltage regulation= A 100%
VR
For short line A=1
Hence option (a) is correct
Vs Vr
Pmax . Maximum Power is also called as Steady State Stability limit so as maximum
X
power reduces stability reduces.
47. Ans: 22
0.2C
Solution: V2 V1 1 m V1 1 1.2V1 12kV
C
Total voltage= V1 V2 =22kV
Total line voltage
A D cos x , LC
sin x
C and B Z c sin x
Zc
1
3
Solution: GMD= 2 5 5
Self GMD= .7788 2 102
3
1
2 5 5
L 2 10 7 ln 2
106 .9859 mH / km
.7788 2 10
Solution: string
3 76.98%
20 15
V1 V2
V2
I1 I
jXr 2
V1 1 0
I1 1 / jxr 1
The entire network can be assumed to be cascading of two
Networks so equivalent parameters are,
Aeq Beq A B 1 0
Ceq Deq C D 1/ jxr 1
B B
Aeq A 1 xr
xr 1 A
B
For3 phase delta reactor xr 3
1 A
61. Ans: (d)
Solution: Since i V the load is lagging pf and addition of a reactor in parallel increases
the total current and reduces the power factor as it also consumes lagging current.
But if a shunt capacitor is added the current is leading in capacitor and thus total current
decreases and power factor also increases.
VA VB IAB Z2 200 300o j1.5 20512.68 V
o
Z c2 0.7 Z c1
V2
SIL1
Z C1
V2 V2 SIL1
SIL2
ZC2 0.7ZC1 0.7
SIL2 SIL1 1
% increment in SIL = 1 19.52%
SIL1 0.7
V2
Q2 V cos V2 . Since cos 1. So, Q2<0 and thus bus 2 delivers reactive power to
X 1
transmission line.
1
=3 108 (approx.)
LC
2 50
1.047 106
3 10 8
B jZ C sin l j250 sin 1.047 106 200000 0.9190o
A A 0.961.0o
B B 10080o
The maximum power transmitted is given by
120 110 0.96 110
2 2
VS VR A VR
PRmax
B
B
cos
100
100
cos 79o
PRmax 109.83 MW
80. Ans: 31 to 32
Solution: For shunt capacitors
Qshunt (3 phase) P1 tan 1 tan 2
Qshunt (3 phase) 120K tan cos1 0.8 tan cos1 0.9
Qshunt (3 phase) 31.88KW
D
Inductance / phase / meter L=2 107 loge m
Ds
282
L 2 107 loge 1.27 H/phase/m
0.4828
20
V1 5.882 kV
1 1.2 1.2
Voltage on the line end unit is V1 1.2V1 7.06 kV
86. Ans: 21 to 22
Solution: Q at G1 Total Reactive Power at Load Ends + Reactive Power By Line
Total Reactive Power at Load Ends = 15 + 5= 20 p.u.
115 1
I 5.227.5
.05 j
Reactive Power by line=(5.22)2 .05 1.36 p.u.
Total 20 1.36 21.36 p.u.
87. Ans: 5 to 6
Vs Vr
Solution: P sin
X
10 0.05
sin1 30
o
1
Distance of the point, at which voltage drop is to be determined, from the feeding point x =
400 metres
Total current in conductor = il
This current will be input from the feeding point
Current at a distance x = il-ix=i(l-x)
Resistance of ‘dx’ length = i(l-x)rdx
Total voltage drop upto distance ‘y’
y y
y2
V= i(l x)rdx=ir (l x)dx ir ly
0 0 2
Voltage drop at a distance of 400 metres from the feeding point
400
2
y2 5 2.4 V
ir ly 1 2 10 500 400
2 2
ER 239.8 2.53 V o
E1 cos E
*
E E EE E
P2 E2 1 2
E2 2 cos 2 1 cos 2 cos
Z Z Z Z Z
To obtain the maximum value of P2* differentiate it with respect to and equate it to zero.
dP2 E2E1
0 => sin sin 0
d Z
i.e. < 90o
*
E E
Similarly P1 E I E1 1
* 2
1 1
Z
Both P1max and P2max occur at <90o
2
3CN Vp 3
KVA taken by the cable =
1000 1000
188.5 KVAR
96. Ans: 94 to 95
Solution: C = 94.3 F
Here motor M is taking a current IM of 31.7 A.
Real Power consumed by motor = VIcos 400 31.7 0.7 8876W
Initial power factor = 0.7
Final Power factor = 0.9
Reactive Power supplied by capacitor =
Q P(tan 1 tan 2 ) 8876 tan(cos1 0.7) tan(cos1 0.9) 4756.48 VAR
Q CV 2
Q 4756.48
C 94.6 F
V 2 50 400
2 2
4 4
C Y j4 104 0.004 S
0.980.14o 63.1479.18o
The ABCD parameters are
0.0004 S 0.980.14o
3.63
L 0.2ln 0.546 mH / km
0.2358
Let us suppose that a current IA flows in section AB of the distributor. The currents in
sections BC and CA will be (IA – 120) and (IA – 200) respectively as shown in the figure.
According to Kirchoff’s voltage law, the voltage drop in the closed ABCA is zero i.e.
IAB RAB + IBC RCB + ICA RCA = 0
or 0.09 IA + 0.03 (IA – 120) + 0.06 (IA – 200) = 0
or 0.18 IA = 15.6
15.6
IA 86.67A
0.18
Current in section AB, = I AB I A 86.67A (from A to B)
Voltage at point B, VB VA I AB R AB 240 88.67 0.09
232.2 V
Consider the two cases when conductors are arranged horizontally and then rearranged at
the corner of an equilateral triangle as shown in the figure.
In horizontal arrangement
d1 d2 and d3 = 2d
d d 2d
3
L=2 107 ln H/m
r
In equilateral triangle
d1 d2 d3
d d d
L 2 10 7 ln H/m
r
So, the inductance decreases.
While the general expression for capacitance of a 3-phase transmission line is given as
20
C H/m
3 d1d2d3
ln
r
So, the capacitance increases when the conductors are arranged to form an equilateral
triangle.
115. Ans: 22 to 23
2 2 8.854 1012 5
Solution: Capacitance per km, C= 0.270F / km
ln R / r ln 2.8 / 1
Cable capacitance C 0.27 20 5.4F
Magnitude of charging current, Ic CV 2 50 5.4 106 13 103 22.054A
Dae Dbd Dce 92 62 62 117
Dcd 92 122 15
GMD between slides x and y
3
Dm 6 92 117 2 15 10.743 m
GMR of side y
0.5 0.7788 10
2
Ds 4 Ddd Dde Dee Ded 4 2
62 0.153 m
The inductance due to current inside y of the line
D 10.743
L y 2 107 ln m 2 107 ln 0.85 H / m
Ds 0.153
V V1 (1 0.1 V1 1 3 0.1 0.12 V1 3.41V1
V 60
or Voltage across the top unit V1 17.6 kV
3.41 3.41
Voltage across the second unit V2 1 k V1 1.1 17.6 19.35 kV
Voltage across the bottom unit V3 1 3k k2 V1 1.31 17.6 23.1 kV
=2540.340o 127 30o 1.475o 2669.022.699o V
The line to line voltage at the substation bus is
3 2669.02 4622.87 4.612kV
We recommend you to take the Chapter Test first and then check
the Solutions.
6kW 50 25 25
Solution: Ploss f 25 P2 6 2kW
P2 0 25 75
Solution: Assuming current I1 from the source, the current in various parts of the line is
shown in figure below,
Applying KVL
220 220 I1 0.06 I1 10 0.08 I1 30 0.05 I1 60 0.01
I1 30 15.5A 0
4. Ans: 18 to 19
mutual capacitance 1
Solution: m
self capacitance 10
10
v3
2
V3 m2 3m 1 V1 1.31V1
10
V1 5.3977kV
1.31 2
V2 m 1 V1 1.1V1
5. Ans: (a)
Solution: The phase angle of voltage and magnitude of voltage is more for source so both
active and reactive power are transformed from source to load
6. Ans: (b)
1
Solution: V where L-Inductance/km; C capacitance/km
LC
0.065
For L, Z = X=2fL l 0.065=2 50 L l L=
100 l
1.4
For C, B C l 1.4 2 50 C l C
100 l
1
V
0.065 1.4
.
100 l 100 l
0.9049 108
0.065 1.4 3 108 100 l =>l 288km
100
7. Ans: 22 to 23
Solution: Since, surge travels from Overhead line to cable, we consider characteristic
impedance of cable as load impedance. Applying expression for transmitted voltage,
2Z cable
Vtransmitted Vsurge
Z OH Z cable
2 50
V1 100 22.22 kV
400 50
8. Ans: 2000
Solution:
1 0
A1 B1 1 XZ Z
Equivalent T-matrix will be 1
C1 D1 Y 1 1
Xr
For, VS VR Al 1
Z
Xr
YZ
1
Xr 2000
Y
2r 0l
Solution: Capacitance of single core cable is, C
R
ln
r
R R
For most economic radius of the core, ln 1 i.e. e
r r
3
VSL L 3 41.44 kV 71.78 kV
12. Ans: 23 to 25
110kV
Solution: Vrph 0o
3
Vsph AVrph
110k
Vrph 0.95 2o
3
110k
Isph C. Vrph 0.6 104 90o
3
110 110
NL Ploss 3 . Vsph Isph . coss 3 0.95 0.6 104 cos88o MW=0.024 MW
3 3
14. Ans: 27 to 29
Solution: Power delivered, P = 10 MW = 10,000 kW
Phase voltage at receiving end,
V 30,000
VR RL 17,320 V
3 3
P 1000 10,000 1000
Line current, I= 240.56 A
3VRL cos R 3 30,000 0.8
power delivered
T
power delivered line losses
3I2R 1
line losses = Power delivered 1
1000 T
3I2R 1
10,000 1 416.67 kW
1000 0.96
416.67 1000
or R= 2.4 / phase
3 240.56
2
VSL VRL A
Solution: Receiving-end true power, PR cos VRL2 cos
B B
where A=0.96, B=100, =1o and 80o and is the phase angle between
sending and receiving end voltages.
Thus, we have
120 110 0.96
cos
110 cos 80o 1o
2
50
100 100
50 22.164
or cos 0.5467 cos1 0.5467 56.86o
132
i.e. line is supplying a leading reactive power of 3.47 MVAR or line is demanding 3.47 a
lagging reactive power of 3.47 MVAR.
Since the load required lagging reactive power of 50tan cos1 0.8 i.e., 37.5 MVAR, the
synchronous capacitor must deliver 37.5 + 3.49 i.e., 40.99 MVAR (lagging)